Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

Ultra-High Strength Concrete Filled Composite

Columns for Multi-Storey Building Construction

J.Y. Richard Liew* and D.X. Xiong


Department of Civil Engineering, National University of Singapore, Singapore

Abstract: A test programme was carried out to investigate the performance of


27 axially loaded column specimens, including 18 steel tubes infilled with ultra-high
strength concrete (UHSC) of compressive strength close to 200 MPa, 4 steel tubes
infilled with normal strength concrete (NSC) and 5 hollow steel tubes. Steel fibres
were added into the UHSC to study their effect in enhancing the ductility and strength.
Concrete filled double-tube columns were also investigated for potential application in
multi-storey and high-rise constructions. Test results showed that UHSC filled tubular
columns achieved ultra-high load-carrying capacities, but they could become brittle
after the maximum load was attained. In addition, the ductility and strength of
composite columns infilled with UHSC was improved by applying load only on the
concrete core, adding steel fibres into the concrete core or increasing the steel
contribution ratio. Comparison of test results with Eurocode 4’s predictions indicates
that the Eurocode 4 method could be safely extended to predict the compressive
resistance of UHSC filled composite stub columns. On average, Eurocode 4 approach
underestimated the resistance by 14.6% if the confinement effect was not considered
and by 3.5% if the confinement effect was considered for all the specimens involving
UHSC. However, to ensure sufficient ductility, it is recommended that a minimum
steel contribution ratio of 0.30 or 1% steel fibres should be used. Furthermore, strength
enhancement due to confinement effect should be ignored in estimating the ultimate
strength of concrete filled composite columns with Class 3 steel sections.

Key words: composite columns, confinement effect, concrete-filled steel tube, double-tube column, ductility, high
strength concrete, multi-storey building, steel fibre.

1. INTRODUCTION storey composite building in which concrete is pumped


Concrete filled steel tubular columns have been used into the hollow steel tubes after several floors above
widely for the construction of multi-storey buildings, them have been constructed.
bridge piers, and other supporting structures. They have It has been found that ultra high strength concrete
significant advantages over conventional reinforced (UHSC) is an attractive alternative to normal strength
concrete and pure steel columns as they can improve concrete (NSC) for high-rise building construction as
space efficiency by using smaller columns, utilize smaller column size can be achieved (Liew et al. 2008).
synergistic material advantages due to composite action, However, current design guides are only applicable to
result in savings in fabrication and construction costs, normal strength concrete. For example, Eurocode 4
and prevent the premature local failure (Saw and Liew limits the concrete strength class only up to C50/60.
2000). Figure 1 shows a typical multi-storey building Additional work should be done to extend current
with internal core wall providing lateral bracing to the design guidelines to high strength concrete (HSC) with
structural steelwork during construction. Figure 2 shows compression strength higher than C50/60 and to UHSC
the tubular steel columns at the perimeter of the building with strength higher than C120/135.
before concrete is pumped into the columns. Figure 3 In recent years, some experimental works have
illustrates a general construction sequence of a multi- provided an important insight into the behaviour of HSC

*Corresponding author. Email address: ceeljy@nus.edu.sg; Fax: +65-6779-1635; Tel: +65-6516-2154.

Advances in Structural Engineering Vol. 15 No. 9 2012 1487


Ultra-High Strength Concrete Filled Composite Columns for Multi-Storey Building Construction

Temporary

framing
bracing

Core
Central core wall Hollow
Steel columns steel
and steel beams tubes

Steel framing
Metal decking

Castin of concrete Bracing

deck concrete
Composite beams framing
Level of

Floors of
Comosite floor slab complete
Composite columns
concrete
Max. preload
filled
on columns
column
in this floor

Figure 1. A high-rise steel-concrete composite building in


construction (Liew 2004)

