Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

HYDROBLOC system

Pressure reducing function - Series K1 10

Description:
Control valve for reducing and stabilising downstream pressure.

Functions:
• R educes and stabilises the pressure of a downstream network, supplied
by an upstream pipe at a greater pressure, regardless of variations in the
upstream pressure and flow rate.
•  C
 loses distribution and restores manual control.

Examples of applications:
•  C
 ontrolling and linking staged networks.
•  S
 upplying a low-pressure network from a high-pressure network
•  B
 alancing supply to a gridiron system from several supplies with different
Fig. I 02 higher pressures.

Operation of the pressure reducing pilot circuit (Fig. I):


•  T
 he action of the pilot’s spring (blue arrow) determines the downstream
01
pressure setting value and tends to open water flow into the pilot.
•  T
 he downstream pressure (green zones) is exerted under the pilot’s
diaphragm and counters the action of the spring. Increasing the downstream
pressure tends to reduce water flow into the pilot (see T manual Pressure
reducing pilot series 51).
•  D
 ark blue zone = upstream pressure, green zone = downstream pressure,
light blue zone = variable balance pressure between the orifice plate (01)
and the pilot.
•  T
 he opening speed controller RO (02) enables to control the draining of the
chamber. The filling of the chamber is not adjustable to ensure the safe
closing of the device.

Operation of Hydrostab pressure reducing control valve:


•  T
 he control valve reproduces the movements of the pilot device:
- Downstream pressure increases: the pilot closes, Hydrostab closes.
- Downstream pressure decreases: the pilot opens, Hydrostab opens.
- Downstream pressure is stable: the pilot regulates, Hydrostab regulates.

This manual supplements:


•  T
 manuals: Hydrobloc System General - Pressure reducing pilot
series 51 - Hydrobloc System Specifications.
•  W
 manuals: Hydrostab pressure reducing valve Operation - Hydrostab
pressure reducing valve Maintenance.

BAYARD - Series K1 10 - T14003


HYDROBLOC system - Pressure reducing function 2

Item Part name No. Materials Standards


01 Main valve 1 See details T manual Hydrobloc System
05 06 07 02 Mesh filter G 3/8 1 Bronze + copper alloy + stainless steel
03 Orifice plate in the filter 02 1 Stainless steel 316L / 1.4404 NF EN 10088
04 Ball valve FF G 3/8 3 Nickel-plated copper alloy
04
05 Fittings and pipes kit 1 Stainless steel 316L / 1.4404 NF EN 10088
06 Position indicator 1 Brass/CW614N + glass + EPDM NF EN 12164
08
02 07 Pressure reducing pilot (NO) G 3/8 1 See T manual Pressure reducing pilot Series 51
09 08 Opening speed controller RO 1 Brass/CW614N + stainless steel A1 + EPDM NF EN 12164 +
NF EN ISO 3506
10 09 Cross connector 1 Stainless steel 316 / 1.4401 NF EN 10088
10 Pressure gauge valve G 3/8 2 Nickel-plated copper alloy

Choosing the model:


01 •  X
 GS model is recommended for network operations in which the Δp available is
higher than or equal to 1 bar (Fig. III).
•  I f the Δp available is constantly lower than 1 bar, we recommend an XG model
03
(Fig. IV).
•  W
 hen the flow rate is low and the Δp available is higher than or equal to 1 bar
(Fig. III) and falls below 1 bar when the flow rate is high (Fig. IV), it may be necessary
to install an in-line model to withstand high flow rates and a small Ø model as
bypass for minimum flow rates. Please consult our Customer Technical Support.

Installation:
In-line mounting
•  Make sure the manhole is drained and ventilated for the safety of the operators and the proper operation of the
3-function air valve.
•  01 - Gate valve Series B1 20, 25 or 92, essential for the setting and for the yearly maintenance of the strainer box and
the 3-yearly maintenance of the control valve.
•  02 - Strainer box Series F3 10, necessary for protecting the device in the presence of foreign bodies.
•  03 - Hydrostab pressure reducing valve Series K1 10.
•  04 - Dismantling joint Series C1 55 or C4 30.
•  05 - Pressure reducing valve Series B1 20, 25 or 92, useful for the safe filling of the downstream network with water.

Optional depending on the network configuration:


•  06 - Vannair air valve Series F1 10 or 20, to guarantee a stable control and a safe and optimal operation of the
installation. Placed downstream.
•  07 - Djet safety valve Series F1 30.

01
06 07

03
02
05

04

Specifications and performance may be changed without


BAYARD notice as a result of technical developments. Images and
Tél. + 33 (0)4 37 44 24 24 - www.bayard.fr photos given for illustration purposes only.
BAYARD - Series K1 10 - T14003