Switchgear Type SIMOSEC, Up To 24 KV, Air-Insulated, Extendable
Switchgear Type SIMOSEC, Up To 24 KV, Air-Insulated, Extendable
Edition
Catalog September
HA 41.43 2015
siemens.com/medium-voltage-switchgear
Neue Bilder von Jens Weibert
R-HA41-115.tif
Example
Transfer switchgear with
integrated low-voltage niche
2 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Contents
Dimensions
Switchgear installation 64 to 66
Panels 67 to 77
Floor openings and fixing points 78 to 80
Installation
Shipping data, transport 81 to 83
Standards
Standards, specifications, guidelines 84 to 87
Product Range
With Removable Circuit-Breaker Type 3AH6
Versions 88
Electrical data of the switchgear 89
Circuit-breaker panels, panel design 90 and 91
Product range overview, options for panels 92 and 93
Three-position switch as
three-position disconnector 94
Cable connection 95
Dimensions of circuit-breaker panels 96
Floor openings and fixing points 97
The products and systems described in this catalog
are manufactured and sold according to a certified
management system (acc. to ISO 9001, ISO 14001
and BS OHSAS 18001).
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 3
Application, Requirements
Features
Reavailability
• Three-position switch-disconnector with gas-insulated,
maintenance-free quenching principle
• Metallic partition between busbar compartment, switch-
ing devices and cable compartment
• Separate pressure relief for each compartment
• C able testing without the need to isolate the busbar
• Mounting location of three-phase current transformer for
selective disconnection of circuit-breaker feeders.
*) For standards, see page 84
4 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Application, Requirements
Features
Cost-efficiency Technology
Low “life-cycle costs” and high availability throughout the • Air-insulated indoor switchgear
entire product service life cycle as a result of: • Gas-insulated, maintenance-free switching functions for
• Minimum space requirement the three-position switch as switch-disconnector
• Easy switchgear extension, without gas work • Partition class: PM (partition of metal)
• Maintenance-free gas-insulated switching functions of the • Three-pole primary enclosure
three-position switch (gas-insulated quenching principle) • Phases arranged one behind the other
• Vacuum circuit-breaker • No cross insulation between phases
• Modular product range and design, e.g. circuit-breaker • Busbar system at the top
panels • Air-insulated busbar and cable connection system
• Low maintenance • Three-position switch, metal-enclosed, with air-insulated
• Option: Numerical multifunction protection relay primary terminals and gas-insulated switching functions
(SIPROTEC protection device family, as well as external • Vacuum circuit-breaker, metal-enclosed, up to 1250 A,
makes). fixed-mounted in gas-insulated switching-device vessel
• Option: Vacuum circuit-breaker (type 3A_), air-insulated,
Quality and environment
up to 1250 A, removable design: Easy to remove after
• Quality and environmental management system according loosening the fixing bolts
to DIN EN ISO 9001 and DIN EN ISO 14001 • Hermetically-sealed by welded, stainless-steel switching-
• Easy switchgear extension, without gas work on site device vessel
• Minimum space requirements. –– For switching devices
–– With insulating gas SF6
Service life
• LSC 2 panels, LSC 1 panels (without isolating distance)
Under normal operating conditions, the expected service
• Pressure relief
life of air-insulated switchgear SIMOSEC is at least 35 years,
–– To the rear and upwards
probably 40 to 50 years, taking the tightness of the her-
–– Separately for each compartment
metically welded switching-device vessel into account. The
–– Option: Pressure relief downwards
service life is limited by the maximum number of operating
cycles of the switchgear devices installed: • Air-insulated cable connection system for conventional
cable sealing ends
• For circuit-breakers, according to the endurance class
defined in IEC 62271-100 • Option: Three-phase current transformer, factory-assem-
bled on the feeder bushings
• For three-position disconnectors and earthing switches,
according to the endurance class defined in IEC 62271-102 • Integrated low-voltage niche (standard) for installation of,
e.g.
• For three-position switch-disconnectors, according to the
–– Terminals, MCBs, pushbuttons
endurance class defined in IEC 62271-103.
–– Protection devices
• Option: Top-mounted low-voltage compartment
• Option: Panel heating for severe ambient conditions,
e.g. condensation.
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 5
Application, Requirements
Features, classification
Electrical features
• Rated voltages up to 24 kV
• Rated short-time withstand current up to 25 kA
• Rated normal current of feeders
–– Up to 800 A, e.g. for ring-main, metering panels
–– Up to 1250 A, for circuit-breaker panels
–– Up to 1250 A, for bus sectionalizer panels
• Rated normal current of busbar up to 1250 A.
6 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Technical Data
Electrical data of the switchgear
Transformer panel types T, T1, T(T) as switch-fuse combination according to IEC 62271-105
Rated normal current Ir **)1) Standard A 200
50 Hz Rated short-time withstand for rated duration of short-circuit tk = 1 s, 2 s *) up to kA 21 25 21 25 21 25 16 20 25
current Ik 1) 4) for rated duration of short-circuit tk = 3 s (4 s *)) up to kA 21 – 21 – 21 – 16 20 –
Rated peak withstand for transformer feeders 1)
current Ip 1) up to kA 52.5 63 52.5 63 52.5 63 40 50 63
Rated short-circuit making for transformer feeders 1)
current Ima 1) up to kA 52.5 63 52.5 63 52.5 63 40 50 63
60 Hz Rated short-time w
ithstand for rated duration of short-circuit tk = 1 s, 2 s *) up to kA 21 25 21 25 21 25 16 20 25
current Ik 1) 4) for rated duration of short-circuit tk = 3 s up to kA 21 – 21 – 21 – 16 20 –
Rated peak withstand for transformer feeders 1)
current Ip 1) up to kA 55 65 55 65 55 65 42 52 65
Rated short-circuit making for transformer feeders 1)
current Ima 1) up to kA 55 65 55 65 55 65 42 52 65
Dimension e of e = 292 mm • • • –
HV HRC fuse-link e = 442 mm • • • •
Circuit-breaker panel 2) types L, L1, L(T), L1(T)
Rated normal current Ir **) Standard: L, L(T), L1, L1(T) A 630
Option: L1, L1(T) A 1250 A )
50 Hz Rated short-time withstand for rated duration of short-circuit tk = 1 s, 2 s *) up to kA 21 25 21 25 21 25 16 20 25
current Ik for rated duration of short-circuit tk = 3 s (4 s *)) up to kA 21 – 21 – 21 – 16 20 –
Rated peak withstand current Ip up to kA 52.5 63 52.5 63 52.5 63 40 50 63
Rated short-circuit making current Ima up to kA 52.5 63 52.5 63 52.5 63 40 50 63
Rated short-circuit breaking current Isc up to kA 21 25 21 25 21 25 16 20 25
60 Hz Rated short-time w
ithstand for rated duration of short-circuit tk = 1 s, 2 s *) up to kA 21 25 21 25 21 25 16 20 25
current Ik for rated duration of short-circuit tk = 3 s up to kA 21 – 21 – 21 – 16 20 –
Rated peak withstand current Ip up to kA 55 65 55 65 55 65 42 52 65
Rated short-circuit making current Ima up to kA 55 65 55 65 55 65 42 52 65
Rated short-circuit breaking current Isc up to kA 21 25 21 25 21 25 16 20 25
Metering panel types M, bus riser panel type H
Rated normal current Ir **) for:
M, M(-K), M(-B), M(-BK), H, M(KK) Standard A 630
M, M(-K), M(-B), M(-BK), H Option A 800, 1250
50 Hz Rated short-time for rated duration of short-circuit tk = 1 s, 2 s *) up to kA 21 25 21 25 21 25 16 20 25
withstand current Ik for rated duration of short-circuit tk = 3 s (4 s *)) up to kA 21 – 21 – 21 – 16 20 –
Rated peak withstand current Ip up to kA 52.5 63 52.5 63 52.5 63 40 50 63
60 Hz Rated short-time for rated duration of short-circuit tk = 1 s, 2 s *) up to kA 21 25 21 25 21 25 16 20 25
withstand current Ik for rated duration of short-circuit tk = 3 s up to kA 21 – 21 – 21 – 16 20 –
Rated peak withstand current Ip up to kA 55 65 55 65 55 65 42 52 65
*) As design option, on request according to some national requirements (e.g.: GOST, GB, …) • possible
**) The rated normal currents apply to ambient air temperatures of max. 40 °C. – not possible
The 24-hour mean value is max. 35 °C (according to IEC 62271-1/ VDE 0671-1)
1) Depending on HV HRC fuse-link (depending on the let-through current of the HV HRC fuse-link),
earthing switch at the feeder: see page 11
2) Vacuum circuit-breaker in gas-filled switching-device vessel (maintenance-free under normal ambient conditions according to IEC 62271-1)
3) On request: Panel types K and K1, each with make-proof earthing switch
4) Busbar
) 1250 A in preparation
8 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Technical Data
Electrical data of the switchgear
*) As design option, on request according to some national requirements (e.g.: GOST, GB, …)
**) The rated normal currents apply to ambient air temperatures of max. 40 °C.
The 24-hour mean value is max. 35 °C (according to IEC 62271-1/ VDE 0671-1)
***) Up to 630 A
1) Depending on HV HRC fuse-link (depending on the let-through current of the HV HRC fuse-link)
2) Busbar
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 9
Technical Data
Electrical data of the switchgear
Three-position switch-disconnector
Rated insulation level Rated voltage Ur kV 7.2 12 17.5 24
Rated short-duration power-frequency withstand voltage Ud
– phase-to-phase, phase-to-earth, open contact gap kV 20 28, 42 *) 38 50
– across the isolating distance kV 23 32, 48 *) 45 60
Rated lightning impulse withstand voltage Up
– phase-to-phase, phase-to-earth, open contact gap kV 60 75 95 125
– across the isolating distance kV 70 85 110 145
Rated frequency fr Hz 50 / 60
Rated normal current Ir**) Standard: A 630
Option: A 800
50 Hz Rated short-time for rated duration of short-circuit tk = 1 s, 2 *) up to kA 21 25 21 25 21 25 16 20 25
withstand current Ik for rated duration of short-circuit tk = 3 s (4 s *)) up to kA 21 – 21 – 21 – 16 20 –
Rated peak withstand current Ip up to kA 52.5 63 52.5 63 52.5 63 40 50 63
Rated short-circuit making current Ima up to kA 52.5 63 52.5 63 52.5 63 40 50 63
60 Hz Rated short-time for rated duration of short-circuit tk = 1 s, 2 *) up to kA 21 25 21 25 21 25 16 20 25
withstand current Ik for rated duration of short-circuit tk = 3 s up to kA 21 – 21 – 21 – 16 20 –
Rated peak withstand current Ip up to kA 55 65 55 65 55 65 42 52 65
Rated short-circuit making current Ima up to kA 55 65 55 65 55 65 42 52 65
Switching capacity for general-purpose switches according to IEC / EN 62271-103
Test duty TDload Rated mainly active 100 operations Iload [I1] *) A 630
load-breaking current Iload 20 operations 0.05 Iload [I1] A 31.5
Test duty TDloop Rated closed-loop breaking current Iloop [I2a]
A 630
Test duty TDcc Rated cable-charging breaking current Icc [I4a]
A 68
Test duty TDlc Rated line-charging breaking current Ilc [I4b]
A 68
Test duty TDma Rated short-circuit making current Ima 50 Hz up to kA 52.5 63 52.5 63 52.5 63 40 50 63
60 Hz up to kA 55 65 55 65 55 65 42 52 65
Test duty TDef1 Rated earth-fault breaking current Ief1 [I6a]
A 200
Test duty TDef2 Cable-charging breaking current under earth-fault conditions with
superimposed load current Iload + √3 · Icc [I1 + √3 · I4a] A 115
Number of mechanical operating cycles / M-classification n 1000 / M1; 2000 *) / M1
Number of electrical operating cycles with Iload / Classification n 100 / E3
Number of short-circuit making operations with Ima / Classification n 5 5 5 5 5 5 5 5 5
C-classification E3 E3 E3 E3 E3 E3 E3 E3 E3
C-classification for general-purpose switch (no restrikes, TD: Icc, Ilc) C2 C2 C2 C2 C2 C2 C2 C2 C2
Classification for disconnectors according to IEC / EN 62271-102 / VDE 0671-102
Number of mechanical operating cycles n 1000 (2000 *))
M-classification M0 (M1 *))
Technical data and switching capacity for earthing switch according to IEC / EN 62271-102 / VDE 0671-102
Rated short-time withstand current Ik 50 Hz up to kA 21 25 21 25 21 25 16 20 25
Rated short-circuit making current Ima 50 Hz up to kA 52.5 63 52.5 63 52.5 63 40 50 63
Rated short-time withstand current Ik 60 Hz up to kA 21 25 21 25 21 25 16 20 25
Rated short-circuit making current Ima 60 Hz up to kA 55 65 55 65 55 65 42 52 65
Number of mechanical operating cycles / M-classification n 1000 / M0
Number of short-circuit making operations with Ima n 5 5 5 5 5 5 5 5 5 / 2 2)
2)
Classification E2 E2 E2 E2 E2 E2 E2 E2 E2/E1
Switch-disconnector / fuse combination according to IEC/EN 62271-105/VDE 0671-105
Rated voltage Ur kV 7.2 12 17.5 24
Rated normal current Ir **) A 200 1)
Rated transfer current Itransfer A 1750 1750 1500 1400
Maximum transformer rating kVA 800 1600 1600 2500
Switching capacity for make-proof earthing switch, arranged on feeder side, downstream from HV HRC fuse, for typical: T, M(VT-F)
Rated short-time withstand current tk = 1 s kA 2
Rated short-circuit making current Ima 50 Hz kA 5
60 Hz kA 5.2
Number of short-circuit making operations with Ima / E-classification n 5 / E2 5 / E2 5 / E2 5 / E2
Number of mechanical operating cycles / M-classification n 1000 / M0
*) As design option, on request according to some national requirements (e.g.: GOST, GB, …)
