Asafeinstall DGB
Installation Handbook
AutroSafe Interactive Fire Detection System
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 2
Table of Contents
1. Introduction ...................................................................... 7
1.1 About the Handbook .......................................................................... 7
1.2 The Reader ....................................................................................... 7
1.3 Reference Documentation................................................................. 8
2. Pre-installation ................................................................. 9
2.1 Location ............................................................................................. 9
2.2 Environmental Requirements ............................................................ 9
2.3 Mounting Height / Space Requirement ............................................. 9
Page 3
7.2.5 Multifunction Serial Port Connection Overview ....................... 37
7.3 Internal Earth Cabling........................................................................ 38
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 4
10. Dual Safety Installation ................................................... 66
10.1 Dual Safety System Overview ........................................................... 66
10.2 Rules of Thumb ................................................................................. 66
10.2.1 Example 1: Connections Using AL_Com+ only ...................... 67
10.2.2 Example 2: Connections using both AL_Com+ and
AutroFieldBus .......................................................................... 68
10.3 Connections Overview ...................................................................... 68
10.3.1 Connections – AutroKeeper BN-180....................................... 70
10.3.2 Switch Settings – AutroKeeper BN-180 .................................. 70
Page 5
12.8 Configuration Settings ....................................................................... 90
12.9 Dipswitch table – S5 and S6 ............................................................. 91
12.10 Connectors ........................................................................................ 92
12.11 Fault Relay Watchdog J26 ................................................................ 93
12.12 Battery Resistance Measurement ..................................................... 94
12.13 Electronic fuses ................................................................................. 94
12.13.1 Power outputs ...................................................................... 94
12.13.2 Battery Input ......................................................................... 95
12.14 Part of an AutroFieldBus Network ..................................................... 95
12.15 Power Unit BPS-405 / BPS-410 as Standalone ................................ 95
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 6
Introduction
1. Introduction
1.1 About the Handbook
This handbook is intended to provide all necessary information for the
installation of the AutroSafe Interactive Fire Detection System,
Release 4. It also gives detailed information on connections to
Autronica’s local area network (AutroNet) and guidelines for the
installation and addressing of loop units.
Note that this handbook deals with the mechanical and electrical
installation only. All tasks described in the handbook are to be
!
POWER OFF!
performed without applying power to the system.
Power must not be applied before commissioning, refer to
Commissioning Handbook.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 7
Introduction
http://select.phoenixcontact.com/phoenix/dwl/dwlfr1.jsp?lang=en
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 8
Pre-installation
2. Pre-installation
2.1 Location
The Fire Alarm Control Panel or Operator Panel must be located in, or
nearby, the entrance according to local regulations and in consultation
with the fire brigade.
175 cm
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 9
System Units – Overview
Dimensions:
HxWxD (mm): 350 x 350 x 194
Dimensions:
HxWxD (mm): 350 x 350 x 84
Dimensions:
HxWxD (mm): 350 x 195 x 84
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 10
System Units – Overview
Controller BC-420
Dimensions:
HxWxD (mm): 350 x 350 x 194
Controller BC-440
Dimensions:
3Ux12HPx200mm
Dimensions:
HxWxD (mm): 420 x 346 x 146
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 11
System Units – Overview
Dimensions:
HxWxD (mm): 130 x 259 x 120
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 12
Mounting Instructions
4. Mounting Instructions
4.1 Introduction
This following chapters deal with the mounting of:
Fireman’s key (delivered with all system units, except for BC-420
and BP-405/BPS-405/BPS-410)
Unbraco key (to lock/unlock the front panel) – (not delivered with
BP-405 /BPS-405/BPS-410)
Plastic cap to cover the key hole (Repeater Panel only; when
Repeater Panel BU-BV-420 is to be used as an Information Panel)
11 Rubber glands for entry of external cables
Text foils
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 13
Mounting Instructions
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 14
Mounting Instructions
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 15
Mounting Instructions
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 16
Mounting Instructions
Page 17
Mounting Instructions
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 18
Mounting Instructions
S2
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 19
Mounting Instructions
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 20
Mounting Instructions
The mounting procedure deals with the mounting of the cabinet and
the internal batteries.
Note that the Power Cabinet can be placed under and fastened
directly to a Fire Alarm Control Panel BS-420 or a Controller BC-420.
The position of the 11 cable inlets/outlets at the bottom of the BS-
420/BC-420 match exactly with the ones on the top of the Power
Cabinet BP-405.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 21
Mounting Instructions
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 22
Mounting Instructions
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 23
Mounting Instructions
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 24
Mounting Instructions
E-2852
E-2852
E-2855
E-2856
E-2856
E-2853 E-2854
Make sure that you are holding the textfoil the correct way.
Bend the small flap towards the panel (as shown on the left most
illustation below), then insert the foil into the appropriate slot, and
slightly push it in as far as possible.
The foils that are to be inserted into the slot on the righ hand side
of the panel front have a small flap which can easily be bent (along
the perforation holes).
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 25
Mounting Instructions
ø29 x 5
ø23 x 6
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 26
Mounting Instructions
85
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 27
Mounting Instructions
85
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 28
Power Consumption
5. Power Consumption
5.1 Mains Power
5.1.1 BPS-405
The current consumption at 115V AC is 3,2A.
The current consumption at 230V AC is 1,6A.
5.1.2 BPS-410
The current consumption at 115V AC is 4,5A.
The current consumption at 230V AC is 1,9A.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 29
Power Consumption
Note:
All Ethernet switches can be used for the Onshore market. Only
Ethernet switches that are indicated in coloured rows (the first 9 that
are listed) can be used for the Maritime market and the Petrochemical
Oil & Gas market.
