Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 125

This document is the property of GVPR ENGINEERS LIMITED and must not be passed on to any third person or firm

not authorised by us, nor be copied/made use of in full or part by such person or firm without our prior

19/03/21 A FOR APPROVAL PSD DHC


DATE REV. NO. DESCRIPTION Designed Checked Approved
REVISIONS

GVPR ENGINEERS LIMITED


PLOT No.739-A,No.82-293/82/A, Road No. 37,
Jubilee hills,Hyderabd Telangana,India.
CLIENT : CONSULTANT :

CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR
PROJECT :
DISTRICT -SONBHADRA

GVPR ENGINEERS LIMITED


SUPPLIER / CONTRACTOR: PLOT No.739-A,No.82-293/82/A, Road No. 37,
Jubilee hills,Hyderabd Telangana,India.
permission writing.

JOB No. GVPR-250KL-25M-001

TOTAL NO. OF PAGES TITLE :


NAME SIGN DATE
DSGN PSD PSD 15/03/21 RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C)
CHKD DHC DHC 19/03/21 UTTAR PRADESH
APPD

CODE REV.

DOC. No. G V P R U P 2 5 0 25 M 0 0 1
IS A

RELEASED FOR PRELIMINARY TENDER INFORMATION P APPROVAL CONSTRUCTION


GVPR ENGINEERS LIMITED
Document No. Rev.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO
Project : GROUP OF VILAGES BLOCK -DUDDHI, BABHANI AND
MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

Design Check Date


RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM
Title : GHATI (Zone-C) UTTAR PRADESH PSD DHC 3/19/2021

INDEX
1.0 Introduction
1.1 General
1.2 References
1.3 Design Philosophy
1.4 Material Specification
1.5 Permissible Stresses in materials
1.6 Analysis

2.0 Tank dimensions and Volume Calculations

3.0 Membrane Analysis


3.1 Parameters
3.2 Design of Top Dome
3.3 Design of Top Ring Beam
3.4 Design of Cylindrical Side Wall
3.5 Design of Middle Ring Beam
3.6 Design of Conical Dome
3.7 Design of Bottom Dome
3.8 Design of Bottom Ring Beam
3.9 Crack Width Calculation
Crack Width Calculation for Top dome
Crack Width Calculation for Top ring beam
Crack Width Calculation for side wall (Bending moment)
Crack Width Calculation for side wall (Hoop tension)
Crack Width Calculation for Middle Ring beam
Crack Width Calculation for conical wall
Crack Width Calculation for Bottom dome
Crack Width Calculation for Bottom ring beam (Bending moment)

4.0 Load Calculations


4.1 Dead Loads
4.2 Live Load
4.3 Water Load
4.4 Wind Loads
4.5 Seismic Loads
4.6 Hydro Dynamic Analysis

5.0 Design of Column(Staad Out put)

6.0 Design of Brace Beam(Staad Out put)

7.0 Design of Footing


7.1 Design of Annular Raft
7.2 Design of Ring beam
8.0 Design of Stair Case
8.1 Staircase

9.0 Annexures
ANNEXURE -A :- Table 10 & 12 Of IS 3370 (PART-IV)-1967 for Moment and Hoop Coefficients
ANNEXURE -B :- Ductile Detailing Of Column as per IS 13920 : 2016
ANNEXURE -C :- Ductile Detailing Of Beam as per IS 13920 : 2016
ANNEXURE -D : Summary of weight of tank & Staging from Stadd
ANNEXURE -E : Summary of displacemnets from Stadd
GVPR ENGINEERS LIMITED
Document No. Rev.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK -
Project : DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) UTTAR Design Check Date
Title : PRADESH
PSD DHC 3/19/2021

1 INTRODUCTION:
1.1 General:
This document covers the design of Elevated service reservoir (Intze Type) with
Capacity = 250 Cum having a staging height = 25 m
The design of OHR includes the design of Roof Dome, Cylindrical wall, Conical Dome, Bottom dome,
Gallery Platform (Walkway Slab), Bottom and top Ring beam , Columns, Tie beams, Foundation
and Staircase.

The following Primary Loads are considered in the design of the tank portion
a) Dead Load
b) Live Load
c) Water Load inside the tank upto top of the cylindrical wall including free board.
d) Wind loads
e) Seismic loads
f) Combination of all the above loads.

1.2 References:
a) IS:456- 2000 - Plain & Reinforced Concrete - Code of Practice (Fourth revision)
b) IS:3370 - 2009 - Code of practice for Concrete Structures for the Storage of Liquids
Part I - General Requirements
Part II - Reinforced Concrete Structures

c) IS:1893 (Part: 2) - 2014 - Criteria for Earthquake resistant Design of Structures (Fifth revision)
d) IS:875 - Part: 1 to 3 - 1987 : Dead, Live and Wind Loads
e) IS:13920 - Ductile detailing of RCC Structures subjected to Seismic forces - Code of Practice

1.3 Design Philosophy :


Limit State Method of Design is adopted for the design of Water Retaining Members, Staging
and Foundation.

1.4 Material Specifications:


a) Grade of Concrete M 30
b) Grade of steel Fe 500
GVPR ENGINEERS LIMITED
Document No. Rev.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK -
Project : DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) UTTAR Design Check Date
Title : PRADESH
PSD DHC 3/19/2021
1.5 Permissible Stresses in materials ( as per IS 3370 (Part:2) - 2009)
Permissible Stresses in Concrete:
Relating to Resistance to Cracking
a) Direct Tension = 1.5 N/mm2 (From Table:1)
b) Bending Tension = 2.0 N/mm 2 (From Table:1)
Relating to Strength Calculation
a) Direct compression = 8 N/mm2 (From Table:2)
b) Bending compression = 10 N/mm2 (From Table:2)

c) Characteristic compressive strength in concrete = 30 N/mm2 (from IS: 456)


Permissible Stresses in Steel:
a) Tensile Stress in steel under bending, direct tension
and shear for water retaining members = 130 N/mm2 (From Table:4)
b) For Staging and Foundation design strength in steel = 500 N/mm2 (from IS: 456)

1.6 Analysis :
Finite Element Analysis of ELSR is done by using STAAD Pro Software.
As Per IS 1893 Part 2 : 2014, P-∆ Analysis for staging is performed.
GVPR ENGINEERS LIMITED
Document No. Rev.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK -
Project : DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) UTTAR Design Check Date
Title : PRADESH
PSD DHC 3/19/2021

2.0 Tank Dimensions and Volume Calculation

Required Capacity of ELSR = 250 m³


Diameter of the Cylindrical Portion, D1 = 10 m
Height of Cylindrical Portion, h1 = 2.95 m
Angle subtended by the conical slab with horizontal, f = 45 deg
Size of columns = 0.45 m dia
Height of the Conical Portion, h2 = 1.25 m
Diameter at base of Conical portion, D2 = 7.5 m
Height of the Bottom Dome, h3 (including thickness) = 1.10 m
Height of the Top Dome, h' = 1.60 m
Radius of Bottom Dome, R1 [ (D2/2)^2/h3 + h3] / 2 = 6.942 m
Radius of Top Dome, R2 [ (D1/2)^2/h' + h'] / 2 = 8.613 m
Free board = 0.30 m
Cylindrical Portion(including freeboard), V1 = (p x D12)/4 x h1 = 231.69 m3
Conical Portion, V2 = (p/12) x h2 x (D12 + D22 + D1 x D2) = 75.68 m3
Vol. occupied by the Bottom Dome in conical portion, V3 = (p h /3) x (3R1 - h3)
3
2
(-) = 25 m3
Volume of free board (-) = 23.56 m3

Height of Bottom of Outlet to base of the bottom dome, h4 = 0.15 m


Diameter of conical dome at 0.15 m above base (at outlet), D4 = 7.80 m
Conical Volume between outlet and base, V4 = (p/12) x h4 x (D42 + D22 + D4 x D2) = 6.90 m3
Rise of the bottom dome above outlet, h5 = 0.95 m
Vol. occupied by the Bottom Dome in conical portion above outlet, = 18.78 m3
Volume of dead storage, Vd (-) = 0.68 m3
Total Effective storage of Water = 258.13 m3
STAAD MODEL- ISOMETRIC VIEW
GVPR ENGINEERS LIMITED
Document No. Rev.
Project : CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK
-DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

3.0) Membrane Analysis:


3.1 Parameters:
3.1.1 Strength parameters
a) Grade of Concrete: M 30

Direct tension stress, σct = 1.5 N/mm²


Direct compressive stress, σCC = 8.0 N/mm²
Bending tensile stress, σCbt = 2.0 N/mm²
Bending comp stress, σcbc = 10 N/mm²
Characteristic comp strength fck = 30 N/mm²
Shear = 2.2 N/mm²

(b) Grade of Steel bars: Fe 500

Tensile Stress in members under direct tension = 130 N/mm²


Tensile stress in members in bending : = 130 N/mm²
Tensile stress in Shear Reinforcement : = 130 N/mm²
Compressive stress in columns subjected to direct load = 140 N/mm²

Min Area of Reinforcement for Walls:


Min Area of Reinforcement = 0.35 %

For M30 Concrete ; Design Constants :


σst = 130 N/mm²
σcbc = 10 N/mm²
m = 280 / ( 3 x σcbc ) = 9.33
r= σst / σ cbc = 13
K= m / ( m+r ) = 0.42
j= 1-(K/3) = 0.86
Q= 0.5 x σ cbc x k x j = 1.81

σst = 275 N/mm²


σcbc = 10 N/mm²
m = 280 / ( 3 x σcbc ) = 9.33
r = σst / σ cbc = 27.5
K = m / ( m+r ) = 0.25
j= 1-(K/3) = 0.92
Q = 0.5 x σ cbc x k x j = 1.15

For Un Cracked Section :


Permissible Bending Tension = 2.0 N/mm²
M.R = Qbd2 = (1/6) xb x d2 x f
Q=(f/6) = 0.33
Considering Reinforcement, Q = 0.35

3.1.2 Design Data :


Capacity = 250 KL
Staging = 25 mt
Seismic Zone = III
GVPR ENGINEERS LIMITED
Document No. Rev.
Project : CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK
-DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

3.1.3 Hydraulic features :


Ground level = 409
Lowest water level (LWL) = 434
Max water level (MWL) = 437.75
Dead storage = 0.15
Free board = 0.30
Effective Water depth H =437.75-434 = 3.75 m

3.1.4 Member sizes :


No. of Rows of Columns = 1
No of columns in a row = 6 No.s
No of Braces (including GL) = 7 Levels
Inside Dia of container D1 = 10 mt
C/C Dia of Columns D2 = 7.05 mt
Thickness of Top dome at Crown = 125 mm
Thickness of Top dome at Springings = 150 mm
Rise of Top Dome h1 = 1.60 mt
Thickness of Bottom dome at Crown = 175 mm
Thickness of Bottom dome at Springings = 200 mm
Rise of Bottom Dome h2 = 1.10 mt
Thickness of Conical Bottom = 200 mm
Size of columns = 450 Ф mm
Size of Braces = 300 x 500
Size of Top ring beam = 300 x 300
Size of Bottom ring beam = 450 x 750
Size of Middle Ring Beam (Walkway slab) = 1100 x 150/250
Thk of Cylindrical side wall = 200 mm
Ht of Cylindrical Portion Excluding Free Board Portion h3 = 2.65 mt
Ht of Conical Portion Including Dead Storage Portion h4 = 1.25 mt

3.1.5 Loads
Wind Velocity = 47 m/s
Live Load on Roof = 1.5 kn/m2
Live Load on Walkway Slab = 3.0 kn/m2
Density of concrete = 25 kn/m³
Density of water = 10 kn/m³

3.1.6 Soil Parameters :


Safe bearing capacity of soil considered = 12 T/m²
Depth of foundation below G.L = 2.5 mt

3.2) DESIGN OF TOP DOME:-


Chord Length of Top Dome = 10 mt
Thickness of top dome
at Crown = 125 mm
at springings = 150 mm
Rise of top dome h = D/6 to D/8 = 1.6 mt
Radius of Top Dome R (2R-h1)h1 = (D2/2)2
(10^2 / 8 x1.6)+1.6/2 = 8.61 mt
From Right angled Triangle H' = √(8.61^2-5^2) = 7.01 mt
GVPR ENGINEERS LIMITED
Document No. Rev.
Project : CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK
-DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

Load:
Average Thickness of Dome = 137.5 mm
Self weight = 0.1375*25 = 3.4375 kN/m²
Live load = 1.5 kN/m²
Finishes = 1.0 kN/m²
Total load W = 5.938 kN/m²
Say W = 6 kN/m²
Total vertical load on Dome = 2π*8.61*1.6*6 = 519.3 KN
Load per meter of periphery w = 519.34/π*10 = 16.53 kN/m
Sin θ = 5/8.61 = 0.581 `
Cos θ = 7.01/8.61 = 0.814
θ = 35.500 < 510 48”
Hence the entire dome is under compression.
Meridional Thrust T = WR / (1 + Cos θ) (Maximum at springings i.e.at θ =35.5)
6*8.61/(1+0.81) = 28.48 Kn/m
Max. Meridional stress
28475.84/(137.5*1000) = 0.21 N/mm²
Horizontal Thrust H = TCos θ
28.48*0.81 = 23.18 kN
Hoop stress = [wR / (1 + Cos θ)] x (-1 + Cos θ + Cos θ2)/(t x 100)
Hoop stress at springings i..e., θ =35.5
28475.84*(-1+0.814+0.663)/(137.5*1000) = 0.10 N/mm²

Max Hoop stress at crown i..e., θ = 00 , cos θ = 1


0.006*8610/(1+1)*(-1+1+1)/(137.5*1000) = 0.1879 N/mm²
Shear stress =16.53/(13.75*100) = 0.12 N/mm²
< stresses
All the stresses are with in the limits and the dome is in pure compression and 2.2are very low. HenceHence
N/mm² safe
provide
minimum reinforcement to take care of temperature and shrinkage stresses
As per Clause 7.10 of IS 3370 Part-II minimum reinforcement to be provided.
Ast = (0.35/100) x 125 x 1000 = 437.5 mm2
Dia of Bar = 10 mm
Area of Bar = 78.54 mm2
Required Spacing = 179.52 mm
Provide Spacing = 150 mm
Provided Area of Steel = 520 mm2

Provide 10 dia tor @ 150 mm c/c Radially and Circumferentially @ bottom (spacing measured at springings)
Bending Moment
Moment due to end restraint (at Springings) = WRt/4 √3 ( Refer Page no 552 of Timoshenko & Waimnesky)
6*8.61*0.15/(4*sqrt(3)) = 1.12 knm
Factored Bending moment = 1.68 knm
Effective thickness = 75 mm
Mu/bd^2 = 0.3
From SP16 table 4 Ast required = 0.07
Ast required = 53 mm2
Dia. Of bar ( f ) = 10 mm
Area of Bar = 79 mm2
Required Spacing = 1490 mm
Provided Spacing = 150 mm
Provided Area = 526.67 mm2
GVPR ENGINEERS LIMITED
Document No. Rev.
Project : CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK
-DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

Stiffen the dome over a length of 0.76√ Rt=0.76*√8.61*0.15 = 0.864 mt


Say = 1.00 mt

Increase the edge of the dome slab to 15 cm and reduce to12.5cm at 1mt from edge and provide extra rods 10mm dia
@150mm c/c on top face both Radially & Circumferentially in1 mtrs length to take care of edge moments

3.3) Design of TOP RING BEAM: 300x300


Width of Top ring beam = 300 mm
Depth of Ring Beam = 300 mm
C/C Length of top ring beam = 10.3 mt
Hoop Tension T = HxD/2
23.18*5.15 = 119.38 kn
Max hoop tension = 1.5* Hooptension/0.50*fy
= 1.5* Hooptension/0.50*500
Area of steel required = 651.16 mm2 on both faces
= 325.58 mm2 on each face
Clear Cover = 45 mm
Effective Depth = 249 mm
Dia of Bar = 12 mm
Area of Bar = 113.1 mm2
Required no of Bars = 5.76 no's
Provide no of Bars = 6 no's
Provided Area of Steel = 678.6 mm2
Provide 6 nos of 12 tor
Provide a nominal shear reinforcement - 8 dia tor 2L stirrups @ 200 mm c/c throughout

3.4) DESIGN OF SIDE WALL:-


The top dome is designed on membrane theory and hence the side wall is taken to be free at top.
At base, the side wall is neither truly fixed nor truly hinged, but very nearer to fixed condition.
The side wall is designed for fixed base and free top for moments and hinged base and free top for Hoop tension as per IS
: 3370 Part IV – 1967,
Inner diameter (D) = 10 mt
Water depth (M) = 2.65 mt
Free Board = 0.3 mt
Total Water Depth For Design H = 3.25 mt
The thickness of side wall = 0.2 mt
H2/Dt =3.25^2/ (10 x0.2) = 5.28 mt
Hoop Tension :
Max Hoop Tension for side wall is considered to be Hinged bottom and free top
Refer ( Appendix-1) Table-12 of IS:3370:Part-1V
Hoop tension T = (Coefficient) WHR
T = ( Coefficient ) x10 x 3.25 x 5
Max Hoop tension coefficient is @ 0.7 H from top
= 0.6232
Hoop tension T = (Coefficient) WHR = 101.27 Kn
Area of steel required = 1.5* Hooptension/0.50 *fy
= 1.5* Hooptension/0.50 *500
= 607.62 mm2 on both faces
= 303.81 mm2 on each face
Minimum Area of steel = 0.35x200 = 700 mm²
Effective Depth = 150 mm
The Cylindrical wall is designed for Hoop tension .
GVPR ENGINEERS LIMITED
Document No. Rev.
Project : CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK
-DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

Dia of Bar = 10 mm
Area of Bar = 78.54 mm2
Required Spacing = 220 mm
Provide Spacing = 180 mm
Provided Area of Steel = 440.00 mm2
Horizontal Steel :
Base to top
10 tor @180 c/c on each face
Vertical steel is provided for restraint and temperature effect .
Vertical Steel :
Bending moment :
Max Bending moment for side wall is considered to be fixed bottom and free top
Refer ( Appendix-1) Table-10 of IS:3370:Part-1V
Max B.M coefficient is @ 1 H for water face = -0.0212165
Max Bending Moment = (Coefficient) WH3 on water face
M =-0.0212165x10 x 3.25 ^3 = 7.28 knm
Max Bending moment Coefficient for Outer face = 0.0057
Max Bending Moment = (Coefficient) WH3 on other face
M =0.0056752x12 x 3.25 ^3 = 2.34 knm
Factored bending moment at water face = 10.92 kNm
Factored bending moment at outer face = 3.51 kNm
Effetive depth of wall required = √10.92x10^6/(0.133x30x1000)
52.31 mm
Provided Thickess = 200 mm Hence OK
Clear Cover on water face = 45 mm
Clear cover on other face = 45 mm
Effective thickness = 150 mm
Factored bending moment at water face = 10.92 kNm
Mu/bd^2 = 0.49
From SP16 table 4 Ast required = 0.115
Ast required = 173 mm2
Minimum Area of steel = 0.35x200 = 700 mm²
Water face :
Dia of Bar = 10 mm
Area of Bar = 78.54 mm2
Required Spacing = 220 mm
Provide Spacing = 180 mm
Provided Area of Steel = 436.33 mm²
Water face :
Provide 10 tor @180c/c Verticals Through
Factored bending moment at outer face = 3.51 kNm
Mu/bd^2 = 0.16
From SP16 table 4 Ast required = 0.04
Ast required = 56 mm2
Minimum Area of steel = 0.35x200 = 700 mm²
Outer face :
Dia of Bar = 10 mm
Area of Bar = 78.54 mm2
Required Spacing = 220 mm
Provide Spacing = 180 mm
Provided Area of Steel = 436.33 mm²
Outer face :
Provide 10tor @180c/c Verticals throughout
GVPR ENGINEERS LIMITED
Document No. Rev.
Project : CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK
-DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

