CCME-TANK TIPS - Tank Tips 1 On Storage Tank Systems For Petroleum Products
CCME-TANK TIPS - Tank Tips 1 On Storage Tank Systems For Petroleum Products
CCME-TANK TIPS - Tank Tips 1 On Storage Tank Systems For Petroleum Products
What’s new in the new regulations? On June 12, 2008 Environment Canada put in place
new regulations governing storage tank systems under federal jurisdiction as described in the
regulations. Compliance with these new regulations is mandatory. This fact sheet highlights
some important changes that may have an impact on your storage tank system. If you need more
information, you’ll find our website address, a list of important documents, and contact numbers
on the last page.
Tank Tips 1 2
Will some tanks or components have to be permanently withdrawn
from service and removed?
Yes. Some tank installations pose a risk to the environment and under the
regulations they must be permanently withdrawn from service and removed
by June 12, 2012. They are as follows.
Data compiled from • Single-walled underground tanks that, as of June 12, 2008, lacked
corrosion protection and leak detection, groundwater monitoring
gasoline spills and
wells or vapour monitoring wells. (section 9)
laboratory studies
indicate that light- • Single-walled underground piping that, as of June 12, 2008, lacked
corrosion protection, leak detection, groundwater monitoring wells,
fraction hydrocarbons vapour monitoring wells, single vertical check valves or mechanical
tend to migrate readily line leak detection devices (see subsection 10(2)).
through soil, potentially
• Aboveground tanks installed underground (section 5)
threatening or affecting
groundwater supplies ... • Underground tanks installed aboveground (section 6)
• Partially buried tanks (section 7)
Tank Tips 1 3
What about installing new storage tank systems? Has anything
changed?
Yes. If you’re considering installing a system it’s important that you get a copy
of the regulations. There are requirements governing who may design and
install systems, as well as new technical requirements (section 14). As with
existing systems, all new systems must have a product transfer area designed
When both production to contain spills.
(“upstream”) Do the new regulations affect your product delivery?
and marketing Yes. As of June 12, 2010, the person who delivers your petroleum or allied
(“downstream”) sectors petroleum product will no longer be allowed to fill tanks that do not have
an Environment Canada identification number visible on the system. Also,
are considered, over a
delivery personnel are now required to immediately inform the system’s
quarter million actual operator of any spills that occur during transfer of the product to your tank,
or potential petroleum or of any evidence of a leak or spill.
product release sites Are there any other requirements?
exist in Canada. You must have an emergency plan in place for your storage tank system by
Liabilities are estimated June 12, 2010 (paragraph 30(3)(a)). There are also, now, specific records
in the billion dollar you must keep, including records on any inspections and/or testing. Annual
reporting, however, is no longer required.
plus range.
Where do you get more information?
On our website: www.ec.gc.ca/st-rs. If you’d like us to mail you the
information below please call: 819-934-2991 (0900 h – 1700 h EST/EDT).
The following documents are available on our website:
• Storage Tank Systems for Petroleum Products and Allied Petroleum
Products Regulations
• Tank Tips fact sheets, each one covering a specific part of the new
regulations
• Environmental Code of Practice for Aboveground and Underground
Storage Tank Systems Containing Petroleum and Allied Petroleum
Products, Canadian Council of Ministers of the Environment
• Canadian Environmental Protection Act, 1999
• Compliance and Enforcement Policy for the Canadian Environmental
Protection Act, 1999
Tank Tips 1 4
If you have specific questions on the regulations please contact your
regional office.
Tank Tips 1 5
Tank Tips 2
on Storage Tank Systems for Petroleum Products
and Allied Petroleum Products Regulations
Do the new regulations apply to you? Environment Canada has passed new regulations
governing storage tank systems under federal jurisdiction as described in the regulations.
This includes tanks located on federal or Aboriginal lands. The regulations cover tanks storing
petroleum products and allied petroleum products, and compliance with these regulations is
mandatory. This fact sheet will help you determine if the new regulations apply to you and it will
provide you with websites and contact numbers for more information.
Petroleum products 2. Are the products I’m storing in my tanks covered by these regulations?
released into soil pose 3. Do these regulations apply to my type of storage tanks or containers?
a variety of risks in
1) Is my tank system located on federal or Aboriginal land, or within
the geo-environment.
federal jurisdiction as described in the regulations?
These risks include
combustion hazards, • The new regulations cover storage tank systems located on federal or
Aboriginal land. For example, storage tank systems operated by band
direct toxic risks to councils are subject to the regulations, as are tanks owned by private
humans, plants and businesses such as lodges or marinas located on Aboriginal land. The
animals, effects on soil regulations also apply to tanks operated by, say, private mining or
processes such as water forestry companies located in a federal park or on Crown land.
retention and nutrient • The new regulations also apply to storage tank systems operated by any
cycling, movement federal department, board or agency, or owned by the Crown.
to water and air, and • Finally, the regulations apply to storage tank systems operated by or
aesthetic problems belonging to a federal work and undertaking that is a railway, port
such as objectionable authority, or airport.
odour and sheen. Left 2) Are the products I’m storing in my tanks covered by these
unmanaged, petroleum regulations?
products in the The new regulations cover only specific products. The most common are
geo-environment can stored petroleum products such as gasoline, diesel, jet fuel and home heating
cause important oil. The definition of petroleum product used in the regulations is:
adverse effects. A single hydrocarbon or a mixture of at least 70% hydrocarbons by volume,
refined from crude oil, with or without additives, that is used or could be used
as a fuel, lubricant or power transmitter, and includes used oil, but does not
include propane or most paints or solvents. (section 1)
What the regulations refer to as ‘allied petroleum products’ include substances
such as isopropanol, uninhibited ethylene glycol and E85 fuel. A complete list
of ‘allied petroleum products’ is found in Schedule 1 of the regulations and at
the end of this fact sheet. If you are storing any of these products, even in an
aboveground tank, then the regulations may apply to you. The regulations do
not, however, apply to unprocessed petroleum products.
Tank Tips 2 2
3) Do these regulations apply to my type of storage tanks or
containers?