Current
Autronica part Consumption
Switch type (Phoenix) Description
number (max.) @ 24V
DC
FL SWITCH SFNT 5TX 5 RJ45 ports 116-5151-030.2127 120mA
4 RJ45 ports
FL SWITCH SFNT 4TX/FX 1 fibre optic multi-mode port (SC) 116-5151-030.2128 160mA
FL SWITCH SFNT 8TX 8 RJ45 ports 116-5151-030.2129 153mA
7 RJ45 ports
FL SWITCH SFNT 7TX/FX 1 fibre optic multi-mode port (SC) 116-5151-030.2130 175mA
FL SWITCH LM 5TX 5 RJ45 ports 116-5151-030.2131 250 mA
4 RJ45 ports
FL SWITCH LM 4TX/FX 1 fibre optic multi-mode port (SC) 116-5151-030.2132 380mA
4 RJ45 ports
FL SWITCH LM 4TX/2FX 2 fibre optic multi-mode ports (SC) 116-5151-030.2133 400mA
4 RJ45 ports
FL SWITCH LM 4TX/FX SM 1 fibre optic single-mode port (SC) 116-5151-030.2134 380mA
4 RJ45 ports
FL SWITCH LM 4TX/2FX SM 2 fibre optic single-mode ports (SC) 116-5151-030.2135 400mA
5 RJ45 ports
FL SWITCH SFNB 5TX 116-5151-030.2136 180mA
8 RJ45 ports
FL SWITCH SFNB 8TX 116-5151-030.2137 138mA
4 RJ45 ports
FL SWITCH SFN 4TX/FX 1 fibre optic multi-mode port (SC) 116-5151-030.2138 140mA
7 RJ45 ports
FL SWITCH SFN 7TX/FX 1 fibre optic multi-mode port (SC) 116-5151-030.2139 190mA
6 RJ45 ports
FL SWITCH SFN 6TX/2FX 2 fibre optic multi-mode ports (SC) 116-5151-030.2140 230mA
4 RJ45 ports
FL SWITCH SFNB 4TX/FX SM 20 1 fibre optic single-mode port (SC) 116-5151-030.2142 175mA
http://select.phoenixcontact.com/phoenix/dwl/dwlfr1.jsp?lang=en
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 30
Power Consumption
Only supplies with output class A may be paralleled with each other.
This also applies to supplies with output class B.
One BPS-405 unit can be connected to one battery set. A battery set
may NOT be shared by several BPS-405 units.
Max 2A
BATT A1 BATT A1 LOAD
Always on
Primary panels, secondary panels Max 2A
A2 A2 LOAD
Max 2A
B1 May be switched off B1 LOAD
Max 3A
Primary panels, secondary panels,
Max 2A
B2 network switches, auxiliary equipment B2 LOAD
Max 2A
C1 C1 LOAD
Will be switched off during system init
Grey stack, auxiliary equipment Max 2A
C2 C2 LOAD
AFB 1 AFB 1
AFB 2 AFB 2
Max 4A
BATT A1 LOAD
Max 4A
BATT A1 LOAD
A2
A2 Max 4A
B1 LOAD
Max 2A Max 3A
B1 LOAD
Max 5A B2
Max 2A
B2 LOAD Max 2A
C1 LOAD
Max 2A
C1 LOAD Max 2A
C2 LOAD
Max 2A
C2 LOAD
AFB 1
AFB 1
AFB 2
AFB 2
Outputs with same letter may be paralleled
No battery increases available current output
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 31
Power Consumption
A2 LOAD A2
B1 B1
B2 LOAD B2 LOAD
C1 LOAD C1 LOAD
C2 LOAD C2 LOAD
AFB 1 AFB 1
AFB 2 AFB 2
Different output classes shall not be paralleled Different output classes shall not be paralleled
LOAD A2 A2 LOAD
LOAD B1 B1 LOAD
LOAD B2 B2 LOAD
LOAD C1 C1 LOAD
LOAD C2 C2 LOAD
AFB 1 AFB 1
AFB 2 AFB 2
A2 LOAD A2
B1 LOAD B1
B2 LOAD B2
C1 LOAD C1
C2 LOAD C2
AFB 1 AFB 1
AFB 2 AFB 2
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 32
Cable Connection Overview
Controller Board 4 -
BSA-400 J18
3 +
2 -
1 +
1
2
3
5
4 Fire Alarm
6
7
8
Control Panel
10
9
8
9
10 TERMINAL BS-420
Power Supply 7
11
12
BLOCK
6 13
Module 5 14
4 - 15
16
BSS-310A
BSS-310A/ 3 -
2 +
17
18
BSS-311 1 + 19
20
Cat.5
1 AFB A
2 AFB A''
3 AFB CT A
4 AFB Earth Fault Sense
5 AFB B
6 AFB B''
7 AFB CT B
8 AFB Earth Fault Sense
+
A2
-
+
A1
-
Power Cabinet
BP-405 +
B2 Power Board
-
+
B1
BSF-400
-
+
C2
-
+
C1
-
Batt 1 2 3
+ - + -
+ - + -
12V 12V
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 33
Connecting Internal Cables
Multifunction cable
XGE-1/20-40
AL_Com+ cable
XGE-1/10-50
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 34
Connecting Internal Cables
Connector J5
Cable XGE-1/10-50
Connector J5 Description
J5.1 AL_Com+ CTS
J5.2 0VIN
J5.3 AL_Com+ RXD
J5.4 0VIN
J5.5 Not Connected The other end of the ribbon cable
is connected to Communication
J5.6 0VIN
Module BSL-310 inside the
J5.7 AL_Com+ TXD cabinet (see chapter 9.8)
J5.8 0VIN
J5.9 AL_Com+ RTS
J5.10 0VIN
Cable XGE-1/10-50
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 35
Connecting Internal Cables
Connector J3
Multifunction cable XGE-1/20-40
Multifunction cable
XGE-1/20-40
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 36
Connecting Internal Cables
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 37
Connecting Internal Cables
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 38
Connecting External Cables
! Remove fuse F8 from the power supply in all Power Cabinets (see
chapter 8.10.2).
