Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

HLBH52-Series Explosion-proof Junction box(e、i、tD)

F
Model implication
HLBH 52-□ /□/□/□D□/□L□/□X□/□R□/□□□ D:Top inlet
Z-With turn lock(optional)
G-With padlock(optional) L:Left inlet R:Right inlet
H-with hinge(optional)
Nos. of inlet/ thread spec.(See P F/19) X:Bottom inlet
Right inlet
Nos. of inlet/ thread spec.(See P F/19)
Bottom inlet
Nos. of inlet/ thread spec.(See P F/19)
Left inlet
Nos. of inlet/ thread spec.(See P F/19)
Top inlet
Rated current
Nos. of terminal
Enclosure serial No.(01,02,03.....)
ia/ib(optional)
Design code Patented product, counterfeiting not allowed.

Explosion-proof junction box

Applications Features
1. Can be used in Zone 1 and Zone 2, group ⅡA,ⅡB and ⅡC 1. The enclosure is made of stainless steel and fine outline(Standard
explosive atmosphere and Zone 21 and Zone22 flammable configuration is 304, other brands need to be specified),
dust atmosphere; stainless steel exposed anti-stripping fastener;
2. Strong erosive environment. 2. Silicone rubber sealing strip with high temperature resistance and
3.Ambient temperature:-20~+40/55℃; aging resistance is used at the joint of enclosure and cover, has good
-40~+40/55℃(indicate it if need); dust-proof and waterproof performance;
4. Temperature class:T1~T6; 3. Increase stainless steel hinge, padlock and turn lock device according
5. Indoor or outdoor(IP66); to user's requirement to facilitate installation and maintenance;
6. Can be used in the chemical, petroleum refining, petroleum 4. Wiring with steel tube or cable.
exploitation, offshore platform, tankers, military industry and
other dangerous place.

Main technical parameters

Rated current (A) Rated voltage (V) Ambient


temperature(℃)
10, 16, 20, 25, 32, 40, 50, AC220, 230, 240,
63, 80, 100, 125, 142
380, 415, 500, 690
-20~+40/55℃
160, 200, 300, 400 DC110/220 Juction box anti-detach screw with
-40~+40/55℃ When juction box with turn lock
limit parts to ensure the best protection device,protection degree up to IP66。
≤5A ≤AC/DC36V of sealing ring。

Ex-mark Degree of Erosion-proof


protection class
Ex eⅡC T5 Gb / Ex tD A21 IP66 T95℃
Ex eⅡC T6 Gb / Ex tD A21 IP66 T80℃

Ex eⅡC T5 Gb / Ex tD A21 IP66 T95℃


IP66 WF2
Ex eⅡC T4 Gb / Ex tD A21 IP66 T130℃
Ex iaⅡC T6 Ga Ex ibⅡC T6 Gb
Juction box with stainless steel hinge, Grounding device with standard
Ex tD A21 IP66 T80℃
open angle up to 120 degrees。 configuration M6。

www.helon.cc F/17
F HLBH52-Series Explosion-proof Junction box(e、i、tD)

Main technical parameters


DIN rail×terminals (spec. and qty.) Ways M16 M20 M25 M32 M40 M50 M63
Enclosure specification 2 of
1.5
2.52 42 62 102 162 352 outlet G1/2 G3/4 G1 G11/4 G11/2 G2 G21/2 G3 G4
01 130 95 4 3 2 1 1 1
D D/X
2 2 1 1
1×12 1×10
130

L R
4 3 2 1 1
L/R
X 2 2 1 1
02 180 95 6 5 3 2 2 1
D D/X
4 3 3 2
1×15 1×12 1×8
130

L R
4 3 2 1 1
L/R
X 2 2 1 1
03 240 95 8 6 4 4 3 2
D D/X
5 4 4 2
1×27 1×23 1×15 1×10 1×8
150

L R 5 4 3 2 1 1
L/R
X 4 3 2 1
04 240 95
8 6 4 4 3 2
D
D/X
1×30 1×26 1×18 1×14 1×12 5 4 4 2
240

L R
2×20 2×17 2×13 8 6 4 4 3 2
L/R
X 5 4 4 2
05/06 10/16 8/14 5/11 5/7 4/6 2/2 --/2
290 95/154
D D/X
6/9 5/8 4/6 3/4 --/2 --/2
1×36 1×30 1×22 1×17 1×12
180

L R 6/11 5/8 3/6 2/4 2/2 1/2


L/R
X 4/6 3/5 2/4 2/2 --/2 --/1
07/08 95/154
290 10/16 8/14 5/11 5/7 4/6 2/2 --/2
D D/X
1×36 1×30 1×22 1×17 1×12 1×10 6/9 5/8 4/6 3/4 --/2 --/2
260