**) T he rated normal currents apply to ambient air temperatures of max. 40 °C.
The 24-hour mean value is max. 35 °C (according to IEC 62271-1/ VDE 0671-1)
12 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Technical Data
Technical data, switching capacity and classification of switching devices
Vacuum circuit-breaker
Switching capacity according to IEC/EN 62271-100/VDE 0671-100
Type CB-f 1) 4), combined with three-position disconnector, in gas-insulated switching-device vessel 4)
On request: Type CB-r [L1(r)], CB-w [L1(w)] 1)
Rated voltage Ur kV 7.2 12 17.5 24
Rated normal current Ir **) A 630
A on request: 800
A 1250
Rated frequency fr Hz 50 / 60
50 Hz Rated short-time for rated duration of short-circuit tk = 1 s, 2 s *) up to kA 21 25 21 25 21 25 16 20 25
withstand current Ik for rated duration of short-circuit tk = 3 s (4 s *)) up to kA 21 – 21 – 21 – 16 20 –
Rated peak withstand current Ip up to kA 52.5 63 52.5 63 52.5 63 40 50 63
Rated short-circuit breaking current Isc up to kA 21 25 21 25 21 25 16 20 25
Rated short-circuit making current Ima up to kA 52.5 63 52.5 63 52.5 63 40 50 63
60 Hz Rated short-time for rated duration of short-circuit tk = 1 s, 2 s *) up to kA 21 25 21 25 21 25 16 20 25
withstand current Ik for rated duration of short-circuit tk = 3 s up to kA 21 – 21 – 21 – 16 20 –
Rated peak withstand current Ip up to kA 55 65 55 65 55 65 42 52 65
Rated short-circuit breaking current Isc up to kA 21 25 21 25 21 25 16 20 25
Rated short-circuit making current Ima up to kA 55 65 55 65 55 65 42 52 65
Classification and number of operating cycles for circuit-breaker according to IEC / EN 62271-100 / VDE 0671-100
Circuit-breaker: CB-f NAR 3)
Mechanical Number of operating cycles n 2000
Class M1
Electrical Number of operating cycles with Ir: 2000 Class E2
Breaking of capacitive currents Class C2
Number of short-circuit breaking operations with Isc n 20
Class S1
Rated operating sequence O - 3 min - CO - 3 min - CO
Classification for disconnector according to IEC / EN 62271-102 / VDE 0671-102 (for panel types L, L1, ...)
Number of mechanical operating cycles n 1000 (2000 *))
M-Classification M0 (M1 *))
Classification for earthing switch according to IEC / EN 62271-102 / VDE 0671-102 (for panel types L, L1, ...)
Number of mechanical operating cycles / M-classification n 1000 / M0
Number of short-circuit making operations with Ima n 5 5 5 5 5 5 5 5 5
Classification E2 E2 E2 E2 E2 E2 E2 E2 E2
*) As design option, on request according to some national requirements (e.g.: GOST, GB, …)
**) The rated normal currents apply to ambient air temperatures of max. 40 °C. The 24-hour mean value is max. 35 °C (acc. to IEC 62 271-1/VDE 0671-1)
1) Definition of the different types of vacuum circuit-breakers (= VCB): VCB version: without AR 3) with AR 3)
Panel type VCB type CB-...NAR CB-...AR
L, L1 CB-f Vacuum circuit-breaker, fixed-mounted in gas-insulated switching-device vessel, CB-f NAR CB-f AR
combined with three-position disconnector
L1(r) CB-r Vacuum circuit-breaker, air-insulated, removable, CB-r AR
separate three-position disconnector
L1(w) CB-w Vacuum circuit-breaker, air-insulated, withdrawable, CB-w AR
separate three-position disconnector
3) AR = Automatic reclosing; NAR = Non automatic reclosing
4) VCB in switching-device vessel (maintenance-free under normal ambient conditions according to IEC 62271-1)
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 13
Product Range
Product range overview
R-HA41-116a.tif
Column No.
Ring-main panel, type R Cable Ring-main panel 1) R 375 630 A, 800 A
feeder R1 500 630 A, 800 A
panels
Transformer panel 1) T 375 200 A
T1 500 200 A
Cable panel K 375 630 A
K1 500 630 A, 1250 A
Cable panel, with earthing switch K *) 375 630 A
K1 *) 500 630 A
Circuit-breaker panel (fixed-mounted CB, gas-insul.) 1) L 500 630 A
(with CB type “CB-f” 2)) L1 750 630 A, 1250 A
Circuit-breaker panel (removable CB) type ”CB-r” L1(r) *) 750 630 A, 1250 A
Circuit-breaker panel (removable CB) type ”CB-r” L2(r) *) 875 630 A, 1250 A
Circuit-breaker panel (withdrawable CB) L1(w) *) 750 630 A, 1250 A
L2(w) *) 875 630 A, 1250 A )
R-HA41-117a.tif
14 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Product Range
Options for panels
l Available
Optionally available
– N ot applicable
y)
or
i.p. In preparation
eg
at
yc
uit
tin
ble
A)
on
M
ca
ec
e4
2 nd
vic
)
yp
VT
VT
p.
er
of
.t
(i.
in
in
fs
.g
ad
es
es
ion
so
(e
t-r
te
t-r
CT
os
at
CT
ns
as
as
ar
(L
pe
ri
sc
sc
T
sin
e
ep
eC
ry
ag
s te
-ty
)a
)a
re
pr
go
olt
as
ble
r re
st-
ole
ole
ble
ble
in
te
ph
dv
ea
ca
ca
ca
-p
-p
ca
ls
ca
e-
te
ne
(2
(1
as
as
rg
2 nd
C
re
3 rd
Ra
LS
Su
Pa
VT
VT
CT
Th
CT
1 2 3 4 5 6 7 8 9 10 11 Panel type
l l*) l l (up to 17.5 kV) – (up to 17.5 kV) 24 kV R
LSC 2
l l*) l l l l – 24 kV R1
l – l – – – – 24 kV T
LSC 2
l – l – – – – 24 kV T1
l l l (up to 17.5 kV) – (up to 17.5 kV) 24 kV K
LSC 1
l l l l l – 24 kV K1
i.p. l l l (up to 17.5 kV) – (up to 17.5 kV) 24 kV K *)
LSC 1
i.p. l l l l l – 24 kV K1 *)
l l l l l l 24 kV L
LSC 2
l l l l l l l*) 24 kV L1
i.p. l l l l l – 24 kV L1(r) *)
i.p. l l l l l – 24 kV L2(r) *)
LSC 2 24 kV L1(w) *)
i.p. l l l l l –
i.p. l l l l l l 24 kV L2(w) *)
– l l l l – 24 kV D *)
LSC 2 24 kV D1
i.p. l l l l l –
l l – – – – LSC 2 24 kV R(T)
l – – – – – – LSC 2 24 kV T(T)
l l l – l l – – – LSC 2 24 kV L(T)
l l l – l l – – – LSC 2 24 kV L1(T)
i.p. l l – l l – – – LSC 2 24 kV L1(r, T)
i.p. l l – l – – – LSC 2 24 kV L1(w, T)
– l – l – – – LSC 2 24 kV D(T) *)
i.p. l – – – – LSC 2 24 kV D1(T)
l – l – l – – – 24 kV M
l – l l – 24 kV M(-K)
l – l – l – – – LSC 1 24 kV M(-B)
l – l l – 24 kV M(-BK)
l – l l l – 24 kV M(KK)
l – – – l – – – 17.5 kV M(VT)
l – – – l – – – 24 kV M1(VT)
LSC 2 17.5 kV M(VT-F)
l – – – l – – –
l – – – l – – – 24 kV M1(VT-F)
i.p. – – – l l – – 12 kV M(PT) *)
LSC 2 12 kV M(PT) *)
i.p. – – – l l – –
l – l – l – – – LSC 1 24 kV H
i.p. – – – – l – – – 24 kV E
LSC 1 24 kV E1 *)
– – – – – l – – –
24 kV R(T) + H ) In preparation
l – – l l – – –
*) On request
24 kV 2 x R(T)
l – – – – – 1) Panel type:
Metal-clad
l – – – – – – – – LSC 1 12 kV CC *)
2) Type designation
of vacuum
circuit-breaker
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 15
Product Range
Product range overview
R-HA41-118a.tif
Column No.