Do not replace the fuse until commissioning of the system. Refer to
the Commissioning Handbook.
POWER OFF!
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 39
Connecting External Cables
POWER OFF!
!
116-BPS-410 for 230VAC
116-BPS-410/115 for 115VAC
POWER OFF! Make sure to use the correct unit according to the appropriate
voltage (115/230VAC).
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 40
Connecting External Cables
Terminal Function
L1.9 AutroFieldBus A
L1.11 AutroFieldBus A’
L1.13 AutroFieldBus CT A
L1.3 AutroFieldBus B
L1.5 AutroFieldBus B’
L1.7 AutroFieldBus CT B
L1.15 Earth
L1.3
AFB Last AFB unit
L1.5
L1.7
L1.9
AFB A First AFB unit
L1.11
L1.13
L1.15
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 41
Connecting External Cables
S5 1 2
AFB Earth Fault Off OFF OFF
AFB Earth Fault On ON ON
J2 J26
1 AFB A
2 AFB A" 1 6
1 Alarm NO
3 AFB CT A 2 Alarm Com
J2 4 AFB Earth Fault Sense 3 RC (Remote test)
5 AFB B 4 Fault Relay NO
6 AFB B" 5 Fault Relay NC
6 Fault Relay Com
7 AFB CT B
8 AFB Earth Fault Sense
F1 A1 F2AL
J19 F2 A2 F2AL
+ 0V
A1
S1 Reset
8 Internal Fault
L1.3
L1.5 B
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 42
Connecting External Cables
Ethernet ports on
Controller Board
BSA-400
Ethernet 2
Ethernet 1
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 43
Connecting External Cables
The example below is similar to the one above (chapter 8.5.1); all
panels have redundant connections to the system, except for the
Repeater Panel, which has a single Ethernet connection.
Between the Repeater Panel and the Ethernet switch, make only a
single Ethernet connection to and from Ethernet 1.
Connect the remaining Ethernet cables as described in chapter
8.5.1
Ethernet 1
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 44
Connecting External Cables
Ethernet ports on
Controller Board
BSA-400
Ethernet 2
Ethernet 1
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 45
Connecting External Cables
1 2
8 1
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 46
Connecting External Cables
8 8
1 1
BU-BV-420
2x2 2x2
24V 24V
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 47
Connecting External Cables
+5v_SER_0
TX_422_X+
Isolation
8
TX_422_Z-
10
RX_422_A+
4
RX_422_B-
6
Signal Reference
16
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 48
Connecting External Cables
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 49
Connecting External Cables
+ 0V
A1
S1 Reset
8 Internal Fault
7 General Fault
6
+ 0V
AFB Com
X11
A2
5
High
4 Fuse Fault
3 Battery Fault
2 Mains Fault
X10
J18
Low
J24
1 Power ON
+ 0V
B1
F3 B1 AFB Adress (H & L)
F2AL
J23 F4 B2
+ 0V F2AL
B2
F5 C1
F2AL 1 Earth Fault Sense ON/OFF
J22 2 Battery relay (see manual)
3 AFB present
+ 0V
C1
F6 C2 4
F2AL 5 Battery present
6
1 6
ON
J21 S6 S2, Start on standby
OFF source (see manual)
+ 0V
C2
Charger +24V
Charger 0V
Earth
F8 Charger
F7 F8 F7 Battery
E-2868
BP-410/01 T10 T10
AH AH
BP-405/01 T5 T5
5 Therm.+ AH AH
4 Therm.- 5 1 J17 1 2 3 J25
3 PSF J20
2 -V BATT
1 Vcon + -
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 50
Connecting External Cables
4 -
BSA-400
Fire Alarm Control Panel BS-420 /
+ +
J18
3
2 - - A2 Outputs
+ 2 x 24VDC/2A
1 +
Controller BC-420
- - A1
4
BSS-310A
(BSS-311)
3 -
2 +
+ +
1
- B2 Outputs
24VDC 24VDC
Ethernet - + 2 x 24VDC/2A
B1
switch + -
BU-BV-420 +
J18
BS-430
3 Outputs
- +
2 -
C2 2 x 24VDC/2A
+ w/interrupt
1 1 + at initialization
2 BU-BV-420 - C1 of panel.
3 BU-BV-420
4 BU-BV-420
Charger
Batt
1 2 3
Power to third party 24VDC/2A + -
equipment with input
+ -
voltage 18 – 32VDC 24VDC/2A
Batt Charger
connection
24V
* External panels type BU-BV-420 and BS-430
can be connected both to output A and B.
Devide total power to both A and B.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 51
Connecting External Cables
L
N
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 52
Installing I/O Modules
9.1 Introduction
This chapter provides information on the mounting and removal of I/O
modules.
Screw
terminal 10
Screw
terminal 1
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 53
Installing I/O Modules
9.3.1 General
9.3.2 Mounting
The connection block on the I/O module must be pointing to the right
when the module is to be inserted.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 54
Installing I/O Modules
9.3.3 Removing
Unplug the connection block.