Environment Canada’s new regulations apply to both aboveground and
underground storage tanks and containers that:
• have a capacity of more than 230 litres
Soils are hydrologically • are vented to the atmosphere (in other words operate at atmospheric
linked to groundwater pressure)
systems. A major • and are designed to be installed in a fixed location
concern with soil
The regulations also apply to all the piping and other equipment associated
contamination is with the tanks.
that it can and does
The following tank systems DO NOT fall under the new regulations.
lead to groundwater
contamination, which • Containers smaller than 230 litres
may be technically, • Indoor storage tanks
economically, or
• Pressurized tanks like those storing propane
otherwise difficult or
currently impossible • Mobile tanks such as those on the back of pickup or other trucks
to remediate. • Outdoor, aboveground tanks that have a total combined capacity
of 2500 litres or less and are connected to a heating appliance or an
emergency generator
• Tanks regulated by the National Energy Board
Tank Tips 2 3
There are now specific requirements for leak detection, corrosion protection
and the removal of high risk tanks and piping. While tank owners/operators
have between two and four years to comply with many of the requirements,
some take effect immediately.
An important new requirement is that storage tank system owners identify
their tank systems with Environment Canada by June 12, 2009 for existing
Petroleum products have systems, and before the first fill for new systems. This can be done quickly
been known to affect online through our website or we can mail you a form. Please note that as
buried infrastructure, of June 12, 2010, suppliers will no longer be allowed to fill tanks that do not
display an Environment Canada identification number.
including underground
utilities. Of particular Where do you get more information?
concern is the On our website: www.ec.gc.ca/st-rs. If you’d like us to mail you the
information below please call: 819-934-2991 (0900 h – 1700 h EST/EDT).
potential for petroleum
products to enter water The following documents are available on our website:
distribution systems, • Storage Tank Systems for Petroleum Products and Allied Petroleum
though impacts on other Products Regulations
utilities are undesirable • Tank Tips fact sheets, each one covering a specific part of the new
as well. regulations
• Environmental Code of Practice for Aboveground and Underground
Storage Tank Systems Containing Petroleum and Allied Petroleum
Products, Canadian Council of Ministers of the Environment
• Canadian Environmental Protection Act, 1999
• Compliance and Enforcement Policy for the Canadian Environmental
Protection Act, 1999
If you have specific questions on the regulations please contact your
regional office.
Tank Tips 2 4
Allied Petroleum Products
1. Thinner for Vinyl Coatings (CGSB 1-GP-124)
2. Antiblush Thinner for Cellulose Nitrate Lacquer (CGSB 1-GP-136)
3. Boiled Linseed Oil (CGSB CAN/CGSB-1.2-89)
4. Petroleum Spirits Thinner (CGSB CAN/CGSB-1.4-92)
5. High Solvency Thinner (CGSB CAN/CGSB-1.70-91)
6. General Purpose Thinners for Lacquers (CGSB CAN/CGSB-1.110-91)
7. Solvent for Vinyl Pretreatment Coating (CGSB CAN/CGSB-1.164-92)
8. Acetone, Technical Grade (CGSB 15-GP-50)
9. Methyl Ethyl Ketone, Technical Grade (CGSB 15-GP-52)
10. Offset Lithographic Printing Ink (CGSB 21.1-93)
11. Isopropanol (CGSB 3-GP-525)
12. Methanol, Technical Grade (CGSB 3-GP-531)
13. Ethylene Glycol, Uninhibited (CGSB 3-GP-855)
14. Benzene
15. Toluene
16. Biodiesel
17. E85 fuel
18. Oxygenated gasoline
This material has been prepared for convenience of reference and accessibility and does not
have an official character. It is of a general nature only. For all purposes of interpreting and
applying the regulations, users must consult the official version of the Storage Tank Systems for
Petroleum Products and Allied Petroleum Products Regulations.
Tank Tips 2 5
Tank Tips 3
on Storage Tank Systems for Petroleum Products
and Allied Petroleum Products Regulations
Critical timelines for existing systems Environment Canada’s new Storage Tank Systems
for Petroleum Products and Allied Petroleum Products Regulations came into effect on June 12,
2008. While many of the requirements are phased in over the next four years, some come into
force immediately. This fact sheet provides you with a checklist of the requirements that come
into force immediately and over the next 1, 2, and 4 years. For each entry, the section number in
the regulations is given in brackets.
What has changed?
On June 12, 2008 Environment Canada put in place new regulations governing storage tank systems
for petroleum and allied petroleum products that are under federal jurisdiction as described in the
regulations. If you are the owner or operator of a storage tank system covered by these regulations there
are new requirements in a variety of areas including spill reporting, leak detection and monitoring,
and record keeping. You must also identify your storage tank system to Environment Canada by
June 12, 2009.
This fact sheet provides you with the checklist covering the major changes coming into force
immediately, and over the next four years, for existing storage tanks systems. Compliance with the
regulations is mandatory.
Are the requirements and deadlines the same for all storage tank systems?
No. If you have single-walled underground tanks or piping, or aboveground tanks or piping without
secondary containment, you will note additional requirements in the checklist that apply to your system.
For more information on the requirements for these types of storage tank systems please see Tank Tips 1:
What’s new in the new regulations.
Tank Tips 3 2
Storage Tank Regulations Checklist
Tank Tips 3 3
√ Requirements in force in 2 years (June 12, 2010)
Tank owners/operators who submitted a Storage Tank System Identification Progress Report have now
identified their tank systems to Environment Canada (section 28).
All storage tank systems are now identified to Environment Canada and an identification number is visible on
or near the system (subsection 28(4)).
Product delivery personnel are no longer permitted to fill tanks without an Environment Canada identification
number visible on or near the system (section 29).
Tank system owners/operators must notify Environment Canada of system changes within 60 days
(subsection 28(5)).
Owners/operators have carried out a visual inspection of sumps and have set up an ongoing leak monitoring
program for sumps (section 25).
An emergency plan is in place for each storage tank system (sections 30 – 32).
An initial tank precision-leak-test as described in the regulations has been completed on all single-walled
underground tanks and an ongoing leak monitoring or detection program is now in place (section 16).
An initial piping precision-leak-test has been completed on all single-walled underground piping and an
ongoing leak monitoring or detection program as prescribed in the regulations is now in place (section 17).
The walls of horizontal aboveground tanks without secondary containment have been visually inspected
for leaks and an ongoing leak monitoring or detection program as prescribed in the regulations is in place
(sections 19 – 21).
Vertical aboveground tanks without secondary containment that have not been inspected since
June 12, 2000 are now inspected in accordance with API Standard 653, and an ongoing leak monitoring or
leak detection program as prescribed in the regulations is in place (section 22).
Aboveground piping without secondary containment has been visually inspected and an ongoing leak
detection program is now in place (sections 23 – 24)
This material has been prepared for convenience of reference and accessibility and does not have an official character. It is of a general
nature only. For all purposes of interpreting and applying the regulations, users must consult the official version of the Storage Tank
Systems for Petroleum Products and Allied Petroleum Products Regulations.
