33/6.

6KV IPPL PLANT


P&B Relays and Services
TEST REPORT FOR MOTOR RELAY

TEST REPORT FOR EFV2 -1A


Customer : 33/6.6kv IPPL
Date : 14-02-2022

Model No : AFV2-1A Aux. Voltage : 110 VDC


Serial No : 153323 Frequency : 50 Hz

MOTOR DETAILS:

CT PRI RATIO 100 A / 1A

VT PRI 415 V

VT SEC 100 V

VOLTAGE REF Ph-N

EF CT 100 A

OVER VOLTAGE PROTECTION:


V< Set : 110%
OPERATING SET TIME OPERATING OPEARTING
S.NO Phase
Volts ( Sec ) Volts TIME ( Sec )
R-N 63.5 64.4
2 1.764 s
1. Y-N 63.5 64.4

B-N 63.5 64.4

EARTH FAULT 1 : D T
IE> Set : 10%
SET SET TIME OPERATING OPEARTING
S.NO Phase
A ( sec ) A TIME ( Sec )
R-N 1.1 1.13
1. Y-N 1 0.5 1 527.0 m
B-N 1 1

1
33/6.6KV IPPL PLANT
P&B Relays and Services
TEST REPORT FOR MOTOR RELAY

OVER CURRENT 1: D T
I> Set : 300%
SET SET TIME OPERATING OPEARTING
S.NO Phase
A ( sec ) A TIME ( Sec )
R-N 3 3.1
1. Y-N 3 2 3.1 2.065 s
B-N 3 3.1

TEST RESULTS:

MEASUREMENT CHECKS FOUND OK


PROTECTION FUNCTION CHECKS FOUND OK
OUTPUT RELAY CHECKS FOUND OK
INPUT CHECKS FOUND OK
RELAY FOUND HEALTHY ON ALL ASPECTS