Figure 3. Fast track construction of a typical steel-concrete


composite building (Liew and Xiong 2009)

performed a series of tests on HSC filled rectangular steel


tubular columns subjected to concentric and eccentric
loading. The cylinder strengths of the HSC were about
60 MPa and 90 MPa. It was concluded that Eurocode 4
underestimated the concentrically loaded columns by 1%
but overestimated the eccentrically loaded columns by less
than 5%. Liu et al. (2003, 2005) conducted some tests on
axially loaded concrete filled rectangular hollow steel
sections involving HSC with cylinder strength ranging
from 55 MPa to 106 MPa. It was shown that Eurocode 4
could predict the column strength accurately on the
average but within a range of −20% and +10%. Han et al.
(2005) tested 50 circular and square hollow structural steel
stub columns infilled with self-compacting concrete of
cube strengths between 50 MPa and 90 MPa. The
comparison showed that Eurocode 4 overestimated the
ultimate strength by 0.6% for circular sections and 2.7%
for square sections. Gho and Liu (2004) studied the
flexural behavior of 12 concrete filled rectangular steel
Figure 2. Hollow circular steel tubes before casting concrete hollow section specimens infilled with HSC of cylinder
(Liew 2004) strengths between 56.3 MPa and 90.9 MPa. It was shown
that Eurocode 4 underestimated the flexural strengths by
which would have a strong impact on the application of 11%. Varma et al. (2002, 2004) conducted a series of tests
concrete-filled steel tubular columns in multi-storey and on the seismic behavior of HSC filled square beam
high-rise constructions. Yu et al. (2008) carried out tests columns subjected to constant axial load and cyclically
on 28 thin-walled hollow square and circular steel tubes varying flexural loading. The cylinder strength of the HSC
infilled with self-compacting concrete with cube strength in the tests was up to 110 MPa. The results showed that the
of 120 MPa. The results showed that Eurocode 4 predicted elastic flexural section stiffness under cyclic loading
conservatively the ultimate strength of circular sections decreased rapidly due to tension cracking of concrete and
but overestimated the strength of square sections by 6%. local buckling of steel tubes. The total dissipated energy
Lue et al. (2007) reported tests on 24 concrete filled square was dominated by the dissipated flexural energy in the
tubes with HSC of cylinder strengths between 29 MPa and plastic hinge region. Varma et al. (2002) also
84 MPa. It was revealed that Eurocode 4 provided investigated the flexural force-deformation behavior of
conservative predictions. Liu (2004, 2005, 2006) several 110 MPa HSC filled square steel tubes subjected to

1488 Advances in Structural Engineering Vol. 15 No. 9 2012


J.Y. Richard Liew and D.X. Xiong

axial load and monotonically increasing flexural loading. For axially loaded concrete filled tubes of circular

The moment capacity could be accurately predicted by the cross-section with relative slenderness λ ≤ 0.5, account
American Concrete Institute code provisions. Based on may be taken of increase in strength of concrete caused
the above review, those investigations showed the by confinement effect as
outstanding unique advantage of high resistance that HSC
resulted in. However, the drawback of brittleness was not
 t fy 
N pl , Rk 2 = ηa Aa f y + Ac fck  1 + ηc (3)
investigated and the ductility was not assessed. In  d fck 
addition, all of the concrete strengths used in previous
researches were limited up to 120 MPa. No prior work has where ηa and ηc are given by the following expressions,
been done on composite columns with ultra high strength
concrete (up to 200 MPa), and the present investigation
takes a pioneer step towards the research on ultra high
( )
ηa = 0.25 3 + 2λ ( but ≤ 1.0 ) (4)

strength composite columns.


