Professional Documents
Culture Documents
P&B Relays and Services Test Report For Motor Relay: 33/6.6Kv Ippl Plant
P&B Relays and Services Test Report For Motor Relay: 33/6.6Kv Ippl Plant
MOTOR DETAILS:
VT PRI 415 V
VT SEC 100 V
EF CT 100 A
EARTH FAULT 1 : D T
IE> Set : 10%
SET SET TIME OPERATING OPEARTING
S.NO Phase
A ( sec ) A TIME ( Sec )
R-N 1.1 1.13
1. Y-N 1 0.5 1 527.0 m
B-N 1 1
1
33/6.6KV IPPL PLANT
P&B Relays and Services
TEST REPORT FOR MOTOR RELAY
OVER CURRENT 1: D T
I> Set : 300%
SET SET TIME OPERATING OPEARTING
S.NO Phase
A ( sec ) A TIME ( Sec )
R-N 3 3.1
1. Y-N 3 2 3.1 2.065 s
B-N 3 3.1
TEST RESULTS:
Tested By