Ring-main panel 1) as feeder R 375
Cable panel R1 500
type K as transfer R(T) 375
R-HA41-141.tif
16 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Product Range
Equipment features
)
)2
l Basic equipment
h)
h1
itc
itc
h
sw
Additional equipment
ac
2N itch
sw
)
)7
Ce
i ng
(option), further
)2
O+ sw
ion
th
h1
si t
er
2N g
ar
additional equipment
h
N in
itc
ov
re
po
itc
PE arth
)
)
sw
tc
er 3
(o
w
7
ee
on request
)
)2
2)
s
2)
en
dO fe
hr
ion
ing
)
h1
1)
ak
er
1)
F”
tm
o
t
– Not available
ak
ro
e
sit
OF
t ch
tch
r th
itc
r
ar
r
ED -p
b
e
itc
ke
po
”/ “
it-
r
sw
p
n
wi
wi
ea
e
b
m
ea
s
a
sw
OS ak
e-
it-
cu
ON
i
ns
or
co
on
re
br
CL m
a
ion
cu
cir
)2
ing
itio
ch
)
th
nt
-p al
it-
iti
)2
e
or nd
cir
gy
h1
sit
l
ee ric
me
m
e
cu
r th
os
ab
1
m en
os
or
e
:F ha
r tm
er
uu
m
o
hr ct
c
h
c
r
p
rf
-p
c
u u we
ea
pla
en
ng
itc
e-
uu
c
r
ele
NG itc
/
i
ac
ee
ve
sw
to
pa
on
re
d-
ati
sw
of
w
ac
r
nv
e
hr
in
ica
er
co
to
om
te
cti
h
dv lb
re
ns
ion
ro
er
rv
rt
ov
ica
ed
ed
ion
o
ei
t
ind
2) ar n
s to
al)
nt
ne
c
an ne
op
p
r
lc
I
tio em
EA itio
fo
tch h e tio
r
a
fo
fo
sit
H
rc
e-
th
k
s
e
ind
n
sit
on
na
) pa
T
oc
a
f
r
r tm
ak
r
ism
ice
wi wit osi
mi
po
m
sm
to
nd os
ica r r
to
e
(fo
n
po
ec
rl
l
rm
nis
h1 r
m
re
ult
mo
r a e-p
ter
ind ) fo
e-
n s CB h p
rv
en
ps
itc ake
i
an
pa
ve
e-
r
r
se
th
re
se
ed
to
fa
te
ha
ha
m
r tm
fo
cto re
ch
on
m
itio V tc
e
co
ice O
s w - b re
th
lea
t
o
et
ica
h-
hr
cla
n
at
ne r th
en
ec
ec
wi
as
or
r v (1N
co
me
ut
red
ck
nt
t
pa
rt
r
er
tch
re
y -f
ow
m
m
ind
-p f 3A r s
r
ipm
fo
k-o
he
ion it
ble
ble
ea
co h fo
a
e
op
o
om
ing
s i t rc u
wi
-se h
ree o fo
nt
br
m
ad
ng
ing
wi
ef
ut
ind
nic
_
loc
or itc
ed
ca
or
ca
qu
t.-
t
g(
hu
dis tc
th ED” vice
rat
es
ec
re
k-o
le
r 4)
n
i
r
vic
at
at
po c
y -f sw
pa
nw
rg
.
h- wi
uit
ge
ye
ed
r
ab
tin
ing
c
s
e- in
ot
pe
al
fo
er
er
g
loc
de
ha
m
LO de
ve
as
as
itc s
os
lt a
lt a
nt
ad g
i rc
sc
nic
em
ea
ar
op
op
tio
lo
re k
th
ck
y
co
re l i n
gc
co
th rl o c
ing
ou
se
se
Sw iliar
“C ing
ing
nd
vo
vo
t-c
lh
il a
ua
ha
rlo
ar
l-r
ec
or
or
na
S
ble
lea
lea
rin
or
em
w-
w-
co
ne
-e
or
ck
ca
ck
n
os
sp
ec
te
ra
ot
ot
te
Sig
Ma
Flo
Au
De
Ca
Sh
Sp
Re
Re
Se
Lo
Lo
Lo
Lo
Lo
Pa
In
C-
Pr
In
In
Cl
M
M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Panel type
R
l1) l – l l – l – – – – – –
R1
l1) l – – l – l – – – – – – – – – R(T)
T
l l – l l l – l l – – – –
T1
K
– – l l l – – – – – – – – – – – – – –
K1
K *)
l l l l l – l – – – – – – – – l –
K1 *)
L
l2) l – l l l l – – –
L1
L(T)
l2) l – – l l l – – – – – –
L1(T)
l2) l – l l l l – – 6) L1(r) *)
l2) l – – l l l – – – – – – 5) L1(r, T) *)
M
– – l – l – – – – – – – – – – – – – – – –
M(-B)
M(-K)
– – l l l – – – – – – – – – – – – – – –
M(-BK)
M(KK)
– – l l l – – – – – – – – – – – – – – –
M(PT) *
– – l – l – – – – – – – – – – – – – – – –
l1) l – – l – – – – – – – – – – M(VT)
l1) l – – l – – – – – – – – – – M1(VT)
l1) l – – l – – – – – – – – – M(VT-F)
l1) l – – l – – – – – – – – – M1(VT-F)
– – l – l – – – – – – – – – – – – – – – – – H
D1
l l – l l – l – – – – – –
D1(T)
l l – – l – l – – – – – – – – –
l – l – l – l – – – – – – – – – – – E
l – l – l – l – – – – – – – – – – – E1 *)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Panel type
*) On request
1) Three-position switch as three-position switch-disconnector 5) Not to be applied for versions with separate feeder earthing
2) Three-position switch as three-position disconnector switch in panel types L1(r), L1(w)
3) Type designation of the vacuum circuit-breaker 6) Inspection window is a standard equipment in panel types L1(r)
4) In special cases, deeper floor cover for panels with cable feeder required. for versions with separate feeder earthing switch at cable
Design of floor cover: Depending of direction of pressure relief 7) Or for earthing switch in panel type E
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 17
Product Range
Ring-main panels
to the
Option * right
Option Option Option: Capacitive voltage
Transfer detecting system
either-or to the
Option * left
Option
Cable-type current
transformer,
e.g. 4MC703 . . .
On request:
Option Option Three-phase current
transformer 4MC63 . . .
either-or
Option
Voltage transformer,
e.g. 4MR, 1-pole,
either-or
Voltage transformer,
e.g. 4MR, 2-pole,
Type R1 either:
cast-resin insulated
500 mm wide Version with
transformers
Option
Option
HA41-4051 eps
Option
Surge arrester
Type R1 or:
500 mm wide Version with
connection
fittings
P1 and P2 are
terminal designa-
tions of the current
* On request up to 12 kV transformer
18 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Product Range
Transformer panels and disconnector panels
Option*
Option Option* Option
Three-position
disconnector
either-or
Option*
Option
Option**
HV HRC fuse
On request:
Option
Earthing switch
Option Option
to the
right On request:
Option Option: Three-phase current
Transfer transformer 4MC63 . . .
to the
left
Voltage transformer,
e.g. 4MR, 1-pole,
cast-resin insulated
Type D(T)
375 mm wide
Cable (not included in
the scope of supply)
) In preparation
* On
*
O n request
** C able-type current transformer located partly
** Surge arrester
underneath the panel
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 19
Product Range
Cable panels
Option* Option*
HV HRC fuse
Option
either-or
Option*
either-or
Option*
Option Option
Capacitive voltage
detecting system
Type K Type K
375 mm wide 375 mm wide
Earthing switch
either-or
either-or
4MC703 . . .
Option Option
Option
Block-type current
transformer 4MA,
cast-resin insulated
Type K1 either: Type K1 either:
500 mm wide Version with 500 mm wide Version with
transformers transformers
Voltage transformer,
e.g. 4MR, 1-pole,
cast-resin insulated
Option Option
either-or
Option Option
Option Option
2nd cable (not included
in the scope of supply)
HA41-4051 eps
P1 and P2 are
terminal designa-
tions of the current
* On request transformer
20 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Product Range
Busbar earthing panels, lateral cable connection box and panel top box
Option
Standard:
With
Voltage transformer,
e.g. 4MR, 1-pole,
cast-resin insulated
Earthing switch
HA41-4051 eps
Type E Type -EB Type CC
375 mm wide 375 mm wide, or 500 mm wide 300 mm wide (up to 12 kV)
Height: 350 mm or 550 mm for end panels type: R, T, L
Cable (not included
in the scope of supply)
On request: On request:
Busbar earthing panel Panel top box as
with voltage transformer voltage transfomer box
Option
Option
On request:
Panel top box as
cable connection box
Type -KB
375 mm wide, or 500 mm wide
Height: 350 mm or 550 mm
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 21
Product Range
Circuit-breaker panels
either-or
either-or
Option * Option
Option Option
Capacitive voltage
detecting system
either-or
Option Option Option Option
Three-phase current
transformer 4MC63 . . .
either-or
Option Option
Option Option
Voltage transformer,
e.g. 4MR, 1-pole,
cast-resin insulated
Type L1 With vacuum circuit-breaker, Type L1(T) With vacuum circuit-breaker,
750 mm wide fixed-mounted 750 mm wide fixed-mounted
Voltage transformer,
e.g. 4MR, 2-pole,
cast-resin insulated
Additional cables
(not included in the
scope of supply)
Surge arrester
HA41-4051 eps
P1 and P2 are
) In preparation terminal designa-
* On request: Combination CT and VT tions of the current
transformer
22 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Product Range
Panel combinations: Bus sectionalizer panels
Option
Panel type H attached
Option Three-position
switch-disconnector
Option
on the left
Option
Three-position
disconnector
Option Option
Panel type H attached
Block-type current
Option Option transformer 4MA,
Option Option cast-resin insulated
on the right
Option Option Three-phase current
transformer 4MC63 . . .
On request:
For panel type: R(T)
Types: L(T) H Types: R(T) H
500 mm wide 375 mm wide 750 mm total width
in combination with bus riser panel, up to 1250 A ) with 2 three-position switch-disconnectors Voltage transformer,
e.g. 4MR, 1-pole,
Option Option With
cast-resin insulated
vacuum
Option Option
circuit-
HA41-4051 eps
on the left
Fixed earthing point
Option Option
vacuum
circuit- Option
fixed-
mounted Option
either-or
either-or
) 1250 A in
Option Option Option preparation
P1 and P2 are
Types: L1(T) H Types: R(T) R(T) terminal designa-
750 mm 375 mm 750 mm total width tions of the current
wide wide transformer
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 23
Product Range
Billing metering panels
Billing metering panels Billing metering panels Billing metering panels Panel design of M:
630 A, 800 A, 1250 A 630 A, 800 A, 1250 A 630 A, 800 A, 1250 A
Standard for additional transformers for busbar connection
Option
M
Option Option Option
either-or
Option
Option Option Option M(-B)
either-or *
Option
Capacitive voltage
Option detecting system
Option Option Option
either-or
Option
Voltage transformer,
Option Option Option e.g. 4MR, 1-pole,
either-or *
cast-resin insulated
Option or:
On request:
Option
age transformers
either-or
Option
Option
Voltage transformer,
e.g. 4MR, 1- or
2-pole, cast-resin
Option insulated
Scheme 3 Scheme 3 Scheme 3
Type M Standard **: Type M Standard **: Type M(-B) Option:
750 mm wide Transfer to 750 mm wide Transfer to the right 750 mm wide Transfer to Fixed earthing point
the right the left
HA41-4051 eps
Option
Option Option Option Fixed earthing point
P1 and P2 are
Option Option Option
either-or *
terminal designa-
Option
tions of the current
transformer
Option
* On request
** Option:
Scheme 4 *** Scheme 4 *** Scheme 4 *** Transfer to the
left
Type M Standard **: Type M Standard **: Type M(-B) Option:
*** Transformer
750 mm wide Transfer to 750 mm wide Transfer to the right 750 mm wide Transfer to
terminals
the right the left
interchanged
24 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Product Range
Billing metering panels
Option Option
M(-BK)
Capacitive voltage
Scheme 1 Scheme 1 detecting system
Type M(-K) Standard **: Type M(-BK) as right or left
750 mm wide Transfer to the right 750 mm wide end panel
Block-type current
transformer 4MA,
Option
Option cast-resin insulated
HA41-4051 eps
Transformer
terminals Fixed earthing point
Scheme 2 interchanged Scheme 2
Type M(-K) Standard **: Type M(-BK) as right or left
750 mm wide Transfer to the right 750 mm wide end panel
Option Option
Option Option
Scheme 3 Scheme 3
Type M(-K) Standard **: Type M(-BK) as right or left
750 mm wide Transfer to the right 750 mm wide end panel
1) On request:
Option Option
As single metering
* Connection for
2nd cable possible
** Option:
Transfer to the left
Scheme 4 Scheme 4
P1 and P2 are
Type M(-K) Standard **: Type M(-BK) as right or left
terminal designa-
750 mm wide Transfer to the right 750 mm wide end panel
tions of the current
transformer
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 25
Product Range
Busbar voltage metering panels and bus riser panels
Option Option
Option
HV HRC fuse
Option
Capacitive voltage
detecting system
Option
Scheme 1
Earthing switch
Type M(VT) ** Type M1(VT) Type H *
375 mm wide 500 mm wide 375 mm wide
Block-type current
Option
transformer 4MA,
cast-resin insulated
Option
Option
Voltage transformer,
Option e.g. 4MR, 1- or 2-pole,
cast-resin insulated
Option
Option
Voltage transformer,
Scheme 2 e.g. 4MR, 1-pole
Type M(VT-F) ** Type H * cast-resin insulated
375 mm wide 375 mm wide
HA41-4051 eps
Option
Fixed earthing point
Option
Option
Option
Option
Option
Scheme 3
Type M1(VT-F) Type H *
500 mm wide 375 mm wide
Option
Option
On request:
Switch-disconnector panels
Three-position
for auxiliary transformer
switch-disconnector
Option
HV HRC fuse
Capacitive voltage
Option
detecting system
Voltage transformer,
e.g. 4MR, 1- or 2-pole,
Option cast-resin insulated
Option
on request
Voltage transformer,
e.g. 4MR, 1-pole
cast-resin insulated
HA41-4051 eps
Option
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 27
Product Range
On request: Circuit-breaker panels
nection
either-or
either-or
of max.