L R
2×20 2×23 2×18 9/15 7/13 5/10 4/6 3/5 2/2 --/2 --/2 --/1
L/R
X 5/8 4/7 3/5 2/3 --/2 --/2
09/10
360 95/154 12/20 10/18 6/14 4/8 4/6 3/4 --/3
D D/X
1×51 1×43 1×32 1×26 1×21 1×15 6/10 5/9 4/8 4/5 --/3 --/2 --/2 --/2
290

L R
2×49 2×41 2×20 10/16 8/14 5/11 5/7 4/6 2/2 --/2
L/R
X 6/9 5/8 4/6 3/4 --/2 --/2
11/12/13
360 95/154/232 12/20/30 10/18/26 6/14/20 4/8/12 4/6/9 3/4/5 --/3/4
D 1×51 1×43 1×32 1×26 1×21 1×17 D/X
6/10/16 5/9/14 4/8/12 4/5/6 --/3/4 --/2/4 --/2/3 --/1/ 2 --/1/ 2
2×49 2×41 2×31 2×24 2×20
360

L R 12/20/30 10/18/26 6/14/20 4/8/12 4/6/9 3/4/5 --/3/4


3×49 3×41 L/R
X
6/10/16 5/9/14 4/8/12 4/5/6 --/3/4 --/2/4 --/2/3 --/1/ 2 --/1/ 2
14/15 727 95/154
D
24/40 20/36 11/28 9/16 8/12 6/8 --/6
1×102 1×86 1×64 1×52 1×42 1×34 D/X
11/20 10/18 8/16 8/10 --/6 --/5 --/4 --/3
L
2×98 2×82 2×62 2×48 2×40
360

R
12/20 10/18 6/14 4/8 4/6 3/4 --/3
3×98 3×82 L/R
X 6/10 5/9 4/8 4/5 --/3 --/2 --/2 --/2
16/17 727 232/276
60/74 56/66 44/52 26/30 18/20 9/11 7/8
D
1×102 1×86 1×64 1×52 1×42 1×34 D/X
34/40 30/36 25/30 14/16 9/10 7/8 6/7 5/6 4/4
360

L R
2×98 2×82 2×62 2×48 2×40
30/37 28/33 22/26 13/15 9/10 4/5 4/4
3×98 3×82 L/R
X 17/20 15/18 12/15 7/8 4/5 4/4 3/4 3/4 2/2
18/19 727 154/276 40/74 36/66 28/52 16/30 12/20 6/11 6/8
D
4×98 4×82 3×62 3×48 3×40 2×34 D/X
20/40 18/36 16/30 10/16 6/10 5/8 4/7 3/6 --/4
5×98 5×82 4×62 4×48 4×40 3×30
727

L R
40/74 36/66 28/52 16/30 12/20 6/11 6/8
6×98 6×82 L/R
20/40 18/36 16/30 10/16 6/10 5/8 4/7 3/6 --/4
X

Note: The specifications and size are only for reference, the specific drawing shall prevail。

F/18 www.helon.cc
HLBH52-Series Explosion-proof Junction box(e、i、tD)
F
Outline & installation dimensions
Outline drawing(Models for HLBH52-…□)

A
B 4-13×9
C 14 G 9

D
E
F

With hinge and turn lock outline drawing With hinge and/or padlock outline drawing
(Models for HLBH52-□…HZ) (Models for HLBH52-□…HG)
A A
B 4-13×9
B 4-13×9
14 G
C 14 G C

D
E
D

F
E
F

Enclosure specification A B C D E F G
B×E(mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm)
130×130 156 130 100 100 130 156 95

180×130 206 180 150 100 130 156 95


240×150 266 240 210 120 150 176 95
240×240 266 240 210 210 240 266 95

290×180 316 290 260 150 180 206 95/154


290×260 316 290 260 230 260 286 95/154

360×290 386 360 330 260 290 316 95/154


360×360 386 360 330 330 360 386 95/154/232
727×360 753 727 697 330 360 386 95/154/232/276

727×727 753 727 697 697 727 753 154/276

1)
Explosion-proof cable gland
Inch gland (G) Metric gland (M)):BDM-7

Pipe path(mm) Cable outer dia. Specification Thread Cable outer dia.
Pipe thread
(mm) (mm)
G1/ 2 15 φ7~φ10 M16 M16×1.5 φ5~φ10

M20 M20×1.5 φ6~φ12


G3/4 20 φ10~φ14
M25 M25×1.5 φ10~φ14
G1 25 φ12~φ18
M32 M32×1.5 φ13~φ19
G11/ 4 32 φ15~φ26
M40 M40×1.5 φ17~φ26
G11/ 2 40 φ18~φ30 M50 M50×1.5 φ24~φ36
G2 50 φ25~φ37 M63 M63×1.5 φ37~φ44

1):The general configuration of inlet and outlet are G thread、BDM-7 cable gland,if other types of introducing devices are required,see P C/15。

www.helon.cc F/19

You might also like