3.5) Design of Middle Ring Beam 1100x150/250


Chord Length of Middle Ring Beam = 10 mt
Let The width of Ring Beam = 1100 mm
Depth of Ring Beam = 250 mm
Depth of Ring Beam at End = 150 mm
Average Depth of Ring Beam = 200 mm

W
2
fo
B
2

B
LOADS : 3
Load from top dome = 2*∏*R*h1*w = 519.3 Kn
Weight of Top Ring Beam = Π * (D1+b)*b*d*25
Π*10.3*0.3*0.3x25 = 72.81 Kn
Weight of Cylindrical Side Wall = Π * (D1+t)*h*t*25
Π*( 10+0.2)*2.825*0.2*25 = 452.62 Kn
Self weight of beam = Π * (D1+b) *b*h*2500
Π*(10+1100/1000)*1100*200/1000000*25 = 191.79 Kn
Live Load = 3.0 kn/m²
Load due to Railing = 1.0 kn/m²
Load due to Live load & Railing = 139.48 kn
Total Load W = 1376.0 kn
Vertical Load at ring beam level w = W / пD
Perimeter at Middle Ring Beam level = пD = 34.87 mt
Vertical Load at ring beam level w = 1376.04/34.87 = 39.46 kn/mt
Radial / Horizontal thrust H = w cotФ
tanФ = 1.25/1.475 = 0.847
Ф = 40°
cotФ = 1/ tanФ = 1.181
Radial / Horizontal thrust = 39.46*1.181 = 46.6 kn/mt
D = 10+1.1 = 11.1 mt
Hoop Tension = 46.6*11.1/2 = 258.63 Kn
Area of steel required = 1.5* Hooptension/0.50 *fy
= 1.5* Hooptension/0.50 *500
= 1551.78 mm2 on both faces
= 775.89 mm2 on each face
Ast = (0.35/100) x200 x 1000 = 700 mm²
Clear Cover on Water face = 45 mm
Clear Cover on outer face = 45 mm
Effective Depth = 197.00 mm
Dia of Bar = 16 mm
Area of Bar = 201.06 mm2
Required Spacing = 259.13 mm
Provided Spacing = 200 mm
Provided Area of Steel = 2010 mm2
No of bars required = 7.72 no
No of bars provided = 10 (5no on top & bottom)
Provide 16 tor @ 200 mm c/c Circumferentially at top & bottom
No of Bars = 7.00 no
Radial Steel
Min Area of Steel = 0.35 %
GVPR ENGINEERS LIMITED
Document No. Rev.
Project : CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK
-DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

Ast = (0.35/100) x200 x 1000 = 700 mm²


Dia of Bar = 10 mm
GVPR ENGINEERS LIMITED
Document No. Rev.
Project : CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK
-DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

Area of Bar = 78.54 mm2


Required Spacing = 224.40 mm
Provided Spacing = 150 mm
Provided Area of Steel = 523.6 mm2
Provide 10 tor @ 150 mm c/c Radially at top & bottom

3.6) Design of Conical Dome :


Thickness at Middle Ring Beam level = 200 mm
Thickness at Bottom Ring Beam level = 200 mm
Ht of Conical Portion h4 = 1.25 mt
Clear Horizontal Length between BRB & MRB = 1.25 mt
Length of Conical Slab Lc =√1.25^2+1.25^2 = 1.77 mt
W2 Ww

h2
f0

LOADS :
a) Weight of structure upto Middle Ring Beam level = 1376.0 kn
b) Weight of water in portion of conical slab
Π*(7.5+2*1.25/3)*0.5*1.25*1.25*10 = 204.53 kn
c) Weight of water above frustrum of cone
Π*(10^2 -7.5^2)*2.95/4*10 = 1013.65 kn
d) Weight of conical slab
Π*(7.5+1.25)*1.77*200*25/1000 = 243.28 kn
Total Load W = 2837.5 kn
Load per metre length w = W/ΠD
Outer Diameter D = 7.5 mt
Load per metre length w =2837.5/ Π *7.5 = 120.43 kn/m
RADIAL REINFORCEMENT : sinØ
cosecØ = 0.646
= 1.548
Meridional stress at Ring Beam = w* cosecØ / 100 t = 9.32 kn/m2
0.00932 N/mm2
permissible direct compressive stress = 8.0 N/mm2
Minimum % of reinforcement for 200mm thk Wall = 0.35 %
Minimum area of reinforcement for 200mm thk Wall = 700 mm2 both faces
Dia of Bar = 10 mm

Area of Bar = 78.54 mm2


Required Spacing = 220 mm
Provide Spacing = 150 mm
Provided Area of Steel = 523.60 mm2
Provide #10 Radially @ 150 mm c/c at both faces spacing measured at middle of conical dome

HOOP TENSION IN CONICAL DOME :


W
2
p
h
f
2 q
0

Hoop Tension T = (p*cosecØ + q*cotØ ) *D/2


GVPR ENGINEERS LIMITED
Document No. Rev.
Project : CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK
-DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

p = Intensity of water pressure


q = Unit Weight of conical bottom
P = (H+X)*10
H = 3.25 mt
X = 0 mt at middle ring beam
X = 1.25 mt at bottom ring beam
Dia of Conical Bottom at 'X' D = ( D1-2*X*cotØ )
D1 = 10.00 mt
Cot Ǿ = 1.181
cosecØ = 1.548
q = 5 kn/m2
Hoop Tension ( at any depth ' X ' ) T = ((H+X)*10*cosecØ + q*cotØ )*D/2

Hoop Tension at Middle Ring Beam Level:


X = 0 m
P = (H+X)*10 = 32.5
Dia of Conical Bottom at 'X' D = ( D1-2*X*cotØ ) = 10 m
Hoop Tension T = ((H+X)*10*cosecØ + q*cotØ )*D / 2 = 281.08 kn

Hoop Tension at Middle Height of Conical Bottom:


X = 0.625 m
P = (H+X)*10 = 38.75
Dia of Conical Bottom at 'X' D = ( D1-2*X*cotØ ) = 8.52375
Hoop Tension T = ((H+X)*10*cosecØ + q*cotØ )*D / 2 = 280.81 kn

Hoop Tension at Bottom Ring Beam:


X = 1.25 m
P = (H+X)*10 = 45
Dia of Conical Bottom at 'X' D = ( D1-2*X*cotØ ) = 7.0475 m
Hoop Tension T = ((H+X)*10*cosecØ + q*cotØ )*D / 2 = 266.27 kn

HOOP REINFORCEMENT :
Max Hoop Tension = 281.08 kn
Area of steel required = 1.5* Hooptension/0.50 *fy
= 1.5* Hooptension/0.50 *500
= 1686.48 mm2 on both faces
= 843.24 mm2 on each face
Minimum area of reinforcement for 200mm thk Wall = 700 mm2 on both faces
Dia of Bar = 16 mm
Area of Bar = 201.06 mm2
Required Spacing = 240 mm
Provide Spacing = 180 mm
Provided Area of Steel = 2230 mm²
Provide Hoops of # 16 @ 180 mm c/c uniformly throughout on both faces ( 2230 sqmm)

3.7) DESIGN OF BOTTOM DOME:-


C/C Dia of Columns, D2 = 7.05 mt
Chord Length of Bottom Dome = 7.05 mt
Thickness of Bottom dome
at Crown = 175 mm
at Springings = 200 mm
GVPR ENGINEERS LIMITED
Document No. Rev.
Project : CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK
-DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

Rise of Bottom dome = D/6 to D/8 = 1.10 mt

Radius of Bottom Dome R (2R-h1)h1 = (D2/2)2 = 6.20 mt


From Right angled Triangle H' = √(6.2^2-3.525^2)
sqrt(38.44-12.43) = 5.10 mt
Load:
Average Thickness of Dome = 187.5 mm
Self Weight of Dome = 2π*6.2*1.1*0.1875*25 = 200.87 Kn
Wt of water
Cylindrical Portion above Dome = π x3.525^2 x4.2x10 = 1639.52 Kn
Deduct Bottom Dome Portion =
π x 1.1^2/ 3* ((3*6.2)-1.1)*10
Total = -221.74 Kn
= 1618.64 Kn
Load per unit area w = 1618.64 / (2π x6.2X1.1) = 37.77 kn/m2

Load per meter of periphery = Sin θ = 3.525/6.2 = 73.08 kn/m


Cos θ = 5.1/6.2 = 0.569
θ = 0.820
= 34.650 < 510 48”
Hence the Entire Dome is under Compression.
Meridional Thrust T = wR / (1 + Cos θ) (Maximum at springings i.e.at θ =34.65)
37.77*6.2/(1+0.82) = 128.67 kn/m
Max. Meridional stress =128.67/ (187.5 x 1000) = 0.69 N/mm²
Horizontal Thrust H = TCos θ=128.67*0.82 = 105.51 kn/m
Hoop stress = [wR / (1 + Cos θ)] x (-1 + Cos θ + Cos θ2)/(t x 1000)
Hoop stress at springings i..e., θ =34.65
128670*(-1+0.82+0.672)/(187.5*1000) = 0.34 N/mm²
All the stresses are with in the
Max Hoop stress at crown i..e.,
limits and the dome is in pure θ = 0 0
, cos θ = 1
128670*(-1+1+1)/(187.5*1000)
compression and stresses are = 0.69 N/mm²
very
Shearlow. Hence
stress provide ÷(187.5x 1000)
=73.08*10^3 = 0.39 N/mm²
minimum reinforcement to
take care of temperature and < 2.2 N/mm² Hence OK
shrinkage stresses
As per clause 7.10 of IS 3370 Part-II minimum reinforcement to be provided.
Ast = (0.35/100) x175 x 1000 = 612.5 mm²
Dia of Bar = 10 mm
Area of Bar = 78.54 mm2
Required Spacing = 260 mm
Provide Spacing = 180 mm
Provided Area of Steel = 436.33 cm² on E/F

Provide 10 dia tor @180mm c/c radially and circumferentially @ Top and bottom (spacing measured at springings)

Bending Moment

Load per unit area w =1618.64 / (2π x6.2X1.1) = 37.77 kn/m2


Moment at sprinings = WRt/4 √3 =37.77 x6.2x0.2/(4x√3) = 6.76 kNm
Factored Bending moment = 10.14 knm
Effective thickness = 155 mm
Mu/bd^2 = 0.42
From SP16 table 4 Ast required = 0.098
Ast required = 152 mm2
Stiffen the dome over a length of 0.76√ Rt=0.76*√6.2*0.2 = 0.850 mt say 1
GVPR ENGINEERS LIMITED
Document No. Rev.
Project : CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK
-DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

Dia of Bar = 10 mm
Area of Bar = 78.54 mm2
Required Spacing = 260 mm
Provide Spacing = 180 mm
Provided Area of Steel = 436.33 cm² on E/F
Provide thickness for dome slab to 200 mm at springings and provide 10mm dia @180mm c/c on top and bottom both
Radially & Circumferentially

3.8) Design of Bottom Ring Beam 450x750


C/C Dia of Columns = 7.05 mt
Chord Length of Bottom Ring Beam = 7.05 mt
Let The width of Ring Beam = 450 mm
Depth of Ring Beam = 750 mm
(a) Design for Hoop Tension
Horizontal Inward Thrust on bottom Ring beam due to conical bottom = T1*cos Ø
T1 = Thrust from conical bottom / meter = w* cosecØ
w = 120.43 kn/m
cosecØ = 1.548
cosØ = 0.763
T1 = 1.548*0.763 = 186.43 kn/m
Horizontal Inward Thrust = T1*cos Ø =186.43*0.763 = 142.25 kn/m
Horizontal Outward Thrust on bottom Ring beam due to bottom spherical dome = T2*cos Ø
T2 = Thrust from spherical dome / meter = w*R / (1+Cosφ)
w = 37.77 kn/m2
R = 6.20 mt
cosφ = 0.820
T2 = 128.67 kn/m
Horizontal Outward Thrust = T2*cos θ = 105.51 kn/m
Net Inward Horizontal thrust on bottom ring beam T = (T1*cosØ-T2*cosØ)*D/2
(142-106)*7.5/2 = 137.78 kn Compression
Area of section provided = 450x750 = 337500 mm2
Direct compressive stress = 137780/337500 = 0.41 N/mm²

Permissible Direct compressive stress = 8.0 N/mm²


Hence Safe

(b) Design for Bending :


Vertical Loads on Ring beam
(1) Load from Bottom dome = 1618.64 Kn
(2) Load from Conical Bottom = 2837.50 Kn
(3) Wt of Water above Beam
π *7.05*4.5*4.2*10 = 418.60 Kn
(4) Self wt of beam
π *7.05*4.5*7.5*25 = 186.88 Kn
Total Load W = 5061.62 Kn
GVPR ENGINEERS LIMITED
Document No. Rev.
Project : CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK
-DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

Load per meter length of beam =5061.62/(π*7.05) = 228.53 kn/m


Size of Columns Supporting Beam = 450 Ф
The Beam is supporting on no of colum 2α = 6
β0 = 60° 1.047 radians
α = 12.75 0.223 radians
= 30° 0.524 radians
Bending moment Coefficients are
At support λ- = 0.089
At span λ+ = 0.045
Torsional moment coefficient is λt = 0.009
Max Support Moment = 2α * w * r2 * λ-
0.089*228.53*1.05*3.525^2 = 264.659 knm
Max span Moment = 2α * w * r2 * λ+
0.045*228.53*1.05*3.525^2 = 133.82 knm
Max Torsional Moment = 2α * w * r2 * λt
0.009*228.53*1.05*3.525^2 = 26.76 knm
Shear Force at Support ( Vo ) = Π * D1 * w/ 2 * n
(22*7.05*229 /(2*6*7)) = 421.80 kn
Shear Force at the section of max Torsion V' = Vo * ( 1- βo/α)
(422*(1-12.75/30) = 242.54 kn
Moment at Face of Column = w*r *(-1+α sinφ +α cosφ*cotα )
1
2

Tanφ = 0.225
r1
0.225/3.525 = 0.064
φ = 3.65° 0.064 radians
α*Sinφ = 0.0334
α*Cosφ*cotα = 0.9051

Moment at Face of column M1


(229*3.525^2* (-1+0.0334+0.9051)) = -174.892 knm
Torsional Moment at Face of column = w*r *(φ-α+α cos φ -α sin φ * cotα)
1
2

α*Cosφ = 0.5225
α*Sinφ*cotα = 0.0578
Torsional Moment at Face of column
(229*3.525^2* (0.064-0.524+0.5225-0.0578)) = 13.94 knm
Distance of max torsion from face of the supports
2*Π*3.525*12.75/360-0.225 = 0.559 m < 0.644
Hence Safe
Equivalent Bending Moment at face of column M2 = T ( 1+D/b) / 1.7
D = 750 mm
b = 450 mm
M2 = (14*(1+0.75/0.45)/1.70) = 22 knm
Total Bending Moment at face of column M =M1+M2
M =174.89+21.87 = 196.76 knm
Factored Bending moment = 295.14 knm
Effective thickness = 644 mm
Mu/bd^2 = 1.58
From SP16 table 4 Ast required = 0.385
Ast required = 1116 mm2
GVPR ENGINEERS LIMITED
Document No. Rev.
Project : CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK
-DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

LONGITUDINAL REINFORCEMENT:
At Top :
Straight Bars Extra Bars
Dia of Bar = 16 mm 16 mm
Area of Bar = 201.06 mm2 201.06 mm2
Required no of Bars at top = 5.55 no's 1.55 no's
Provide no of Bars = 4 no's 4 no's
Provided Area of Steel = 804.24 mm2 804.24 mm2
Total Provided Area of Steel at top = 1608.48 mm2

Max span Moment = 2α * w * r2 * λ+ = 133.82 knm


Factored Bending moment = 200.72 knm
Effective thickness = 644 mm
Mu/bd^2 = 1.08
From SP16 table 4 Ast required = 0.258
Ast required = 748 mm2

At Bottom :
Straight Bars Extra Bars
Dia of Bar = 16 mm 12 mm
Area of Bar = 201.06 mm2 113.1 mm2
Required no of Bars at Bottom = 3.72 no's -0.50 no's
Provide no of Bars = 4 no's 4 no's
Provided Area of Steel = 804.24 mm2 452.4 mm2
Total Provided Area of Steel at Bottom = 1256.64 mm 2

At top:
Provide 4 - # 16 tor through + 4- # 16 extra at supports(1608.48sqmm >1116sqmm)
At Bottom:
Provide 4 - # 16 tor through + 4- # 12 extra over mid span(1256.64sqmm >748sqmm)
Shear force at 644 mm from face of column V'= Vo - w*(d+S2/2)
(666.5 mm from centre of column ) V
422-229*(666.5) = 223 kn
Equivalent shear at section of max torsion Ve = V' + 1.6 * T / b
(243+1.6*27/0.45) = 337.69 kn
Equivalent Shear Stress ζve = Ve/ (b*d)
506535/(450*644) = 1.75 N/mm2
Area of Steel at Support = 1608 mm2
pt = 0.55
ζc = 0.520 N/mm2
< 1.75
ζc < ζve
Shear Capacity of Section ‫ﺡ‬cbd = 150624.00 N
Net Shear = 337.69-150.624 = 187.07 Kn
TRANSVERSE REINFORCEMENT :
Dia of Stirrups = 8 mm
No of Legs = 4
Area of shear reinforcement as per Cl 41.4.3.of IS 456 -2000
Spacing should be lesser of the following :
A) Asv / Sv = (Tu / b1 * d1 * 0.87 fy) + (Vu / 2.5 * d1 * 0.87fy)
0.87fy = 435 N/mm2
Dia of main reinforcement = 16 mm
Dia of stirrups = 8 mm
Cover = 45 mm
b1 = 328.00 mm
GVPR ENGINEERS LIMITED
Document No. Rev.
Project : CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK
-DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

d1 = 628.00 mm
Asv = 201.06 mm2

Asv / Sv = 40*100/(328*628*435)+(280.61/(2.5*628*435)) = 0.41


Asv / Sv = 0.41
Sv = 488.82 mm
B) Sv = (Asv * σsv) / (b * ( ζve - ζc ))
201.06*435 / (450*(1.75-0.52)) = 158.26 mm

Provided Spacing is Lesser of above two cases = 125.00 mm


Say = 110 mm
Dia of Stirrups = 8 mm
No of Legs = 4
Asv = 201.06 mm2
Minimum Shear Reinforcement = Asv / bSv >= (0.4/0.87f
Sv <= 0.87fyAsv
y) / 0.4b
Sv < = = 485.9 mm
0.75 d = 483.00 mm
= 300 mm
Provided Spacing is Lesser of above two cases = 200 mm
Stirrups :
Provide support to 800 # 8 - 4L stirrups @ 110 mm c/c
Provide 800 to center # 8 - 4L stirrups @ 200 mm c/c

Ductile Detailing of Beam:


As per IS 13920 : 2016
the same spacing as above, shall also be provided over a length equal to 2d on either side of a
section where flexural yielding may occur under the effect of earthquake forces. Elsewhere, the
Width of Beam = 450 mm
Depth of beam = 750 mm
Clear cover = 45 mm
Dia of Hoop = 8 mm
Dia of Main bar provided = 16 mm
Effective depth = 704.2 mm

The spacing of hoops over a length of 2d at either ends of a beam shall not exceed
(a) d/4 = 176.05 mm
(b) 8 times the diameter of the smallest longitudinal bar = 128 mm
(c) 100 mm = 100 mm
The spacing of hoops over a length of 2d at either end of a beam shall be provided is
Min ( = 100 mm
Provide Spacing at Supports = 100 mm

Length of Confining steel from face of the support, 2d = 1408.4 mm


Say = 1450 mm

Elsewhere, the beam shall have vertical hoops at a spacing not exceeding d/2.
d/2 = 352.1 mm
Elsewhere, the beam shall have vertical hoops at a spacing of = 200 mm
Stirrups :
Hence Provide 4L - Y8 stirrups Spacing @ 100 mm c/c throughout
GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project : BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check
Title : UTTAR PRADESH PSD DHC
Crack width calculation for Top dome :
Check for Crack Width for Bending Moment
As Per IS 3370-2009 (Part II) Annex-B