Option Option ** Option Option **
2 cables Three-position
disconnector
Option Option Option Option
Cable-type current
either-or
either-or
either-or
either-or
Option Option transformer,
Option Option
Option Option e.g. 4MC703 . . .
Block-type current
Type L1(r) With vacuum circuit-breaker, Type L1(w) With vacuum circuit-breaker,
transformer 4MA,
750 mm wide type 3A_, removable 750 mm wide type 3A_, withdrawable
cast-resin insulated
Option Option Option Option
for con- for con-
either-or
either-or
either-or
either-or
either-or
either-or
Option Option
Option Option
Cable (not included in
the scope of supply)
Type L2(r) With vacuum circuit-breaker, Type L2(w) With vacuum circuit-breaker,
875 mm wide type 3A_, removable 875 mm wide type 3A_, withdrawable
Additional cables
(not included in the
as transfer panel for attachment as transfer panel for attachment scope of supply)
to panel types M, ... to panel types M, ...
Transfer
Transfer
Option Option Option Option possible
possible Surge arrester
only to
only to
the right
the right
Option Option Option Option
Capacitive voltage
detecting system
either-or
either-or
Option Option
Make-proof
earthing switch
HA41-4051 eps
Type L1(r, T) With vacuum circuit-breaker, Type L1(w, T) With vacuum circuit-breaker,
750 mm wide type 3A_, removable 750 mm wide type 3A_, withdrawable
Fixed earthing point
28 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Product Range
Panel combinations
4
Panel combinations 630 A Vacuum circuit-breaker
Option Option (type “CB-f”)
Option Option
Three-position
switch-disconnector
either-or
Option Option
Three-position
either-or
Three-phase current
Further panel combinations available: Rated current transformer 4MC63 . . .
On request:
For example: Total width: Ir (A)
For panel type: R(T)
L(T) + R(T) 875 mm up to 630 A
L(T) + H 875 mm up to 630 A
L1(T) + D1(T) 1250 mm up to 1250 A Voltage transformer,
e.g. 4MR, 1-pole,
cast-resin insulated
HA41-4051 eps
Voltage transformer,
e.g. 4MR, 2-pole,
cast-resin insulated
P1 and P2 are
terminal designa-
tions of the current
transformer
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 29
Design
Panel design (examples)
Type R Section Type T Section
Billing metering panel Legend for pages 30 and 31 (contin. on page 31)
1 Option: Low-voltage compartment
2 Niche for optional low-voltage equipment,
cover can be unscrewed
3 Option: CAPDIS-Sx voltage detecting system
4 Option: Short-circuit /earth-fault indicator
5 Option: Ready-for-service indicator
for switching device
6 Position indication for load-break
function “CLOSED – OPEN”
7 Position indication for earthing
function “OPEN – EARTHED”
8 Feeder designation label
9 Mimic diagram
10 Option: Sockets for capacitive voltage
detecting system (depending on arrangement)
10.1 for feeder
10.2 for busbar
11 Option: Momentary-contact rotary control
switch “CLOSED – OPEN” for motor operating
mechanism with local-remote switch for
three-position switch-disconnector
12 Option: Locking device for three-position
switch-disconnector
13 Pressure relief device for switching device
14 Manual operation for the mechanism of
30 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Design
Panel design (examples)
Circuit-breaker panel (with vacuum circuit-breaker type CB-f NAR) Legend for pages 30 and 31
20 Bushing-type insulator for feeder
21 Terminal for HV HRC fuse assembly (with tripping)
22 C able bracket with cable clamps (option) for fastening
cables
23 Busbar
24 Spring charged indicator for stored-energy “OPEN”
25 Spring-operated mechanism for three-position
switch-disconnector
26 Spring-operated / stored-energy mechanism for
three-position switch-disconnector
27 Three-position switch-disconnector
28 Cable connection
29 Cable compartment cover
30 Earthing connection (for location, see dimension
drawings)
31 Earthing switch for cable connection
32 Inspection window
33 Post insulator
34 Operation for stored-energy mechanism
– stored-energy “OPEN” (red)
– stored-energy “CLOSED” (black)
35 Option: HV HRC fuse-link (e = 292 mm or 442 mm)
36 Option: Heating in the panel
37 Option: Secondary protection for voltage transformer
38 Cover, screwed on
Type L1 (750 mm) Section
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 31
Design
Operation (examples)
Control board
Front of ring-main feeder, type R
The control boards are function-related. They integrate
operation, mimic diagram and position indication. Further-
more, the respective indicating, measuring and monitoring
equipment as well as locking devices and control elements
(e.g. local-remote switch) are arranged there according to
the panel type and version. The ready-for-service indicator
and rating plates are also located at the operating front.
Operation is identical for transformer and circuit-breaker
feeders. First, the operating mechanism must be charged;
then, closing / opening is done through separate pushbut-
tons. The condition of the energy store is indicated.
All actuating openings are functionally interlocked against
each other, and are optionally lockable. The operating lever Panel width: 375 mm
carries two plug inserts, separately for the disconnecting
Front of transformer feeder, type T
and earthing function.
Panel width: 375 mm
Front of circuit-breaker feeder, type L
1 Manual operation of load-break function (R, T) or disconnecting
function (L)
2 Locking function (option for ring-main feeders)
3 Manual operation of earthing function
4 Panel designation label
5 Position indicator for switch-disconnector
6 Position indicator for earthing switch
7 Sockets of capacitive voltage detecting system
8 “Fuse tripped” indicator Panel width: 500 mm, with circuit-breaker type CB-f NAR *)
9 ON pushbutton for transformer or circuit-breaker function
10 OFF pushbutton for transformer or circuit-breaker function
11 Manual operation for "spring charging"
12 “Spring charged” indicator
13 Position indicator for circuit-breaker
14 Ready-for-service indicator
15 Operations counter
16 Preselection for manual charging of circuit-breaker panels
*) AR = Automatic reclosing
NAR = Non automatic reclosing Panel width: 500 mm, with circuit-breaker type CB-f AR *)
32 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Components
Three-position switch
Features
• Switch positions:
CLOSED – OPEN – EARTHED Three-position switch-disconnector
• Switching functions as general-purpose switch-disconnector
(class E3) according to
–– IEC / EN 62271-103 / VDE 0671-103 *)
–– IEC / EN 62271-102 / VDE 0671-102 *)
• Designed as a three-position switch with the functions
–– Switch-disconnector and
–– Make-proof earthing switch
R-HA41-132a.tif
• Operation via rotary bushing welded gas-tight into the
front of the switching-device vessel
• Climate-independent contact in the gas-filled
switching-device vessel
• Maintenance-free according to IEC / EN 62271-1 / VDE 0671-1
• Individual secondary equipment
• No cross insulation between phases. Busbar
The operating shaft forms one unit together with the three OPEN
contact blades. Due to the arrangement of the fixed con-
tacts (earth – busbar), it is not necessary to interlock the
CLOSE and EARTHING functions.
During the closing operation, the operating shaft with the Moving contact
OPEN / CLOSE CLOSE OPEN
Opening operation
During the opening operation, the arc is caused to rotate
by the arc-suppression system. This rotation movement
prevents the development of a fixed root.
The isolating distance in gas established after breaking
OPEN / EARTH OPEN EARTH
fulfills the conditions applicable to isolating distances in
accordance with
– IEC / EN 62271-102 / VDE 0671-102 *)
and
– IEC / EN 62271-1 / VDE 0671-1 *).
Due to the arc rotation caused by the arc-suppression
system, both load currents and minor no-load currents are Switch positions: CLOSED OPEN Feeder EARTHED
safely interrupted.
as
Earthing operation three-position
switch-
The EARTHING operation is implemented by changing from
disconnector
the “OPEN” to the “EARTHED” position. up to 630 A
as
three-position
disconnector
up to 1250 A
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 33
Components
Operating mechanisms for the three-position switch
Legend
R = Ring-main feeder
T = Transformer feeder
L = Circuit-breaker feeder
M(VT), M(VT-F) = Busbar voltage metering panel
D = Disconnector feeder
34 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Components
Equipment (optional)
up to 230 10 24 10 10
48 10 9
60 9 7
R-HA41-124a.tif
110 5 4
240 2.5 2
Panel type R:
Operating mechanism for three-position switch, and
Rated switching capacity
low-voltage niche with terminals and MCB's (options)
Rated insulation level 250 V AC / DC
Insulation group C according to VDE 0110
Continuous current 10 A
Making capacity 50 A
R-HA41-144.tif
Abbreviations:
NO = Normally open contact Panel type L:
NC = Normally closed contact Operating mechanism for three-position switch,
and circuit-breaker type “CB-f NAR“
** Depending on the secondary equipment of the three-position switch
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 35
Components
Vacuum circuit-breaker
Operating mechanism
The operating mechanism assigned to a circuit-breaker
feeder consists of the following components:
• Operating mechanism for circuit-breaker
• Operating mechanism for three-position disconnector
• Motor operating mechanism (optional)
• Position indicators
• Pushbuttons for CLOSING and OPENING the circuit-breaker
• Operations counter (optional)
• Interlocking between circuit-breaker and disconnector.
Trip-free mechanism
The vacuum circuit-breaker is fitted with a trip-free mecha-
nism according to IEC / EN 62271-100 / VDE 0671-100 *.
In the event of an opening command being given after a
closing operation has been initiated, the moving contacts
return to the open position and remain there even if the
closing command is sustained. This means that the contacts Explanations:
are momentarily in the closed position, which is permissible • Design option
according to the mentioned standard. – Not available
*) AR = Automatic reclosing
NAR = Non automatic reclosing
) D esign of circuit-breaker:
• CB-r as removable
* For standards, see page 84 • CB-w as withdrawable
36 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Components
Secondary equipment of the vacuum circuit-breaker
Max. number of
short-circuit breaking operations
n = 30
n = 50
Max. number of
short-circuit breaking operations
n = 20
38 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Components
Secondary equipment of the vacuum circuit-breaker, busbars
Busbars
• Safe-to-touch due to metallic enclosure Busbars
• Metal-clad busbar compartment 1 Busbar
• Three-pole design, bolted from panel to panel 2 Bushing-
1 type insu-
• Easy switchgear extension
lator for
• Made of copper: Round E-Cu. busbar
R-HA41-125a.tif
2
1 Busbar
2 Bushing-
1 type insu-
lator for
busbar
R-HA41-140.tif
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 39
Components
Cable connection
General features
Cable connection (examples)
• Connecting lugs for sealing
L1 L2 L3 L1 L2 L3
ends arranged one behind the
other
• Uniform cable connection
height for the respective
panel types
• With cable bracket, 5
e.g. type C40 according to 1
4
DIN EN 50024 2
3
• Access to the cable compart-
ment only if feeder has been
R-HA41-126a.tif
R-HA41-127a.tif
isolated and earthed.
Special features
– In cable panels Ring-main panel type R Cable compartment with
– In ring-main panels Cable compartment as delivered cable sealing ends (options: A, B, C 1)
and D 1), see below)
– In circuit-breaker panels
• For thermoplastic-insulated
L1 L2 L3 L1 L2 L3
cables
• For paper-insulated mass-
impregnated cables with
adapter systems
• For connection cross-sections
up to 300 mm2
• Cable routing downwards.