Tank Tips 3 4
Tank Tips 4
on Storage Tank Systems for Petroleum Products
and Allied Petroleum Products Regulations
New storage tank system installations If you’re installing a storage tank system for
petroleum or allied petroleum products your system must now comply with new Environment
Canada regulations. This fact sheet will give you an overview of the major changes you need to
be aware of when choosing equipment and contractors, and it will provide you with contacts and
references if you need more detailed information.
What has changed?
On June 12, 2008, Environment Canada implemented new regulations
governing storage tank systems under federal jurisdiction as described in the
regulations, including tank systems located on federal and Aboriginal lands.
These regulations have specific requirements for the design and installation of
Spills occur most often
storage tank systems. You’ll need to read the regulations to plan your system.
at the fill pipe opening Copies of the Storage Tank Systems for Petroleum Products and Allied Petroleum
when the delivery Products Regulations are available on our website.
truck’s hose is being Your new system must be identified with Environment Canada before you
disconnected. Repeated have it filled for the first time. You’ll be issued an identification number which
releases of even small must then be visible on or near your storage tank system. After June 12, 2010,
volumes of product the person who delivers your product will be prohibited from filling tank
systems without a visible identification number.
can cause significant
environmental Can anyone design and install your new system?
problems. Under the regulations your storage tank system must be built using design
documents that bear the stamp and signature of a professional engineer
(subsection 34(1)). The system must also be installed by a person approved to
do so in the province or territory in which the system is being installed. If no
approval process exists in your province or territory, then the installation must
be supervised by a professional engineer.
What are the requirements for new tanks and components?
New storage tank systems must bear a certification mark to indicate that
they conform to the standards set out in section 14 of the regulations. Many
of these standards are drawn from the Canadian Council of Ministers of
the Environment Environmental Code of Practice for Aboveground and
Underground Storage Tank Systems Containing Petroleum and Allied Petroleum
The volume of crude oil Products. This document is also available on our website. Some of the
requirements for new systems are as follows, but for detailed and specific
or petroleum products information you will need to read section 14 of the regulations as well as the
that is used today dwarfs referenced sections of the CCME Code of Practice.
all other chemicals of
Underground tanks must be double-walled with an interstitial space that can
environmental and be monitored, and have:
health concern. Due
• corrosion protection
to the numbers of
facilities, individuals, • overfill protection
and processes and • spill containment
the various ways the
• containment sumps
products are stored and
handled, environmental • liquid- and vapour-tight connections
contamination is Aboveground field-erected tanks must have:
potentially widespread. • corrosion protection
• secondary containment
• containment sumps, if applicable
• overfill protection
Aboveground shop-fabricated tanks must have:
• corrosion protection
• secondary containment
• containment sumps
• overfill protection
Tank Tips 4 2
• bear a certification mark and be of steel, copper or non-metallic
construction; or be a flexible metallic hose
• no buried or concealed mechanical joints
• underground piping, up to 75 mm in diameter, must have secondary
containment and, in the case of double-walled steel piping, cathodic
Without proper leak protection
detection, a loss of • underground piping larger than 75 mm in diameter must have
five litres of fuel per secondary containment or cathodic protection
day from a relatively Are there any other major requirements?
large tank (20 000 to As with piping and tanks, all components of your system must bear
30 000 litres) could go certification marks indicating that they conform to the standards set out
undetected for several in the regulations. In addition, your product transfer area must now be
designed to contain spills (section 15). Finally, it is mandatory that you
years … Over the have an emergency plan in place before your system receives its first fill
lifespan of the tank, (sections 30 – 32).
such a fuel loss rate
What about record keeping?
would amount to tens Under the new regulations you are required to keep records of the design
of thousands of litres of and installation of your system for the life of the system. These must include
leaked fuel. a record establishing that the system was installed by an approved installer
or supervised by a professional engineer, as well as a set of ‘as-built’ drawings
bearing the stamp and signature of a professional engineer. Please see section
46 of the regulation for details of this, and other, record keeping requirements.
Tank Tips 4 3
• Compliance and Enforcement Policy for the Canadian Environmental
Protection Act, 1999
If you have specific questions on the regulations please contact your
regional office.
Tank Tips 4 4
Tank Tips 5
on Storage Tank Systems for Petroleum Products
and Allied Petroleum Products Regulations
If you suspect or find a leak Under the new Storage Tank Systems for Petroleum Products
and Allied Petroleum Products Regulations you must take immediate action if you discover,
or even suspect, a leak. In this fact sheet you’ll find information on the regulations related to
leaking tanks, piping and other storage tank system components, including when and how to
report a leak.
Tank Tips 5 2
What do you do if you can’t immediately withdraw the leaking
component or system from service?
If circumstances make it impossible for you to temporarily withdraw the
component or system from service you must:
• take immediate measures to minimize any short- or long-term
harm to the environment and/or danger to human life or health.
A 1984 study found that In practical terms, this usually means taking immediate action to
the compounds most reduce the amount of product escaping into the environment. In some
likely to be measured aboveground systems this may be as simple as placing a bucket under
in water in contact with the leak to contain it, or building an ice tub beneath the tank and
lining it with a tarp. If your leak is part way up a tank, reduce the level
gasoline, kerosene, and of product in your tank so that it sits below the leak.
fuel oil #2 were the
• Without delay, notify Environment Canada, in writing, of the
light-fraction, aromatic
circumstances that have made it impossible for you to temporarily
hydrocarbons such withdraw the component or system from service and the measures
as benzene, toluene, that you will be taking to comply with this requirement. The addresses
ethylbenzene, and are listed at the end of the fact sheet.
xylenes. By decreasing the amount of product coming in contact with the soil and
groundwater, you not only reduce the damage to the environment and
the risk to human health, you also minimize your clean-up costs
(subsection 3(4)).
Tank Tips 5 3
Where do I call to report a leak or spill?
Region Emergency Number
Alberta 780-422-4505 • 1-800-222-6514*
British Columbia 1-800-663-3456
Manitoba 204-944-4888
The compounds in New Brunswick 902-426-6030 • 1-800-565-1633*
Newfoundland and Labrador 709-772-2083 • 1-800-563-9089*
different petroleum
Northwest Territories 867-920-8130
product fractions affect
Nova Scotia 902-426-6030 • 1-800-565-1633*
the body in different
Nunavut 867-920-8130
ways. Some of the Ontario 416-325-3000 • 1-800-268-6060
compounds, particularly Prince Edward Island 902-426-6030 • 1-800-565-1633*
the smaller compounds Quebec 514-283-2333 • 1-866-283-2333*
such as benzene, Saskatchewan 1-800-667-7525
toluene, and xylene Yukon 867-667-7244
(which are present in *Telephone number accessible in province/region.
gasoline), can affect the What about a leak in a single-walled underground tank?
human central Because single-walled underground tanks pose a significant risk to the
nervous system. environment, if you find a leak in a single-walled tank the system must
be immediately and permanently withdrawn from service following the
requirements in section 44. You then have two years from the date on which
you found the leak to remove the system entirely, following the procedures in
section 45.