1) Sectional Properties:
Width, b = 1000 mm fc/Ec
Depth, d = 150 mm
Clear Cover, Cmin = 45 mm
Dia of bar, dc = 10 mm d D
Spacing, S = 150 mm
d-x fs/Es
Effective Depth, d = 100 mm
Area of Steel, Ast = 523.33
Total Cover, ec = 50 mm b ε1
Section Strain Diagram
Grade Of Concrete, fck = M 30
Grade Of Steel, fy = Fe 500

Elastic Modulus Of Concrete, Ec = 5000 √fck = 27386.13 N/mm²


Elastic Modulus Of Steel, Es = 200000 N/mm²
Modular Ratio, m = Es/Ec = 7.303
Reinforcement ratio factor, p = Ast/bd = 0.0052
Maximum Moment, Ms = 1.12 kN-m

2) Depth of Neutral Axis:


From The Method of The Transformed Section,
C = T
⇒ b*x*x/2 = m*As*(d-x)

By solving the above equation for roots,


x/d = -mp+√(mp*(mp+2))
= 0.24089

⇒ x = 0.24089 x 100
= 24.089 mm

Lever Arm, z = d-(x/3)


= 91.971 mm
3) Induced Stress in the Concrete & Reinforcement:
For the crack width formula to be valid, the compressive stress in concrete and the tensile stress in steel
under service conditions must be less than the limiting values as follows:
Concrete: fc ≤ 0.45 fck
Steel: fs ≤ 0.8 fy

Stress induced in Concrete can be calculated as


Limiting Moment, Ms = C*Lever Arm
= (x*b*fc /2) * z

⇒ fc = 2 Ms/(x*b*z)
= ### N/mm²
< 0.45 fck (13.5) N/mm² Hence Safe

Stress induced in Reinforcement can be calculated as


Limiting Moment, Ms = T*Lever Arm
= As*fs* z

⇒ fs = Ms/(As*z)
= 23.27 N/mm²
< 0.8 fy (400) N/mm² Hence Safe
< 130 N/mm²

Hence as per Clause No. 4.4.3.1 of IS 3370:2009 (Part II), Check for Crack width is not Required

4) Nominal Strain ε1 :
From Strain Diagram,
ε1 = fs × D − x
Es d − x

= 0.000193

5) Strain Hardening due to Stiffening effect, ε2 :


As per Annexure B of IS 3370:2009 (Part II)

For limiting design surface crack width of 0.2 mm

ε2 = bt ሺD − xሻ(a′ − x)
3 Es As (d − x)

= 0.0006651 > ε1

Hence there will be no crack


6) Design Crack Width, w:

Average strain at the level where crack is being considered,


εm = ε1 - ε2
= -0.000472

Distance from considered point to the surface of the nearest


longitudinal bar, acr = √((S/2)²+ec²) - (dc/2)
= 85.139 mm
S
Design Surface Crack width,

3 acr εm
w =
2 (acr − Cmin )
1+ D−x

= -0.077 mm
< 0.2 mm

Hence the design crack width is with in the allowable limit.


Rev.

Date
3/19/2021

D-x

ain Diagram
tensile stress in steel
ec =
cmin+ dia/2
50 mm
GVPR ENGINEERS LIMITED
Document No. Rev.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project : BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

Crack width calculation for Top dome:


Check for Crack Width for Horizontal Thrust
As Per IS 3370-2009 (Part II) Annex-B

1) Sectional Properties:
Width, b = 1000 mm
Depth, d = 125 mm
Clear Cover, Cmin = 45 mm
Dia of bar, dc = 10 mm
Spacing, S = 150 mm

Effective Depth, d = 75 mm
Area of Steel, As = 523 mm²
Area of Concrete, Ac = 125000 mm²
Total Cover, ec = 50 mm

Grade Of Concrete, fck = M 30


Grade Of Steel, fy = Fe 500

Elastic Modulus Of Concrete, Ec = 5000 √fck = 27386.128 N/mm²


Elastic Modulus Of Steel, Es = 200000 N/mm²
Modular Ratio, m = Es/Ec = 7.303
Reinforcement ratio factor, p = Ast/bd = 0.0070
Maximum Thrust, T = 23 kN

2) Induced Strain in Reinforcement:

For the crack width formula to be valid, the tensile stress in steel under service conditions must
be less than the limiting values as follows:
Strain in Reinforcement, ε1 ≤ 0.8 fy/Es

Stress induced in Reinforcement can be calculated as

fs =

= 1.315 N/mm²
Strain in Reinforcement,
ε1 = fs/Es
= 0.000007
< 0.8 fy/Es (0.002) Hence Safe

Hence as per Clause No. 4.4.3.1 of IS 3370:2009 (Part II), Check for Crack width is not Required

3) Strain Hardening due to Stiffening effect, ε2 :


As per Annexure B of IS 3370:2009 (Part II)

For limiting design surface crack width of 0.2 mm

ε2 =

= 0.0007967 > ε1

Hence there will be no crack

4) Design Crack Width, w:

Average strain at the level where crack is being considered,


εm = ε1 - ε2
= -0.000790 ec =
cmin+ dia/2
Distance from considered point to the surface of the 50 mm
nearest longitudinal bar, acr = √((S/2)²+ec²) - (dc/2)
= 85.14 mm
S
Design Surface Crack width,

w = 3 acr εm
= -0.202 mm
< 0.2 mm
Hence the design crack width is with in the allowable limit.
GVPR ENGINEERS LIMITED
Document No. Rev.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project : BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

Crack width calculation for Top Ring beam:


Check for Crack Width for Direct Tension
As Per IS 3370-2009 (Part II) Annex-B

1) Sectional Properties:
Width, b = 300 mm
Depth, d = 300 mm
Clear Cover, Cmin = 45 mm
Dia of bar, dc = 12 mm
Spacing, S = 186 mm

Effective Depth, d = 249 mm


Area of Steel, As = 678 mm²
Area of Concrete, Ac = 90000 mm²
Total Cover, ec = 51 mm

Grade Of Concrete, fck = M 30


Grade Of Steel, fy = Fe 500

Elastic Modulus Of Concrete, Ec = 5000 √fck = 27386.128 N/mm²


Elastic Modulus Of Steel, Es = 200000 N/mm²
Modular Ratio, m = Es/Ec = 7.303
Reinforcement ratio factor, p = Ast/bd = 0.0091
Maximum Direct Tension, T = 119 kN

2) Induced Strain in Reinforcement:

For the crack width formula to be valid, the tensile stress in steel under service conditions must
be less than the limiting values as follows:
Strain in Reinforcement, ε1 ≤ 0.8 fy/Es

Stress induced in Reinforcement can be calculated as

fs =

= 9.182 N/mm²
Strain in Reinforcement,
ε1 = fs/Es
= 0.000046
< 0.8 fy/Es (0.002) Hence Safe

Hence as per Clause No. 4.4.3.1 of IS 3370:2009 (Part II), Check for Crack width is not Required

3) Strain Hardening due to Stiffening effect, ε2 :


As per Annexure B of IS 3370:2009 (Part II)

For limiting design surface crack width of 0.2 mm

ε2 =

= 0.0004425 > ε1

Hence there will be no crack

4) Design Crack Width, w:

Average strain at the level where crack is being considered,


εm = ε1 - ε2
= -0.000397 ec =
cmin+ dia/2
Distance from considered point to the surface of the 51 mm
nearest longitudinal bar, acr = √((S/2)²+ec²) - (dc/2)
= 100.07 mm
S
Design Surface Crack width,

w = 3 acr εm
= -0.119 mm
< 0.2 mm
Hence the design crack width is with in the allowable limit.
GVPR ENGINEERS LIMITED
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF Document No. Rev.
Project : VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -
SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI


Design Check Date
Title : (Zone-C) UTTAR PRADESH PSD DHC 3/19/2021
Crack width calculation for Cylindrical wall :
Check for Crack Width for Bending Moment
As Per IS 3370-2009 (Part II) Annex-B

1) Sectional Properties:
Width, b = 1000 mm fc/Ec
Depth, d = 200 mm
Clear Cover, Cmin = 45 mm x
Dia of bar, dc = 10 mm d D
Spacing, S = 180 mm
d-x fs/Es D-x
Effective Depth, d = 150 mm
Area of Steel, Ast = 436.1
Total Cover, ec = 50 mm b ε1
Section Strain Diagram
Grade Of Concrete, fck = M 30
Grade Of Steel, fy = Fe 500

Elastic Modulus Of Concrete, Ec = 5000 √fck = 27386.13 N/mm²


Elastic Modulus Of Steel, Es = 200000 N/mm²
Modular Ratio, m = Es/Ec = 7.303
Reinforcement ratio factor, p = Ast/bd = 0.0029
Maximum Moment, Ms = 7.28 kN-m

2) Depth of Neutral Axis:


From The Method of The Transformed Section,
C = T
⇒ b*x*x/2 = m*As*(d-x)

By solving the above equation for roots,


x/d = -mp+√(mp*(mp+2))
= 0.18594

⇒ x = 0.18594 x 150
= 27.891 mm

Lever Arm, z = d-(x/3)


= 140.703 mm
3) Induced Stress in the Concrete & Reinforcement:
For the crack width formula to be valid, the compressive stress in concrete and the tensile stress in
steel under service conditions must be less than the limiting values as follows:
Concrete: fc ≤ 0.45 fck
Steel: fs ≤ 0.8 fy

Stress induced in Concrete can be calculated as


Limiting Moment, Ms = C*Lever Arm
= (x*b*fc /2) * z

⇒ fc = 2 Ms/(x*b*z)
= ### N/mm²
< 0.45 fck (13.5) N/mm² Hence Safe

Stress induced in Reinforcement can be calculated as


Limiting Moment, Ms = T*Lever Arm
= As*fs* z

⇒ fs = Ms/(As*z)
= 118.64 N/mm²
< 0.8 fy (400) N/mm² Hence Safe
< 130 N/mm²

Hence as per Clause No. 4.4.3.1 of IS 3370:2009 (Part II), Check for Crack width is not Required

4) Nominal Strain ε1 :
From Strain Diagram,
ε1 = fs × D − x
Es d − x

= 0.000836

5) Strain Hardening due to Stiffening effect, ε2 :


As per Annexure B of IS 3370:2009 (Part II)

For limiting design surface crack width of 0.2 mm

ε2 = bt ሺD − xሻ(a′ − x)
3 Es As (d − x)

= 0.0009271 > ε1

Hence there will be no crack


6) Design Crack Width, w:

Average strain at the level where crack is being considered,


εm = ε1 - ε2
= -0.000091 ec =
cmin+ dia/2
Distance from considered point to the surface of the nearest 50 mm
longitudinal bar, acr = √((S/2)²+ec²) - (dc/2)
= 97.956 mm
S
Design Surface Crack width,

3 acr εm
w =
2 (acr − Cmin )
1+ D−x

= -0.017 mm
< 0.2 mm

Hence the design crack width is with in the allowable limit.


GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP
Project : OF VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -
SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM Designed Checked Date Rev.
Title : GHATI (Zone-C) UTTAR PRADESH PSD DHC 3/19/2021 A
Crack width calculation for Cylindrical wall :
Check for Crack Width for Direct Tension
As Per IS 3370-2009 (Part II) Annex-B

1) Sectional Properties:
Width, b = 1000 mm
Depth, d = 200 mm
Clear Cover, Cmin = 45 mm
Dia of bar, dc = 10 mm
Spacing, S = 180 mm

Effective Depth, d = 150 mm


Area of Steel, As = 436 mm²
Area of Concrete, Ac = 200000 mm²
Total Cover, ec = 50 mm

Grade Of Concrete, fck = M 30


Grade Of Steel, fy = Fe 500

Elastic Modulus Of Concrete, Ec = 5000 √fck = 27386.128 N/mm²


Elastic Modulus Of Steel, Es = 200000 N/mm²
Modular Ratio, m = Es/Ec = 7.303
Reinforcement ratio factor, p = Ast/bd = 0.0029
Maximum Direct Tension, T = 101 kN

2) Induced Strain in Reinforcement:

For the crack width formula to be valid, the tensile stress in steel under service conditions must be less than the
limiting values as follows:
Strain in Reinforcement, ε1 ≤ 0.8 fy/Es

Stress induced in Reinforcement can be calculated as

fs =

= 3.64 N/mm²
Strain in Reinforcement,
ε1 = fs/Es
= 0.000018
< 0.8 fy/Es (0.002) Hence Safe

Hence as per Clause No. 4.4.3.1 of IS 3370:2009 (Part II), Check for Crack width is not Required
3) Strain Hardening due to Stiffening effect, ε2 :
As per Annexure B of IS 3370:2009 (Part II)

For limiting design surface crack width of 0.2 mm

ε2 =

= 0.0015291 > ε1

Hence there will be no crack

4) Design Crack Width, w:

Average strain at the level where crack is being considered,


εm = ε1 - ε2
= -0.001511 ec =
cmin+ dia/2
Distance from considered point to the surface of the 50 mm
nearest longitudinal bar, acr = √((S/2)²+ec²) - (dc/2)
= 97.96 mm
S
Design Surface Crack width,

w = 3 acr εm
= -0.444 mm
< 0.2 mm

Hence the design crack width is with in the allowable limit.


GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project : BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check
Title : UTTAR PRADESH
PSD DHC

Crack width calculation for Middle Ring beam:


Check for Crack Width for Direct Tension
As Per IS 3370-2009 (Part II) Annex-B

1) Sectional Properties:
Width, b = 1100 mm
Depth, d = 200 mm
Clear Cover, Cmin = 45 mm
Dia of bar, dc = 16 mm
Spacing, S = 200 mm

Effective Depth, d = 147 mm


Area of Steel, As = 2010 mm²
Area of Concrete, Ac = 220000 mm²
Total Cover, ec = 53 mm

Grade Of Concrete, fck = M 30


Grade Of Steel, fy = Fe 500

Elastic Modulus Of Concrete, Ec = 5000 √fck = 27386.128 N/mm²


Elastic Modulus Of Steel, Es = 200000 N/mm²
Modular Ratio, m = Es/Ec = 7.303
Reinforcement ratio factor, p = Ast/bd = 0.0124
Maximum Direct Tension, T = 259 kN

2) Induced Strain in Reinforcement:

For the crack width formula to be valid, the tensile stress in steel under service conditions must be
less than the limiting values as follows:
Strain in Reinforcement, ε1 ≤ 0.8 fy/Es

Stress induced in Reinforcement can be calculated as

fs =

= 8.049 N/mm²
Strain in Reinforcement,
ε1 = fs/Es
= 0.000040
< 0.8 fy/Es (0.002) Hence Safe

Hence as per Clause No. 4.4.3.1 of IS 3370:2009 (Part II), Check for Crack width is not Required

3) Strain Hardening due to Stiffening effect, ε2 :


As per Annexure B of IS 3370:2009 (Part II)

For limiting design surface crack width of 0.2 mm

ε2 =

= 0.0003648 > ε1

Hence there will be no crack

4) Design Crack Width, w:

Average strain at the level where crack is being considered,


εm = ε1 - ε2
= -0.000325 ec =
cmin+ dia/2
Distance from considered point to the surface of the 53 mm
nearest longitudinal bar, acr = √((S/2)²+ec²) - (dc/2)
= 105.18 mm
S
Design Surface Crack width,

w = 3 acr εm
= -0.102 mm
< 0.2 mm

Hence the design crack width is with in the allowable limit.


Rev.

Date

3/19/2021
cmin+ dia/2
GVPR ENGINEERS LIMITED
Document No. Rev.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project : BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

Crack width calculation for Conical wall:


Check for Crack Width for Direct Tension
As Per IS 3370-2009 (Part II) Annex-B

1) Sectional Properties:
Width, b = 1000 mm
Depth, d = 200 mm
Clear Cover, Cmin = 45 mm
Dia of bar, dc = 16 mm
Spacing, S = 180 mm

Effective Depth, d = 147 mm


Area of Steel, As = 1116 mm²
Area of Concrete, Ac = 200000 mm²
Total Cover, ec = 53 mm

Grade Of Concrete, fck = M 30


Grade Of Steel, fy = Fe 500

Elastic Modulus Of Concrete, E c = 5000 √fck = 27386.128 N/mm²


Elastic Modulus Of Steel, E s = 200000 N/mm²
Modular Ratio, m = Es/Ec = 7.303
Reinforcement ratio factor, p = Ast/bd = 0.0076
Maximum Direct Tension, T = 281 kN

2) Induced Strain in Reinforcement:

For the crack width formula to be valid, the tensile stress in steel under service conditions must be
less than the limiting values as follows:
Strain in Reinforcement, ε1 ≤ 0.8 fy/Es

Stress induced in Reinforcement can be calculated as

fs =

= 9.862 N/mm²
Strain in Reinforcement,
ε1 = fs/Es
= 0.000049
< 0.8 fy/Es (0.002) Hence Safe

Hence as per Clause No. 4.4.3.1 of IS 3370:2009 (Part II), Check for Crack width is not Required

3) Strain Hardening due to Stiffening effect, ε2 :


As per Annexure B of IS 3370:2009 (Part II)

For limiting design surface crack width of 0.2 mm

ε2 =

= 0.0005974 > ε1

Hence there will be no crack

4) Design Crack Width, w:

Average strain at the level where crack is being considered,


εm = ε1 - ε2
= -0.000548 ec =
cmin+ dia/2
Distance from considered point to the surface of the 53 mm
nearest longitudinal bar, acr = √((S/2)²+ec²) - (dc/2)
= 96.45 mm
S
Design Surface Crack width,

w = 3 acr εm
= -0.159 mm
< 0.2 mm

Hence the design crack width is with in the allowable limit.


GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF
Project : VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -
SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI Design Check
Title : (Zone-C) UTTAR PRADESH PSD DHC
Crack width calculation for Bottom dome :
Check for Crack Width for Bending Moment
As Per IS 3370-2009 (Part II) Annex-B

1) Sectional Properties:
Width, b = 1000 mm fc/Ec
Depth, d = 200 mm
Clear Cover, Cmin = 45 mm
Dia of bar, dc = 10 mm d D
Spacing, S = 180 mm
d-x fs/Es
Effective Depth, d = 150 mm
Area of Steel, Ast = 436.11
Total Cover, ec = 50 mm b ε1
Section Strain Diagram
Grade Of Concrete, fck = M 30
Grade Of Steel, fy = Fe 500

Elastic Modulus Of Concrete, Ec = 5000 √fck = 27386.13 N/mm²


Elastic Modulus Of Steel, Es = 200000 N/mm²
Modular Ratio, m = Es/Ec = 7.303
Reinforcement ratio factor, p = Ast/bd = 0.0029
Maximum Moment, Ms = 1.12 kN-m

2) Depth of Neutral Axis:


From The Method of The Transformed Section,
C = T
⇒ b*x*x/2 = m*As*(d-x)

By solving the above equation for roots,


x/d = -mp+√(mp*(mp+2))
= 0.18594

⇒ x = 0.18594 x 150
= 27.891 mm

Lever Arm, z = d-(x/3)


= 140.703 mm

3) Induced Stress in the Concrete & Reinforcement:


For the crack width formula to be valid, the compressive stress in concrete and the tensile stress in
steel under service conditions must be less than the limiting values as follows:
Concrete: fc ≤ 0.45 fck
Steel: fs ≤ 0.8 fy

Stress induced in Concrete can be calculated as


Limiting Moment, Ms = C*Lever Arm
= (x*b*fc /2) * z

⇒ fc = 2 Ms/(x*b*z)
= ### N/mm²
< 0.45 fck (13.5) N/mm² Hence Safe

Stress induced in Reinforcement can be calculated as


Limiting Moment, Ms = T*Lever Arm
= As*fs* z

⇒ fs = Ms/(As*z)
= 18.253 N/mm²
< 0.8 fy (400) N/mm² Hence Safe
< 130 N/mm²

Hence as per Clause No. 4.4.3.1 of IS 3370:2009 (Part II), Check for Crack width is not Required

4) Nominal Strain ε1 :
From Strain Diagram,
ε1 = fs × D − x
Es d − x

= 0.000129

5) Strain Hardening due to Stiffening effect, ε2 :


As per Annexure B of IS 3370:2009 (Part II)

For limiting design surface crack width of 0.2 mm

ε2 = bt ሺD − xሻ(a′ − x)
3 Es As (d − x)

= 0.0009271 > ε1

Hence there will be no crack


6) Design Crack Width, w:

Average strain at the level where crack is being considered,


εm = ε1 - ε2
= -0.000798

Distance from considered point to the surface of the nearest


longitudinal bar, acr = √((S/2)²+ec²) - (dc/2)
= 97.956 mm
S
Design Surface Crack width,

3 acr εm
w =
2 (acr − Cmin )
1+ D−x

= -0.151 mm
< 0.2 mm

Hence the design crack width is with in the allowable limit.