In this study, an experimental investigation was ηc = 4.9 − 18.5λ + 17λ 2 ( but ≥ 0 ) (5)
carried out on 27 axially loaded circular specimens,
including 18 steel tubes infilled with UHSC of There is no need to consider the overall buckling for
compressive strength close to 200 MPa, 4 steel tubes axially loaded
infilled with NSC and 5 hollow steel tubes. Steel fibres – composite columns with relative
slenderness, λ , less than 0.2. Local buckling can be
were added into the UHSC to study their effect in ignored when the diameter to thickness ratio satisfies
enhancing the ductility and strength. Two of the UHSC following condition,
filled steel tubes were loaded only on the UHSC cores to
investigate the performance of UHSC subjected to high
tri-axial compression. Concrete filled double-tube d 235 (6)
≤ 90
columns were also investigated with different concrete t fy
strengths for potential application in high-rise
constructions. The test results were analyzed with Eurocode 4 method is limited to columns and
respect to ultimate strengths, failure modes, load- compression members with steel grades between S235
displacement behaviour and ductility requirements. The to S460, NSC of strength classes C20/25 to C50/60, and
test results were also compared with the predictions by steel contribution ratio, δ, in the range of 0.2 to 0.9. As
Eurocode 4 method. Finally, important findings with follows, the experimental investigation work was
regard to the use of UHSC and NSC as infilling materials described in detail with an aim to extend the Eurocode 4
for tubular composite columns were highlighted. method to tubular sections infilled with UHSC of
compression strength up to 200 MPa.
2. DESIGN OF COMPOSITE COLUMNS
BASED ON EUROCODE 4 METHOD 3. EXPERIMENTAL INVESTIGATION
According to Eurocode 4, the characteristic value of the 3.1. Material Properties
plastic resistance to compression of a composite cross- The materials included NSC, UHSC, steel fibres and hollow
section without steel reinforcement may be estimated by structural steel tubes. For each batch of concrete, at least
three concrete cylinder specimens (100 mm × 200 mm) were
N pl , Rk = Aa f y + 0.85 Ac fck (1) tested to obtain their mechanical properties. For each type of
steel sections, three steel coupon samples were tested.
Eqn 1 applies for concrete encased and partially
concrete encased steel sections without reinforcement. 3.1.1. Normal strength concrete (NSC)
For concrete filled sections, the coefficient 0.85 may be The NSC was made from ordinary Portland cement,
replaced by 1.0, i.e. sand, coarse aggregates with maximum size 10 mm, and
water. For the investigation, only one batch of NSC was
N pl , Rk1 = Aa f y + Ac fck (2) cast. The mix proportions are shown in Table 1.

Table 1. Mix proportions of NSC

Water Cement Sand Coarse aggregate


Water/Cement (kg/m3) (kg/m3) (kg/m3) (kg/m3)
0.5 225 450 625 1005

Advances in Structural Engineering Vol. 15 No. 9 2012 1489


Ultra-High Strength Concrete Filled Composite Columns for Multi-Storey Building Construction

Table 2. Mix proportions of UHSC

Water Pre-blended mixture Concrete volume


Water/Pre-blended mixture (kg) (kg) (liters)
0.076 1.9 25 9.4

Table 3. Properties of steel fibre


Tensile Elastic
Diameter Length Specific strength modulus
(mm) (mm) Aspect ratio gravity (MPa) (GPa) Coating
0.16 13 80 7.85 2300 200 Brass

3.1.2. Ultra-high strength concrete (UHSC) reinforced UHSC specimens exhibited some post-peak
The UHSC was made from a commercial pre-blended ductility. Loud cracking noise was heard during the
mixture comprising cementitious material, super testing of UHSC and steel fibre reinforced UHSC. It was
plasticizer and fine aggregates with maximum sizes less found that steel fibres improved the ductility of UHSC.
than 4.75 mm. Since no coarse aggregate was used, it The mechanical properties obtained from the concrete
was actually a kind of “mortar” material rather than cylinders are summarized in Table 4, where fck,100 is the
“concrete” material. However, the term of “concrete” is compressive strength obtained from testing the 100 mm
still used in this paper for convenience. For the present diameter concrete cylinders, and fck is the compressive
investigation, three batches of UHSC were cast. The mix strength based on 150 mm diameter concrete cylinder
proportions are shown in Table 2. which is estimated to be fck,100 /1.05.