Tank Tips 5 4
Is there anything else you need to know?
If you carry out an inspection or leak test for any reason, including a
suspected leak, you must keep a record of this. Please see section 27 for what
must be in the record.
Tank Tips 5 5
Where do you send your written reports?
Manager of Inspection
Program
Environment Canada
Pacific and Yukon Region Fax: 604-666-9059
201-401 Burrard Street
(4th floor)
Vancouver BC V6C 3S5
Manager of Inspection
Program
Environment Canada
Prairie and Northern
Twin Atria Building Fax: 780-495-2451
Region
4999-98th Avenue NW
Room 200
Edmonton AB T6B 2X3
Manager of Inspection
Program
Ontario Region Environment Canada Fax: 905-333-3952
845 Harrington Court
Burlington ON L7N 3P3
Manager of Inspection
Program
Environment Canada
Quebec Region Fax: 514-496-2087
105 McGill Street
(3rd floor)
Montreal QC H2Y 2E7
Manager of Inspection
Program
Environment Canada
Atlantic Region Fax: 902-426-7924
Queen Square
45 Alderney Drive
Dartmouth NS B2Y 2N6
This material has been prepared for convenience of reference and accessibility and does not
have an official character. It is of a general nature only. For all purposes of interpreting and
applying the regulations, users must consult the official version of the Storage Tank Systems for
Petroleum Products and Allied Petroleum Products Regulations.
Tank Tips 5 6
Tank Tips 6
on Storage Tank Systems for Petroleum Products
and Allied Petroleum Products Regulations
Identifying your system Under Environment Canada’s new Storage Tank Systems for
Petroleum Products and Allied Petroleum Products Regulations you must now identify your
storage tank system directly to Environment Canada. This fact sheet will give you information
on how to identify your system and contact numbers to call if you need more information.
Tank Tips 6 2
capacity, the products being stored and the systems’ safety features.
Identification in our database provides a secure and central location for your
storage tank information, and gives you an effective way to maintain and
manage the information, independent of staff or contractor changes. Once
your tank is identified with us, you can review and update your information
at any time. For Environment Canada, access to information on storage tank
Statistically, releases systems under federal jurisdiction as described in the regulations allows us to
manage the long-term risks inherent in these systems, and to respond in the
of petroleum products event of an emergency.
from storage tank
systems are responsible What happens if you can’t identify your system before the June 12,
2009 deadline?
for approximately If you are unable to identify your tank system by the deadline you must
66% of the soil submit a written Storage Tank System Identification Progress Report to
contamination on the Environment Canada by June 12, 2009 (subsection 28(1)). The information
contaminated sites on required in this report is found in Schedule 3 of the regulations, and includes
a description of the measures you are taking to collect the information, as well
federal and Aboriginal as the problems you might encounter in the course of identifying the system.
lands in Canada. You then have one additional year (until June 12, 2010) to identify your tank
system. No extensions are possible beyond that date.
Tank Tips 6 3
• Compliance and Enforcement Policy for the Canadian Environmental
Protection Act, 1999
If you have specific questions on the regulations please contact your
regional office.
Tank Tips 6 4
16. Type of overfill protection of each tank
17. Type of the piping of the storage tank system
18. Material used in the construction of the piping
19. Diameter of the piping
20. Type of corrosion protection of the piping
21. Type of secondary containment of the piping
22. Type of spill containment devices
23. Description of petroleum product and allied petroleum product transfer
areas
24. Type of leak detection
25. Type of pump for transfer to the oil-water separator
This material has been prepared for convenience of reference and accessibility and does not
have an official character. It is of a general nature only. For all purposes of interpreting and
applying the regulations, users must consult the official version of the Storage Tank Systems for
Petroleum Products and Allied Petroleum Products Regulations.
Tank Tips 6 5
Tank Tips 7
on Storage Tank Systems for Petroleum Products
and Allied Petroleum Products Regulations
Preparing your emergency plan Under Environment Canada’s new Storage Tank
Systems for Petroleum Products and Allied Petroleum Products Regulations you must prepare
an emergency plan for each of your storage tank systems. This fact sheet will tell you what is
required in an emergency plan, and give you an idea of how to prepare one. Contact numbers
and information on where to get help if you need it are found at the end of the fact sheet.
Tank Tips 7 2
Are you near a wetland or above an aquifer used for drinking water? Is your
system located on a hill such that spilled product will flow down the slope? Is
there a populated area or underground utilities nearby? In many cases a map
of the site and the surrounding area, noting relevant geographical features,
is helpful. Any additional information – for example aerial photographs,
bore-hole logs, the location of any other hazards (e.g. propane tanks) – will
The regulations will help facilitate a fast and effective response in an emergency. Because the
determination of site characteristics is so important to your plan, you may
generate benefits such choose to hire an emergency planning professional to help you identify these
as the avoidance of loss features, although Environment Canada does not and will not recommend
of watersheds used for specific companies or individuals.
drinking water, negative Emergency response measures: In this section you lay out your emergency
impacts on human scenarios. You determine:
health, and emergency 1. the emergency scenarios that may cause danger to human life or
response cost associated health
with spills and leaks
2. the emergency scenarios that may harm the environment and
from storage tank
systems. 3. for each emergency scenario, you describe – step-by-step – the
measures and actions you will take to
• prevent
• prepare for
• respond to
• recover from
each emergency. If you are unsure of how to go about this, there are
emergency planning professionals who can help you develop your plan.
Emergency response team and training: The regulations require you to list the
people designated to carry out your plan, their roles and responsibilities in
an emergency, and any training they have or require to carry out their duties.
This information can be presented as a table.
Emergency response equipment: Environment Canada requires you to list
the type and location of equipment that would be used in your emergency
scenarios such as shovels, spill kits and fire extinguishers. If only a small
amount of equipment is needed then a simple text description of the locations
may be sufficient, but if your emergency plan requires a large quantity of
onsite equipment it may be easier to provide locations using a diagram or
map of the site/area.
Tank Tips 7 3
Notification of affected public: Your emergency plan must include the measures
you will take to notify members of the adversely affected public in the case
of an emergency. This could involve the use of emergency announcements
on local radio and television, door-to-door notification and/or the use of
emergency e-mail and text messages.