Rev.

Date
3/19/2021

D-x

in Diagram
nd the tensile stress in
:

th is not Required
ec =
cmin+ dia/2
50 mm
GVPR ENGINEERS LIMITED
Document No. Rev.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project : BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

Crack width calculation for Bottom dome:


Check for Crack Width for Horizontal Thrust
As Per IS 3370-2009 (Part II) Annex-B

1) Sectional Properties:
Width, b = 1000 mm
Depth, d = 175 mm
Clear Cover, Cmin = 45 mm
Dia of bar, dc = 10 mm
Spacing, S = 180 mm

Effective Depth, d = 125 mm


Area of Steel, As = 436.11
Area of Concrete, Ac = 175000 mm²
Total Cover, ec = 50 mm

Grade Of Concrete, fck = M 30


Grade Of Steel, fy = Fe 500

Elastic Modulus Of Concrete, Ec = 5000 √fck = 27386.128 N/mm²


Elastic Modulus Of Steel, Es = 200000 N/mm²
Modular Ratio, m = Es/Ec = 7.303
Reinforcement ratio factor, p = Ast/bd = 0.0035
Maximum Direct Tension, T = 106 kN

2) Induced Strain in Reinforcement:

For the crack width formula to be valid, the tensile stress in steel under service conditions must
be less than the limiting values as follows:
Strain in Reinforcement, ε1 ≤ 0.8 fy/Es

Stress induced in Reinforcement can be calculated as

fs =

= 4.325 N/mm²
Strain in Reinforcement,
ε1 = fs/Es
= 0.000022
< 0.8 fy/Es (0.002) Hence Safe

Hence as per Clause No. 4.4.3.1 of IS 3370:2009 (Part II), Check for Crack width is not Required

3) Strain Hardening due to Stiffening effect, ε2 :


As per Annexure B of IS 3370:2009 (Part II)

For limiting design surface crack width of 0.2 mm

ε2 =

= 0.0013376 > ε1

Hence there will be no crack

4) Design Crack Width, w:

Average strain at the level where crack is being considered,


εm = ε1 - ε2
= -0.001316 ec =
cmin+ dia/2
Distance from considered point to the surface of the 50 mm
nearest longitudinal bar, acr = √((S/2)²+ec²) - (dc/2)
= 97.96 mm
S
Design Surface Crack width,

w = 3 acr εm
= -0.387 mm
< 0.2 mm
Hence the design crack width is with in the allowable limit.
GVPR ENGINEERS LIMITED
Document No. Rev.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF
Project : VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI Design Check Date
Title : (Zone-C) UTTAR PRADESH PSD DHC 3/19/2021
Check for Crack Width for Bottom Ring beam
Check for Crack Width for Bending Moment
As Per IS 3370-2009 (Part II)

1) Sectional Properties:
Width, b = 450 mm fc/Ec
Depth, d = 750 mm
Clear Cover, Cmin = 45 mm x
Dia of bar, dc = 16 mm d D
Spacing, S = ###
d-x fs/Es D-x
Effective Depth, d = 697 mm
Area of Steel, Ast = 1206 mm²
Total Cover, ec = 53 mm b ε1
Section Strain Diagram
Grade Of Concrete, fck = M 30
Grade Of Steel, fy = Fe 500

Elastic Modulus Of Concrete, Ec = 5000 √fck = 27386.128 N/mm²


Elastic Modulus Of Steel, E s = 200000 N/mm²
Modular Ratio, m = Es/Ec = 7.303
Reinforcement ratio factor, p = Ast/bd = 0.0038
Maximum Moment, Ms = 196.76 kN-m

2) Depth of Neutral Axis:


From The Method of The Transformed Section,
C = T
⇒ b*x*x/2 = m*As*(d-x)

By solving the above equation for roots,


x/d = -mp+√(mp*(mp+2))
= 0.21057
GVPR ENGINEERS LIMITED
Document No. Rev.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF
Project : VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI Design Check Date
Title : (Zone-C) UTTAR PRADESH PSD DHC 3/19/2021
⇒ x = 0.21057 x 697
= 146.767 mm

Lever Arm, z = d-(x/3)


= 648.078 mm

3) Induced Stress in the Concrete & Reinforcement:


For the crack width formula to be valid, the compressive stress in concrete and the tensile stress in steel
under service conditions must be less than the limiting values as follows:
Concrete: fc ≤ 0.45 fck
Steel: fs ≤ 0.8 fy

Stress induced in Concrete can be calculated as


Limiting Moment, Ms = C*Lever Arm
= (x*b*fc /2) * z

⇒ fc = 2 Ms/(x*b*z)
= ### N/mm²
< 0.45 fck (13.5) N/mm² Hence Safe

Stress induced in Reinforcement can be calculated as


Limiting Moment, Ms = T*Lever Arm
= As*fs* z

⇒ fs = Ms/(As*z)
= 251.746 N/mm²
< 0.8 fy (400) N/mm² Hence Safe
> 130 N/mm²

Hence as per Clause No. 4.4.3.1 of IS 3370:2009 (Part II), Check for Crack width is Required

4) Nominal Strain ε1 :
From Strain Diagram,
fs D−x
ε1 = ×
Es d − x
= 0.001380
GVPR ENGINEERS LIMITED
Document No. Rev.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF
Project : VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI Design Check Date
Title : (Zone-C) UTTAR PRADESH PSD DHC 3/19/2021

5) Strain Hardening due to Stiffening effect, ε 2 :


As per Annexure B of IS 3370:2009 (Part II)

For limiting design surface crack width of 0.2 mm

bt ሺD − xሻ(a′ − x)
ε2 =
3 Es As (d − x)

= 0.0004113 < ε1

Hence there will be crack

6) Design Crack Width, w:

Average strain at the level where crack is being considered,


εm = ε1 - ε2
= 0.000969 ec =
cmin+ dia/2
Distance from considered point to the surface of the nearest 53 mm
longitudinal bar, acr = √((S/2)²+ec²) - (dc/2)
= 68.141 mm
S
Design Surface Crack width,

3 acr εm
w =
2 (acr − Cmin )
1+
D−x

= 0.189 mm
< 0.2 mm

Hence the design crack width is with in the allowable limit.


GVPR ENGINEERS LIMITED
Document No. Rev.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project : BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Design Check Date
Title : UTTAR PRADESH
PSD DHC 3/19/2021

Crack width calculation for Bottom Ring beam:


Check for Crack Width for Direct Tension
As Per IS 3370-2009 (Part II) Annex-B

1) Sectional Properties:
Width, b = 450 mm
Depth, d = 750 mm
Clear Cover, Cmin = 45 mm
Dia of bar, dc = 16 mm
Spacing, S = ###

Effective Depth, d = 697 mm


Area of Steel, As = 1206 mm²
Area of Concrete, Ac = 337500 mm²
Total Cover, ec = 53 mm

Grade Of Concrete, fck = M 30


Grade Of Steel, fy = Fe 500

Elastic Modulus Of Concrete, Ec = 5000 √fck = 27386.128 N/mm²


Elastic Modulus Of Steel, Es = 200000 N/mm²
Modular Ratio, m = Es/Ec = 7.303
Reinforcement ratio factor, p = Ast/bd = 0.0038
Maximum Direct Tension, T = 138 kN

2) Induced Strain in Reinforcement:

For the crack width formula to be valid, the tensile stress in steel under service conditions must
be less than the limiting values as follows:
Strain in Reinforcement, ε1 ≤ 0.8 fy/Es

Stress induced in Reinforcement can be calculated as

fs =

= 2.906 N/mm²
Strain in Reinforcement,
ε1 = fs/Es
= 0.000015
< 0.8 fy/Es (0.002) Hence Safe

Hence as per Clause No. 4.4.3.1 of IS 3370:2009 (Part II), Check for Crack width is not Required

3) Strain Hardening due to Stiffening effect, ε2 :


As per Annexure B of IS 3370:2009 (Part II)

For limiting design surface crack width of 0.2 mm

ε2 =

= 0.0009328 > ε1

Hence there will be no crack

4) Design Crack Width, w:

Average strain at the level where crack is being considered,


εm = ε1 - ε2
= -0.000918 ec =
cmin+ dia/2
Distance from considered point to the surface of the 53 mm
nearest longitudinal bar, acr = √((S/2)²+ec²) - (dc/2)
= 68.14 mm
S
Design Surface Crack width,

w = 3 acr εm
= -0.188 mm
< 0.2 mm
Hence the design crack width is with in the allowable limit.
GVPR ENGINEERS LIMITED
Document No Rev
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF
Project VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -
SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI


Title Date 3/19/2021
(Zone-C) UTTAR PRADESH

4.0. Load Calculations


4.1. Dead Loads (As per IS: 875 - Part: 1 - Dead Loads)
Self-weight of the structures has been generated in analysis using self weight command in STAAD Pro.

4.2 Live loads (As per IS: 875 - Part: 2 - Live Loads)
Live load on Top dome = 1.5 kN/Sqm
Live load on Staircase = 3 kN/Sqm
Live load on walkway = 3 kN/Sqm

Total Load due to Staircases on Landing Beams


Landing Beam (1-14 flights) = 38.31 kN/m

4.3. Water Loads


Unit weight of water = 10 kN/Cum
Max. Min.
Water pressure on cylindrical wall = 32.5 0.0 kN/Sqm
Water pressure on conical dome = 45.0 32.5 kN/Sqm
Water pressure on bottom dome = 45.0 34.0 kN/Sqm

3.3. Load Combinations


As per IS: 456:2000 , IS:1893 (Part-1) , IS: 1893 (PART-2):2014
i) Service Load Combinations
Load Combination 1: DL+LL
Load Combination 2: DL+ EQ+X + 0.3EQ+Z
Load Combination 3: DL+ EQ-X + 0.3EQ-Z
Load Combination 4: DL+ EQ+Z + 0.3EQ+X
Load Combination 5: DL+ EQ-Z + 0.3EQ-X
Load Combination 6: DL+WLX+
Load Combination 7: DL+WLX-
Load Combination 8: DL+WLZ+
Load Combination 9: DL+WLZ-
Load Combination 10: DL+LL+ EQ+X + 0.3EQ+Z
Load Combination 11: DL+LL+ EQ-X + 0.3EQ-Z
Load Combination 12: DL+LL+ EQ+Z + 0.3EQ+X
Load Combination 13: DL+LL+ EQ-Z + 0.3EQ-X
Load Combination 14: DL+LL+WLX+
Load Combination 15: DL+LL+WLX-
Load Combination 16: DL+LL+WLZ+
Load Combination 17: DL+LL+WLZ-
GVPR ENGINEERS LIMITED
Document No Rev
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF
Project VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -
SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI


Title Date 3/19/2021
(Zone-C) UTTAR PRADESH

Load Combination 18: DL+0.8(LL+ EQ+X + 0.3EQ+Z)


Load Combination 19: DL+0.8(LL+ EQ-X + 0.3EQ-Z)
Load Combination 20: DL+0.8(LL+ EQ+Z + 0.3EQ+X)
Load Combination 21: DL+0.8(LL+ EQ-Z + 0.3EQ-X)
Load Combination 22: DL+0.8(LL+WLX+)
Load Combination 23: DL+0.8(LL+WLX-)
Load Combination 24: DL+0.8(LL+WLZ+)
Load Combination 25: DL+0.8(LL+WLZ-)

ii) Ultimate Load Combinations


Load Combination 26: 1.5(DL+LL)
Load Combination 27: 1.5(DL+ EQ+X + 0.3EQ+Z)
Load Combination 28: 1.5(DL+ EQ-X + 0.3EQ-Z)
Load Combination 29: 1.5(DL+ EQ+Z + 0.3EQ+X)
Load Combination 30: 1.5(DL+ EQ-Z + 0.3EQ-X)
Load Combination 31: 1.5(DL+WLX+)
Load Combination 32: 1.5(DL+WLX-)
Load Combination 33: 1.5(DL+WLZ+)
Load Combination 34: 1.5(DL+WLZ-)
Load Combination 35: 0.9DL+1.5(EQ+X + 0.3EQ+Z)
Load Combination 36: 0.9DL+1.5(EQ-X + 0.3EQ-Z)
Load Combination 37: 0.9DL+1.5(EQ+Z + 0.3EQ+X)
Load Combination 38: 0.9DL+1.5(EQ-Z + 0.3EQ-X)
Load Combination 39: 0.9DL+1.5WLX+
Load Combination 40: 0.9DL+1.5WLX-
Load Combination 41: 0.9DL+1.5WLZ+
Load Combination 42: 0.9DL+1.5WLZ-
Load Combination 43: 1.2(DL+LL+ EQ+X + 0.3EQ+Z)
Load Combination 44: 1.2(DL+LL+ EQ-X + 0.3EQ-Z)
Load Combination 45: 1.2(DL+LL+ EQ+Z + 0.3EQ+X)
Load Combination 46: 1.2(DL+LL+ EQ-Z + 0.3EQ-X)
Load Combination 47: 1.2(DL+LL+WLX+)
Load Combination 48: 1.2(DL+LL+WLX-)
Load Combination 49: 1.2(DL+LL+WLZ+)
Load Combination 50: 1.2(DL+LL+WLZ-)

Legend:
DL : Dead Load/Dead+Water Loads
LL : Live Load
EQ+X : Seismic Load in X+ Direction WLX+ : Wind Load in X+ Direction
EQ-X : Seismic Load in X- Direction WLX- : Wind Load in X- Direction
EQ+Z : Seismic Load in Z+ Direction WLZ+ : Wind Load in Z+ Direction
GVPR ENGINEERS LIMITED
Document No Rev
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF
Project VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -
SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI


Title Date 3/19/2021
(Zone-C) UTTAR PRADESH

EQ-Z : Seismic Load in Z- Direction WLZ- : Wind Load in Z- Direction


GVPR ENGINEERS LIMITED
Document no
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF
PROJECT VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -
SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI Date 19-Mar-21
TITLE
(Zone-C) UTTAR PRADESH Rev A

4.4 Wind Load Calculation


Basic wind Speed considered (Vb) = = 47 m/sec
Design Wind Speed is given by Vz = K1 x K2 x K3 x Vb
Risk Coefficient, K1 (Table:1 IS 875 - PART 3) = = 1.00

Table 2: Terrain, Height and structure size Coefficient (K 2 - 0 m to 10 m)= 1.00


IS 875 Terrain, Height and structure size Coefficient (K 2 - 10 m to 15 m)= 1.05
(PART 3) Terrain, Height and structure size Coefficient (K 2 - 15 m to 20 m)= 1.07
Terrain, Height and structure size Coefficient (K 2 - 20 m to 30 m)= 1.12
(for Terrain Catergory = 3, Class-B)
Topography Factor (K3) = 1.00
Importance factor for cyclonic region (K4)= 1.00

Design Wind Speed is given by Vz (0m- 10m) = 47 x 1 x 1 x 1 x 1 = 47.00 m/sec


Design Wind Speed is given by Vz (10m- 15m) = 47 x 1 x 1.05 x 1 x 1 = 49.35 m/sec
Design Wind Speed is given by Vz (15m- 20m) = 47 x 1 x 1.07 x 1 x 1 = 50.29 m/sec
Design Wind Speed is given by Vz (20m- 30m) = 47 x 1 x 1.12 x 1 x 1 = 52.64 m/sec

Design Wind Pressure (0m - 10m) = 0.6 x 47² = 1.325 KN/m2


Design Wind Pressure (10m - 15m) = 0.6 x 49.35² = 1.461 KN/m2
Design Wind Pressure (15m - 20m) = 0.6 x 50.29² = 1.517 KN/m2
Design Wind Pressure (20m - 30m) = 0.6 x 52.64² = 1.663 KN/m2

Tributary Area of container= (3.25+1.25)*10 45.00 m2


CL 7.2.1 Wind directionality factor Kd= 1.00
CL 7.2.2 Area averaging factor Ka= 0.87
Combination Factor kc= 1.00
Design wind Pressure Pd = KdxKaxKcxPz

Design Wind Pressure (0m - 10m) = 1.325*1*0.87*1= 1.153 kN/m2


Design Wind Pressure (10m - 15m) = 1.461*1*0.87*1= 1.271 kN/m2
Design Wind Pressure (15m - 20m) = 1.517*1*0.87*1= 1.320 kN/m2
Design Wind Pressure (20m - 30m) = 1.663*1*0.87*1= 1.447 kN/m2
For all Circular members in Plan consider Shape Factor as 0.7
GVPR ENGINEERS LIMITED
Document no
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF
PROJECT VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -
SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI Date 19-Mar-21
TITLE
(Zone-C) UTTAR PRADESH Rev A
Projected area of the Tank upto top of bottom slab
Shape factor for circular Structure= 0.70
GVPR ENGINEERS LIMITED
Document no
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF
PROJECT VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -
SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI Date 19-Mar-21
TITLE
(Zone-C) UTTAR PRADESH Rev A

a) Wind load on Cylindrical & Conical Walls


Height of cylindrical wall = 4.50 m
Projected area of cylindrical wall = 10.2 x 4.5 = 46.80 m2
Wind load acting on the projected area (0m - 10m) = 0.7 x 1.153= 0.81 kN/m2
Wind load acting on the projected area (10m - 15m) = 0.7 x 1.271= 0.89 kN/m2
Wind load acting on the projected area (15m - 20m) = 0.7 x 1.32= 0.92 kN/m2
Wind load acting on the projected area (20m - 30m) = 0.7 x 1.447= 1.01 kN/m2

b) Wind load on Top Dome


Height of the staging = 25.00 m
Height of the Tank above staging, H = 4.50 m
Total Height(Staging + Tank), Z = 29.50 m
Diameter of the Tank, D = 10.40 m
H/D = 0.43

Wind pressure on Roof and Bottom Domes:


(Z/H) -1 = = 5.56
Top Bottom
External Pressure coefficient, Cpe = -0.75 -0.6
Internal Pressure coefficient, Cpi = 0 0
Wind pressure (kN/m²) = -0.76 -0.606
Upwards Downwards

c) Wind load on staging


Staging Height = 25.00 m
Columns along wind ( columns) = 3 Nos
Column diameter = 0.45 m

Frame area of staging = 25 x 7.5 = 187.50 m2


No. of tie level beam exposed to wind = 7 Levels
Area of beams exposed to wind = 7 x (9.225) x 0.5 = 32.29 m2
Area of columns exposed to wind = 3 x 25 x 0.45 = 33.75 m2
Total exposed Area of staging = 32.2875 + 33.75 = 66.04 m2
Solidity Ratio 66.0375/187.5 = 0.352
GVPR ENGINEERS LIMITED
Document no
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF
PROJECT VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -
SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI Date 19-Mar-21
TITLE
(Zone-C) UTTAR PRADESH Rev A
From table Force Coefficient for flat-sided Members, Cf = 1.700
-28 of IS
875
GVPR ENGINEERS LIMITED
Document no
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF
PROJECT VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -
SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI Date 19-Mar-21
TITLE
From table (Zone-C) UTTAR PRADESH Rev A
-28 of IS
875 Force Coefficient for Circular-Sections, Cf = 0.800