Before connecting cables, make sure that the mains power is not
!
POWER OFF!
connected.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 55
Installing I/O Modules
Schematics
BSF-400
+ BSS-310
C1+ 5 1
+ 2
5
6
Power Cabinet
Chassis
0V BSS-310 Internal
3 + 5V reg
Chassis Internal
5 0V
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 56
Installing I/O Modules
Schematics
+24V output
Power supply 1
0V output 1
BSS-311
2
3 BSS-310A
4
5
+24V output
6
BSL-310
7
Power supply 2 +24V Out
+24V Out 8
0V output 0V Out 9
0V Out 10
NOTE! The power supply module BSS-310A receive power from the internal plug-in connector
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 57
Installing I/O Modules
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 58
Installing I/O Modules
1 INT
2 RS_GND
3 TX The other end of the ribbon
4 RS_GND
5 N.C. (GND)
cable XGE-1/10-50 is
6 RS_GND connected to the Controller
7 RX Board BSA-400 (refer to
8 RS_GND chapter 7.2.1).
9 CTS
10 RS_GND
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 59
Installing I/O Modules
Schematics
Failsafe connection
7
Loop +
Driver F/S Signal
Module -
8
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 60
Installing I/O Modules
Ext. 24V
Ext. 0V
Diodes min 1A
2k
2k
Non-Inductive
BSB-310A load
DEK-Ext
OE-5DC/48DC/100
FW Routing Eq
8
(Not connected)
24V_BAT
910Ω
Sense FWRE
0V_BAT External 0V
BAT
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 61
Installing I/O Modules
+24 Volt
BSB-310A Optocoupler
A1 +
7 connection
8 A is the uppermost
9 A termination point
10 A2
Phoenix DEK-OE-
5DC/48DC/100
0V
0V
+24 Volt
External receiver
with power
supply
0V
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 62
Installing I/O Modules
+ Output
Terminal 9
+24V
External terminal list
Output 1
Maximum 100 mA
Output 8
Schematics
+ 24V Output 9
Output 1-8
0V_BAT
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 63
Installing I/O Modules
1 Signal resistor
250-2000 Ohm
Input 2K (Recommended value
is 470 Ohm)
2
Monitoring resistor
Schematics
R Signal
V+
Terminal point 1, 3, 5, 7
Sense 0V
Terminal point 2, 4, 6, 8
0V
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 64
Installing I/O Modules
Screw-
terminal 10
Screw-
terminal 1
External
Input module 24V power
+ + -
+24V
10
- External minus
connection list
1 Signal input 1
Sense 1
2 Signal input 2
Sense 2
Schematics
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 65
Dual Safety Installation
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 66
Dual Safety Installation
The distance from the Secondary Panel to the Secondary Loop Driver
Module is less than 3 meters. An AL_Com+ flat ribbon cable is used
between the panel AL_Com port and the I/O stack (including the
Secondary Loop Driver Module).
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 67
Dual Safety Installation
The distance from the Secondary Panel to the Secondary Loop Driver
Module is more than 3 meters. An AL_Com+ flat ribbon cable
(maximum 3 meters) is used between the AutroFieldBus (AFB)
Protocol Converter BSD-321 and the I/O stack (including the
Secondary Loop Driver Module). The AFB Protocol Converter is
connected to the panel’s AFB. The AFB cable length can be up to
1000 meters. Booster equipment can be added to exceed the AFB
cable length even further.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 68
Page 69
Primary System Secondary System
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Dual Safety Installation
Pin Description
number
1 TTL COM Debug port (internal
use only)
2 TTL IN Debug port (internal
use only)
3 TTL OUT Debug port (internal
use only)
4 GND
5 24V IN Power In (Green LED)
6 0V IN Power In
7 FAILSAFE COM FailSafe Rel. (future)
8 FAILSAFE NO FailSafe Rel. (future)
9 OUTLOOP + To “first” Loop Unit
10 OUTLOOP - --“--
11 INLOOP + To “last” Loop Unit
12 INLOOP - --“--
13 OUT + To Loop Driver’s IN +
14 OUT - To Loop Driver’s IN -
15 IN + To Loop Driver’s OUT+
16 IN - To Loop Driver’s OUT -
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 70
Controller Board BSA_400
S6
J3 J2
S7
J21
S5 J1
S3
J9
J16 J14
J10 J11
J5
X6 X4 S2
J17 J18
X5 X3
J12
J13
Label on cover
E-2878
To main Terminal Block. See
J3
manual for connections
J2 Ethernet 2
S6 1 2 3 J1 Ethernet 1
S6 RS-422 OFF OFF OFF
RS-485 ON ON ON
S7 S7 1 2
Serial J14
Console RS-422 Termination ON ON
OFF
Port RS-485 Termination ON OFF
ON
Push
Button S3 1 2
Reset AFB EARTH Fault Off OFF OFF
J5 To BSL-310
AFB EARTH Fault On ON ON
USB OTG
0V 2 IN 4
2 x USB Host
24V 2 IN 3
J18
0V 1 IN 2
Panel ID 24V 1 IN 1
Panel Type
LCD Backlight
S2
Network ID
To Front Panel To LCD
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 71
Controller Board BSA_400
BSA-400
11.3 Description
The Controller Board BSA-400 is the main CPU which controls all
system functionality.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 72
Controller Board BSA_400
D20 D21
J18
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 73
Controller Board BSA_400
BSA-400
S5
BSA-400
J10 J11
There are 2 standard USB full speed (480Mbit) host ports; type A
connector. The ports are to be used for connection of an optional
printer or a memory stick .