Tank Tips 7 4
If you have specific questions on the regulations please contact your
regional office.
Tank Tips 7 5
Tank Tips 8
on Storage Tank Systems for Petroleum Products
and Allied Petroleum Products Regulations
Leak detection and monitoring Storage tank systems that lack secondary containment,
have single-walled underground tanks or piping, or make use of sumps pose a greater risk to
the environment than other types of installations. Under Environment Canada’s Storage Tank
Systems for Petroleum Products and Allied Petroleum Products Regulations, there are now specific
leak detection and/or monitoring requirements for these systems. This fact sheet will help you
determine if the requirements apply to your storage tank system and give you the steps you must
take if they do. You will also find additional information, resources and contact numbers at the
end of the fact sheet.
What has changed?
On June 12, 2008 Environment Canada put in place new regulations governing
storage tank systems under federal jurisdiction as described in the regulations.
Prior to these regulations there were no leak monitoring or leak detection
Even with pre-existing requirements for storage tank systems. Under the new regulations certain
types of tank systems now have specific requirements around leak detection
corrosion protection and
and monitoring which must be in place by June 12, 2010.
leak detection, all single-
walled underground Compliance with the regulations is mandatory.
storage tank systems will What systems require leak detection and/or monitoring?
eventually leak as Systems that do not have double walls or secondary containment pose
a higher risk to the environment because, in the event of a leak or spill,
they age.
product is released directly into soil and water. Once there, it can migrate
over a considerable distance and cause extensive and long-term damage
to the environment. If the system you operate or own has tanks, piping or
sumps as described in the list below, then the leak detection and monitoring
requirements apply to your installation.
• single-walled underground tanks
• single-walled underground piping
• aboveground tanks without secondary containment
• aboveground piping without secondary containment
If petroleum products • sumps (turbine, transition, dispenser or pump)
are introduced at
What do you need to do if your system has single-walled
any depth within the underground tanks?
soil matrix, as in the 1) Carry out a third-party certified tank precision leak test that meets the
case of leaks from specifications laid out in section 21 of the regulations by June 12, 2010.
underground storage 2) Immediately following your initial tank precision leak test, set up an
tanks, natural weather ongoing leak detection or monitoring program using one of the three
and biodegradation options below: (section 16)
processes are rendered • carry out a third-party certified tank precision leak detection test once
less effective and a year (subsection 16(b) and section 21), OR
the chances are • use automatic tank gauging (section 18), OR
increased that some
• use continuous in-tank leak detection (section 20).
of the petroleum
product fractions 3) Remove your single-walled underground tank no later than June 12, 2012
(section 9). There are two exceptions:
may contaminate
groundwater. • Steel tanks that have – as of June 12, 2008 – cathodic protection
plus either leak detection, groundwater monitoring wells, or vapour
monitoring may stay in place.
• In addition, single-walled underground tanks made of a material other
than steel may stay in place if – as of June 12, 2008 – they have either
leak detection, groundwater monitoring wells, or vapour monitoring
wells.
4) If your single-walled underground tank leaks, immediately and
permanently withdraw it from service. You then have two years from the
time you found the leak to remove it. (subsection 3(2))
Tank Tips 8 2
2) Following the initial piping precision leak detection test, immediately set
up an ongoing leak detection program using one of the options below:
• perform an annual third-party certified piping leak detection test
(paragraph 17(1)(b) and section 24), OR
• set up external underground pipe leak monitoring that complies with
In Canada, pollution the requirements in subsection 17(2), OR
of surface water by • use automatic tank gauging as described in section 18, OR
groundwater is probably
• use in-tank leak detection as described in section 20.
at least as serious as
the contamination of 3) Remove all single-walled underground piping by June 12, 2012. You may
either replace it with piping approved in the regulations (subsection 14(5)),
groundwater supplies.
or permanently withdraw your storage tank system from service
(section 10). There are two exceptions to the removal requirement
(subsection 10(2)) for single-walled piping. You do not need to remove:
• single-walled steel piping that, as of June 12, 2008, has cathodic
protection as well as one of leak detection, groundwater monitoring
wells, vapour monitoring wells, single vertical check valves or
mechanical line leak detection devices
• non-metallic or copper piping that – as of June 12, 2008 – has one of
leak detection, groundwater monitoring wells, vapour monitoring
wells, single vertical check valves or mechanical line leak detection
devices.
4) If your single-walled piping leaks, immediately and permanently withdraw
it from service and remove it (subsection 3(3)). You may either replace the
piping with piping approved in the regulations or permanently withdraw
the storage tank system from service. If you permanently withdraw the
storage tank system from service you have two years from the time you
found the leak to remove the system in accordance with the procedures
laid out in the regulations (paragraph 3(3)(b)).
Tank Tips 8 3
• carry out an annual third-party certified tank precision leak test as
described in section 21, OR
• visually inspect the walls of the tanks once per month and do an
inventory reconciliation as detailed in subsection 19(2), OR
• use continuous in-tank leak detection (section 20), OR
When petroleum
• use continuous external horizontal aboveground tank leak monitoring
products are released (subsection 19(3)).
directly into water
What do you need to do if your system has vertical aboveground
through spills or leaks,
tanks without secondary containment?
certain petroleum 1) Inspect the tank in accordance with subsection 22(2), OR the floor of the
fractions will float in tank by the procedure laid out in subsection 22(3) by June 12, 2010.
water and form thin 2) Immediately following this inspection set up an ongoing leak detection or
surface films. Other monitoring program using one of the following methods/procedures:
heavier fractions will
• every 10 years from the date of the initial inspection, inspect the
accumulate in the tanks (subsection 22(2)) or the floor of the tanks (subsection 22(3))
sediment at the bottom following the requirements in the regulations, OR
of the water, which may • use continuous in-tank leak monitoring as described in section 20, OR
affect bottom-feeding
• use continuous external vertical aboveground tank leak monitoring
fish and organisms.
that complies with the specifications (leak detection rate etc.) laid out
in subsection 22(4).
3) If your tanks were inspected by one of the approved methods after June 12,
2000, then you must do your initial inspection, and set up your ongoing
leak detection/monitoring program, no later than 10 years from the date of
that inspection. For example, if you inspected your tanks on July 12, 2004,
then your initial inspection under the new regulations must be carried out
no later than July 12, 2014, and your ongoing leak detection/monitoring
program set up immediately following that inspection (subsections 22(5)
and 22(6)).