Wind force on Column:


Force on columns (0m - 10m) 0.8 x 0.45 x 1.325 = 0.415 kN/m
Force on columns (10m - 15m) 0.8 x 0.45 x 1.461 = 0.458 kN/m
Force on columns (15m - 20m) 0.8 x 0.45 x 1.517 = 0.475 kN/m
Force on columns (20m - 30m) 0.8 x 0.45 x 1.663 = 0.521 kN/m

Wind Force for Tie Beams


Depth of Tie Beam = 500 mm

Force on Tie Beams(0m - 10m) 0.5 x 1.7 x 1.153 = 0.980 kN/m


Force on Tie Beams(10m - 15m) 0.5 x 1.7 x 1.271 = 1.080 kN/m
Force on Tie Beams (15m - 20m) 0.5 x 1.7 x 1.32 = 1.122 kN/m
Force on Tie Beams (20m - 30m) 0.5 x 1.7 x 1.447 = 1.230 kN/m

Wind Force for Ring Beam


Depth of Ring Beam = 750 mm

Force on Ring Beam (0m - 10m) 0.75 x 0.8 x 1.153 = 1.470 kN/m
Force on Ring Beam (10m - 15m) 0.75 x 0.8 x 1.271 = 1.621 kN/m
Force on Ring Beam (15m - 20m) 0.75 x 0.8 x 1.32 = 1.683 kN/m
Force on Ring Beam (20m - 30m) 0.75 x 0.8 x 1.447 = 1.845 kN/m
GVPR ENGINEERS LIMITED
Document No Rev.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO
PROJECT GROUP OF VILAGES BLOCK -DUDDHI, BABHANI AND
MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT


TITLE Date 19-Mar-21
KARAM GHATI (Zone-C) UTTAR PRADESH

4.5 Seismic Loads (As per IS:1893 - 2002 Part-2)

Seismic Zone = III


Zone Factor, Z = 0.16
Importance Factor, I = 1.5
Response reduction Factor, R = 4
Type of soil = Medium
Damping ratio = 5%

Volume of water inside the Container = 258.13 m³


Total Height of the tank = 29.5 m
Weight of tank container, wt = 1717 kN Calculated from STAAD
Weight water , ww = 2581.30 kN
Weight of the staging, ws = 1199.00 kN Calculated from STAAD
Distance of CG from Bottom Ring Beam = 2.45 m Calculated from STAAD

a) Tank Full Condition:


Seismic weight = Container wt. + water wt. + Staging wt. /3 acting at CG of container
w1 = wt + ww + ws/ 3 = 4698 kN
Time period, T = 0.075 × h0.75 = 2.195 sec
Sa/g = 0.619 (Refer Cl. 6.4.2 of IS 1893 (Part 1)-2016)
Time period, T (From Hydrodynamic effect) = 1.74 sec
Horizontal Seismic Coefficient, A h = (Z/2)×(I/R)×(Sa/g) = 0.018584
Seismic weight on staging, (2/3)w s = 799.3333 kN
Total Base shear, V = Ah x [w1 + 2/3(ws)] = 102 kN

b) Tank Empty Condition:


Seismic weight = Tank container + Staging weight/3,
w1 = wt + ws/ 3 = 2117 kN
Time period, T = 0.075 × h 0.75
= 1.474 sec Calculated from STAAD
Sa/g = 0.923 (Refer Cl. 6.4.2 of IS 1893 (Part 1)-2016)
Time period, T (From Hydrodynamic effect) = 1.46 sec
Horizontal Seismic Coefficient, A h = (Z/2)×(I/R)×(Sa/g) = 0.027684
Seismic weight on staging, (2/3)w s = 799.3333 kN
Total Base shear, V = Ah x [w1 + 2/3(ws)] = 81 kN
GVPR ENGINEERS LIMITED
Document No Rev.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO
PROJECT GROUP OF VILAGES BLOCK -DUDDHI, BABHANI AND
MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT


TITLE Date 19-Mar-21
KARAM GHATI (Zone-C) UTTAR PRADESH
Base shear in tank full condition is more than tank empty condition,
So design will be governed by tank full condition
Seismic weight of the container portion is applied as joint weights by dividing seismic weight by number of divisions at
C.G of container. (Seismic weight contains total Dead Weight of container and one third weight of staging)

For staging portion two third weight of staging weight is applied at Beam column joints.

At CG of container , in the STADD model the no of nodes are 60

Total seismic weight by the no of nodes for Full Tank Condition is = 78.30 kN
By assign Pinned joints in staad and taken the forces at joints from staad.

Total seismic weight by the no of nodes for Tank empty Condition is = 35.28 kN
By assign Pinned joints in staad and taken the forces at joints from staad.

Staging in the STADD model, the no of nodes at all levels are 42

Total seismic weight by the no of nodes will get the joint weight at one node i.e 19.03 kN
By assign Pinned joints in staad and taken the forces at joints from staad.
GVPR ENGINEERS LIMITED
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF Document no
VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA
PROJECT:
GVPR-250KL-25M-001

DESIGNED
RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM
TITLE :
GHATI (Zone-C) UTTAR PRADESH PSD

4.6 Hydro Dynamic Analysis Calculations


Tank Properties:
Capacity of tank = 250
Inner Dia of Tank, D = 10.0
c/c of columns = 7.05
Height of Free board of the tank = 0.30
Height of Dead storage in the tank = 0.15
Thickness of Circular wall = 0.20
Thickness of Bottom dome = 0.175
Rise of bottom dome = 1.10
Height of Cylindrical wall = 2.95
Height of Conical wall = 1.25
Radius of curvature of dome = 6.198
Total Volume of Water = 258.1
> 250

Total Weight of Water, w = 258.13x10 = 2581.3


Total Mass of Water m =2581.3x1000/10 = 258130
Weight of empty container = 1717
Weight of Staging = 1199
(Weight of empty container+ 1/3 weight of staing ) ms = 2116.67
For obtaining Parameters of Spring mass model, an equivalent circular container of same volume and
diameter equal to dia of tank at top level of liquid will be considered.
Let ' h' be the height of equivalent circular cylinder
П/4 ( D2)x h = 258
h = 3.29
For h /D = 0.329

2) Parameters of Spring Mass Model:


mi / m ( Fig 2 (a) IS 1893(PART-2):2014) = 0.35
mi = impulsive mass of liquid = 90345.50
= 903.46
Liquid mass is excited in impulsive mode = 35%
mc/m ( Fig 2 (a) IS 1893(PART-2):2014) = 0.55
mc = Convective mass of liquid = 141971.50
Liquid mass is excited in convective mode = 55%
Sum of Impulsive and Convective mass is = 232317.00

hi / h ( Fig 2 (b) IS 1893(PART-2):2014) = 0.375

hi = height of impulsive mass above bottom of tank wa ll ( without Considering base pressure) = 1.234
hi* / h (Fig 2 (b) IS 1893(PART-2):2014) = 1.30
GVPR ENGINEERS LIMITED
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF Document no
VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA
PROJECT:
GVPR-250KL-25M-001

DESIGNED
RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM
TITLE :
GHATI (Zone-C) UTTAR PRADESH PSD

hi*=height of impulsive mass above bottom of tank wall(Considering base


pressure) = 4.277
hc/h ( Fig 2 (b) IS 1893(PART-2):2014) = 0.55
GVPR ENGINEERS LIMITED
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF Document no
VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA
PROJECT:
GVPR-250KL-25M-001

DESIGNED
RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM
TITLE :
GHATI (Zone-C) UTTAR PRADESH PSD

hc= height of convective mass above bottom of tank wall( without Considering base pressure) = 1.810
hc*/h (Fig 2 (b) IS 1893(PART-2):2014) = 1.10
hc* =height of convective mass above bottom of tank wall( Considering base
pressure) = 3.619

3) Time Period :
i) Time Period of Impulsive Mode :
Ti = 2*Π √(mi+ms) /(Ks) (clause 4.3.1.3 of IS 1893(PART-2):2014))
mi = impulsive mass of liquid = 903.46
(Weight of empty container+ 1/3 weight of staing ) ms = 2116.67
Deflection from stadd when 10 kn force obtained at CG = 0.0026
Lateral stiffness of staging = 10/0.002552
= 3919
Time Period = 1.74

ii) Time Period of Convective Mode :


Tc = Cc√D/g (clause 4.3.2.2 of IS 1893(PART-2):2014))
For h /D = 0.329
Cc = Coefficient of time period for convective mode and obtained from Fig 5 IS 1893(PART-2):2014)
Cc = = 3.5

Tc = 3.5√10/9.81 = 3.534

4) Design Horizontal Seismic coefficient: (clause 4.5 of IS 1893(PART-2):2014))


i) for Impulsive Mode :
Damping = 5%
Ahi = Z*I*Sa/(2*R*g)
Seismic Zone = 3
Zone factor (Z) (From Table-2 IS: 1893-part-1) = 0.16
Importance factor (I) (From Table-5 IS: 1893-Part-1) = 1.50
Response reduction factor, R (From Table-3 IS: 1893-Part-2) = 4.00
For 0= T < 0.10, Sa /g for medium Soil = 2.500
Multiplication factor for 5 % Damping = 1
Average response acceleration coefficient Sa /g = 2.500
Design Horizontal Seismic Coefficient Ahi = Z*I*Sa/(2*R*g) = 0.075

ii) for Convective Mode :


Damping = 0.5%
Ahc = Z*I*Sa/(2*R*g)
Zone factor (Z) (From Table-2 IS: 1893-part-1) = 0.16
Importance factor (I) (From Table-5 IS: 1893-Part-1) = 1.50
Response reduction factor, R (From Table-3 IS: 1893-Part-2) = 4.00
GVPR ENGINEERS LIMITED
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF Document no
VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA
PROJECT:
GVPR-250KL-25M-001

DESIGNED
RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM
TITLE :
GHATI (Zone-C) UTTAR PRADESH PSD

For 0.67 < T > 4.0, Sa /g for Medium Soil = 1.36/T = 0.38
Multiplication factor for 0.5 % Damping = 1.75
GVPR ENGINEERS LIMITED
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF Document no
VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA
PROJECT:
GVPR-250KL-25M-001

DESIGNED
RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM
TITLE :
GHATI (Zone-C) UTTAR PRADESH PSD

Average response acceleration coefficient Sa /g = 0.67


Design Horizontal Seismic Coefficient Ahc = Z*I*Sa/(2*R*g) = 0.020

5) Hydrodynamic Pressure : (clause 4.9 of IS 1893(PART-2):2014))


i) Impulsive Hydrodynamic Pressure :
Lateral Impulsive hydrodynamic pressure on the wall
Piw = Qiw(y) Ahi ρgh cosФ
Qiw(y) = 0.866 (1-(y/h)2)tanh(0.866D/h)
Max Pressure will occur at Ф = 0
Qiw(y=0) = 0.866 (1-(0/h)2)tanh(0.866xD/h) = 0.857
Piw(y=0) = Qiw(y) Ahi ρgh cos(0) = 2074.68
= 207.47

Impulsive hydrodynamic Pressure in vertical direction on base slab


Pib = 0.866 Ahi ρgh Sinh(1.732*(x/h)) / Cosh(0.866*(L/h))
Considering, x = D/4 = 10/4 = 2.5
D = 10

Pib = 0.866 Ahi ρgh Sinh(1.732*(x/h)) / Cosh(0.866*(L'/h)) = 519.05


= 51.91

ii) Convective Hydrodynamic Pressure :


Lateral Convective hydrodynamic pressure on the wall
Pcw = Qcw(y) Ahc ρgD (1- (1/3)cos2Ф)cosФ
Qcw(y) = 0.5625cosh(3.674 y/D)/cosh(3.674 h/D)
Max Pressure will occur at Ф = 0
Qcw(0) = 0.5625 cosh(0)/cosh(3.674 h/D) = 0.3084
Pcw (y=0)= Qcw(y) Ahc ρgD (1- (1/3)cos Ф)cosФ
2
= 403.3879
= 40.34
Convective hydrodynamic Pressure in vertical direction on base slab
Pcb =Qcb(x) Ahc ρgD
Qcb (x)= 1.125 ((x/D)-(4/3)(x/D)³) Sech (0.367 h/D)
Considering, x = D/4 =10/4 = 2.50
D = 10.00

Qcb (x=D/2)= 1.125 ((2.50/10)-(4/3)(2.50/10)³) Sech (0.367 *3.25/10) = 0.26


Pcb =Qcb(x) Ahc ρgD = 502.16
= 50.22

Pressure on wall due to Inertia Pww =(Ah)I t ρ mg = 0.075x0.2x 25000


= 375.00
Pressure due to vertical Excitation Pv= Av ρ g h (1-y/h)
Where Av
GVPR ENGINEERS LIMITED
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF Document no
VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA
PROJECT:
GVPR-250KL-25M-001

DESIGNED
RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM
TITLE :
GHATI (Zone-C) UTTAR PRADESH PSD

Zone factor (Z) (From Table-2 IS: 1893-part-1) = 0.16


Importance factor (I) (From Table-5 IS: 1893-Part-1) = 1.5
GVPR ENGINEERS LIMITED
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF Document no
VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA
PROJECT:
GVPR-250KL-25M-001

DESIGNED
RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM
TITLE :
GHATI (Zone-C) UTTAR PRADESH PSD

Response reduction factor, R (From Table-3 IS: 1893-Part-2) = 4


Damping in impulsive mode (As per cl: 4.4 IS:1893-part-2-2014) = 5%
Time period of impulsive mode, Ti = 1.743
Sa/g (For soft soils from Cl:6.4.5 IS1893-Part-1:2002) = 2.500
Av = 2/3
(Z/2 X I/R X Sa/g) = 0.050
Pressure due to vertical Excitation Pv= Av ρ g h (1-y/h)
0.05x 1000 x 9.81x 3.29(1-0/3.29) = 1613.75

Maximum hydrodynamic pressure,


p =√ (Piw+ Pww)2 + Pcw^2 +Pv^2
Maximum hydrodynamic pressure on the wall at base of wall, P = 2961.06
= 2.96
Maximum hydrostatic pressure at the base of the wall, Ps
3.29x 10= = 32.9
Maximum hydrodynamic pressure is about 2.962/32.9x 100
= 9.0
of hydrostatic pressure
Hydrodynamic pressure in this case does not affect container design.
GVPR ENGINEERS LIMITED
Document no

GVPR-250KL-25M-001

CHECKED
DHC

cum
mt
mt
mt
mt
mt
mt
m
m
m
m

KN
Kg
kn
kn
kn
of Spring mass model, an equivalent circular container of same volume and
nk at top level of liquid will be considered.

mt

kg
kn

kg

kg

mt
GVPR ENGINEERS LIMITED
Document no

GVPR-250KL-25M-001

CHECKED
DHC

mt
GVPR ENGINEERS LIMITED
Document no

GVPR-250KL-25M-001

CHECKED
DHC

mt

mt

kn
kn
m

kn/m
Sec

eriod for convective mode and obtained from Fig 5 IS 1893(PART-2):2014)

Sec
GVPR ENGINEERS LIMITED
Document no

GVPR-250KL-25M-001

CHECKED
DHC

N/m²
Kg/m²

m
m

N/m²
Kg/m²

N/m²
Kg/m²

m
m

N/m2
Kg/m²

0.075x0.2x 25000
N/m2
GVPR ENGINEERS LIMITED
Document no

GVPR-250KL-25M-001

CHECKED
DHC

N/m2

N/m2
kN/m2

kN/m2
2.962/32.9x 100
%
of hydrostatic pressure
dynamic pressure in this case does not affect container design.
GVPR ENGINEERS LIMITED
Document
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO
PROJECT: GROUP OF VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR
GVPR-250KL-25M-001
DISTRICT -SONBHADRA

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM DESIGNED


TITLE :
GHATI (Zone-C) UTTAR PRADESH PSD
5.0 DESIGN OF COLUMNS
Typical Design of Columns (Staad output)

C O L U M N N O. 2011 D E S I G N R E S U L T S

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH: 3500.0 mm CROSS SECTION: 450.0 mm dia. COVER: 45.0 mm

** GUIDING LOAD CASE: 43 END JOINT: 1720 SHORT COLUMN


REQD. STEEL AREA : 2097.76 Sq.mm.
REQD. CONCRETE AREA: 156945.36 Sq.mm.
MAIN REINFORCEMENT : Provide 19 - 12 dia. (1.35%, 2148.85 Sq.mm.)
(Equally distributed)
TIE REINFORCEMENT : Provide 8 mm dia. circular ties @ 190 mm c/c

SECTION CAPACITY BASED ON REINFORCEMENT REQUIRED (KNS-MET)


----------------------------------------------------------
Puz : 3304.79 Muz1 : 185.75 Muy1 : 185.75
INTERACTION RATIO: 0.98 (as per Cl. 39.6, IS456:2000)
SECTION CAPACITY BASED ON REINFORCEMENT PROVIDED (KNS-MET)
----------------------------------------------------------
WORST LOAD CASE: 43
END JOINT: 1720 Puz : 2923.89 Muz : 151.01 Muy : 151.03 IR: 0.97
Rev

CHECKED
DHC
GVPR ENGINEERS LIMITED
Document Rev
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO
PROJECT: GROUP OF VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR
DISTRICT -SONBHADRA GVPR-250KL-25M-001 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM DESIGNED CHECKED


TITLE :
GHATI (Zone-C) UTTAR PRADESH PSD DHC
6.0 DESIGN OF TIE BEAM

BB EE AA M
M NN O.
O. 2007
562 D
D EE SS II G
GNN RR EE SS U
U LL TT SS

M30 Fe500 (Main) Fe500 (Sec.)