3.1.3. Steel fibre reinforced UHSC 3.1.4. Steel tubes


High tensile strength steel fibres, as shown in Figure 4, Four sizes of S355 hot finished circular hollow sections,
were used to improve the performance of UHSC. Their 114 mm × 3.6 mm, 114 mm × 6.3 mm, 219 mm × 5.0 mm
basic mechanical properties are shown in Table 3. For and 219 mm × 10 mm were used in the tests. The
the investigation, two batches of steel fibre reinforced “exact” dimensions were measured and the mechanical
UHSC were cast, one with 1% steel fibres in volume and properties were obtained by coupon tests as shown in
the other with 0.5%. Table 5. The sections were classified according to
Compression tests carried out on concrete cylinder Eurocode 3.
specimens showed that NSC had lower strength but
better ductility than UHSC. Figure 5 compares the 3.2. Test Specimens
failure modes of various types of concrete specimens. There were 27 specimens comprising 5 hollow steel
UHSC cylinders were crushed into pieces after their tubes, 18 concrete filled single-tube columns and 4
maximum loads were reached whereas NSC and fibre- concrete filled double-tube columns, as shown
schematically in Figure 6. The specimens were further
classified into three series.
Series 1 comprised 11 specimens with column height
250 mm, nominal tube diameter 114 mm, and tube
thicknesses 3.6 mm and 6.3 mm, including three hollow
steel tubes, six UHSC filled tubes and two steel fibre
reinforced UHSC filled tubes. The specimen details are
given in Table 6. The– design plastic resistance, Npl, Rd, the
relative slenderness, λ , and the steel contribution ratio, δ,
are also shown in Table 6. Specimens S1-2-1(a) and
S1-2-1(b) were axially loaded only on the concrete cores
and the other specimens were loaded simultaneously on
both of the steel tubes and concrete cores as shown in
Figure 7. Series 1 was tested to observe the performance
of the UHSC filled single-tube columns under different
loading conditions and with different steel contribution
Figure 4. Steel fibre-SF 13/80 ratios, δ.

1490 Advances in Structural Engineering Vol. 15 No. 9 2012


J.Y. Richard Liew and D.X. Xiong

(a) NSC (b) UHSC (c) SF reinforced UHSC

Figure 5. Failure modes of different concrete

Table 4. Basic mechanical properties of different batches of concrete

Batch fck,100* fck* Ecm Density


No. Type (MPa) (MPa) (GPa) νc (kg/m3) Specimens
B1 UHSC 173 165 63 0.24 S1-2-1(a, b), S1-3-1(a, b),
S1-3-3(a, b)
B2 UHSC + %1 SF 184 175 63 0.24 S1-3-2(a, b)
B3 NSC 54 51 28 0.20 2317 Specimens containing
NSC
B4 UHSC 175 167 66 0.23 2704 S3-1-2, S3-1-3, S3-2-2
B5 UHSC 185 176 66 0.23 2717 S2-1-3, S2-2-2, S3-2-3
B6 UHSC + 0.5% SF 193 184 67 0.25 2703 S2-1-4, S2-2-4,
S3-1-4, S3-2-4
*f
ck,100 representsthe strengths obtained by testing cylinders of dimension 100 mm diameter × 200 mm height
fck represents the strengths based on cylinders of dimension 150 mm diameter × 300 height, estimated by fck = fck, 100 /1.05

Table 5. Basic mechanical properties of steel tubes

Measured dimension fy fu Ea d fy Section


Circular hollow sections d (mm) t (mm) (MPa) (MPa) (GPa) t 235 class
CHS114 × 3.6 114.67 3.54 406 505 213 56 (< 70) 2
CHS114 × 6.3 114.33 6.13 428 521 209 34 (< 50) 1
CHS219 × 5 219.43 4.87 377 511 205 72 (< 90) 3
CHS219 × 10 219.43 9.69 381 509 212 37 (< 50) 1

fck fy fck2 fy2 fy1


fy

fck1

(a) Hollow section tube (b) Concrete filled single-tube (c) Concrete filled double-tubes

Figure 6. Three types of test specimens

Advances in Structural Engineering Vol. 15 No. 9 2012 1491


Ultra-High Strength Concrete Filled Composite Columns for Multi-Storey Building Construction