Tank Tips 8 4
• do a monthly visual inspection of the piping (paragraph 23(1)(b)), OR
• use continuous external aboveground pipe leak monitoring
(subsection 23(2)), OR
• implement a corrosion analysis program for piping that is developed
and conducted by a corrosion expert and includes, at a minimum, an
The frequency, annual inspection (subparagraph 23(1)(a)(ii)).
duration and intensity What must you do if your storage tank system has sumps?
with which people 1) If you have turbine, transition, dispenser or pump sumps, visually
contact pollutants at a inspect those sumps to determine if they are leaking by June 12, 2010
contaminated site are (subsection 25(1)).
related to the nature 2) Immediately following the initial inspection set up an ongoing leak
of the land use. Also, monitoring or detection program using one of the two choices below:
the critical receptor in • visually inspect the sumps annually, OR
any land category is • use continuous sump leak monitoring. If you choose this option, the
dependent on the ease sump leak monitoring must conform to the specifications laid out in
of public access and the subsection 25(2).
activities inherent to that Where do you get more information?
land use. On our website: www.ec.gc.ca/st-rs. If you’d like us to mail you the
information below please call: 819-934-2991 (0900 h – 1700 h EST/EDT)
The following documents are available on our website:
• Storage Tank Systems for Petroleum Products and Allied Petroleum
Products Regulations
• Tank Tips fact sheets, each one covering a specific part of the new
regulations
• Environmental Code of Practice for Aboveground and Underground
Storage Tank Systems Containing Petroleum and Allied Petroleum
Products, Canadian Council of Ministers of the Environment
• Canadian Environmental Protection Act, 1999
• Compliance and Enforcement Policy for the Canadian Environmental
Protection Act, 1999
Tank Tips 8 5
If you have specific questions on the regulations please contact your regional
office.
Tank Tips 8 6
Tank Tips 9
on Storage Tank Systems for Petroleum Products
and Allied Petroleum Products Regulations
Withdrawing and removing systems Under the new Storage Tank Systems for Petroleum
and Allied Petroleum Products Regulations, there are specific requirements if you withdraw from
service or remove a storage tank system or a component of a storage tank system. This fact sheet
summarizes the requirements, directs you to the relevant sections in the regulations and, at the
end of the fact sheet, provides you with telephone numbers and web addresses if you need more
information.
What has changed?
On June 12, 2008 Environment Canada put in place new regulations
governing storage tank systems within federal jurisdiction as described in
the regulations. Under the previous regulations, there were no requirements
when owners or operators withdrew tank systems from service or removed
Tanks inappropriately them. Under the new Storage Tank Systems for Petroleum and Allied Petroleum
Products Regulations tank owners and operators must follow specified
disposed of can re-enter
procedures. In addition, the permanent withdrawal from service and removal
the market and cause of systems must be done by a person approved to do the work. Owners or
site contamination or be operators are also required to keep records pertaining to the withdrawal from
used for inappropriate service and removal of storage tank systems and their components.
purposes, such as bus Why has Environment Canada put in new requirements for the
shelters for children or withdrawal from service and removal of storage tank systems?
for watering livestock. Storage tank systems that are not properly withdrawn from service can pose
a serious risk to both the environment and to the people who live or work
around them. For example:
• tanks that are not properly withdrawn from service contain liquids,
sludge and vapours that, with a single spark on a hot day, can cause a
catastrophic tank explosion.
• tanks that are abandoned – particularly underground tanks –
can corrode and leak pollutants. It may take years before the
contamination is discovered and the source located.
• ‘decommissioned’ storage tanks have been found ‘recycled’ into items
like water troughs or bus shelters, uses that put people at risk.
Generation of The new storage tank regulations are designed to protect both Canadians and
combustible vapours the environment by putting in place mandatory requirements for the proper
withdrawal from service and removal of storage tank systems.
is a hazard not only
for the storage of pure Can anyone permanently withdraw a system from service or
flammable liquids, but remove it?
No. If your tank system is located in a province or territory that licences or
also for the storage of certifies contractors to remove storage tank systems, then the system must be
any sludge or mixture permanently withdrawn from service and removed by a person approved to
where a combustible do so. If the province or territory has no licensing or certification procedure,
component is present then the work must be supervised by a professional engineer (subsections
44(1) and 45(1)). For an up-to-date list of the provinces and territories that
or can be produced by license or certify contractors to withdraw and/or remove storage tank
reaction. systems, please consult our website.
Tank Tips 9 2
Is there anything you have to do before bringing the system or
component back into service?
If your system or a component of your system has been withdrawn from
service for more than a year then you must test it for leaks or inspect it before
returning it to service. The test you carry out depends on the tank type:
• Underground tanks (except vertically-oriented underground tanks)
In a 1992 incident, while or shop-fabricated aboveground tanks require a tank precision leak
workers were welding detection test (subsection 43(b) and section 21).
the outside of a tank
• Field-erected aboveground tanks or vertically-oriented underground
empty of liquid, the tanks require an inspection of the floor in accordance with
residual vapour in the subsection 43(c).
storage tank exploded
What do you have to do to permanently withdraw a system from
and propelled the tank service?
upward and into an If you permanently withdraw a storage tank system or component of a tank
adjacent river. Three system from service, the withdrawal must be done by a person approved to
do the work (subsection 44(1) and see above). You must also keep a record
workers were killed and
(for example an invoice) to prove that the work was indeed carried out by
one was injured. someone designated to do so, along with a record of the date the withdrawal
from service took place (subsection 44(2)). In addition, you must ensure that:
• all the liquids and sludge in the tank are properly removed and
disposed of (paragraph 44(3)(a))
• the tank is purged of vapour to less than 10% of the lower
flammability limit and checked with a combustible gas meter
(paragraph 44(3)(b))
• the withdrawal is done in such a way that it poses no short- or
long-term threat to the environment or human health or safety
(paragraph 44(3)(c))
• you affix a label to the fill pipe saying that the tank system is
permanently out of service (44(4))
• you notify Environment Canada within 60 days that the system has
been withdrawn from service (subsection 44(5)). The easiest way to do
this is to update your tank identification file through our tank registry
at: www.ec.gc.ca/st-rs.
Tank Tips 9 3
Do you have to remove a tank that has been permanently withdrawn
from service?
If you permanently withdraw a tank system from service you are required
to remove the system (section 4). The removal must be done by a person
approved to remove storage tank systems (subsection 45(1)) and the tank
system owner/operator must keep a record that establishes that the system
was removed by someone designated to do so.