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 74
Controller Board BSA_400
BSA-400
J3
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 75
Controller Board BSA_400
The ring loop topology ensures that no detectors/field units will be lost
due to a single break or short circuit of the AutroFieldBus cable.
BSA-400
Ribbon cable connector Terminal block L1
J3.9 L1.9
J3.11 L1.11
J3.13
J3.3 L1.3
J3.5 L1.5
J3.7
J3.15 L1.15
Cable XGE-1/20-48
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 76
Controller Board BSA_400
S6
ON
123
BSA-400
S7
ON
12
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 77
Controller Board BSA_400
Cable XGE-1/20-48
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 78
Controller Board BSA_400
+5v_SER_0
TX_422_X+
Isolation
8
TX_422_Z-
RX_422_A+
RX_422_B-
Signal Reference
Cable XGE-1/20-48
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 79
Controller Board BSA_400
BSA-400
J21
AL_Com+ debug
J5 Connected to Communication
Module BSL-310.
Connector Description
J5.1 AL_Com+ CTS
J5.2 0VIN
J5.3 AL_Com+ RXD
J5.4 0VIN
J5.5 Not Connected
J5.6 0VIN
J5.7 AL_Com+ TXD
J5.8 0VIN
J5.9 AL_Com+ RTS
J5.10 0VIN
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 80
Controller Board BSA_400
Connector Description
J17.1 Backlight LED + 5V DC
J17.2 Backlight LED -
J17.3 Backlight LED -
J17.4 Backlight LED – 0V
J2
1 2
J1
8 1
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 81
Controller Board BSA_400
8 8
1 1
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 82
Power Supply
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 83
Power Supply
S5 1 2
AFB Earth Fault Off OFF OFF
AFB Earth Fault On ON ON
J2 J26
1 AFB A
2 AFB A" 1 6
1 Alarm NO
3 AFB CT A 2 Alarm Com
4 AFB Earth Fault Sense 3 RC (Remote test)
5 AFB B 4 Fault Relay NO
6 AFB B" 5 Fault Relay NC
6 Fault Relay Com
7 AFB CT B
8 AFB Earth Fault Sense
F1 A1 F2AL
J19 F2 A2 F2AL
+ 0V
A1
S1 Reset
8 Internal Fault
7 General Fault
+ 0V 6
5 AFB Com
High
X11
A2 4 Fuse Fault
3 Battery Fault
J24 J18 X10
Low
2 Mains Fault
1 Power ON
+ 0V
B1
J23 F4 B2
F2AL
+ 0V
B2
F5 C1
F2AL 1 Earth Fault Sense ON/OFF
J22 2 Battery relay (see manual)
3 AFB present
+ 0V
C1
F6 C2 4
F2AL 5 Battery present
6
1 6
ON
J21 S6 S2, Start on standby
OFF source (see manual)
+ 0V
C2
Charger +24V
Charger 0V
Earth
F8 Charger
F7 F8 F7 Battery
E-2868
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 84
Power Supply
12.3 Description
BSF-400 is a power monitor and controller board providing a
communication interface, AutroFieldBus. The board has also the
ability to operate stand alone with no communication. The fault relay is
energized as standard with its own watchdog.
BSF-400 has short circuit protection on all outputs such that a short
circuit will not affect other outputs. Batteries that are connected will be
charged with temperature compensation to ensure long battery life
regardless of temperature (within the specified operating temperature
range).
A1
BSA-400 BSA-400 BSA-400
A2
BSF- B1
400 B2
BSL-310
C1 BSS-310A
A power consumption
BSS-311 account must be done
C2
to ensure that max
delivery of power is
not exceeded.
External External
equipment: equipment:
max 2A max 2A
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 85
Power Supply
12.5 Batteries
2
The recommended cable parameter for BSF-400 is minimum 1,5mm /
15,4 AWG.
Batteries that are to be used with BSF-400 are Fiamm batteries with
the maximum size of 18Ah. The minimum size of batteries if batteries
are connected is 7,2Ah.
The maximum current that may be drawn from the batteries when the
primary power source is disconnected is 5A for BPS-405.
Fuse F7:
Maximum battery current output when
I max A Charger,
mains disconnected
Battery
3A 5A T5AH
NOTE:
If power to the system is supplied exclusively from the batteries (in
case of a power supply failure), and the voltage is below 19V, the
Power Board BSF-400 will perform a controlled shutdown (i.e. the
power is switched OFF).
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 86
Power Supply
Batteries that are to be used with BSF-400 are Fiamm batteries with
the maximum size of 18Ah. The minimum size of batteries is 12Ah.
The maximum current that may be drawn from the batteries when the
primary power source is disconnected is 10A for BPS-410.
Fuse F7:
Maximum battery current output when
I max A Charger,
mains disconnected
Battery
8A 10A T10AH
NOTE:
If power to the system is supplied exclusively from the batteries
(in case of a power supply failure), and the voltage is below 19V,
the Power Board BSF-400 will perform a controlled shutdown (i.e.
the power is switched OFF).
Charge current for the BPS-405 is also controlled, so that the charging
voltage will decrease when the charge current reaches 2A.
Note that when the BSF-400 board is turned OFF and batteries are
connected to the battery termination, the leak current of the batteries
is 6mA.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 87
Power Supply
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 88
Power Supply
Note that, if the battery voltage is less than 20V DC, the button will
have no affect (hardware controlled).