LENGTH: 3525.0 mm SIZE: 300.0 mm X 500.0 mm COVER: 30.0 mm

SUMMARY OF REINF. AREA (Sq.mm)


----------------------------------------------------------------------------
SECTION 0.0 mm 881.3 mm 1762.5 mm 2643.8 mm 3525.0 mm
----------------------------------------------------------------------------
TOP 984.40 458.56 236.64 341.51 822.85
REINF. (Sq. mm) (Sq. mm) (Sq. mm) (Sq. mm) (Sq. mm)

BOTTOM 878.85 457.88 236.64 386.20 823.05


REINF. (Sq. mm) (Sq. mm) (Sq. mm) (Sq. mm) (Sq. mm)
----------------------------------------------------------------------------

SUMMARY OF PROVIDED REINF. AREA


----------------------------------------------------------------------------
SECTION 0.0 mm 881.3 mm 1762.5 mm 2643.8 mm 3525.0 mm
----------------------------------------------------------------------------
TOP 5-16í 3-16í 3-16í 3-16í 5-16í
REINF. 1 layer(s) 1 layer(s) 1 layer(s) 1 layer(s) 1 layer(s)

BOTTOM 8-12í 5-12í 3-12í 4-12í 8-12í


REINF. 2 layer(s) 1 layer(s) 1 layer(s) 1 layer(s) 2 layer(s)

SHEAR 2 legged 8í 2 legged 8í 2 legged 8í 2 legged 8í 2 legged 8í


REINF. @ 300 mm c/c @ 300 mm c/c @ 300 mm c/c @ 300 mm c/c @ 300 mm c/c
GVPR ENGINEERS LIMITED
Document No
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO
Project GROUP OF VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR
DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM


Title GHATI (Zone-C) UTTAR PRADESH Date 3/19/2021

7.0) Design of Footing


Size of column = 450 Ф
Diameter in which the columns are placed = 7.05
Width of annular footing = 3.80
Outer diameter of the footing = 10.00
Inner diameter of the footing = 2.40
Area of the footing = 74
Sectional modulus of footing = 97.8
Soil bearing capacity in static load case = 120
Soil bearing capacity in wind load case Increase in SBC = 1.25 = 150
Soil bearing capacity in Earthquake load case Increase in SBC = 1.25 = 150
Overburden height of soil = 0
Overburden soil pressure = 0.00 x 18 = 0
Soil bearing capacity including over burden soil 120
Force-Y Moment-X Moment-Z
Load Combination pmax pmin pmax check
kN kNm kNm
11 DL+LL 6765.821 -1.37 -16.347 92 91 Safe
12 DL+ EQ+X + 0.3EQ+Z 6082.735 -0.103 -19.865 82 82 Safe
13 DL+ EQ-X + 0.3EQ-Z 6082.735 -0.103 -19.865 82.4 82 Safe
14 DL+ EQ+Z + 0.3EQ+X 6082.735 -0.103 -19.865 82 82 Safe
15 DL+ EQ-Z + 0.3EQ-X 6082.735 -0.103 -19.865 82 82 Safe
16 DL+WLX+ 6063.547 -0.24 309.999 82 79 Safe
17 DL+WLX- 6063.545 0.038 -349.723 82 78 Safe
18 DL+WLZ+ 6063.547 -396.693 -19.696 86 78 Safe
19 DL+WLZ- 6063.546 396.5 -20.037 86 78 Safe
20 DL+LL+ EQ+X + 0.3EQ+Z 6765.821 -1.37 -16.347 92 91 Safe
21 DL+LL+ EQ-X + 0.3EQ-Z 6765.821 -1.37 -16.347 92 91 Safe
22 DL+LL+ EQ+Z + 0.3EQ+X 6765.821 -1.37 -16.347 92 91 Safe
23 DL+LL+ EQ-Z + 0.3EQ-X 6765.821 -1.37 -16.347 92 91 Safe
24 DL+LL+WLX+ 6746.633 -1.51 314.528 91 88 Safe
25 DL+LL+WLX- 6746.633 -1.226 -347.217 91 88 Safe
26 DL+LL+WLZ+ 6746.633 -399.145 -16.173 95 87 Safe
27 DL+LL+WLZ- 6746.634 396.418 -16.521 95 87 Safe
28 DL+0.8(LL+ EQ+X + 0.3EQ+Z) 6629.202 -1.114 -17.052 90 89 Safe
29 DL+0.8(LL+ EQ-X + 0.3EQ-Z) 6629.202 -1.114 -17.052 90 89 Safe
30 DL+0.8(LL+ EQ+Z + 0.3EQ+X) 6629.202 -1.114 -17.052 90 89 Safe
31 DL+0.8(LL+ EQ-Z + 0.3EQ-X) 6629.202 -1.114 -17.052 90 89 Safe
32 DL+0.8(LL+WLX+) 6613.852 -1.228 247.496 90 87 Safe
33 DL+0.8(LL+WLX-) 6613.853 -1 -281.596 90 87 Safe
GVPR ENGINEERS LIMITED
Document No
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO
Project GROUP OF VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR
DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM


Title GHATI (Zone-C) UTTAR PRADESH Date 3/19/2021

34 DL+0.8(LL+WLZ+) 6613.854 -319.158 -16.916 93 86 Safe


35 DL+0.8(LL+WLZ-) 6613.853 316.939 -17.192 93 86 Safe

Force-Y Moment-X Moment-Z


Critical load combination pmax pmin
kN kNm kNm
26 DL+LL+WLZ+ 6747 -399 -16 95 87
11 DL+LL 6766 -1 -16 92 91
GVPR ENGINEERS LIMITED
Revision

m
m
m
m
sqm
cum
kN/sqm
kN/sqm
kN/sqm
m
kN/sqm
kN/sqm

pmin check

Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
Safe
GVPR ENGINEERS LIMITED
Revision

Safe
Safe
GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project
BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Date
Title
UTTAR PRADESH 19-Mar-21
7.1) Design of Annular Raft :
Grade of concrete ( fck ) = M 30
Grade of steel ( fy ) = Fe 500
Total Load coming from columns = 6765.82 Kn
Maximum Bending moment due to wind = 396.50 knm
Add 10 % for Weight of Footing = 676.58 Kn
Total Weight = 7442.40 Kn
Say = 7500.00 Kn
Net Safe Bearing Capacity of Soil = 120.00 kn/m2
Soil bearing capacity in wind load case = 150.00 kn/m2
Area of Footing required (A) = 62.50 m2
Area of footing on either sides of ring beam is equal
Centre to centre diameter of staging = 7.05 mt
Radius of inner edge of Footing Ri
Π*( R2 - Ri2 ) = A / 2
Ri = (SQRT((3.525^2-(62.5/2*Π)) = 1.574 mt
Say Ri = 1.2 mt
Radius of outer edge of Footing Ro
Π*( Ro2 - R2 ) = A / 2
Ro = (SQRT((3.525^2+(62.5/(2*Π)) = 4.73 mt
Say Ro = 5 mt
(2/3)*( Ro3 - Ri3 )/( Ro2 - Ri2 ) = R
(2/3)*( 5^3 - 1.2^3 )/( 5^2 - 1.2^2 ) = 3.49 mt
= 3.53 mt

Area of Raft provided (A) = Π*( Ro2 - Ri2 )


Π*(5^2-1.2^2) = 74.02 m2
> 62.50 m2
Sectional modules of footing Z = Π*( Ro4 - Ri4 )/4Ro = 97.80 m3

Check for foundation :


Upward pressure for DL + LL case =7500/74.02 = 101.32 kn/m2
Net Upward pressure for DL + LL case =6765.821/74.02 = 91.41 kn/m2
< 120.00 kn/m2
GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project
BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Date
Title
UTTAR PRADESH 19-Mar-21

Upward pressure for DL + WL case P/ A + M/ Z =7500/74.02 +


396.5/97.8 = 105.38 kn/m2
Net Upward pressure for DL + WL case P/ A + M/ Z
=6765.821/74.02 + 396.5/97.8 = 95.46 kn/m2
< 150.00 kn/m2
Hence Safe
P/ A - M/ Z = 6765.821/74.02 - 396.5/97.8 = 97.27 kn/m2
Hence Safe

7.2) Design of Raft Ring Beam


Let The width of Ring Beam = 450 mm
Depth of Ring Beam = 900 mm
Size of columns supporting beam = 450 Dia
The Beam is supporting on no of columns = 6
2α = 60° 1.047
β0 = 12.75 0.223
α = 30° 0.524
Bending moment Coefficients are
At support λ- = 0.089
At span λ+ = 0.045
Torsional moment coefficient is λt = 0.009
Net upward Pressure per mt w = 95.46 kn/m2
load per meter run = 362.75 kn/m
Radius r =7.05/2 = 3.53 mt
Max Support Moment = 2α * w * r2 * λ-
0.089*362.75*1.047*3.525^2 = 420.090 kn/m
Max span Moment = 2α * w * r2 * λ+
0.045*362.75*1.047*3.525^2 = 212.40 knm
Max Torsional Moment = 2α * w * r2 * λt
0.009*362.75*1.047*3.525^2 = 42.48 knm
Shear Force at Support ( Vo ) Π * D1 * w/ 2 * n
(22*7.05*363 /(2*6*7)) = 669.52 kn
Shear Force at the section of max Torsion V' = Vo * ( 1- βo/α)
(670*(1-12.75/30) = 384.97 kn
GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project
BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Date
Title
UTTAR PRADESH 19-Mar-21

Moment at Face of column = w*r12*(-1+α sin φ +α cos φ * cotα )


GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project
BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Date
Title
UTTAR PRADESH 19-Mar-21
Tanφ = 0.225
r1
= 0.064 radians
φ = 3.65 °
α*Sinφ = 0.0334
α*Cosφ*cotα = 0.9051
Moment at Face of column M1
(363*3.525^2* (-1+0.0334+0.9051)) = -277.600
Torsional Moment at Face of column = w*r12*(φ-α+α cos φ -α sin φ * cotα )
α*Cosφ = 0.5225
α*Sinφ*cotα = 0.0578
Torsional Moment at Face of column
(363*3.525^2* (0.064-0.524+0.5225-0.0578)) = 22.52 knm
Distance of max torsion from face of the supports
2*PI()*3.525*12.75/360-0.225 = 0.559 m
< 0.780
Equivalent Bending Moment at face of column M 2 = T ( 1+D/b) / 1.7
D = 900 mm
b = 450 mm
M2 = (23*(1+0.9/0.45)/1.70) = 40 knm

Total Bending Moment at face of column M =M1+M2


M=(277.6+39.75) = 317.35 knm
Effective depth of beam required dreq = 514.90 mm
Dia of Reinf. = 20.00 mm
Dia of Stirrups = 10.00 mm
Clear Cover = 75.00 mm
Effective Depth = 780.00
Equivalent Bending Moment (where torque is maximum ) M = T ( 1+D/b)/1.7
(42.48*(1+0.9/0.45)/1.70) = 74.97 knm

Area of Reinforcement for support moment at face of column


Mu/bd2 = 1.739
Percentage of steel required as per SP-16 = 0.426
GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project
BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Date
Title
UTTAR PRADESH 19-Mar-21

Ast required = 1495 mm2


Pt reqd = 0.42593 %
GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project
BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Date
Title
UTTAR PRADESH 19-Mar-21
Area of Reinforcement for span moment

Mu/bd2 = 1.38
Percentage of steel required as per SP-16 = 0.33
Ast required = 1172 mm2

LONGITUDINAL REINFORCEMENT:
At Bottom :
Straight Bars
Dia of Bar = 20 mm
Area of Bar = 314.16 mm2
Required no of Bars at top = 4.76 no's
Provide no of Bars = 6 no's
Provided Area of Steel = 1884.96 mm2
Provided Area of Steel at bottom = 1884.96 mm2
Total Provided Area of Steel at bottom = 1884.96 mm2
At Top :
Straight Bars
Dia of Bar = 20 mm
Area of Bar = 314.16 mm2
Required no of Bars at Bottom = 3.73 no's
Provide no of Bars = 6 no's
Provided Area of Steel = 1884.96 mm2
Total Provided Area of Steel at top = 1884.96 mm2
At Bottom:
Provide 3 - # 20 tor through + 3- # 20 extra at supports(1884.96sqmm >1495sqmm)
At Top:
Provide 3 - # 20 tor through + 3- # 20 extra at supports(1884.96sqmm >1172sqmm)
GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project
BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Date
Title
UTTAR PRADESH 19-Mar-21
Shear force at 78cm from face of column V '= Vo - w * ( d + S2/2)
(100.5cm from centre of column ) V
(670-95*(1.005) = 574 kn
Equivalent shear at section of max torsion Ve = V' + 1.6 * T / b
(385+1.6*42/0.45) = 536.02 kn
Equivalent Shear Stress ζve = 1.5 x Ve/ (b*d)
536020 x 1.5 /(450*780) = 2.29 N/mm2
Area of Steel at Support = 1884.96 mm2
pt = 0.54
From table 19 of IS 456, permissible shear stress of concrete ζc = 0.510 N/mm2
Shear Capacity of Section ‫ﺡ‬cbd=0.51*450*780 = 179010 N
Net Shear =536020-179010 = 357010 N
TRANSVERSE REINFORCEMENT :
Dia of Stirrups = 10 mm
No of Legs = 4
Area of shear reinforcement as per Clause 41.4.3. of IS 456 - 2000
Spacing should be lesser of the following :
A) Asv / Sv = (T / b1 * d1 * σsv) + (V / 2.5 * d1 * σsv)
σsv = 0.87 fy = 435 N/mm2
Dia of main reinforcement = 20
Dia of stirrups = 10
Cover = 75.00
b1=(450-10*2-75*2-20)/10 = 260.00 mm
d1=(900-10*2-75*2-20)/10 = 710.00 mm
Asv = 314.16 sqmm
Asv / Sv = 42*1.5
*10^6/(260*710*435)+(384973.3x1.5/(2.5*710*435)) = 1.54
Asv / Sv = 1.54
Sv=314.16/1.54 = 203.81 mm

B) Sv = (Asv * σsv) / (b * ( ζve - ζc ))


314.16*435 = 170.55 mm
45*(2.29-0.51) x 10
Spacing is Lesser of above two cases = 170.55 mm
Say = 150.00 mm
GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project
BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Date
Title
UTTAR PRADESH 19-Mar-21
Dia of Stirrups = 10 mm
No of Legs = 4
Asv = 314.16 mm2
Minimum Shear Reinforcement = Asv / bSv >= (0.4/0.87fy )
Sv < = = 759.22 mm
0.75 d = 532.5 mm
= 300 mm
Provided Spacing is Lesser of above two cases = 200 mm
Stirrups :
Provide support to 800 # 10 - 4L stirrups @ 150 mm c/c
Provide 800 to center # 10 - 4L stirrups @ 200 mm c/c

Ductile Detailing of Beam:


As per IS 13920 : 2016
same spacing as above, shall also be provided over a length equal to 2d on either side of a section
where flexural yielding may occur under the effect of earthquake forces. Elsewhere, the beam shall
Width of Beam = 450 mm
Depth of beam = 900 mm
Clear cover = 45 mm
Dia of Hoop = 10 mm
Dia of Main bar provided = 16 mm
Effective depth = 854.2 mm
The spacing of hoops over a length of 2d at either ends of a beam shall not exceed
(a) d/4 = 213.55 mm
(b) 8 times the diameter of the smallest longitudinal bar = 128 mm
(c) 100 mm = 100 mm
Min (213.55,128,100) = 100 mm
Provide Spacing at Supports = 100 mm
Length of Confining steel from face of the support, 2d = 1708.4 mm
Say = 1750 mm
Elsewhere, the beam shall have vertical hoops at a spacing not exceeding d/2.
d/2 = 450 mm
Elsewhere, the beam shall have vertical hoops at a spacing of = 200 mm
Stirrups :
Hence Provide 4L - Y10 stirrups Spacing @ 100 mm c/c throughout

b.) Design of Slab :


GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project
BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Date
Title
UTTAR PRADESH 19-Mar-21
Net Upward pressure = 95.46 kn/m2
Length of projection of footing inner side Li=3.525-1.2-0.225 = 2.1 mt
Length of projection of footing outer side Lo=5-3.525-0.225 = 1.25 mt
GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project
BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Date
Title
UTTAR PRADESH 19-Mar-21

Bending Moment at inner face of ring beam Mi = 95.46*2.1^2/2 = 210.49 knm

Bending Moment at outer face of ring beam Mo = 95.46*1.25^2/2 = 74.58 knm


Effective depth of slab required dreq = 281 mm

Provided Depth of Footing at end is 250mm. O.K = 250.00 mm


Provided Depth of Footing at Beam Edge is 900mm. O.K = 900.00 mm
Dia of Main Reinforcement = 16 mm
Area of Bar = 201.06 mm2
Clear cover = 75.00 mm
Effective Depth = 824.2 mm
Area of Reinforcement at face of Beam
from table 20 of SP:16
Required Spacing ( S ) = 228.27 mm
Provided Spacing = 175 mm
Area of Steel Provided = 1148.91 mm2
Provide 16 tor @175 mm c/c as Radials ( spacing measured at outer face of Ring Beam )
Distribution Steel :
Minimum reinforcement = 0.12 %
Area of cross section of footing inner side =(2.1*(25+90)/200) = 1.2075 m2
m^2 in width of
Area of reinforcement = 0.12*120.75 = 0.001449 2.1mt

= 0.00069 m2 in 1 mt
Dia of Bar = 12 mm
Area of Bar = 113.1 mm2
Spacing required = 0.16 m
Spacing Provided = 163.91
= 125 mm
Area of Steel Provided 1610 mm2
Provide 12 tor Rings @125 mm c/c ( spacing measured at outer face of Ring Beam )

CHECK FOR PUNCHING SHEAR :


Shear force at a distance ( 824.2)/2 mm from face of ring beam
95.46*(2.1-0.4121) = 161.13 Kn
GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project
BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Date
Title
UTTAR PRADESH 19-Mar-21
Depth of footing at distance = d/2 = (824.2)/2 mm
900-(900-250)*412.1/2100 = 772.45 mm
Effective depth 'd' = 689.45 mm
GVPR ENGINEERS LIMITED
Document No.
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
Project
BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) Date
Title
UTTAR PRADESH 19-Mar-21
Shear Stress ζve = 1.5 x Ve/ (b*d) = 0.35 N/mm2
< ζc
ζc = 0.16√fck = 0.88 N/mm2
Hence, Safe

CHECK FOR BEAM SHEAR :


Shear force at a distance 824.2 cm from face of ring beam
95.46*(2.1-0.8242) = 121.79 Kn
Depth of footing at distance d = 824.2cm
900-(900-250)*824.2/2100 = 644.89 mm
Effective depth 'd' = 561.89 mm
Shear Stress ζve = 1.5 x Ve/ (b*d) = 0.33 N/mm2
% of steel provided ( p ) = 0.20
As per table -19 of IS 456-2000, Permissible shear stress 0.34 N/mm2
Hence, Safe
All stresses for portion of footing on either side of ring beam will be within permissible stresses
as length of projection is higher on inner side than outer side
cument No.

250KL-25M-001

Rev
A
cument No.

250KL-25M-001

Rev
A

rad
rad
rad
cument No.

250KL-25M-001

Rev
A

de of a section
the beam shall

ut
cument No.