A socio-economic
analysis was undertaken When you remove a system do you have to remove tanks, piping and
all components?
that confirmed
Under these regulations you are prohibited from abandoning storage tank
that liabilities for systems in place. All systems must be permanently withdrawn from service
remediation of and removed according to the regulations. The requirements for removal
petroleum-contaminated depend on the type of tanks you have (section 4).
sites in Canada are in • For underground tanks and shop-fabricated aboveground tanks, you
the multi-billion dollar must remove all tanks, piping and components (subsection 4(a)).
range and remediation • For field-erected aboveground tanks, you must remove all piping and
will take many years to components that are outside the tanks (paragraph 4(b)). While field-
accomplish, given the erected aboveground tanks may remain in place, they still must be
properly cleaned following section 44 of the regulations.
size of the remediation
industry. What kind of records do you have to keep when you withdraw or
remove a system or component?
You must keep the following records for five years.
• Temporary withdrawal: you must keep a record of the date you
withdrew the system or component (section 43)
• Permanent withdrawal: you must keep a record that includes the date
that you withdrew the system and establishes that the withdrawal was
done by a person designated in the regulations to withdraw storage
tank systems from service (section 44)
• Removal: you must maintain a record that establishes that the removal
was done by a person designated within the regulations to remove
storage tank systems (section 45)
Tank Tips 9 4
Where can I get more information?
On our website: www.ec.gc.ca/st-rs. If you’d like us to mail you the
information below please call: 819-934-2991 (0900 h – 1700 h EST/EDT)
The following documents are available on our website:
• Storage Tank Systems for Petroleum Products and Allied Petroleum
Products Regulations
• Tank Tips fact sheets, each one covering a specific part of the new
regulations
• Environmental Code of Practice for Aboveground and Underground
Storage Tank Systems Containing Petroleum and Allied Petroleum
Products, Canadian Council of Ministers of the Environment
• Canadian Environmental Protection Act, 1999
• Compliance and Enforcement Policy for the Canadian Environmental
Protection Act, 1999
If you have specific questions on the regulations please contact your regional
office.
Tank Tips 9 5
Tank Tips 10
on Storage Tank Systems for Petroleum Products
and Allied Petroleum Products Regulations
Record keeping for your storage tank system Environment Canada’s new Storage Tank
Systems for Petroleum Products and Allied Petroleum Products Regulations require tank system
owners or operators to maintain specific records. This fact sheet will give you an overview of the
records you are required to keep, how long you must keep them and where they must be filed.
Website addresses, useful documents and contact numbers for additional help are listed at
the end.
Recurrent spills or a What has changed?
long history of disposal On June 12, 2008 Environment Canada implemented new regulations
governing storage tank systems under federal jurisdiction as described in
at specific sites can lead the regulations, including privately owned systems located on federal and
to concerns. Oil dumped Aboriginal lands. Prior to these regulations, tank operators were required
onto soils can saturate to register their storage tank systems with their federal department, and the
the soil matrix. This type federal departments reported annually to Environment Canada. There were,
however, no record-keeping obligations for tank owners or operators.
of very concentrated
contamination can be Under the new regulations tank owners and operators are now required to
maintain specific records on their storage tank systems. While some of these
virtually impossible
records must be kept for five years, you are required to keep others until the
to eliminate without system is removed.
excavating and removing
Compliance with these regulations is mandatory.
all the soil materials.
What records do you have to keep for five years?
You must keep the following records for five years:
• records of all inspections and tests carried out on your system or
components of your system, including leak tests carried out on tanks,
piping or other components (sections 16 – 27 of the regulations)
As [spilled] bulk oil • records related to the operation and maintenance of oil-water
migrates through the separators (sections 35 – 38)
soil column, a small • all test results related to maintaining and operating corrosion
amount of the product protection (sections 16 – 27)
mass is retained by • records on the disposal of water from tank bottoms (section 40)
soil particles. The bulk
• records documenting the temporary or permanent withdrawal from
product retained by the service of a system or any component of a system (sections 42 – 44)
soil particles is known
• records of the removal of any system or component (section 45).
as “residual saturation.”
Depending upon the What information do you include in leak-testing and inspection
persistence of the bulk records?
The information required for your records is laid out in section 27 as follows:
oil, residual saturation
can potentially reside in • the test or inspection date
the soil for years. • the storage tank system identification number
• the type of petroleum or allied petroleum product stored in the system
• the test or inspection results
• the testing method
• the name and address of the individual and, if applicable, the company
that performed the test or inspection
• the components of any corrosion analysis program, if this applies to
your system (see subparagraph 23(1)(a)(ii)).
Tank Tips 10 2
What kind of record do you have to keep when you dispose of water
from your tank bottom?
When you dispose of water from your tank bottom you must ensure that it is
disposed of in a way that doesn’t harm the environment or pose a risk
to human health, and you are required to keep a record of its disposal
(section 40) as follows:
Residual saturation of • the quantity of tank-bottom water removed
the soil is important as
• the date of its removal
it determines the degree
of soil contamination • the name and address of the individual (and company, if applicable)
and can act as a who removed it
continuing source of • the disposal method
contamination for • the place where it was disposed of.
individual compounds
to separate from the What happens if you withdraw your system, or a component of the
system, from service?
bulk product and If, for any reason, you decide to withdraw your system, or a component
migrate independently of your system, from service either temporarily or permanently, there are
in air or groundwater. specific records you must keep. For a temporary withdrawal (less than
2 years) you must keep a record of the date on which you withdrew the
system or component from service (section 43). For a permanent withdrawal,
you must keep a record of the date on which the system or component was
withdrawn from service, and a record establishing that the work was
carried out by a person designated to do so as laid out in the regulations.
(subsection 44(2))
What records are required if you remove a system, and how long do
you keep those records?
If you remove a component of a system or an entire storage-tank system you
need a record establishing that the procedure was carried out by a person
designated to do so under the regulations. You must retain these records for
five years after the removal (subsection 45(2)).
Tank Tips 10 3
• for aboveground piping without secondary containment, any inspection
records related to components of a corrosion analysis program
(subparagraph 46(2)(a)(ii)).
• for new systems, the records listed in the next section.
Tank Tips 10 4
Do all types of storage tank systems have the same record-keeping
requirements?
If you have:
• single-walled underground tanks or piping
• aboveground tanks or piping without secondary containment
• sumps
there are specific inspection and leak monitoring requirements that apply to
you. In addition to the records already mentioned, you must maintain records
of the initial leak-test or inspection required in the regulations, as well as
records on your ongoing leak-detection program (sections 16 to 27). These
records must be held for a minimum of five years. (See Tank Tips 8: Leak
detection and monitoring)
Tank Tips 10 5
If you have specific questions on the regulations please contact your regional
office.