Troubleshooting:
In some cases the voltage can be slightly above 20V DC and drop
rapidly to below 20V DC. The relay will then tend to chatter. In this
case, it is recommended that the system is not started until the battery
is fully charged.
Charger +24V
Charger 0V
Earth
F8 Charger
F7 F8 F7 Battery
E-2868
BP-410/01 T10 T10
AH AH
BP-405/01 T5 T5
5 Therm.+ AH AH
4 Therm.- 5 1 J17 1 2 3 J25
3 PSF J20
2 -V BATT
1 Vcon + -
S2:
Start on
standby source
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 89
Power Supply
The power has two modes of user interaction; standalone (S6.3 OFF)
or with communication to the AutroSafe system.
S5 1 2
AFB Earth Fault Off OFF OFF
AFB Earth Fault On ON ON
Dipswitch S5
J2
1 AFB A
2 AFB A" 1 6
1 A
3 AFB CT A 2 A
4 AFB Earth Fault Sense 3 R
5 AFB B 4 F
6 AFB B" 5 F
6 F
7 AFB CT B
8 AFB Earth Fault Sense
F1
J19 F2
+ 0V
A1
S1 Reset
8
7 S1 Reset button
6
+ 0V
5
High
X11
A2
4 AutroFieldBus
3 Address Switch
J18 2
Low
X10
F3 B1 A
F2AL
J23 F4 B2
F2AL
+ 0V
B2
F5 C1
F2AL 1 Earth Fa
J22 2 Battery
3 AFB pre
+ 0V
C1
F6 C2 4
F2AL 5 Battery
6
1 6
ON
J21 S6 Dipswitch S6
OFF
+ 0V
C2
Charger +24V
F8 Charger
F7 F8 F7 Battery
BP-410/01 T10 T10
AH AH
BP-405/01 T5 T5
5 Therm.+ AH AH
4 Therm.- 5 1 J17 1
3 PSF J20
2 -V BATT
1 Vcon + -
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 90
Power Supply
Dipswitch table – S6
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 91
Power Supply
12.10 Connectors
Connector Description BPS-405 / BPS-410
J25 Power Supply To BSP-405 (Mean Well Power Supply)
J20 Battery To Battery 27,3VDC charging
connector
J17 Temp. Applies to BPS-405 only.
sensor/Mean Temperature sensor (close to battery) and Mean
Well Control Well PSU
(1-3) from power, (4-5) temp. sensor
J26 1-3 Powernet Applies to BPS-410 only.
control Control wires for power supply.
J26 4-6 Fault Relay Applies to both BPS-405 and BPS-410.
Fault Relay (NO, NC, com) Fault output.
J19 Output A1 24V/2A (BSA-400 Vin1 +/0V)
J18 Output A2 24V/2A (BSA-400 Vin2 +/0V)
J24 Output B1 24V/2A, general power output
J23 Output B2 24V/2A, general power output
J22 Output C1 24V/2A with interrupt at init
J21 Output C2 24V/2A with interrupt at init
The power outputs have different properties. They can all deliver 2A
each (limited by total power available).
Output Description
Output A These will always be ON. Will be turned OFF by a
short- circuit only.
Output B These are initially ON, but may be switched OFF/ON
from AutroSafe.
Output C These will be turned OFF during start-up of BSF-400
(initialization). May be switched OFF/ON from
AutroSafe. Power to I/O modules.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 92
Power Supply
If for any reason the BSF-400 restarts, it takes 5 seconds before the
fault relay is in the correct position:
J26.4 (normally open contact): closed contact when the unit is not
supplied with power or there is a fault on the unit
J26.5 (normally closed contact): closed when no faults exist
J26.6 (common): common for fault relay
Fault relay
NO J26.4
CPU Watch
dog NC J26.5
COM J26.6
Note that the fault relay will not be turned over for communication
faults on the AutroFieldBus.
The green and red LED beneath the cover are indicators for AFB-RX
and – TX. Hearbeat is indicated when these LEDs are blinking
simultaneously. Rapid blinking indicates heavy traffic on the
AutroFieldBus. If the red LED is weak and the green one is not lit,
there is no communication between the BSF-400 board and the
AutroFieldBus.
All blinking LEDs, except where otherwise stated, will blink with 0,5
seconds ON and 0,5 seconds OFF.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 93
Power Supply
This is conducted by lowering the PSU voltage so that all loads are
powered from the batteries for a period of 60 seconds, then a built in
resistor is turned ON for 2 seconds. BPS-405/BPS-410 will then
measure the voltage increase between the resistor ON and OFF and
thus calculate the battery resistance. This measurement includes the
wires to and from the battery.
The battery high resistance fault is given when the total resistance of
the battery and battery cables is:
Type Resistance
Power Unit BPS-405 0.8Ω
Power Unit BPS-410 0.6Ω
IMPORTANT:
To be safe, remove regular fuse before troubleshooting external faulty
equipment.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 94
Power Supply
Diagnostic outputs are given onboard with LEDs and alarm relay, and
on AutroSafe panels with audible alarms and display messages.
The LEDs and fault relay will not indicate any failure before the
AutroSafe has AutroFieldBus connection and the AutroSafe system
has been initialized.