Table 6. Specimen details for test Series 1: Concrete filled tubes

L Section fy fck,100 Npl,Rd


No. (mm) no (MPa) (MPa) (kN) λ δ
S1-1-1(a) 250 CHS114 × 3.6 406 502 0.088
S1-1-2(a) 250 CHS114 × 6.3 428 892 0.094
S1-1-2(b) 250 CHS114 × 6.3 428 892 0.094
S1-2-1(a)* 200 CHS114 × 6.3 428 173 1836 0.105 0.486
S1-2-1(b)* 200 CHS114 × 6.3 428 173 1836 0.105 0.486
S1-3-1(a) 250 CHS114 × 3.6 406 173 1550 0.142 0.324
S1-3-1(b) 250 CHS114 × 3.6 406 173 1550 0.142 0.324
S1-3-2(a)** 250 CHS114 × 3.6 406 184 1617 0.145 0.310
S1-3-2(b)** 250 CHS114 × 3.6 406 184 1617 0.145 0.310
S1-3-3(a) 250 CHS114 × 6.3 428 173 1836 0.132 0.486
S1-3-3(b) 250 CHS114 × 6.3 428 173 1836 0.132 0.486
* Loaded only on the concrete core which was 200 mm in length; the steel tubes were 250 mm in length
** The UHSC in the two specimens was reinforced by 1% SF

Series 2 comprised 8 specimens with column height


600 mm, and nominal tube diameter 219 mm and
thicknesses 5 mm and 10 mm, including 2 hollow steel
20 mm tubes, 2 NSC filled tubes, 2 UHSC filled tubes and 2
steel fibre reinforced UHSC filled tubes. The specimen
details are shown in Table 7 and Figure 8(a). All the
specimens were loaded simultaneously on both of the
steel tubes and concrete cores. Series 2 was tested to
210 mm
verify the behavior of axially loaded UHSC filled
single-tube columns, compared to NSC filled columns.
Series 3 comprised 8 concrete filled double-tube
specimens with the length 600 mm and nominal overall
diameter 219 mm, including 2 specimens infilled with
20 mm
NSC, 2 specimens infilled with UHSC, 2 specimens
infilled with UHSC core and NSC in between tubes, and
(a) Loading applied only on the concrete core 2 specimens infilled with steel fibre reinforced UHSC
core and NSC in between tubes. The specimen details
are shown in Table 8 and Figure 8(c). All the specimens
were loaded simultaneously on both of the steel tubes
Actuator
and concrete cores. Series 3 was tested to investigate the
behavior of axially loaded UHSC and NSC filled
25 mm double-tube columns.
Hoop ring stiffener

3.3. Test Setup


250 mm

Four post yield strain gauges, placed at 900 apart, were


attached to the external surface at the mid-height of the
steel tube, as shown in Figure 9. Each strain gauge consists
of two components, one aligned in the longitudinal
direction and the other in the circumferential direction.
3~5 mm The axial shortening displacements were measured by
four linear varying displacement transducers (LVDTs)
which were also placed at 90° apart. The axial load was
(b) Loading applied on both the concrete core and steel tube
applied by a displacement control actuator with a
Figure 7. Different loading conditions for Series 1 specimens maximum capacity of 10,000 kN. To avoid premature

1492 Advances in Structural Engineering Vol. 15 No. 9 2012


J.Y. Richard Liew and D.X. Xiong

Table 7. Specimen details for test Series 2: Concrete filled tubes

L Section fy fck Npl,Rd


No. (mm) no. (MPa) (MPa) (kN) λ δ
S2-1-1 600 CHS219 × 5 377 1238 0.108
S2-1-2 600 CHS219 × 5 377 51 2412 0.141 0.513
S2-1-3 600 CHS219 × 5 377 176 5290 0.187 0.234
S2-1-4* 600 CHS219 × 5 377 184 5474 0.190 0.226
S2-2-1 600 CHS219 × 10 381 2433 0.109
S2-2-2 600 CHS219 × 10 381 51 3501 0.129 0.695
S2-2-3 600 CHS219 × 10 381 176 6121 0.166 0.397
S2-2-4* 600 CHS219 × 10 381 184 6288 0.168 0.387