– In transformer panels
• For thermoplastic-insulated
7
cables 6
8
R-HA41-129a.tif
R-HA41-128a.tif
Cable sealing end, e.g. for panel types R..., K…, D…, M(-K), M(-BK), L… and T...2) Connection height ***
(for connection heights of cables, see opposite dimension drawings) of cables above
Make Type Cross-section in mm2 floor or above
lower edge of panel:
Single-core thermoplastic-insulated cables for ≤ 12 kV (6 / 10 kV); for IEC standard *
Euromold AIN 10, AFN 10 *) 25–300 (500 **)
17 TTGI •) 25–300 (500 **)
ITK-212 •) 50–300 (400 **)
Prysmian Kabel und Systeme ELTI mb-1C-12 35–240
ELTI-1C-12 25–300
Tyco Electronics Raychem IXSU-F 16–300 (500 **)
MVTI-31xx- 25–300 (400 **)
EPKT 2) 16–300
Lovink-Enertech IAEM 10 25–300
IAES 10 25–300 (500 **)
3M 92-EB 6x-1 35–300 (400 **) Panel type R...
Südkabel SEHDI 10.2 35–300 (500 **)
nkt cables TI 12 25–240
TO 12 25–300 (500 **)
Three-core thermoplastic-insulated cables for ≤ 12 kV (6 / 10 kV); for IEC standard *
Euromold AIN 10 •) 25–300 (500 **)
17 TTGI •) 35–300 (500 **)
Prysmian Kabel und Systeme ELTI-3C-12 25–300 Panel type L...
Tyco Electronics Raychem IXSU-F33xx 16–300 (500 **)
Lovink-Enertech IAES 10 25–300
GHKI 16–300 (400 **)
Single-core thermoplastic-insulated cables for > 12 kV to ≤ 24 kV (12 / 20 kV) •)
Euromold AIN 20, AFN 20 20–300 (630 **)
24 TTGI 25–300 (500 **)
36 MSC 3) 95–300 (500 **)
36 MSC (Option 4)) 95–300 (500 **) Panel type T...
ITK-224 25–240
Dimension a
Prysmian Kabel und Systeme ELTI mb-1C-24 35–240
~ 384 mm:
ELTI-1C-24 25–300
At fuses with e = 442 mm
Tyco Electronics IXSU-F 25–300 (500 **) (standard for 24 kV)
MVTI-51xx- 25–300 (400 **) ~ 534 mm:
EPKT 16–300 (500 **) At fuses with e = 292 mm
Lovink-Enertech IAEM 20 25–300
IAES 20 25–300 (500 **)
Note:
3M 93-EB 6x-1 50–300 (400 **)
Depending on make and
Südkabel SEHDI 20.2 35–300 (500 **)
type, the termination of
SEI 24 25–240 the cable sealing end
nkt cables TI 24 25–240 (= shield earth) for the 3-core
TO 24 25–300 (500 **) thermoplastic-insulated cable
and the fitted cable clamp
Three-core thermoplastic-insulated cables for > 12 kV to ≤ 24 kV (12 / 20 kV) •) (option) may be located
Euromold SR-DI 24 3) 35–300 (500 **) underneath the panel in the
cable basement. This must be
AFN 10 35–300
taken into account in panels
Lovink-Enertech GHKI 25–300 (500 **)
with floor cover (option).
Tyco Electronics Raychem o.r. IXSU-F53xx o.r.
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 41
Components
Cable cross-sections
Cable cross-sections
Panel type Panel width Version Connected cables Transformer combination in the connection
x connection cross-section compartment
number x mm2
for rated voltage Current transformer
12 kV 17.5 kV 24 kV 4MC70 4MA 4MR
K 375 Standard 1 x 300 1 x 300 1 x 300
On request 2 x 300 2 x 300 2 x 300
K1 500 Standard 1 x 300 1 x 300 1 x 300
Option 2 x 400 2 x 300 2 x 300
R, D 375 Standard 1 x 300 1 x 300 1 x 300
On request 2 x 300 2 x 300 2 x 300
R1, D1 500 Standard 1 x 300 1 x 300 1 x 300
Option 2 x 300 2 x 300 2 x 300
L 500 Standard 1 x 300 1 x 300 1 x 300
Option 2 x 240 2 x 240 2 x 240 – –
L1 750 Standard 1 x 300 1 x 300 1 x 300
Option 2 x 300 2 x 300 2 x 300
M(-K), 750 Standard 1 x 400 1 x 300 1 x 300
M(-BK) Option 3 x 400 3 x 300 3 x 300
M(KK) 750 Standard 1 x 400 1 x 300 1 x 300
Option 2 x 300 2 x 300 2 x 300
L1(r), 750 Standard 1 x 300 1 x 300 1 x 300 –
L1(w) Option 2 x 300 2 x 300 2 x 300 –
CC 300 Standard 1 x 240 1 x 240 – – – –
possible – not possible
Cable fixing:
Depending on the cable type (1-core cable, 3-core cable) or the associated panel type and its components,
the cable may also be fixed in the cable basement: (for local installation):
1-core cable 3-core cable
(= Option)
connection: From the
mounted cable clamp 5)
Optionally, a deep floor cover is also possible:
42 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Components
HV HRC fuse assembly
• Requirements according IEC 62271-105 fulfilled as
HV alternating current switch-fuse combination
• Selection of HV HRC fuses for transformers
• Fuse replacement possible only when feeder is earthed Control board of a transformer feeder
R-HA41-129a.tif
Replacement of HV HRC fuse-links (without any tools)
• Isolating and earthing of the transformer feeder
• Opening the connection compartment cover HV HRC fuses in transformer panel type T
• Subsequent manual replacement of the HV HRC fuse-link. Side view
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 43
Components
Allocation of HV HRC fuses and transformers
Recommended HV HRC fuses make SIBA for switchgear type SIMOSEC
44 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Components
Allocation of HV HRC fuses and transformers
Recommended HV HRC fuses make SIBA for switchgear type SIMOSEC
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 45
Components
Allocation of HV HRC fuses and transformers
Recommended HV HRC fuses make SIBA for switchgear type SIMOSEC
46 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Components
Allocation of HV HRC fuses and transformers
Recommended HV HRC fuses make SIBA for switchgear type SIMOSEC
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 47
Components
Three-phase current transformer 4MC63
Features
Three-phase current transformer 4MC63 ... installed on
• According to
bushing-type insulators
IEC 61869-2 /
DIN EN 61869-2 *)
R-HA41-142.tif
R-HA41-044.eps
• D esigned as a three-pole
ring-core current trans-
former
• Free of dielectrically
stressed cast-resin parts
(due to design)
• Insulation class E
• Inductive type Technical data Three-phase current transformer 4MC63 60 (Standard type) 1)
• Climate-independent for IN ≤150 A for IN ≤ 400 A for IN ≤ 1000 A
for ID = 630 A for ID = 630 A for ID = 1250 A
• Secondary connection by
means of a terminal strip
in the panel. Primary data
Highest voltage 0.72 kV 0.72 kV 0.72 kV
Installation for equipment Um
Rated current INA 150 100 75 50 400 300 200 1000 750 600 500
• Arranged outside the
Rated short-duration 3 kV 3 kV 3 kV
switching-device vessel on power-frequency
the bushings withstand voltage
(winding test)
• Factory-assembled Rated short-time 25 kA / 1 s, 2 s 1) 25 kA / 1 s, 2 s 1) 25 kA / 1 s, 2 s 1)
• Mounting location: thermal current Ith or 20 kA / 3 s or 20 kA / 3 s or 20 kA / 3 s
48 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Components
Cable-type current transformers 4MC70 33 and 4MC70 31
Features
• According to IEC 61869-2 / Cable-type current transformer Cable-type current
DIN EN 61869-2 *) 4MC70 33, 4 overall heights transformer 4MC70 31
• D esigned as a single-pole
R-HA41-024a eps
ring-core current trans-
R-HA41-025 eps
former
H
• Climate-independent
H
• Free of dielectrically
stressed cast-resin parts
(due to design) On request:
Cable-type current transformer
• Insulation class E
R-HA41-027.eps
• Inductive type
• Secondary connection by
means of a terminal strip
inside the panel. B
Application
• For circuit-breaker panels Technical data Cable-type current Cable-type current
type L... transformer 4MC70 33 transformer 4MC70 31
• For ring-main panels
type R... Primary data
Highest voltage 0.72 kV 0.72 kV
• For transformer panels
for equipment Um
type T...
Rated current IN 20 A to 600 A 50 A to 600 A
Dimensions
Overall height H 2) mm 65 1) 110 1) 170 1) 285 1) 89
Outside diameter 150 mm 85 mm x 114 mm
Inside diameter 55 mm 40 mm
For cable diameter 50 mm 36 mm
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 49
Components
Current transformers 4MA7 and voltage transformers 4MR for air-insulated billing metering panels
Features Application
Current transformer 4MA7 • For panel types:
• According to IEC 61869-2 / DIN EN 61869-2 *) –– Billing metering panels type M...
• Dimensions according to DIN 42600-8 –– Bus riser panel type H
• D esigned as a single-pole indoor block-type current –– Busbar voltage transformer panel types M(VT), M(VT-F), L …
transformer • For mounting at the feeder.
• Cast-resin insulated
• Insulation class E
R-HA41-030a eps
R-HA41-029a eps
• Secondary connection by means of screw-type terminals.
Voltage transformer 4MR
• According to IEC 61869-3 / DIN EN 61869-3 *)
• Dimensions according to DIN 42600-9 (small model)
• Designed as an indoor voltage transformer:
–– Type 4MR, single-pole
–– Option: Type 4MR, two-pole
• Cast-resin insulated Current transformer 4MA7, Voltage transformer 4MR14,
• Insulation class E single-pole single-pole
• Secondary connection by means of screw-type terminals.
Technical data
Current transformer 4MA7, single-pole (other values on request)
Primary data
Highest voltage for equipment UmkV 3.6 7.2 12 12 17.5 24
Rated short-duration power-frequency withstand voltage UdkV 10 20 28 42 38 50
Rated lightning impulse withstand voltage UpkV 20 60 75 75 95 125
Rated current INA 20 to 1200
Rated short-time thermal current IthkA up to 20 kA / 3 s, or up to 25 kA / 1 s
Rated continuous thermal current ID up to 1.0 x In (option: 1.2 x In)
Rated dynamic current Idyn max. 2.5 x Ith
Secondary data
Rated current A 1 or 5
Measuring core Class 0.2 0.5 1
Overcurrent factor without FS5 FS10
Rating VA 2.5 to 30
Protection core Class 5 P or 10 P
Overcurrent factor 10
RatingVA 2.5 to 30
50 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Components
Indicating and measuring equipment
Ready-for-service indicator
Gas monitoring
Features
• Self-monitoring; easy to read
• Independent of temperature and pressure variations
• Independent of the site altitude
• Only responds to changes in gas density
• Option: Alarm switch “1 NO” for remote electrical indication.
Mode of operation
Indicator on control board: 1 Green indication:
For the ready-for-service indicator, a gas-tight measurement Ready for service Ready for service
box is installed inside the switching-device vessel. (red indication:
Not ready for service)
A coupling magnet, which is fitted to the bottom end of
the measurement box, transmits its position to an outside
armature through the non-magnetizable stainless-steel
switching-device vessel. This armature moves the ready-
for-service indicator of the switchgear.
While changes in the gas density during the loss of gas,
which are decisive for the dielectric strength, are displayed,
temperature-dependent changes in the gas pressure are
not. The gas in the measurement box has the same
temperature as that in the switching-device vessel. Stainless-steel vessel Ready-for-service
The temperature effect is compensated via the same filled with SF6 gas indicator
pressure change in both gas volumes.