Diagnostic outputs are given onboard with LEDs and fault relay.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 95
Cable Specifications
PowerLoop Dual shielded The Power 1000m. The PowerLoop Maximum loop
cable, twisted pair Loop Calculator Tool shall be used to resistance
cables shall be Calculator determine the permissible cable depends on load.
used. Tool shall be length. Dual shielded cable shall
used to be used. The PowerLoop
determine the Calculator Tool
cable Long parallel PowerLoop cable shall be used to
dimension. runs may introduce cross-talk determine the
Typically CSA between PowerLoops, thus it is maximum
2
2,5mm recommended to avoid such resistance.
long parallel runs. The
permissible length of parallel
PowerLoop cable runs will
depend on the quality of the
cable shield. Segregation of
parallel PowerLoop cable runs
by 30cm (1 feet) will increase
permissible parallel length
significantly. Contact Autronica
for design-advice for
applications with long parallel
PowerLoop cable runs.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 96
Cabling Cable type / Cable Maximum cable length (m) Cable Specifications
Maximum resistance
category dimension (Ω) / capacitance (F)
2
(mm )
AutroFieldBus Twisted-pair Short length cables (< 600m): Characteristic
(AFB) cables. The cable length is limited to 600m. impedance 100 ohm +/-
Category 4, 5 or 6 Capacitance per 1000m shall be less 15%.
For example, ABB than 200nF. Attenuation @100KHz,
art. no 10892 30 Max. 9 dB over full cable
CAT.5 FTP Medium length cables (< 1000m): segments (or between
2
4x2/0.5mm The AutroFieldBus cable length is limited boosters).
Fibre, to 1000m. Capacitance per 1000m shall
SGL/Multimode be less than 100nF. Attenuation is defined by
the wire to wire
Shielded cable Cable length > 1000m: capacitance mostly, as
required. Boosters shall be used if the long as the wire is at
2
AutroFieldBus cable is more than 1km in least 0.5mm . The total
length. Boosters shall be evenly spread attenuation of the cable
round the AFB ring. NOTE: The length shall not exceed
maximum length for a total ring with 9 dB. If attenuation is
Boosters is 2,8km (see also rightmost not specified, normally
column). the capacitance is
defined. The
The booster can also be used in cases capacitance shall not
when different cable types (AFB cables) exceed the specified
are used in a distributed system (see value in order to achieve
also rightmost column). the total communication
length.
Page 97
Cable Specifications
Cat5e/Cat6
Type indication FTP
Unmanaged
FL SWITCH SFNT 5TX 100m
FL SWITCH SFNT 8TX 100m
FL SWITCH SFNT 4TX/FX 100m
FL SWITCH SFNT 7TX/FX 100m
Managed
FL SWITCH LM 5TX 100m
FL SWITCH LM 8TX 100m
FL SWITCH LM 4TX/FX 100m
FL SWITCH LM 4TX/2FX 100m
FL SWITCH LM 4TX/FX SM 100m
FL SWITCH LM 4TX/2FX SM 100m
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 98
Cable Specifications
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 99
System Shielding and Earthing
14.1 Definitions
Local Frame Earth
The electrical connection to the framework at the described physical
position, such as the frame or chassis of a cabinet, the power cable
outlet etc.
Shield
Conductive structure encapsulating the wire in a harness or cable,
normally in the form of a mesh or foil forming a Faraday cage.
Armour
Mechanical protection to avoid physically damaging electrical cables
or circuits.
Earth
Synonym for Earth, in this handbook Earth is used.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 100
System Shielding and Earthing
Please note that an Integrated Fire and Gas system with PowerLoop
shall by no means be designed as a single earth system. Refer to
section 14.3 for details about keeping the PowerLoop as a dual earth
system.
PLA+ 6
PLA- 7
IE 8
IE
BSD-340
PLB+ 9
PLB- 10
Max 30 cm
This implies that the internal cabling in a rack or enclosure where the
BSD-340 and / or the Loop Units are installed also needs to be fully
shielded. The requirement includes termination / junction boxes and
all field wiring as well.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 101
System Shielding and Earthing
PLA+ 6
PLA- 7
IE 8
IE
BSD-340
PLB+ 9
PLB- 10
Note jumper !
If there are break-outs from the main loop (to make local small loops
that return to the same break-out box), care shall be taken to avoid
local closed loops. See the figure below.
PLA+ 6
PLA- 7
IE 8
IE
BSD-340 Break!
PLB+ 9
PLB- 10
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 102
System Shielding and Earthing
PLA+ 6
PLA- 7
IE 8
IE
BSD-340 PE PE
PLB+ 9
PLB- 10
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 103
System Shielding and Earthing
BSD-340
AFB-A
BSL- BSL-
AFB-A’
AFB-CT
322 Fiber 322
IE
EAU-341 /
BSA-400 1
AFB-B
AFB-B’ BSL-
AFB-CT’
325
3 Junction
2 BSD-340
Box
An alternative is to rather bring the reference from the other side of the
Booster across it, to continue the shield in that way. Note that the bus
needs to be referenced by connecting the CenterTap (pin 3 or 6) to
Earth. On the left side, this is ensured by the AFB-CT to Earth at the
EAU-341 / BSA-400, while the BSL-325 right side needs to be tied to
Earth or to the reference of It’s left side, by for instance connecting pin
3 to 6.
Further on, the BSL-322 to BSL-322 also isolates. If there had been
several fiber jumps, each individual cable segment between the fiber
segments would have to be earthed. In this case, the segment
following passes through a BSD-340, the shield is kept continuous
and it is referenced to Earth at Earthpoint 1, close to the EAU-341 /
BSA-400. An alternative to this would be to terminate at the other end
of this segment, at the BSL-322.
The main rule is: Ensure that all segment’s shield are terminated at
one end and one end only.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 104
System Shielding and Earthing
Care shall be taken to avoid two units monitoring the same segment,
as they may interfere with each other on this feature.
All earth fault monitoring is done towards Instrument Earth (IE) in the
units.