250KL-25M-001

Rev
A

m^2 in width of
2.1mt
m2 in 1 mt
Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 11 DL+LL 2.496 1147.281 0.068 -0.202 -0.011 -3.534
1727 11 DL+LL 2.436 1137.926 -0.92 -0.875 -0.085 -3.346
1728 11 DL+LL 0.893 1113.704 0.166 0.439 0.106 -2.157
1729 11 DL+LL 2.59 1120.895 0.134 -0.127 0.001 -2.637
1730 11 DL+LL 0.673 1107.116 0.267 -0.451 -0.083 -1.854
1731 11 DL+LL 1.861 1138.899 0.284 -0.154 0.094 -2.819
11 DL+LL 10.949 6765.821 -0.001 -1.37 0.022 -16.347

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 12 DL+ EQ+X + 0.3EQ+Z 2.293 1044.509 0.015 0.007 0 -3.721
1727 12 DL+ EQ+X + 0.3EQ+Z 2.578 1027.198 -0.406 -0.313 -0.002 -3.925
1728 12 DL+ EQ+X + 0.3EQ+Z 1.541 999.375 -1.21 -0.972 0.015 -3.092
1729 12 DL+ EQ+X + 0.3EQ+Z 0.492 984.926 -0.002 -0.034 0.001 -2.182
1730 12 DL+ EQ+X + 0.3EQ+Z 1.529 997.822 1.21 0.916 -0.002 -3.073
1731 12 DL+ EQ+X + 0.3EQ+Z 2.517 1028.905 0.393 0.293 0.014 -3.872
12 DL+ EQ+X + 0.3EQ+Z 10.95 6082.735 -1.2143E-17 -0.103 0.026 -19.865

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 13 DL+ EQ-X + 0.3EQ-Z 2.293 1044.509 0.015 0.007 0 -3.721
1727 13 DL+ EQ-X + 0.3EQ-Z 2.578 1027.198 -0.406 -0.313 -0.002 -3.925
1728 13 DL+ EQ-X + 0.3EQ-Z 1.541 999.375 -1.21 -0.972 0.015 -3.092
1729 13 DL+ EQ-X + 0.3EQ-Z 0.492 984.926 -0.002 -0.034 0.001 -2.182
1730 13 DL+ EQ-X + 0.3EQ-Z 1.529 997.822 1.21 0.916 -0.002 -3.073
1731 13 DL+ EQ-X + 0.3EQ-Z 2.517 1028.905 0.393 0.293 0.014 -3.872
13 DL+ EQ-X + 0.3EQ-Z 10.95 6082.735 -1.2143E-17 -0.103 0.026 -19.865

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 14 DL+ EQ+Z + 0.3EQ+X 2.293 1044.509 0.015 0.007 0 -3.721
1727 14 DL+ EQ+Z + 0.3EQ+X 2.578 1027.198 -0.406 -0.313 -0.002 -3.925
1728 14 DL+ EQ+Z + 0.3EQ+X 1.541 999.375 -1.21 -0.972 0.015 -3.092
1729 14 DL+ EQ+Z + 0.3EQ+X 0.492 984.926 -0.002 -0.034 0.001 -2.182
1730 14 DL+ EQ+Z + 0.3EQ+X 1.529 997.822 1.21 0.916 -0.002 -3.073
1731 14 DL+ EQ+Z + 0.3EQ+X 2.517 1028.905 0.393 0.293 0.014 -3.872
14 DL+ EQ+Z + 0.3EQ+X 10.95 6082.735 -1.2143E-17 -0.103 0.026 -19.865

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 15 DL+ EQ-Z + 0.3EQ-X 2.293 1044.509 0.015 0.007 0 -3.721
1727 15 DL+ EQ-Z + 0.3EQ-X 2.578 1027.198 -0.406 -0.313 -0.002 -3.925
1728 15 DL+ EQ-Z + 0.3EQ-X 1.541 999.375 -1.21 -0.972 0.015 -3.092
1729 15 DL+ EQ-Z + 0.3EQ-X 0.492 984.926 -0.002 -0.034 0.001 -2.182
1730 15 DL+ EQ-Z + 0.3EQ-X 1.529 997.822 1.21 0.916 -0.002 -3.073
1731 15 DL+ EQ-Z + 0.3EQ-X 2.517 1028.905 0.393 0.293 0.014 -3.872
15 DL+ EQ-Z + 0.3EQ-X 10.95 6082.735 -1.2143E-17 -0.103 0.026 -19.865

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 16 DL+WLX+ -21.42 668.646 0.064 -0.003 -0.014 47.008
1727 16 DL+WLX+ -32.454 840.277 -8.968 -8.097 0.605 54.594
1728 16 DL+WLX+ -32.705 1181.669 5.48 3.837 -0.475 54.95
1729 16 DL+WLX+ -19.954 1350.533 -0.03 -0.051 -0.015 43.721
1730 16 DL+WLX+ -32.976 1180.953 -5.367 -3.789 0.453 55.187
1731 16 DL+WLX+ -32.353 841.469 8.821 7.863 -0.63 54.539
16 DL+WLX+ -171.862 6063.547 1.9429E-16 -0.24 -0.076 309.999

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 17 DL+WLX- 22.534 1409.69 -0.032 0.02 0.013 -49.469
1727 17 DL+WLX- 37.184 1209.847 6.269 4.506 0.487 -62.27
1728 17 DL+WLX- 36.204 812.83 -9.786 -8.746 -0.595 -61.299
1729 17 DL+WLX- 24.419 608.654 0.027 -0.016 0.016 -53.071
1730 17 DL+WLX- 36.458 810.445 9.674 8.587 0.644 -61.503
1731 17 DL+WLX- 36.961 1212.079 -6.152 -4.313 -0.445 -62.111
17 DL+WLX- 193.76 6063.545 -1.0755E-16 0.038 0.12 -349.723

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 18 DL+WLZ+ 4.193 1044.294 -46.79 -74.222 0.067 -6.677
1727 18 DL+WLZ+ -6.305 1383.514 -30.847 -60.615 -0.509 3.324
1728 18 DL+WLZ+ 10.201 1356.814 -31.642 -61.338 0.505 -10.037
1729 18 DL+WLZ+ -1.203 984.327 -47.001 -74.371 -0.1 0.609
1730 18 DL+WLZ+ -7.438 631.864 -31.874 -62.776 -0.6 4.195
1731 18 DL+WLZ+ 11.5 662.734 -32.6 -63.371 0.587 -11.11
18 DL+WLZ+ 10.948 6063.547 -220.754 -396.693 -0.05 -19.696

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 19 DL+WLZ- 3.72 1042.971 46.817 74.233 -0.069 -6.218
1727 19 DL+WLZ- 11.731 662.162 32.661 63.299 -0.571 -11.382
1728 19 DL+WLZ- -7.384 633.203 31.843 62.704 0.606 4.057
1729 19 DL+WLZ- -1.15 983.811 47.006 74.314 0.101 0.486
1730 19 DL+WLZ- 10.234 1355.058 31.67 61.305 -0.488 -10.141
1731 19 DL+WLZ- -6.202 1386.341 30.756 60.645 0.522 3.161
19 DL+WLZ- 10.949 6063.546 220.753 396.5 0.101 -20.037

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 20 DL+LL+ EQ+X + 0.3EQ+Z 2.496 1147.281 0.068 -0.202 -0.011 -3.534
1727 20 DL+LL+ EQ+X + 0.3EQ+Z 2.436 1137.926 -0.92 -0.875 -0.085 -3.346
1728 20 DL+LL+ EQ+X + 0.3EQ+Z 0.893 1113.704 0.166 0.439 0.106 -2.157
1729 20 DL+LL+ EQ+X + 0.3EQ+Z 2.59 1120.895 0.134 -0.127 0.001 -2.637
1730 20 DL+LL+ EQ+X + 0.3EQ+Z 0.673 1107.116 0.267 -0.451 -0.083 -1.854
1731 20 DL+LL+ EQ+X + 0.3EQ+Z 1.861 1138.899 0.284 -0.154 0.094 -2.819
20 DL+LL+ EQ+X + 0.3EQ+Z 10.949 6765.821 -0.001 -1.37 0.022 -16.347

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 21 DL+LL+ EQ-X + 0.3EQ-Z 2.496 1147.281 0.068 -0.202 -0.011 -3.534
1727 21 DL+LL+ EQ-X + 0.3EQ-Z 2.436 1137.926 -0.92 -0.875 -0.085 -3.346
1728 21 DL+LL+ EQ-X + 0.3EQ-Z 0.893 1113.704 0.166 0.439 0.106 -2.157
1729 21 DL+LL+ EQ-X + 0.3EQ-Z 2.59 1120.895 0.134 -0.127 0.001 -2.637
1730 21 DL+LL+ EQ-X + 0.3EQ-Z 0.673 1107.116 0.267 -0.451 -0.083 -1.854
1731 21 DL+LL+ EQ-X + 0.3EQ-Z 1.861 1138.899 0.284 -0.154 0.094 -2.819
21 DL+LL+ EQ-X + 0.3EQ-Z 10.949 6765.821 -0.001 -1.37 0.022 -16.347
Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 22 DL+LL+ EQ+Z + 0.3EQ+X 2.496 1147.281 0.068 -0.202 -0.011 -3.534
1727 22 DL+LL+ EQ+Z + 0.3EQ+X 2.436 1137.926 -0.92 -0.875 -0.085 -3.346
1728 22 DL+LL+ EQ+Z + 0.3EQ+X 0.893 1113.704 0.166 0.439 0.106 -2.157
1729 22 DL+LL+ EQ+Z + 0.3EQ+X 2.59 1120.895 0.134 -0.127 0.001 -2.637
1730 22 DL+LL+ EQ+Z + 0.3EQ+X 0.673 1107.116 0.267 -0.451 -0.083 -1.854
1731 22 DL+LL+ EQ+Z + 0.3EQ+X 1.861 1138.899 0.284 -0.154 0.094 -2.819
22 DL+LL+ EQ+Z + 0.3EQ+X 10.949 6765.821 -0.001 -1.37 0.022 -16.347

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 23 DL+LL+ EQ-Z + 0.3EQ-X 2.496 1147.281 0.068 -0.202 -0.011 -3.534
1727 23 DL+LL+ EQ-Z + 0.3EQ-X 2.436 1137.926 -0.92 -0.875 -0.085 -3.346
1728 23 DL+LL+ EQ-Z + 0.3EQ-X 0.893 1113.704 0.166 0.439 0.106 -2.157
1729 23 DL+LL+ EQ-Z + 0.3EQ-X 2.59 1120.895 0.134 -0.127 0.001 -2.637
1730 23 DL+LL+ EQ-Z + 0.3EQ-X 0.673 1107.116 0.267 -0.451 -0.083 -1.854
1731 23 DL+LL+ EQ-Z + 0.3EQ-X 1.861 1138.899 0.284 -0.154 0.094 -2.819
23 DL+LL+ EQ-Z + 0.3EQ-X 10.949 6765.821 -0.001 -1.37 0.022 -16.347

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 24 DL+LL+WLX+ -21.192 769.898 0.117 -0.209 -0.026 47.334
1727 24 DL+LL+WLX+ -32.623 950.243 -9.508 -8.678 0.524 55.359
1728 24 DL+LL+WLX+ -33.366 1296.753 6.892 5.275 -0.383 56.067
1729 24 DL+LL+WLX+ -17.809 1488.023 0.106 -0.149 -0.016 43.419
1730 24 DL+LL+WLX+ -33.845 1291.008 -6.348 -5.194 0.375 56.582
1731 24 DL+LL+WLX+ -33.028 950.708 8.741 7.445 -0.548 55.767
24 DL+LL+WLX+ -171.863 6746.633 1.027E-15 -1.51 -0.074 314.528

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 25 DL+LL+WLX- 22.712 1513.982 0.022 -0.192 0.004 -49.418
1727 25 DL+LL+WLX- 37.066 1321.34 5.784 3.962 0.403 -61.877
1728 25 DL+LL+WLX- 35.571 926.406 -8.443 -7.366 -0.508 -60.545
1729 25 DL+LL+WLX- 26.47 743.1 0.163 -0.105 0.017 -53.683
1730 25 DL+LL+WLX- 35.619 918.976 8.765 7.261 0.563 -60.46
1731 25 DL+LL+WLX- 36.323 1322.829 -6.29 -4.786 -0.368 -61.234
25 DL+LL+WLX- 193.761 6746.633 0.001 -1.226 0.111 -347.217

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 26 DL+LL+WLZ+ 4.391 1147.061 -46.783 -74.66 0.057 -6.484
1727 26 DL+LL+WLZ+ -6.482 1495.739 -31.339 -61.358 -0.591 3.936
1728 26 DL+LL+WLZ+ 9.593 1472.649 -30.247 -60.113 0.593 -9.13
1729 26 DL+LL+WLZ+ 0.905 1120.302 -46.891 -74.699 -0.1 0.146
1730 26 DL+LL+WLZ+ -8.333 739.661 -32.806 -64.323 -0.679 5.443
1731 26 DL+LL+WLZ+ 10.874 771.221 -32.688 -63.992 0.665 -10.084
26 DL+LL+WLZ+ 10.948 6746.633 -220.754 -399.145 -0.055 -16.173

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 27 DL+LL+WLZ- 3.924 1145.75 46.917 74.253 -0.08 -6.042
1727 27 DL+LL+WLZ- 11.623 771.395 32.127 62.921 -0.655 -10.836
1728 27 DL+LL+WLZ- -8.071 746.025 33.203 64.303 0.699 5.021
1729 27 DL+LL+WLZ- 0.944 1119.774 47.168 74.456 0.101 0.045
1730 27 DL+LL+WLZ- 9.418 1465.847 30.713 60.114 -0.57 -8.95
1731 27 DL+LL+WLZ- -6.888 1497.843 30.626 60.371 0.605 4.241
27 DL+LL+WLZ- 10.95 6746.634 220.754 396.418 0.1 -16.521

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 28 DL+0.8(LL+ EQ+X + 0.3EQ+Z) 2.455 1126.727 0.058 -0.16 -0.009 -3.572
1727 28 DL+0.8(LL+ EQ+X + 0.3EQ+Z) 2.464 1115.781 -0.817 -0.762 -0.068 -3.462
1728 28 DL+0.8(LL+ EQ+X + 0.3EQ+Z) 1.023 1090.838 -0.109 0.157 0.088 -2.344
1729 28 DL+0.8(LL+ EQ+X + 0.3EQ+Z) 2.171 1093.7 0.107 -0.108 0.001 -2.546
1730 28 DL+0.8(LL+ EQ+X + 0.3EQ+Z) 0.844 1085.256 0.455 -0.177 -0.067 -2.098
1731 28 DL+0.8(LL+ EQ+X + 0.3EQ+Z) 1.992 1116.9 0.306 -0.064 0.078 -3.03
28 DL+0.8(LL+ EQ+X + 0.3EQ+Z) 10.949 6629.202 6.245E-17 -1.114 0.023 -17.052

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 29 DL+0.8(LL+ EQ-X + 0.3EQ-Z) 2.455 1126.727 0.058 -0.16 -0.009 -3.572
1727 29 DL+0.8(LL+ EQ-X + 0.3EQ-Z) 2.464 1115.781 -0.817 -0.762 -0.068 -3.462
1728 29 DL+0.8(LL+ EQ-X + 0.3EQ-Z) 1.023 1090.838 -0.109 0.157 0.088 -2.344
1729 29 DL+0.8(LL+ EQ-X + 0.3EQ-Z) 2.171 1093.7 0.107 -0.108 0.001 -2.546
1730 29 DL+0.8(LL+ EQ-X + 0.3EQ-Z) 0.844 1085.256 0.455 -0.177 -0.067 -2.098
1731 29 DL+0.8(LL+ EQ-X + 0.3EQ-Z) 1.992 1116.9 0.306 -0.064 0.078 -3.03
29 DL+0.8(LL+ EQ-X + 0.3EQ-Z) 10.949 6629.202 6.245E-17 -1.114 0.023 -17.052

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 30 DL+0.8(LL+ EQ+Z + 0.3EQ+X) 2.455 1126.727 0.058 -0.16 -0.009 -3.572
1727 30 DL+0.8(LL+ EQ+Z + 0.3EQ+X) 2.464 1115.781 -0.817 -0.762 -0.068 -3.462
1728 30 DL+0.8(LL+ EQ+Z + 0.3EQ+X) 1.023 1090.838 -0.109 0.157 0.088 -2.344
1729 30 DL+0.8(LL+ EQ+Z + 0.3EQ+X) 2.171 1093.7 0.107 -0.108 0.001 -2.546
1730 30 DL+0.8(LL+ EQ+Z + 0.3EQ+X) 0.844 1085.256 0.455 -0.177 -0.067 -2.098
1731 30 DL+0.8(LL+ EQ+Z + 0.3EQ+X) 1.992 1116.9 0.306 -0.064 0.078 -3.03
30 DL+0.8(LL+ EQ+Z + 0.3EQ+X) 10.949 6629.202 6.245E-17 -1.114 0.023 -17.052

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 31 DL+0.8(LL+ EQ-Z + 0.3EQ-X) 2.455 1126.727 0.058 -0.16 -0.009 -3.572
1727 31 DL+0.8(LL+ EQ-Z + 0.3EQ-X) 2.464 1115.781 -0.817 -0.762 -0.068 -3.462
1728 31 DL+0.8(LL+ EQ-Z + 0.3EQ-X) 1.023 1090.838 -0.109 0.157 0.088 -2.344
1729 31 DL+0.8(LL+ EQ-Z + 0.3EQ-X) 2.171 1093.7 0.107 -0.108 0.001 -2.546
1730 31 DL+0.8(LL+ EQ-Z + 0.3EQ-X) 0.844 1085.256 0.455 -0.177 -0.067 -2.098
1731 31 DL+0.8(LL+ EQ-Z + 0.3EQ-X) 1.992 1116.9 0.306 -0.064 0.078 -3.03
31 DL+0.8(LL+ EQ-Z + 0.3EQ-X) 10.949 6629.202 6.245E-17 -1.114 0.023 -17.052

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 32 DL+0.8(LL+WLX+) -16.445 825.047 0.097 -0.166 -0.02 37.087
1727 32 DL+0.8(LL+WLX+) -25.559 965.755 -7.677 -6.994 0.418 43.473
1728 32 DL+0.8(LL+WLX+) -26.403 1237.164 5.272 4.029 -0.303 44.208
1729 32 DL+0.8(LL+WLX+) -14.207 1387.163 0.084 -0.125 -0.012 34.291
1730 32 DL+0.8(LL+WLX+) -26.79 1232.256 -4.837 -3.974 0.298 44.625
1731 32 DL+0.8(LL+WLX+) -25.896 966.467 7.06 6.002 -0.435 43.812
32 DL+0.8(LL+WLX+) -135.3 6613.852 -0.001 -1.228 -0.054 247.496

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 33 DL+0.8(LL+WLX-) 18.683 1419.849 0.02 -0.151 0.003 -40.274
1727 33 DL+0.8(LL+WLX-) 30.186 1262.399 4.548 3.113 0.321 -50.259
1728 33 DL+0.8(LL+WLX-) 28.743 941.119 -6.985 -6.075 -0.402 -49.027
1729 33 DL+0.8(LL+WLX-) 21.228 791.691 0.13 -0.091 0.013 -43.344
1730 33 DL+0.8(LL+WLX-) 28.779 934.864 7.242 5.978 0.449 -48.956
1731 33 DL+0.8(LL+WLX-) 29.58 1263.931 -4.955 -3.774 -0.29 -49.736
33 DL+0.8(LL+WLX-) 157.199 6613.853 -3.5041E-16 -1 0.094 -281.596

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 34 DL+0.8(LL+WLZ+) 3.958 1126.561 -37.417 -59.692 0.045 -5.915
1727 34 DL+0.8(LL+WLZ+) -4.665 1401.798 -25.211 -49.133 -0.472 2.358
1728 34 DL+0.8(LL+WLZ+) 7.977 1377.759 -24.498 -48.269 0.477 -7.919
1729 34 DL+0.8(LL+WLZ+) 0.835 1093.234 -37.511 -59.731 -0.08 -0.337
1730 34 DL+0.8(LL+WLZ+) -6.354 791.517 -25.948 -51.236 -0.543 3.735
1731 34 DL+0.8(LL+WLZ+) 9.198 822.985 -26.018 -51.097 0.534 -8.838
34 DL+0.8(LL+WLZ+) 10.949 6613.854 -176.603 -319.158 -0.039 -16.916

Node L/C Force-X kN Force-Y kN Force-Z kN Moment-X kNm Moment-Y kNm Moment-Z kNm
1726 35 DL+0.8(LL+WLZ-) 3.583 1125.511 37.53 59.37 -0.064 -5.558
1727 35 DL+0.8(LL+WLZ-) 9.808 822.781 25.567 50.236 -0.523 -9.449
1728 35 DL+0.8(LL+WLZ-) -6.143 796.921 26.266 51.209 0.561 3.393
1729 35 DL+0.8(LL+WLZ-) 0.868 1092.813 37.731 59.523 0.081 -0.421
1730 35 DL+0.8(LL+WLZ-) 7.834 1372.007 24.87 48.26 -0.456 -7.771
1731 35 DL+0.8(LL+WLZ-) -5.003 1403.82 24.639 48.341 0.485 2.614
35 DL+0.8(LL+WLZ-) 10.947 6613.853 176.603 316.939 0.084 -17.192
GVPR ENGINEERS LIMITED

CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF Document no


PROJECT VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -
SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI Date Rev
TITLE
(Zone-C) UTTAR PRADESH 3/19/2021 A
8.0) DESIGN OF STAIRCASE
8.1) Design of Staircase Flight-1 to 14
Design of waist slab
Staircase is carried on staging columns
staircase is from GL to Mid landing beam
Riser of staircase, R = = 185.00 mm
Tread of staircase, T = = 300.00 mm
Width of staircase = = 1000 mm
Assume thickness of waist slab = = 150 mm
Clear cover to reinforcement = = 30 mm
Grade of Concrete, fck = = 30 N/mm2
Grade of steel, fy = = 500 N/mm2
Loads
Live load acting on the staircase = = 3 kN/m2
Inclined length of each step = b = SQRT(R*R+T*T)/T = 1.175
1) Self weight of RCC step = 0.5 x 185/1000 x 25 = = 2.310 kN/m2
2) Self weight of waist slab = 0.15* 25* 1.175 = 4.406 kN/m2
Total dead load acting = 4.41+ 2.31 = 6.716 kN/m2
Total load on waist slab = 6.72+ 3 = 10.000 kN/m2
Effective span of flight = 3.525 m
Max Bending moment = 10* 3.525* 3.525/ 10
= 12.43 knm
Area of steel required on bottom face of waist slab at span
Mu =1.5 x 12.425625= 18.64 kN-m/m
Diameter of bar provided = 12 mm
Effective depth of slab = 150 - 30 - 6 114 mm
Mu/bd 2
= 1.43 N/mm2
Percentage of steel required = 0.349 %
Area of steel required = 397.86 mm2/m
Minimum area of steel required 0.12/100 x 1000 x 150 = 180 mm2/m
Provide 12 dia @ 150 mm c/c as main steel
Provide 8 dia @ 150 mm c/c as distribution steel

Design of Landing beam


Span of landing beam = 0.9 m
Depth of beam = 0.35 m
width of beam = 0.35 m
Load from flights = 3.525* 10
= 35.25 kn/m
Self wt of beam = 3.063 kn/m
Total load = 38.31 kn/m
Max Bending moment = 38.3125* 0.9"* 0.9"/ 2
= 15.52 knm
GVPR ENGINEERS LIMITED

CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF Document no


PROJECT VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -
SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI Date Rev
TITLE
(Zone-C) UTTAR PRADESH 3/19/2021 A
Mu =1.5 x 15.5165625= = 23.27 kN-m/m
GVPR ENGINEERS LIMITED

CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF Document no


PROJECT VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -
SONBHADRA GVPR-250KL-25M-001

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI Date Rev
TITLE
(Zone-C) UTTAR PRADESH 3/19/2021 A
Diameter of bar provided = = 12 mm

Effective depth of slab = 350 - 30 - 6 = 314 mm

Mu/bd2 = 1.03 N/mm2

Percentage of steel required = 0.215 %

Area of steel required = 155.273 mm2/m

No of bars required = 1.374 no

= 4.000 no

Provide 4 no of 12 tor top as main reinforcemnt.