Ready-for-service indicator
Principle of operation 2 Measurement box
of gas monitoring with 3 Magnetic coupling
ready-for-service indicator
R-HA41-122b.tif
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 51
Components
Indicating and measuring equipment
Short-circuit / earth-fault indicators
make Horstmann
Short-circuit / earth-fault indicators (option)
R-HA40-136.tif
Ring-main, cable, transformer and circuit-breaker feeders
can optionally be equipped with short-circuit or earth-fault
indicators in different designs.
The equipment features are shown in the table on page 53.
Short-circuit and earth-fault indicators reduce the down-
times of a power system by limitation of fault locations
in medium-voltage systems. ALPHA E
R-HA40-137.tif
Local ring-main unit
Short-circuit indicator has picked up
Short-circuit indicator has not picked up
SIGMA
Response of protection device with tripping
Basic functions
• Adjustable pickup values
• Phase-selective fault indication
• Reset of fault indication: ComPass B
manually, automatically, from remote
• Remote indication with relay contacts.
Short-circuit / ALPHA ALPHA SIGMA SIGMA SIGMA SIGMA ComPass ComPass ComPass ComPass EARTH /
earth-fault indicators M E F+E D D+ A AP B BP EARTH ZERO
Horstmann
Function
Short-circuit indication x x x x x x x x x x
Earth-fault indication x x x x x x x x
Indication of direction,
short circuit / earth fault x x x x
Undervoltage and
overvoltage indication x x
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 53
Components
Indicating and measuring equipment
R-HA40-141.tif
can optionally be equipped with short-circuit or earth-fault
indicators in different designs. The equipment features are
shown in the opposite table.
The three most common types of faults in medium-voltage
systems are earth faults in cables and switchgear, faults
and overloads of distribution transformers, as well as short
circuits in cables and switchgear. For fast fault location and IKI-20
minimization of downtimes, electronic fault indicators are
used:
• Selective fault detection, and thus minimization of
downtimes
R-HA40-142.tif
• Reliable fault detection through electronic
measured-value acquisition
• Remote indication of fault events and measured values.
6. Short-circuit-to-earth indicator
–– Short-circuit-to-earth detection in systems with
impedance-earthed neutral or temporarily impedance
earthed-neutral
–– Adjustable.
IKI-10light
54 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Components
Indicating and measuring equipment
Short-circuit / IKI- IKI- IKI- IKI-20PULS IKI-20C IKI- IKI-22 IKI- IKI- IKI- IKI- IKI-
earth-fault indicators 20B 20T 20U 20CPULS 50_1F 50_1F_ 50_2F 50_2F_ 10-light-P
Kries EW_PULS EW_PULS
Function
Short-circuit indication x x x x x x x x x x x
Earth-fault indication x x x x x x x
Short-circuit-to-earth
x x x x x x x x x x
indication 5)
Direction indication x x x x x
Applicable for the following neutral earthing options
Impedance x x x x x x x x x x
Solid x x x x x x x x x x
Isolated x x x x x x x x x x
Compensated x x x x x x x x x x
Pickup current
Short-circuit current 100, 200, 400, 600, 800, 1000, 400, 600, 100, 200, 300, 400, 600,
100 ... 1000 A (steps of 100 A)
2000 A 800, 1000 A 800, 1000, 2000 A
Earth-fault current Transient fault detection 4 ... 30 A (steps of 1 A)
Short-circuit-to-earth 20, 40,
40, 80, 100, 150 A 40, 80, 100, 200 A 40 ... 200 A (steps of 10 A)
current 5) 60, 80 A
Pulse location x x x x
Pickup time
Short-circuit current 60, 80, 150, 200 ms 100 ms 60, 80, 150, 200 ms 60 – 1600 ms
Short-circuit-to-earth 70, 250
60, 80, 150, 200 ms 100 ms 60, 80, 150, 200 ms 60 – 1600 ms
current 5) ms
Earth-fault current Pulse loca- Pulse loca-
Transient fault detection 400 – 3000 ms
tion tion
Reset
Manual x x x x x x x x x x x x
Automatic x x x x x x x x x x x x
From remote x x x x x x x x x x
Remote indication
Passing contact adjustable x x x adjustable
Maintained contact adjustable adjustable
Interface
RS485 / MODBUS x x x x
Power supply
Lithium battery x x x
External auxiliary voltage Only for transient fault
x x x Buffered for 6 h by internal capacitor x
detection
Current inputs
Phase current 3 3 3 3 3 3 3 3 3 6 6
Summation current 1 1 1 1 1 1 1) 0 2) 0 2) 0 2) 1
Voltage inputs
Via CAPDIS + Y-cable 3 3 6 6
Measuring function
Current x 4) x 4) x 4) x 4)
Voltage x 4) x 4) x 4) x 4)
Load flow direction x 4) x 4) x 4) x 4)
cos phi x 4) x 4) x 4) x 4)
Frequency x 4) x 4) x 4) x 4)
Active power x 4) x 4) x 4) x 4)
Apparent power x 4) x 4) x 4) x 4)
Reactive power x 4) x 4) x 4) x 4)
Release outputs
Potential-free 1–3 1–3 1–3 1–3 2 2 4 4 4 4 4 1
Supplied by internal
2 3) 2 3) 2 3) 2 3)
capacitor
Binary inputs
Number 2 (test + reset) 2 (test + reset) 4
1) Optional for wattmetric detection of earth-fault direction 4) Momentary value, mean value and min / max value, directional
2) Creation of sum signal via 3 transformers mounted around the conductor 5) Short-circuit to earth = Earth fault in impedance-earthed system
3) 0.1 Ws, 24 V DC
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 55
Components
On request: Indicating and measuring equipment
R-HA40-146.tif
Earth-fault function
x
(impedance-earthed system)
Indication of direction,
x
short-circuit/earth-fault
Undervoltage and overvoltage indica-
x
tion
Applicable for the following neutral earthing options SICAM FCM
Impedance x
Solid x Short-circuit and earth-fault indicators, make Siemens
Isolated x SICAM FCM is a short-circuit and earth-fault indicator with
Compensated x direction indication, operating with protection algorithms
Pickup current and advanced low-power current and voltage sensors
Short-circuit current 50 ... 2000 A (steps of 1 A) according to IEC 60044.
Earth-fault current 1 ... 1000 A (steps of 1 A)
Pulse location – Main features:
Pickup time • Usable in earthed, isolated and resonance-earthed
Short-circuit current 40 ms systems
< t < 60 s
• Directional short-circuit and earth-fault detection
Earth-fault current 40 ms
< t < 60 s • Precise and fast fault localization reduces expenses
Reset for personnel and traveling costs
Manual x • Selective fault information with direction indication as a
Automatic x basis for "self-healing" applications
From remote x • Resupply times possible in the range of minutes or
Remote indication seconds (depending on the primary part of the switchgear)
Passing contact adjustable • Minimum loss of power grid and end consumer revenues
Maintained contact adjustable • Reliable measured values for operational management and
Interface planning
RS485 / MODBUS x • Targeted application of investment funds during network
Power supply planning and grid expansion
Lithium battery x • Use of low-power sensors and high-quality measuring
External auxiliary voltage x systems with a measuring accuracy of 99%.
Current inputs
Phase current 3 (2) 1) SICAM FCM operates with sensors conforming to the
Summation current 0 (1) 1) standard IEC 60044-7/8. This enables exact measurements
Voltage inputs without calibration or adjustment to the primary
Via WEGA 1.2C / WEGA 2.2C 3x magnitudes.
Measuring function
Current x
Voltage x
Load flow direction x
cos phi x
Frequency x
Active power x
Apparent power x
Reactive power x
Relay outputs
Potential-free 2 2)
Binary inputs
Number 1
56 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Components
Indicating and measuring equipment, transformer monitor systems
R-HA40-107.eps
• Tripping of the circuit-breaker when the short-circuit
current arises.
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 57
Components
Indicating and measuring equipment
• To verify safe isolation from supply
• Detecting systems
–– HR or LRM system with plug-in indicator
–– LRM system with integrated indicator, type VOIS+,
VOIS R+, WEGA ZERO
–– LRM system with integrated indicator,
with integrated repeat test of the interface and
function test: Volt. indicator CAPDIS-Sx+, VOIS+
plugged in or WEGA installed
– type CAPDIS-S1+, WEGA 1.2, WEGA 1.2 Vario;
(HR, LRM)
with additional integrated signaling relay
– type CAPDIS-S2+, WEGA 2.2. Voltage indication
via capacitive voltage divider (principle)
– C1 Capacitive coupling electrode integrated into bushing
– C2 Capacity of the coupling unit (as well as connection
leads of the voltage detecting system) to earth
Temperature range –40 °C to +55 °C –25 °C to +55 °C –25 °C to +55 °C –25 °C to +55 °C –25 °C to +55 °C
Integrated signaling relays – – with – with – – with
(auxiliary voltage required)
58 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Components
Indicating and measuring equipment
VOIS+, VOIS R+
• Integrated display
R-HA40-104e.eps
R-HA40-134.eps
• With indication “A1” to “A3” (see legend, page 58)
• Maintenance-free, repeat test required
• With integrated 3-phase LRM test socket for phase
comparison
• With integrated signaling relays (only VOIS R+).
Integrated voltage indicator Integrated voltage detecting
CAPDIS-Sx+ VOIS+, VOIS R+ system CAPDIS-S2+ (-S1+)
Common features
• Maintenance-free Symbols shown
• Integrated display VOIS+, VOIS R+ CAPDIS-S1+ CAPDIS-S2+
• Integrated repeat test of the interfaces (self-monitoring)
• With integrated repeat test (without auxiliary power)
A0
by pressing the “Test” button
• With integrated 3-phase LRM test socket for phase A1
comparison.
CAPDIS-S1+ A2
• With indication “A1” to “A7” (see legend, page 58)
A3
• Without auxiliary power
• Without signaling relay (without auxiliary contacts). A4
CAPDIS-S2+
A5
• With indication “A0” to “A8” (see legend, page 58)
• Signaling relay (integrated, auxiliary power required). A6
WEGA 1.2 / WEGA 1.2 Vario / WEGA 2.2 A7
Common features
• Integrated display A8
• Maintenance-free For legend, see page 58
• Integrated repeat test of the interface (self-monitoring)
• With integrated function test (without auxiliary power)
by pressing the "Display Test" button
R-HA35-141.eps
R-HA35-143.eps
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 59
Components
Indicating and measuring equipment
Verification of correct
terminal-phase connections Phase comparison test units according to IEC 61243-5 or VDE 0682-415
• Verification of correct terminal-
R-HA40-059 eps
R-HA40-089.tif
phase connections possible by
means of a phase comparison
test unit (can be ordered
separately)
• Safe-to-touch handling of
the phase comparison test unit
by inserting it into the capaci-
tive taps (socket pairs) of the
switchgear.
R-HA35-175.eps
60 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Components
Protection systems
• Protection device with auxiliary voltage supply Relay
–– Siemens: Type 7SJ46
• Release at the circuit-breaker as
–– Shunt release (f)
Scheme
or
–– C.t.-operated release (low-energy 0.1 Ws)
• Instrument transformer as
–– Cable-type current transformer (standard)
–– Three-phase current transformer as option for SIMOSEC
switchgear panels type L…
Mounting location
• In 350-mm-high top low-voltage compartment of the
circuit-breaker feeder, or in the low-voltage niche.
LSP 2874-afp.eps
R-HA35-104.eps
7SJ80
• LC text display (6 lines) and keyboard for local operation,
parameterizing and indication
• Control of circuit-breaker and disconnector.
7SJ61 / 7SJ62
• For stand-alone or master operation
• LC text display (4 lines) for process and equipment data
LSP2339-afp.tif
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 61
Components
Low-voltage compartment
R-HA41-058 eps
• Installation on the panel: 3 2 LCD
Possible per feeder 3 Navigation keys
4
4 Function keys
• Customer-specific equipment
For accommodation of protection, control, measuring On circuit-breaker panel type L, L1, …
for additional low-voltage equipment
and metering equipment
• O verall height depends on the panel-specific
configuration of primary and secondary equipment
• D oor with hinge on the left
Low-voltage compartment (example 750 x 350 mm)
(standard for heights of 350 and 550 mm)
Option: Door with hinge on the right.