For a normal system the Earth voltage level is floating between plus
and minus in order to be able to monitor an earth fault. If you measure
between the battery minus and earth on a healthy system, you will find
a difference on 3-5V. The plus terminal and earth will have a
difference of approximately 22-25 V (the charger load is 27 V DC).
Such faults are most likely to occur on one of the detection loops.
If the system still has this fault after all external wires are
disconnected, the problem is either on the main board itself, the
batteries or the power supply.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 105
System Shielding and Earthing
Example 1
In this example there is only one earth fault detection zone. The earth
fault monitoring for the BSF-400 must be switched off so it does not
interfere with the BSL-310 earth fault detector, as these use different
earth voltage potentials. If there is an earth fault present in this system
the whole system must be searched to find the earth fault.
Example 1
Switch S6.1 OFF
Earth Fault
Monitoring
deactivated
BSF-400 BSA-400
BSL-310
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 106
Example 2
In this example, both the BSL-310 and BSF-400 will monitor for earth
faults. This will divide the installation into two separate earth fault
zones with different earth potential; 3,5 VDC and 12 VDC. Any fault
detected by the BSL-310 will be located on the same side of the
galvanic isolator as BSL-310, and vice versa for BSF-400.
Switch S6.1 ON
Example 2
Earth Fault
Galvanic Monitoring
isolator activated
3,5V DC 12V DC
BSL-310 BSF-400
BSA-400
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 107
Service and Maintenance
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 108
Service and Maintenance
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 109
Service and Maintenance
Step Description √
2 Make sure that possible changes in the building structure or storage environment have not
affected the detectors’ capability to detect a potential fire.
3 Make sure that the detectors are not covered with paint or contaminated with dust or dirt.
Check the log for contaminated detectors (Service/Log menu).
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 110
Service and Maintenance
1 To test the panel indicator lights and internal buzzer, press and hold the Reset button for at
least 5 seconds. All indicators are lit and the buzzer is turned on. The test will automatically
stop. The lamp test can be performed in access level 1 (no use of key).
2 Test all operating keys by pressing each key (refer also to Operator’s Handbook):
All buttons will give a short "Beep" when pressed, except Mute button, Menu button and
Reset System button (plus the ones that are not supported, see below).
Menu button
Close Window button
Alphanumeric keyboard
Manoeuvre buttons
Note that the left/right arrow buttons and the two buttons in the lowermost right hand corner
(indicated with a white line) are not yet supported:
3 Perform a visual and functional inspection of manual call-points and automatic detectors.
Check the log for contaminated detectors (Service/Log menu).
4 Disable any alarm transference to the Fire Alarm Routing Equipment -FARE output.
5 Activate the alarm system. Test all sounders by activating an alarm from a corresponding
manual call-point.
7 Activate alarms from at least one detector/manual call-point in each zone and a check that all
respective outputs are activated.
8 Test the action of any auxiliary operating functions (disabling, cancelling and resetting
buttons).
9 Check the alarm transference outputs by connecting from outgoing outputs (potential free
relay and 24V output) activated by alarm in a zone.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 111
Service and Maintenance
Step Description √
10 Check the fault warning function from detector zones by removing a detector in each zone.
Activate a fault (remove battery fuse) and observe:
- the Fault indicator starts to blink
- a fault warning is displayed
- the internal buzzer is turned ON
- the Fault Warning Routing Equipment (FWRE) output is activated (if any)
12 On completion of checks, ensure that only the green "Power" indicator is ON when the panel
is in its idle state (normal operation).
13 Enable alarm transference to the Fire Alarm Routing Equipment -FARE output.
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Page 112
Reader’s Comments
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Reader’s Comments
Name: ------------------------------------------------------------------------------------------------
Title: ------------------------------------------------------------------------------------------------
Company: ------------------------------------------------------------------------------------------------
Address: ------------------------------------------------------------------------------------------------
------------------------------------------------------------------------------------------------
------------------------------------------------------------------------------------------------
Telephone: ------------------------------------------------------------------------------------------------
Fax: ------------------------------------------------------------------------------------------------
Date: ------------------------------------------------------------------------------------------------
Tel: + 47 73 58 25 00
Fax: + 47 73 58 25 01
www.autronicafire.com
Installation Handbook, AutroSafe Interactive Fire Detection System, Release 4, 116-P-ASAFE-INSTALL/DGB Rev. H, 2013-02-20,
Autronica Fire and Security AS
Autronica Fire and Security is an international company, headquartered in Trondheim, one of the largest cities in Norway.
The company is owned by United Technologies Corporation and employs more than 319 persons with experience in developing,
manufacturing and marketing of fire safety equipment. Our products cover a broad range of systems for integrated solutions,
including fire detection systems, integrated fire and gas detection systems, control and presentation systems, voice alarm
systems, public address systems, emergency light systems, plus suppression systems.
All products are easily adaptable to a wide variety of applications, among others, hospitals, airports, churches and schools, as
well as to heavy industry and high-risk applications such as power plants, computer sites and offshore installations, world wide.
The company's strategy and philosophy is plainly manifested in the business idea:
Protecting life, environment and property.
Quality Assurance
Stringent control throughout Autronica Fire and Security assures the excellence of our products and services. Our products are
CE marked and developed for worldwide standards and regulations, and conform to the CEN regulation EN54. Our quality
system conforms to the Quality System Standard NS-EN ISO 9001:2000 and is valid for the following product and service
ranges: marketing, sales, development, engineering, manufacture, installation, commissioning and servicing of suppression,
integrated fire and gas detection and alarm systems, plus petrochemical, oil and gas instrumentation systems for monitoring and
control.