Tank Tips 10 6
Tank Tips 11
on Storage Tank Systems for Petroleum Products
and Allied Petroleum Products Regulations
If you deliver products On June 12, 2008 Environment Canada brought in new regulations
governing storage tank systems for petroleum and allied petroleum products that are under
federal jurisdiction as described in the regulations. If you deliver petroleum or allied petroleum
products to storage tank systems covered by these regulations you have new responsibilities. This
fact sheet explains who is covered by the regulations, and the new responsibilities for delivery
personnel. If you have questions, contact information is listed at the end.
What has changed?
Under the new Storage Tank Systems for Petroleum Products and Allied
Petroleum Products Regulations there are specific requirements for people who
deliver petroleum products and allied petroleum products to storage tank
systems under federal jurisdiction as described in the regulations. Compliance
Processed petroleum with these regulations is mandatory.
products provide up to What are your new responsibilities?
50% of the world’s total If you deliver petroleum products or allied petroleum products to storage
energy supply, major tanks systems covered by these regulations you are now required to:
forms of transportation, • immediately report any spill of product that occurs during transfer to
electric utilities, and the system’s operator
space heating. • immediately report to the system’s operator any evidence of a leak or
spill that you note on or around the tank system
• as of June 12, 2010, keep a record of the Environment Canada
identification number of the tank system you are filling.
After June 12, 2010 you are prohibited from filling tanks that do not have an
Environment Canada identification number visible for you to record.
How do you know if a storage tank system is under federal
jurisdiction as described in the regulations?
For a complete explanation of which tanks are covered you must read
section 2 of the regulations, but the following summary will provide you with
some guidance. The regulations apply to:
• Storage tank systems operated by federal departments, boards or
Petroleum products agencies; or owned by the Crown. This includes tanks owned or
released to the soil may operated by groups such as the Department of National Defence,
move through the soil Fisheries and Oceans Canada, Parks Canada, the RCMP, Canada Post,
to the groundwater. and Public Works and Government Services Canada (PWGSC). If,
for example, you have customers who pay you through contracts or
Individual compounds standing offers with PWGSC, then their tank systems are under federal
may then separate from jurisdiction as described in the regulations and must comply with the
the original mixture, regulations.
depending on the • Storage tank systems owned or operated by federal works and
chemical properties of undertakings that are railways, port authorities or airports.
the compound. Some of • Storage tank systems located on federal and Aboriginal lands. This
these compounds will includes storage tank systems operated by band councils, as well as
evaporate into the air those owned by private companies or individuals operating on federal
and others will dissolve or Aboriginal land. For example, a company mining within a federal
park must comply with the regulations, as must a forestry operation
into the groundwater sited on federal Crown land, or private lodges and marinas located on
and move away from the Aboriginal land.
release area.
What is an Environment Canada identification number?
Under the regulations, owners of storage tank systems have until June 12,
2009 to identify their systems to Environment Canada (or provide us with
an identification progress report). The process of identifying their tank
system with Environment Canada can be done online and, if the tank system
owner has provided all the required information, they will receive their
Environment Canada identification number immediately as the last step in
the identification process. They are then required to post the number on or
near the tank system in a location that is readily visible. This is the number
that – after June 12, 2010 – must be visible, and you must record, in order to
fill the tank.
Tank Tips 11 2
could be used as a fuel, lubricant or power transmitter, and includes used oil,
but does not include propane or most paints or solvents.”
A complete list of ‘allied petroleum products’ can be found in Schedule 1
of the regulations. If you are delivering, for example, general purpose
thinners for lacquers or E-85 fuel, then the tank system may fall within the
regulations.
Furthermore, the
effects of groundwater Do the regulations cover all types of tanks and containers storing
contamination do not these products?
Environment Canada’s new regulations apply to outdoor aboveground and
end with the loss of underground storage tanks and containers that:
well-water supplies.
• have a capacity of more than 230 litres
Several studies
have documented • operate at atmospheric pressure and
the migration of • are designed to be installed in a fixed location.
contaminants from
The following tank systems DO NOT fall under the new regulations.
disposal or spill sites to
nearby lakes and rivers • containers with a capacity of 230 litres or less
as this groundwater • indoor storage tanks
passes through the • pressurized tanks like those storing propane
hydrologic cycle, but the
• mobile tanks such as those on the back of pickup or other trucks
processes are not as yet
well understood. • outdoor, aboveground tanks that have a total combined capacity of
2500 litres or less and are connected to a heating appliance or an
emergency generator
• tanks regulated by the National Energy Board
• tanks that contain unprocessed petroleum products
Tank Tips 11 3
identified the tank system to Environment Canada, as a first course of action
check with the system’s operator. The system may have been identified but the
identification number not posted where you can see it. Once the number is
visible, you may go ahead and fill the tank.
If the owner has not yet identified the system with Environment Canada, and
they have onsite access to the internet, they can identify their storage tank
Many federal system and have the number available for posting within a relatively short
contaminated sites period of time, if they have all the required information in hand (see
are located in remote Schedule 2 of the regulations). In the worst case scenario, however, if it is
after June 12, 2010, the system is not identified, and the owner is unwilling or
regions with harsh
unable to do so while you wait, then you are prohibited from transferring any
climates. It is impossible petroleum or allied petroleum product into their storage tank system.
to work at some of these
After June 12, 2010, what are the penalties for filling a tank without
locations year-round,
an identification number?
lengthening the time If you fill a tank that does not have an identification number you will be in
required to remediate violation of the regulations. Environment Canada’s enforcement officers can
the sites. take a wide variety of enforcement measures, as indicated in the Compliance
and Enforcement Policy for the Canadian Environmental Protection Act, 1999
(CEPA 1999). Among these possible measures are warnings, environmental
protection compliance orders and prosecutions. The sections in CEPA 1999
including and following section 272 identify the offences and punishment for
persons who commit an offence under the Act and regulations.
Is there any information you can give out to your customers to make
sure they identify their tanks with Environment Canada by June 12,
2010?
As suppliers and delivery personnel, you have direct access to tank owners
and operators covered by these regulations. If you need information to
Tank Tips 11 4
hand out to your customers Tank Tips 1: What’s new in the new regulations
and Tank Tips 2: Do the new regulations apply to you? are both available in
.pdf format on our website. These fact sheets will cover your clients’ basic
questions about the new regulations and provide them with contacts, websites
and additional information. Tank Tips 6: Identifying your system covers the
specifics of how to identify your tank system with Environment Canada.
Again, it is available as a .pdf file on our website and can be sent electronically
to your clients or printed off and handed to them.
Tank Tips 11 5