R-HA41-040a tif
Low-voltage cables
• Control cables of the panel to the low-voltage compart-
ment via multi-pole, coded module plug connectors
• Option: Plug-in bus wires from panel to panel inside the
low-voltage niche, or optionally in the separate wiring
duct on the panel.
Switchgear height
1750 mm
62 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Components
Low-voltage niche
(with max. 75 mm wide
mounting frame), e.g.
– Type 7SJ45, 7SJ46:
For type L and L1
– Make Woodward / SEG, In circuit-breaker panel In circuit-breaker panel
type WIC1: For type L and L1 type L (500 mm) type L1 (750 mm)
On request: (with CB-f NAR*))
– 7SJ60, 7SJ80
– Make Woodward / SEG, Protection relay as option:
WIP-1 1 Protection relay type 7SJ45 12
• For bus wires and / or control 2 On request: Protection relay type
cables; niche open at the side 7SJ80 in LV niche
to the adjacent panel 3 Protection relay make 1, 3
Woodward (SEG), type WIC 11
• Safe-to-touch, separated from
4 On request:
high-voltage part of the panel
Multifunction protection relay
• Degree of protection IP3X SIPROTEC 4 type 7SJ61 on swing-out
(standard). frame
R-HA41-143a tif
8 Option: Local-remote switch for
three-position switch-disconnector
9 Option: Momentary-contact rotary
control switch ON-OFF for motor
In circuit-breaker panel type L (500 mm)
operating mechanism of the
three-position switch-disconnector
10 Panel front
11 Low-voltage niche open
12 Option:
Installed equipment
*)
A R = Automatic reclosing
N AR = Non automatic reclosing
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 63
Dimensions
Switchgear installation
Room planning
Room planning
Switchgear installation
Wall-standing arrangement,
Switchgear room Switchgear room
free-standing arrangement
–– 1 row
–– 2 rows (for face-to-face
arrangement).
Room dimensions
See opposite dimension
drawings.
Door dimensions
The door dimensions depend
on the
–– Number of panels in a
transport unit
low-voltage compartment.
Switchgear fastening
• For floor openings and fixing
Wall-standing arrangement (side view) Free-standing arrangement (side view)
points of the switchgear, see
pages 78 to 80
• Foundations:
–– Steel girder construction
–– Steel-reinforced concrete.
Panel dimensions
See pages 67 to 77
Weight
The weight of a panel d
epends
on the extent to which it is
equipped (e.g. with motor
operating mechanism, voltage
transformer). For details, please
refer to page 81.
Plan view Plan view
64 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Dimensions
Switchgear installation
Wall- – – ) 1750 ≥ 2400
stand-
ing
Free- – – ) 1750 ≥ 2400
stand-
ing
Floor cover: Available as option
stan- 21 kA, 1 s
ding
Floor cover: Available as option
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 65
Dimensions
Switchgear installation
Compartment Dimensions for: in mm
“Available mounting approx.
depth for low-voltage
equipment”
LV niche – with front cover a1 201
LV niche – with door (option) a2 246
LV compartment (option) a3 443
* Option:
Low-voltage compartment or front cover
available in two heights: 350 mm or 550 mm
1) Option: Pressure relief duct
)
T he position of the cables in the panel depends on
the additional, optional built-in panel components
(e.g. current and voltage transformers).
Therefore, the dimensions x1 and x2 may be different.
) Option: Low-voltage niche with door: Additionally 45 mm: Switchgear depth approx. 1041 mm
*) Panel depth: additionally deeper by 60 mm
Panel depth: 1080 mm, switchgear depth: 1230 mm
•C
ircuit-breaker panel types L, L1, L(T), L1(T): with circuit-breaker type “CB-f AR (3AH569)”
•C
ircuit-breaker panel types LS11, LS31, LS32: with circuit-breaker type 3AH6 / “CB-r”
**) In addition, a low-voltage compartment can be selected optionally. The switchgear height is changed respectively
66 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Dimensions
Ring-main panels, transformer panels
Ring-main
panels
Type R Type R1
Ring-main panel
Ring-main panel
type R(T)
type R(T)
for panel combinations,
for panel combinations,
as transfer panel left
as transfer panel right
type R(T)
type R(T)
(placed on the left
(placed on the right
side of panel
side of panel
combination)
combination)
Type R(T) Type R(T)
Transformer
panels
* Option:
Low-voltage compartment
** For panel design with 4MA
in left-hand panel
2) Dimension a
~ 384 mm: At fuses with e = 442 mm
~ 534 mm: At fuses with e = 292 mm
Dimensions x1 and x2:
Type T Type T1
See pages 66 and 78
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 67
Dimensions
Cable panels
Cable panels
Type K Type K1
On request:
* Option:
Low-voltage compartment
Earthing panel
Dimensions x1 and x2:
Type E See pages 66 and 78
68 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Dimensions
Circuit-breaker panels
Circuit-breaker
panel 630 A
Type L (500 mm) Type L(T) Type L(T)
as transfer panel as transfer panel
to the left to the right
Circuit-breaker
panel 630 A, 1250 A
Type L1 (750 mm) Type L1(T) Type L1(T)
as transfer panel as transfer panel
to the left to the right
* Option:
Low-voltage compartment
** For panel design with 4MA
block-type current transformer,
Position of L1, L2 and L3: See page 66 the cable connection height is
Dimensions x1 and x2: reduced
See pages 66 and 78 ∆ Option: Protection relay
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 69
Dimensions
Panel combinations: Bus sectionalizer panels (circuit-breaker panel and bus riser panel)
70 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Dimensions
Panel combinations: Bus sectionalizer panels
Ur Dimensions in mm
x1 x2
Up to 17.5 kV 187 210
* Option:
24 kV 215 250
Low-voltage compartment
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 71
Dimensions
Billing metering panels
Panel design
M M
Panel design
M M
Panel design
Billing metering panel type M(-B)
(for busbar connection)
M(-B)
Ur Dimensions in mm
x1 x2
Up to 17.5 kV 187 210
24 kV 215 250
Type M(-B) * Option:
Low-voltage compartment
72 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Dimensions
Billing metering panels
Panel design
Billing metering panel type M(-K)
(for cable connection)
Type M(-K)
Panel design
M(-BK) M(-BK)
Billing metering panel type M(-BK)
(for cable connection)
Type M(-BK)
* Option:
Low-voltage compartment
** The cable connection height
depends on the rated voltage,
the transformer design and the
Dimensions x1 and x2 for cable connection: See pages 78 and 80 number of cable connections
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 73
Dimensions
Bus riser panels, busbar voltage metering panels
Ur Dimensions in mm
x1 x2
Up to 17.5 kV 187 210
24 kV 187 210
Busbar voltage
metering panels
Ur Dimensions
in mm
x1 x2
Up to 17.5 kV 187 210
24 kV 215 250
* Option:
Low-voltage compartment
1) Mounting location of
voltage transformer
Type M(VT) Type M1(VT) Type M(VT-F) Type M1(VT-F) in left-hand panel
2)
Option: Fuses
(with fuses) (with fuses)
74 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Dimensions
Disconnector panels
Disconnector panels
Type D1
* Option:
Low-voltage compartment
** For panel design with 4MA block-type
current transformer, the cable connection
height is reduced
1) Mounting location of voltage transformer
in left-hand panel
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 75
Dimensions
On request: Circuit-breaker panels (for removable circuit-breaker type CB-r)
2)
Type L1(r, T)
as transfer panel
* Option:
Low-voltage compartment
76 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Dimensions
On request: Panel top box, cable connection box
Panel top box as *)
voltage transformer box type: -VB
(For arrangement on top of the panel)
On request:
Cable connection box type CC (end panel)
for attachment to end panels as type R, T, L, L1
(up to 12 kV)
Type CC Type CC *
Each without low-voltage niche
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 77
Dimensions
Floor openings (dimensions in red) and fixing points
For Dimensions in mm
panel type x1 x1 x2 c1
K 187 187 210 210 187.5 187.5
T 187 187 210 210 187.5 187.5
D 187 187 210 210 187.5 187.5
For Dimensions in mm
panel type x1 x1 x2 c1
K1 187 187 210 210 187.5 187.5
T1 187 187 210 210 187.5 187.5
L 187 187 210 210 187.5 187.5
Position of cables 1)
For Dimensions in mm
1 187 235 210 230 235 335
L1 mit CTs,
VTs
2 187 235 210 230 235 335
1 Wall distance (see page 66) 4 Position of the led-in cables for the feeder 1)
2 Fixing frame (base) of an individual panel or panel block 5 Fixing points
3 Floor opening for high-voltage cables and, where applicable, 6 Floor opening if required for panels without cable connection
control cables 7 Option: Pressure relief duct
78 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Dimensions
Floor openings (dimensions in red) and fixing points
Position of cables 1)
For Dimensions in mm
panel type Number x1 x1 x2 c1 c1
of cables
For Dimensions in mm
L1(r)
2 187 235 210 230 390 390
1 187 235 210 230 390 390
L1(w)
2 187 235 210 230 390 390
Position of cables 1)
For Dimensions in mm
L1(r) 2 187 235 210 230 390 390
3 187 235 210 230 390 390
1 187 235 210 230 390 390
1 Wall distance (see page 66) 4 Position of the led-in cables for the feeder 1)
2 Fixing frame (base) of an individual panel or panel block 5 Fixing points
3 Floor opening for high-voltage cables and, where applicable, 6 Floor opening if required for panels without cable connection
control cables 7 Option: Pressure relief duct
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 79
Dimensions
Floor openings (dimensions in red) and fixing points
R(T) E1
M(VT), M1(VT),
M(VT-F) M1(VT-F)
H, E L(T)
D(T) D1(T)
T(T) T1(T)
For panel width 750 mm On request: For panel width L1(r, T), L1(w, T), width 750 mm
L1(T) L1(r, T)
M, M(-B) L1(w, T)
Panel combinations:
R(T) + H, R(T)+R(T)
T(T) + H
1 Wall distance (see page 66) 4 Position of the led-in cables for the feeder 1)
2 Fixing frame (base) of an individual panel or panel block 5 Fixing points
3 Floor opening for high-voltage cables and, where applicable, 6 Floor opening if required for panels without cable connection
control cables 7 Option: Pressure relief duct
80 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Installation
Shipping data, transport
Individual panels or Panel type Panel or panel Transport unit “TU” (including packing) for standard panels
combinations thereof for standard combination (without / with pressure relief duct, option)
switchgear
Width Net Width Height H ) Depth Volume Gross
B1 weight 1) B2 of “TU“ T2 weight 1)4)
mm approx. kg m m m m3 approx. kg
without / with without / with without / with without / with
LV C* / LV C* LV C* / LV C* LV C* / LV C* LV C* / LV C*
* Low-voltage compartment, 350 mm high, 1) The net weight and the gross weight depend on the extent to which
weight approx. 60 kg depending on the panel type and on the the panel is equipped (e.g. current transformers, motor operating
extent to which it is equipped, or optionally 550 mm high mechanisms) and are therefore given as mean value
n.a. = not applicable 2) Sum of the net weights of individual panels
Δ) O ther heights “H“ of “TU“ possible (depending on the 3) Panel types including CTs and VTs: Weight per CT or VT as cast-resin
equipment of the panel type and the packing type) design: Approx. 20 kg (example: 3 CTs and 3 VTs approx.
