Ravin Cables LTD: Marking Details
Ravin Cables LTD: Marking Details
2. Construction Details(Material)
2.1 Conductor Aluminium conductor
2.2 Insulation XLPE
2.3 Inner Shealth No Inner Sheath
2.4 Armour Aluminium flat
2.5 Outer Shealth FRLS
3. Dimensional Details
3.1 Number of Cores 1
3.2 Conductor Cross-Sectional Area mm² 300
3.3 Approximate Overall Diameter mm 30.5 ± 2.0
3.4 Approximate Cable Weight kg/km 1345
3.5 Conductor :
3.5.1 Conductor Flexibility class Class-2
3.5.2 Approximate number of Wires & Wire Diameter (For Guidance) No/mm 37/3.25
3.5.3 Shape Stranded compact circular
3.6 Insulation :
3.6.1 Average Thickness mm 2.6
3.6.2 Minimum Thickness mm 2.24
3.6.3 Core identification As per IS 7098-2
3.7 Inner Shealth :
3.7.1 Minimum Thickness mm Not applicable
3.8 Armour :
3.8.1 Approximate size of Armour mm 4.0 X 0.8
3.9 Outer Sheath :
3.9.1 Minimum Thickness mm 1.56
3.9.2 Colour Black
4. Electrical Parameters
4.1 Rated Voltage Uo / U kV 1.9/3.3 KV (E)
4.2 Maximum Conductor DC Resistance at 20°C ohm/km 0.1000
4.3 Permissible Current Rating in Air at 40°C A 498
4.4 Maximum Continous Operating Temperature °C 90
4.5 Maximum Short Circuit Temperature °C 250
4.6 Short Circuit Current Rating of Conductor for 1sec. kA 28.20
5. Packaging
5.1 Standard Delivery Length metres 1000 or as Mutually agreed
5.2 Individual & overall quantity tolerance % ±5
6. Applicable Standards
6.1 Cable IS 7098-2
6.2 Conductor IS 8130
6.3 Insulation IS 7098-2
6.4 Armour IS 3975
6.5 Sheath Material IS 5831
7. Installation Guidelines
7.1 Minimum Bending Radius ( 15 x Overall Dia ) mm 480
7.2 Safe Pulling Force 30
N/mm²