Provide 2 no of 12 tor at bottom

Shear force

Max shear force = 38.3125* 0.9/ 2

= 17.24 kn

% of Steel Provided = 100 x3x113/(230x314) = 0.30846


Permissible shear stress in concrete ( tc ) = 0.43105 N/mm2
Nominal shear stress ( tv ) = Vu/bd =17240.625/ (314*350)
= 0.14119 N/mm2
Provide Minimum Shear Reinforcement
Minimum Shear Reinforcement = Asv / bSv >= (0.4/0.87f y )
Sv <= 0.87fyAsv / 0.4b
Dai of bar = 8 mm
Sv = 156.103 mm

Provide 8tor2L@150 /c stirrups@150 c/c


GVPR ENGINEERS LIMITED
Document Rev
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO
PROJECT: GROUP OF VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR
GVPR-250KL-25M-001 A
DISTRICT -SONBHADRA

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM DESIGNED CHECKED


TITLE :
GHATI (Zone-C) UTTAR PRADESH PSD DHC

9.0 ANNEXURES
Water & Environment Division

GVPR ENGINEERS LIMITED


DOCUMENT NO.
PROJECT:
CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK -DUDDHI, BABHANI AND MYORPUR
DISTRICT -SONBHADRA GVPR-250KL-25M-001

TITLE : RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) UTTAR PRADESH Date. 3/19/2021

ANNEXURE - A

MOMENT COEFFICIENTS IN CYLINDRICAL WALL,FIXED BASE ,FREE TOP AND SUBJECTED TO TRIANGULAR LOAD

Table 10 - IS 3370 (PART-IV)-1967


H2/Dt 0.10h 0.20h 0.30h 0.40h. 0.50 h 0.60 h 0.70 h 0.80 H 0.90 h
0 1 2 3 4 5 6 7 8 9
0.4000 0.0005 0.0014 0.0021 0.0007 0.0042 -0.0150 -0.0303 -0.0529 -0.0816
0.8000 0.0011 0.0037 0.0063 0.0080 0.0070 0.0023 -0.0068 -0.0024 -0.0465
1.2000 0.0012 0.0042 0.0077 0.0103 0.0112 0.0090 0.0022 -0.0108 -0.0311
1.6000 0.0011 0.0041 0.0075 0.0107 0.0121 0.0111 0.0058 -0.0051 -0.0232
2.0000 0.0010 0.0035 0.0068 0.0099 0.0120 0.0115 0.0075 -0.0021 -0.0185
3.0000 0.0006 0.0024 0.0047 0.0071 0.0090 0.0097 0.0077 0.0012 -0.0119
4.0000 0.0003 0.0015 0.0028 0.0047 0.0066 0.0077 0.0069 0.0023 -0.0080
5.0000 0.0002 0.0008 0.0016 0.0029 0.0046 0.0059 0.0059 0.0028 -0.0058
6.0000 0.0001 0.0003 0.0008 0.0019 0.0032 0.0046 0.0051 0.0029 -0.0041
8.0000 0.0000 0.0001 0.0002 0.0008 0.0016 0.0028 0.0038 0.0029 -0.0022
10.0000 0.0000 0.0000 0.0001 0.0004 0.0007 0.0019 0.0029 0.0028 -0.0012
12.0000 0.0000 -0.0001 0.0001 0.0002 0.0003 0.0013 0.0023 0.0026 -0.0005
14.0000 0.0000 0.0000 0.0000 0.0000 0.0001 0.0008 0.0019 0.0023 -0.0001
16.0000 0.0000 0.0000 -0.0001 -0.0002 -0.0001 0.0004 0.0013 0.0019 0.0001

Height of side wall ( H )-mts 3.250 Diameter of container ( D )-mts 10.00 Thickness ( T )- mm 200
OPERATE FIGURES IN RED ONLY
H2/Dt 0.10h 0.20h 0.30h 0.40h. 0.50 h 0.60 h 0.70 h 0.80 H 0.90 h
5.281 0.00017 0.0007 0.0014 0.0026 0.0042066 0.00553 0.0056752 0.0028281 -0.0053223

DESIGN FOR BENDING MOMENT


TENSION IN CIRCULAR RING WALL,HINGED BASE ,FREE TOP AND SUBJECTED TO TRIANGULAR LOAD

Table 12 - IS 3370 (PART-IV)-1967

H2/Dt 0.0 H 0.10 H 0.20 H 0.30 H 0.40 H 0.50 H 0.60 H 0.70 H 0.80 H
0 1 2 3 4 5 6 7 8 9
0.4000 0.4740 0.4400 0.3950 0.3520 0.3080 0.2640 0.2150 0.1650 0.1110
0.8000 0.4230 0.4020 0.3810 0.3580 0.3300 0.2970 0.2490 0.2020 0.1450
1.2000 0.3500 0.3550 0.3610 0.3620 0.3580 0.3420 0.3090 0.2560 0.1860
1.6000 0.2710 0.3030 0.3410 0.3690 0.3850 0.3850 0.3620 0.3140 0.2330
2.0000 0.2050 0.2600 0.3210 0.3730 0.4110 0.4340 0.4190 0.3690 0.2800
3.0000 0.0740 0.1790 0.2810 0.3750 0.4490 0.5060 0.5190 0.4790 0.3750
4.0000 0.0170 0.1370 0.2530 0.3670 0.4690 0.5450 0.5790 0.5530 0.4470
5.0000 -0.0080 0.1140 0.2350 0.3560 0.4690 0.5620 0.6170 0.6060 0.5030
6.0000 -0.0110 0.1030 0.2230 0.3430 0.4630 0.5660 0.6390 0.6430 0.5470
8.0000 -0.0150 0.0960 0.2080 0.3240 0.4430 0.5640 0.6610 0.6970 0.6210
10.0000 -0.0080 0.0950 0.2000 0.3110 0.4280 0.5520 0.6660 0.7300 0.6780
12.0000 -0.0020 0.0970 0.1970 0.3020 0.4170 0.5410 0.6640 0.7500 0.7200
14.0000 0.0000 0.0980 0.1970 0.2990 0.4080 0.5310 0.6590 0.7610 0.7520
16.0000 0.0020 0.1000 0.1980 0.2990 0.4030 0.5210 0.6500 0.7640 0.7760

DESIGN FOR HOOP TENSION

TENSION COEFFICIENTS K AT DIFFERENT DEPTHS IN CIRCULAR WALL


H2/Dt 0.0 H 0.10 H 0.20 H 0.30 H 0.40 H 0.50 H 0.60 H 0.70 H 0.80 H
5.281 -0.0088 0.1109 0.2316 0.3523 0.467314 0.5631 0.623182 0.616397 0.515364

Hoop Tention T = Coefficient * W H D / 2 K * 162.5 KN


Steel required =1.5* T Steel req-Sqmm On Min Steel Required Provide Dia of Required Provided
Sl No Ht from Top ( W L ) Coefficient Hoop Tention * 10 ^ 2 / 0.50*500
K T in kn
(mm2) each face (mm2) on each face (cm2) Bar Spacing (mm) Spacing (mm)

1 0.0 H -0.0088 -1.437 -8.62 -4.31 350.00 10.00 220.00 180.00


2 0.10 H 0.1109 18.023 108.14 54.070 350.00 10.00 220.00 180.00
3 0.20 H 0.2316 37.640 225.84 112.920 350.00 10.00 220.00 180.00
4 0.30H 0.3523 57.256 343.54 171.770 350.00 10.00 220.00 180.00
5 0.40 H 0.4673 75.939 455.63 227.815 350.00 10.00 220.00 180.00
6 0.50 H 0.5631 91.508 549.05 274.525 350.00 10.00 220.00 180.00
7 0.60 H 0.6232 101.267 607.60 303.800 350.00 10.00 220.00 180.00
8 0.70 H 0.6164 100.165 600.99 300.495 350.00 10.00 220.00 180.00
9 0.80 H 0.5154 83.747 502.48 251.240 350.00 10.00 220.00 180.00
10 0.90 H 0.3033 49.282 295.69 147.845 350.00 10.00 220.00 180.00
Rev

1.0 h
10
-0.1205
-0.0795
-0.0602
-0.0505
-0.0436
-0.0333
-0.0268
-0.0222
-0.0187
-0.0146
-0.0122
-0.0104
-0.0090
-0.0079

1.0 h
-0.02122
0.90 H
10
0.0570
0.0760
0.0980
0.1240
0.1510
0.2100
0.2560
0.2940
0.3270
0.3860
0.4330
0.4770
0.5130
0.5360

0.90 H
0.303273

Provided Area
of Steel (mm2)

440.00
440.00
440.00
440.00
440.00
440.00
440.00
440.00
440.00
440.00
GVPR ENGINEERS LIMITED

CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK - DATE REV. No.
PROJECT:
DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA 3/19/2021 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) UTTAR DESIGNED CHECKED
TITLE :
PRADESH PSD DHC

Annex-B Ductile Detailing as per IS 13920 : 2016


Confining Links in Circular Column :

Column of Section = 450 mm dia


Clear Cover = 45 mm
Dia of Hoops = 10 mm
Provided Dia of smallest longitudinal bar = 20 mm
Clear Height of column = 3000 mm
h = Longer Dimension of Rectangular confining hoop measured to its outer face
(It shall not exceed 300 mm)
The Size of Core Dk = 380 mm

Spacing of Hoops :
Spacing not more than following :
1.) 1/4 of Minimum Member Dimension = 112.5 mm
2.) 6 times the dia smaalest longitudinal reinforecement = 120 mm
3.) 100 = 100 mm
Provide Spacing of Hoops, S = 90 mm

Area of Concrete Core Ak =380*380*0.785 = 113354 mm2


Gross area of Column C/S Ag =450*450*0.785 = 158962.5 mm2
Grade of Concrete fck = 30
Grade of Steel fy = 500

1 Area of C/S of bar forming circular hoop is Ash = 0.09 Sv Dk fck/fy ((Ag/Ak)-1)
Ash = 0.09 * 90*380*(30/500)*((158962.5/113354)-1) = 74.31 mm2
2 Area of C/S of bar forming circular hoop is Ash = 0.024 Sv Dk fck/fy
Ash = 0.024 * 90*380*(30/500) = 49.25 mm2
Maximum of 1 and 2 = 74.31 mm2
Provided C/S of bar forming hoop = 78.54 mm2
Provided hoop bar of dia 10mm is O.K
Thus Circular Hoops of Dia 10mm at a spacing of 90mm c/c will be adequate.

The special confining reinforcement Lo is not lessthan following


1 larger lateral dimension of the member = 450 mm
2 1/6 of clear span of member = 500.0 mm
3 450 = 450 mm
Provide Length of confining reinforcement, Lo = 600 mm

Hencce Provide the confining reinforcement over a height of 600 mm from face of the Joint.
GVPR ENGINEERS LIMITED

CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES BLOCK - DATE REV. No.
PROJECT:
DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA 3/19/2021 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) UTTAR DESIGNED CHECKED
TITLE :
PRADESH PSD DHC
Transverse Reinforcement:
Diameter of Lateral ties:
The dia of lateral ties shall not be less than the following,
1 1/4 th of dia of largest longitudinal bar = 5 mm
2 6 mm = 6 mm
Required dia of lateral ties (Maximum of 1 & 2) = 6 mm
However Provide Dia of Lateral tie = 8 mm
Spacing of Lateral ties:
Shall not be more than least of the following
1 The least lateral dimension of compression member = 450 mm
2 16 times the smallest dia of longitudinal reinforcement = 320 mm
= 300 mm
Required Pitch of lateral ties = 300 mm
However Provide Pitch of Lateral tie = 150 mm
Provide 8 dia ties @150mm c/c
GVPR ENGINEERS LIMITED

DATE REV. No.


PROJECT: CONSTRUCTION OF PIPE WATER SUPPLY SCHEME in JHILO GROUP OF VILAGES
BLOCK -DUDDHI, BABHANI AND MYORPUR DISTRICT -SONBHADRA 3/19/2021 A

RCC DETAILS OF 250 KL OHSR WITH 25 M STAGING AT KARAM GHATI (Zone-C) DESIGNED CHECKED
TITLE :
UTTAR PRADESH PSD DHC

Annex_C: Ductile Detailing of Beam:


As per IS 13920 : 2016

The first hoop shall be at a distance not exceeding 50 mm from the joint face. Vertical hoops at
the same spacing as above, shall also be provided over a length equal to 2d on either side of a
section where flexural yielding may occur under the effect of earthquake forces. Elsewhere, the
beam shall have vertical hoops at a spacing not exceeding d/2.

Width of Beam = 300 mm


Depth of beam = 500 mm
Clear cover = 45 mm
Dia of Hoop = 8 mm
Dia of Main bar provided = 16 mm
Effective depth = 454.2 mm

The spacing of hoops over a length of 2d at either ends of a beam shall not exceed
d/4
8 times the diameter of the smallest longitudinal bar and
(a) d/4 = 113.55 mm
(b) 8 times the diameter of the smallest longitudinal bar = 128 mm
(c) 100 mm = 100 mm
The spacing of hoops over a length of 2d at either end of a beam shall be provided is
Min (113.55,128,100) = 100 mm
Provide Spacing at Supports = 100 mm

Length of Confining steel from face of the support, 2d = 908.4 mm


Say = 1000 mm

Elsewhere, the beam shall have vertical hoops at a spacing not exceeding d/2.
d/2 = 227.1 mm
Elsewhere, the beam shall have vertical hoops at a spacing of 200 mm
Stirrups :

Hence Provide 2L - Y8 stirrups Spacing @ 100 mm c/c throughout


Annexure D: Summary of weight of tank & Staging from Stadd

Node L/C Fx kN Fy kN Fz kN Mx kN-m My kN-m Mz kN-m


421 9 DL -146.543 285.96 0.024 0 0 0
431 9 DL -73.2 285.942 126.892 0 0 0
441 9 DL 73.311 285.939 126.748 0 0 0
451 9 DL 146.017 286.312 -0.001 0 0 0
461 9 DL 73.328 285.938 -126.728 0 0 0
471 9 DL -73.241 285.954 -126.965 0 0 0
Tank Weight: 1716.045

Node L/C Fx kN Fy kN Fz kN Mx kN-m My kN-m Mz kN-m


1684 9 DL -1.275 28.151 -0.007 0 0 0
1685 9 DL -0.694 28.143 1.193 0 0 0
1686 9 DL 0.674 28.074 1.158 0 0 0
1687 9 DL 1.538 30.529 0.002 0 0 0
1688 9 DL 0.469 30.101 -0.817 0 0 0
1689 9 DL -0.464 28.683 -0.79 0 0 0
1690 9 DL 0.638 29.286 -0.003 0 0 0
1691 9 DL 0.382 27.814 -0.644 0 0 0
1692 9 DL -0.192 27.16 -0.313 0 0 0
1693 9 DL -0.161 27.171 0.008 0 0 0
1694 9 DL 0.072 27.838 -0.15 0 0 0
1695 9 DL -0.007 29.321 -0.013 0 0 0
1696 9 DL -0.476 27.714 0.01 0 0 0
1697 9 DL -0.213 29.148 0.366 0 0 0
1698 9 DL -0.114 29.46 -0.192 0 0 0
1699 9 DL -0.427 27.935 -0.013 0 0 0
1700 9 DL -0.04 27.166 0.084 0 0 0
1701 9 DL -0.052 27.167 -0.113 0 0 0
1702 9 DL 0.009 27.165 -0.013 0 0 0
1703 9 DL -0.038 27.158 0.057 0 0 0
1704 9 DL 0.204 27.594 0.336 0 0 0
1705 9 DL 0.412 28.973 0.001 0 0 0
1706 9 DL -0.113 29.609 0.187 0 0 0
1707 9 DL 0.057 27.048 0.109 0 0 0
1708 9 DL 0.59 28.184 0.01 0 0 0
1709 9 DL 0.123 27.139 -0.204 0 0 0
1710 9 DL -0.081 27.157 -0.109 0 0 0
1711 9 DL -0.041 27.165 0.007 0 0 0
1712 9 DL 0.123 27.395 -0.222 0 0 0
1713 9 DL 0.121 29.838 0.213 0 0 0
1714 9 DL -1.008 28.65 0.001 0 0 0
1715 9 DL -0.203 29.655 0.334 0 0 0
1716 9 DL 0.051 28.347 0.034 0 0 0
1717 9 DL 0.251 27.111 -0.009 0 0 0
1718 9 DL 0.249 27.191 -0.374 0 0 0
1719 9 DL -0.41 27.354 -0.709 0 0 0
1720 9 DL 1.441 30.152 -0.003 0 0 0
1721 9 DL 0.594 30.313 -1.018 0 0 0
1722 9 DL -0.496 31.398 -0.826 0 0 0
1723 9 DL -1.188 33.216 0.006 0 0 0
1724 9 DL -0.71 29.958 1.191 0 0 0
1725 9 DL 0.729 30.128 1.264 0 0 0
Staging Weight: 1198.759
Annexure E: Summary of displacemnets from Stadd

Horizontal Vertical Horizontal Resultant Rotational


Node L/C X mm Y mm Z mm mm rX rad rY rad rZ rad
Max X 1885 9 NODAL LOAD 2.552 0 0 2.552 0 0 0
Min X 1726 9 NODAL LOAD 0 0 0 0 0 0 0
Max Y 1877 9 NODAL LOAD 1.669 0.178 0.002 1.678 0 0 0
Min Y 1883 9 NODAL LOAD 2.183 -0.188 -0.001 2.191 0 0 0
Max Z 1879 9 NODAL LOAD 1.822 0.091 0.004 1.825 0 0 0
Min Z 1873 9 NODAL LOAD 1.334 -0.082 -0.004 1.336 0 0 0
Max rX 1689 9 NODAL LOAD 2.117 0.046 0.001 2.118 0 0 0
Min rX 1685 9 NODAL LOAD 2.12 0.046 0.001 2.12 0 0 0
Max rY 1714 9 NODAL LOAD 0.377 0.035 0.002 0.379 0 0 0
Min rY 1726 9 NODAL LOAD 0 0 0 0 0 0 0
Max rZ 1726 9 NODAL LOAD 0 0 0 0 0 0 0
Min rZ 1880 9 NODAL LOAD 2.021 -0.045 0.004 2.022 0 0 0
Max Rst 1885 9 NODAL LOAD 2.552 0 0 2.552 0 0 0