* The UHSC in the two specimens was reinforced by 0.5% SF

LVDT Strain
gauges

Actuator

3∼5 mm
+ =
Hoop ring stiffener Hoop ring

Specimen

LVDT

(a) Infilled (b) Internal tube with (c) Infilled Strain gauges
single-tube shear connectors double-tubes Strain
gauges
Figure 8. Concrete filled single-tube and double-tube columns

local failure at both ends due to stress concentration, two


Hoop ring stiffener
pairs of hoop ring stiffeners made of high tensile steel
were provided to clamp the ends of the specimens so as to
induce failure near the central height of the specimens. Figure 9. Test setup and locations of strain gauges and LVDTs

3.4. Loading Procedure respectively up to 10% of its capacity estimated by Eqn 2;


A quasi-static loading procedure was introduced in four (2) unload at a rate of 0.5 mm/min and 1.0 mm/min
steps: (1) preload at a rate of 0.2 mm/min for 250 mm long respectively for the two different lengths of specimens; (3)
specimen and 0.3 mm/min for 600 mm long specimen reload at the same rate as in Step 1 to 60% ~ 70% of its

Table 8. Specimen details for test Series 3: Concrete filled double-tube system

L External Internal fy1** fy2** fck1** fck2** Npl,Rd


No. (mm) section section (MPa) (MPa) (MPa) (MPa) (kN) λ δ
S3-1-1 600 CHS219 × 5 CHS114 × 3.6 377 406 51 51 2871 0.146 0.606
S3-1-2 600 CHS219 × 5 CHS114 × 3.6 377 406 167 167 5447 0.183 0.319
S3-1-3 600 CHS219 × 5 CHS114 × 3.6 377 406 51 167 3575 0.165 0.487
S3-1-4* 600 CHS219 × 5 CHS114 × 3.6 377 406 51 184 3678 0.168 0.473
S3-2-1 600 CHS219 × 10 CHS114 × 6.3 381 428 51 51 4322 0.137 0.769
S3-2-2 600 CHS219 × 10 CHS114 × 6.3 381 428 167 167 6592 0.164 0.504
S3-2-3 600 CHS219 × 10 CHS114 × 6.3 381 428 51 176 5004 0.150 0.664
S3-2-4* 600 CHS219 × 10 CHS114 × 6.3 381 428 51 184 5048 0.151 0.659
*The UHSC in the internal tubes of the two specimens was reinforced by 0.5% SF
**f and fy2 are the yield strengths of external and internal steel tubes respectively;
y1
fck1 and fck2 are the strengths of the concrete filled in-between tubes and the center core respectively

Advances in Structural Engineering Vol. 15 No. 9 2012 1493


Ultra-High Strength Concrete Filled Composite Columns for Multi-Storey Building Construction

capacity, and then decrease the rate to 0.1 mm/min and 3000
S1-3-1 (a)
0.2 mm/min respectively until the peak load was reached; S1-3-1 (b)
(4) finally in the post-peak range, increase the rate to 2500
0.5 mm/min and 1.0 mm/min respectively until visible
2000
deformation was observed.

Load (kN)
1500
3.5. Test Results and Observations
3.5.1. Series 1: performance of small scale stub 1000
columns under different loading
conditions 500
The load-axial displacement curves obtained from
Series 1 test specimens are shown in Figures 10–14. 0
0 10 20 30 40
Figure 10 shows that specimen S1-1-1(a), which was a
Axial shortening (mm)
CHS 114 × 3.6 steel tube with Class 2 section, could
almost reach the expected plastic resistance but it Figure 12. Load-shortening curves for specimens S1-3-1(a) and
unloaded immediately after that; while Specimens S1-3-1(b)
S1-1-2(a) and S1-1-2(b), which were of Class 1
3000
S1-3-2 (a)
1200 S1-3-2 (b)
S1-1-1 (a) 2500
S1-1-2 (a)
1000 S1-1-2 (b) 2000