) Depending on the delivering factory additionally 120 kg per panel)
4) Add additional weight for pressure relief duct (according to table values)
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 81
Installation
Shipping data, transport
Individual panels or Panel type Panel or panel Transport unit “TU” (including packing) for standard panels
combinations thereof for standard combination (without / with pressure relief duct, option)
switchgear
Width Net Width Height H ) Depth Volume Gross
B1 weight 1) B2 of “TU“ T2 weight 1)
mm approx. kg m m m m3 approx. kg
without / with without / with without / with without / with
LV C* / LV C* LV C* / LV C* LV C* / LV C* LV C* / LV C*
With individual panel
With combinations of different individual panels
* L ow-voltage compartment, 350 mm high, weight approx. 60 kg 1) The net weight and the gross weight depend on the extent to which
depending on the panel type and on the extent to which it is the panel is equipped (e.g. current transformers, motor operating
equipped, or optionally 550 mm high mechanisms) and are therefore given as mean value
** Packing weight 2) Sum of the net weights of individual panels
*** On request: Max. panel width “B3“ ≤ 1125 mm (e.g. for 3 x 375 mm)
Δ) O ther heights “H“ of “TU“ possible (depending on the equipment
of the panel type and the packing type)
) Depending on the delivering factory
82 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Installation
Shipping data, transport
by seafreight Welded PE protective foil, with closed wooden crate,
with desiccant bag Pallet
Type: Open for container
PE protective foil pulled over the switchgear,
with wooden base Crane transport with pallet
Overseas Type: Open
by airfreight PE protective foil pulled over the switchgear,
with wooden base and lattice or cardboard cover
Transport
SIMOSEC switchgear is completely delivered in transport
units. Please observe the following:
• Transport facilities on site
• Transport dimensions and weights Transport with lifting truck
• Size of door openings in building with or without pallet
• Switchgear with low-voltage compartment: Please
observe other transport dimensions and weights.
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 83
Standards
Standards, specifications, guidelines
Standards
SIMOSEC switchgear complies with the relevant standards
and specifications applicable at the time of type tests.
In accordance with the harmonization agreement reached
by the countries of the European Union, their national
specifications conform to the IEC standard.
Insulating gas Specification for sulfur hexafluoride (SF6) IEC 60376 VDE 0373-1 EN 60376 –
SF6
84 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Standards
Standards, specifications, guidelines
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 85
Standards
Standards, specifications, guidelines
86 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Standards
Standards, specifications, guidelines
For secondary devices in the low-voltage door, the Protection against access to hazardous parts
stipulations of the IP degree of protection apply according Protected against access to hazardous parts with a tool
to the definitions for the switchgear enclosure. (the access probe of 2.5 mm diameter shall not penetrate)
Option on request: IP 3 X D
IP 6 5
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 87
Product Range
Versions with removable circuit-breaker type 3AH6
R-HA41-077.eps
R-HA41-064d.eps
88 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Product Range
Electrical data of the switchgear
*) As design option, on request according to some national requirements (e.g.: GOST, GB, …)
**) Type designation of the vacuum circuit-breaker
1) The rated normal currents apply to ambient air temperatures of max. 40 °C.
The 24-hour mean value is max. 35 °C (according to IEC 62271-1/VDE 0671-1)
2) Pressure values for SF6 -insulated vessels
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 89
Product Range
Circuit-breaker panels
connection
either-or
either-or
of max.
Option Option ** Option Option ** 2 cables
Three-position
switch-disconnector
Option 5) Option Option Option
either-or
either-or
either-or
either-or
Option Option Three-position
Option Option Option Option
disconnector
Cable-type
Type LS11 With vacuum circuit-breaker 3AH6, Type LS31 With vacuum circuit-breaker 3AH6,
current transformer,
750 mm wide removable 750 mm wide removable
e.g. 4MC703 . . .
Option Option Block-type current
for
transformer 4MA,
connection
cast-resin insulated
either-or
of 3 cables
Option Option ** (4 cables *))
Three-phase current
Option Option transformer 4MC63 . . .
Option
either-or
either-or
Additional cables
(not included in the
scope of supply)
Surge arrester
HA41-4140.eps
Capacitive voltage
detecting system
Make-proof
* O n request earthing switch
** Standard: F
eeder earthing via the vacuum circuit-breaker
type 3AH6 (without earthing switch at the feeder)
Option: Feeder earthing via the make-proof earthing switch at the feeder Fixed earthing point
90 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Product Range
Panel design (examples)
Circuit-breaker panel (with vacuum circuit-breaker 3AH6) 17 Gas-insulated vessel for switching device
18 Manual operation for the mechanism of the
earthing function
19 Manual operation for the mechanism of the
load-break function
20 Rating and type plate
21 Pressure relief device for switching device
22 Interlocking of cable compartment cover in
circuit-breaker panels
23 Metallic partition of cable compartment
24 Cover * for screwed joint of the cable connections
25 Cable connection
26 Post insulator
28 Cable sealing end
(not included in scope of supply)
29 Cable bracket with cable clamps (option) for
fastening cables
30 O
ption: Wiring duct removable
for control cables and/or bus wires
31 B
usbar compartment cover for
panel extension
32 Busbar
33 Insulating cap * at the busbar
34 Bushing-type insulator for busbar
35 Metallic partition of busbar compartment
36 S
pring-operated mechanism for three-position
disconnector
37 Three-position disconnector
Type LS11 Section 38 Cable compartment cover
Vacuum circuit-breaker:
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 91
Product Range
Product range overview
R-HA41-077.eps
Circuit-breaker panel
Column No.
Feeder Circuit-breaker panel 630 A, LS11 750
with 3AH6 1)
Circuit-breaker panel 1250 A, LS31 750
with 3AH6 1) LS32 875
l
l
M
an
ua
l
l
lo
In pe
te ra
on request
rlo tin
ck
l
l
gm
– Not available
fo
C-
ra r ca
ec
ha (option), further
l Basic equipment
il a ble nis
l
l
sc co m
Lo ab
le m fo
r
additional equipment
Additional equipment
w- pa th
vo br r tm re
5
ac
lt a ke en e-
Re ge t tc po
lea nic ov sit
se er ion
he sw
as as
M sh te itc
ec un rm h 2)
ha tr
nic ele ina
Sig al as lc
n re
ad e om
re a l i n pa
ad g y - f r tm
Au y - fo s w o r en
-se t
OP xilia r-se itch rv
EN ry r v (1 ice
i
2 N sw ice N
i O n
O itch dic
M + 1 fo ndi ) fo at
ot NC r th cati r re ion
or
e
10
op ac -p
ree on m
ot fo
Lo er h ; m osi or e e f rt
hr
ca at a t i t h l e ee
l-r ing ke on
- r e c t r -p
p s e
l
l
m w i
11
em roo it -p ca os
In o t ec f ch os l iti
te e s h a ea : D i t i on
th rl o c wi nis rth isc on sw
re k t ch m ing on s itc
12
e- in
p fo fo sw nec witc
t
h
c
5)
5)
Lo o s i r r m rt itc or h 2
wi ck-i iti cu o hr h a an )
th n on it- to ee tt dE
-p he A
s br ro
13
ea for pe os fee RTH
r th " C w i t e a k
c e r i t de IN
Cl ed LO
S
h 2 r p
ati
n
ion
os t E ) a g s
r: E G:
hr D a n n m w i
AR For
14
ing ee " p d el
b e c t c h
TH CL
v
6)
6)
loc -p os
os iti a e h an 2) IN O S
G: E
In ko i t i o n c u u t we i s
sp ut o n o m e m 2N Da
f n O nd
ec f s o
15
o w v c f t +1
tio rt i t ac i rc h
Lo nw hr
e
ch u u
2) m
uit r e e
NC
w- ind e- - -po
vo po c i r b re s
o a
16
or c t r . t ch
17
op pa on ch 3 . 2)
er r tm ne 2) AH
Re
lea a tin en c tio 6
to
18
se gm n /
fo ec rc ca
rc h ov ble
Lo
ck .t. an e r co
-o i
–
–
s m m
19
ing pe
d r f pa
ev a t o r tm
Sh
or ice e dr
rv
ac en
e u
fo
20
t-c lea um tc
i rc rt s ov
–S uit hr
ee e in c i rc u er
ec or - p 3 A i t
21
on ea os H -b
da r th iti 1) re
–F ry -fa on ak
loo eq sw er
u ult
22
rc itc
o ve
ipm ind
ica h 2)
–P en
an r 3) t to
r 2)
el
23
Ca he
b at
er 4
m le c
ou la )
n t mp
LS32
LS31
LS11
ed s,
Options for panels
Product Range
Panel type
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 93
Product Range
Three-position switch as three-position disconnector
Three-position disconnector
630 A, 1250 A
R-HA41-1048.eps
R-HA41-057.eps
• Up to 1250 A, for panel types 1
LS11, LS31 and LS32
• Metal-enclosed.
Operating mechanism
• Spring-operated
mechanism as detachable
lever mechanism 2
Switch positions:
EARTHED
OPEN
CLOSED
94 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Product Range
Cable connection
General features
• Connecting lugs for sealing 10 As-delivered condition,
R-HA41-055.eps
ends arranged one behind the e.g. for Up < 95 kV,
other prepared for cable sealing
end
• Uniform cable connection
11 As-delivered condition,
height for the respective
e.g. for Up ≥ 95 kV,
panel types additionally with insulating
• With cable bracket, cap prepared for cable seal-
e.g. type C40 according to ing end
DIN EN 50024 12 Phase L1:
Make Lovink-Enertech,
• Access to the cable com-
type IAES 20,
partment only if the feeder 240 mm2 (20 kV)
10
has been disconnected and
13 Phase L2:
earthed Prysmian Kabel und Systeme
(Pirelli Elektrik),
Special features type ELTI 1C-24-D-T3,
–– In the ring-main panel 240 mm2 (24 kV),
as indoor sealing end,
–– In the circuit-breaker panel
for adverse ambient
–– In the cable panel conditions
• For thermoplastic-insulated 14 Phase L3:
Circuit-breaker panel type LS11 Make Euromold,
cables
cable compartment as delivered type AIN 20,
• For paper-insulated mass- 240 mm2 (24 kV)
impregnated cables with
adapter systems 11
• For connection cross-sections L1 L2 L3
up to 300 mm2 cable routing
R-HA41-067.eps
downwards
–– In the transformer panel:
• For thermoplastic-insulated
cables 14
Cable cross-sections
Panel type Connectable cables
x connection cross-
section
No. x mm2
for rated voltage
Cable compartment with cable sealing ends
12 kV 17.5 kV 24 kV
(options: A, C and D, see below)
LS11, LS31 2 x 400 2 x 400 2 x 300
LS32 Standard 3 x 400 3 x 400 3 x 300
Option 4 x 300 4 x 300 –
Inquiry – – 4 x 300
Options
A Cable clamps, mounted D Suitable for connection of
C Double cable connection surge arresters
make Siemens, type 3EK,
other makes on request
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 95
Product Range
Dimensions of circuit-breaker panels (type LS.., with 3AH6)
2)
Circuit-breaker panels
630 A
with 3AH6 1)
Type LS11 Type LS11
(with make-proof (without earthing switch)
earthing switch)
Circuit-breaker panels
1250 A
with 3AH6 1)
Type LS31 3) Type LS32 3)
(for connection of (for connection of
max. 2 cables) 3 cables)
* Option:
Low-voltage compartment
in heights 350 mm or 550 mm
** Usable mounting depth
for low-voltage devices
– approx. 184 mm with cover
– approx. 230 mm with frame cover
96 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Product Range
Floor openings (with dimensions marked in red) and fixing points
for
LS11-U
LS31-U
LT31
for
panel
type
LS32
1 Wall distance
2 Fixing frame (base) of an individual
panel
3 Floor opening for high-voltage cables
and, where applicable,
control cables
4 Position of the led-in cables for the
feeder
5 Fixing points
Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015 97
Notes
98 Switchgear Type SIMOSEC, up to 24 kV, Air-Insulated, Extendable · Siemens HA 41.43 · September 2015
Siemens AG
Energy Management
Medium Voltage & Systems
Mozartstraße 31 C
91052 Erlangen, Germany
E-Mail: support.energy@siemens.com
www.siemens.com/medium-voltage-switchgear
www.siemens.com/SIMOSEC