800 Load (kN)


1500
Load (kN)

600
1000

400 500

200
0
0 10 20 30 40
0 Axial shortening (mm)
0 10 20 30 40
Axial shortening (mm) Figure 13. Axial load-shortening curves for specimens S1-3-2(a)
and S1-3-2(b)
Figure 10. Axial load-shortening curves for specimens S1-1-1(a),
S1-1-2(a) and S1-1-2(b) 3000

3000 2500
S1-2-1 (a)
S1-2-1 (b)
2000
2500
Load (kN)

1500
2000 1200
1000
Load (kN)

900
1500
500
S1-3-3 (a)
600 S1-3-3 (b)
1000 0
Interfacial bond 0 10 20 30 40
300 Axial shortening (mm)
suddenly failed
500 Figure 14. Axial load-shortening curves for specimens S1-3-3(a)
0
0 1 2 3 4
and S1-3-3(b)
0
0 10 20 30 40
sections, could achieve the expected plastic resistances
Axial shortening (mm)
but also developed hardening effect after yielding.
Figure 11. Axial load-shortening curves for specimens S1-2-1(a) Figure 11 shows the load-displacement curves for
and S1-2-1(b) S1-2-1(a) and S1-2-1(b) which were loaded only on the

1494 Advances in Structural Engineering Vol. 15 No. 9 2012


J.Y. Richard Liew and D.X. Xiong

UHSC cores as shown in Figure 7(a). At the initial loading significantly due to much higher tri-axial compression in
stage, the steel tube was resisting the load together with specimens S1-2-1(a) and S1-2-1(b), compared with the
the UHSC core due the interfacial bond between the two other composite specimens where both of the steel tubes
materials. The bond was subsequently broken due to the and concrete cores were loaded simultaneously and thus
relative slip occurred; subsequently, the load was mainly lower confinement stresses were produced on the UHSC
resisted by the UHSC core and the load-displacement cores as shown in Figures 12–14. These figures show that
curve became softer. After that, when the axial shortening the UHSC cores were cracked suddenly at smaller axial
displacement of the UHSC core was increasing at a rate displacements, and the load dropped sharply after the
faster than the steel tube, significant confinement effect peak load. Comparing the load displacement curves in
and friction forces were developed due to the expanding of Figures 12–14, it is shown that S1-3-2(a) & (b) in which
concrete core. Thus some load was transferred from the the concrete cores were reinforced with 1% steel fibres,
core to the steel tube, and the load-displacement curve and S1-3-3(a) & (b) which had higher steel contribution
became stiffer. Finally, the steel tube and concrete core ratios had higher ultimate loads and higher residual
were compressed together again. strengths than specimens S1-3-1(a) & (b) which did not
Larger relative slip between the steel and concrete have such strong enhancement.
occurred in S1-2-1(a) than S1-2-1(b) and thus higher The test values of the ultimate strength, Ntest,u, and the
confinement stress would be produced at the peak load. residual strength, Ntest,r, are summarized in Table 9 for test
This explains the reason why the ultimate strength of series 1. The residual strength to ultimate strength ratio,
S1-2-1(a) was higher than S1-2-1(b) as shown in Ntest,r/Ntest,u, was the lowest for S1-3-1(a) & (b) at about
Figure 11, although they were identical specimens. At the 71% on average, higher for S1-3-2(a) & (b) at about 79%
peak load, the UHSC core was crushed and its strength and for S1-2-1(a) & (b) at about 85%, and the highest for
was degraded rapidly, leading to rapid softening of the S1-3-3(a) & (b) at about 92%. Therefore, the ductility and
loading curve. The confinement stress was increased strength of the composite column can be improved if steel
quickly due to the dilation effect of the UHSC core. The fibres are added, the steel contribution ratio is increased, or
residual strength of S1-2-1(a) was almost kept constant stronger triaxial confinement is provided to the concrete
for a continuous period of axial deformation up to 40 mm. cores. On the contrary, the ultimate strength of a
Residual strength is defined as the remaining strength composite column may reduce if some axial preload is
beyond 15% yield strain (see Eqn 11). For S1-2-1(b), imposed only on the steel tube (Liew and Xiong 2009).
there was some strength recovery at about 10 mm
displacement. Since the maximum confinement strength 3.5.2. Series 2: performance of NSC and UHSC
of steel tube was the same for the two specimens, the filled single-tube columns
residual strengths of both the specimens were almost The axial-load displacement curves for Series 2
identical, i.e., 2317 kN for S1-2-1(a) and 2293 kN for specimens are shown in two groups as Group S2-1 in
S1-2-1(b). The ductility of the UHSC core were enhanced Figure 15 and Group S2-2 in Figure 16. The specimens

Table 9. Comparison of test results with Eurocode 4 for test Series 1

Eurocode 4 predictions Test results Ntest,u Ntest,u Ntest,r Ntest,r


No. Npl,Rk1 (kN) Npl,Rk2 (kN) Ntest,u (kN) Ntest,r (kN) N pl,Rk 1 N pl,Rk 2 N pl,Rk 1 Ntest,u

S1-1-1(a) 502 486 0.969


S1-1-2(a) 892 1039 1.165
S1-1-2(b) 892 990 1.110
S1-2-1(a) 2307 2721 2866 2317 1.242 1.053 1.004 0.809
S1-2-1(b) 2307 2721 2595 2293 1.125 0.954 0.994 0.883
S1-3-1(a) 2075 2283 2422 1695 1.168 1.061 0.817 0.700
S1-3-1(b) 2075 2283 2340 1689 1.128 1.025 0.814 0.722
S1-3-2(a) 2175 2379 2497 1903 1.148 1.049 0.875 0.762
S1-3-2(b) 2175 2379 2314 1884 1.064 0.973 0.866 0.814
S1-3-3(a) 2307 2661 2610 2309 1.131 0.981 1.001 0.884
S1-3-3(b) 2307 2661 2633 2518 1.141 0.989 1.091 0.957
Mean* 1.130 1.013
Standard Deviation* 0.035 0.037
*Only for the last 6 specimens which were loaded simultaneously on the tubes and concrete cores

Advances in Structural Engineering Vol. 15 No. 9 2012 1495


Ultra-High Strength Concrete Filled Composite Columns for Multi-Storey Building Construction

10000
S2-1-1
in Group S2-1 consisted of CHS219 mm × 5 mm and
S2-1-2 specimens in Group S2-2 consisted of CHS219 mm ×
S2-1-3 10 mm. CHS219 mm × 5 mm was a Class 3 section and
8000 S2-1-4
it could not develop the full plastic resistance after
yielding, whereas CHS219 mm × 10 mm, which was a
Load (kN)

6000
Class 1 section, developed the full plastic resistance
4000 and hardening effect, as shown in Figure 16. Similar
effect could also be observed from the NSC filled tubes
2000
S2-1-2 and S2-2-2; however, compared with S2-1-1
and S2-2-1 respectively, S2-1-2 developed higher
0
plastic resistance and S2-2-2 achieved its ultimate
0 20 40 60 80 strength at a larger displacement due to the
Axial shortening (mm) confinement effect provided by the steel tube and the
constraint afforded by the concrete core. The other
Figure 15. Axial load-shortening curves for specimens in Group
four specimens in Series 2 achieved higher ultimate
S2-1 of Series 2
resistances due to the presence of UHSC. However, the
post-peak load-displacement behavior was more brittle
than NSC filled specimens. The UHSC core was
10000
S2-2-1 cracked suddenly and the unloading occurred sharply.
S2-2-2
S2-2-3
The ultimate load, Ntest,u, and the residual strength,
8000 S2-2-4 Ntest,r, are summarized in Table 10. The concrete core
of specimen S2-1-4 was reinforced with 0.5% steel
fibres and thus it had higher maximum strength than
6000 S2-1-3. Specimen S2-2-3 had higher steel contribution
Load (kN)

ratio and thus it had higher residual strength ratio


Ntest,r /Ntest,u than S2-1-3. This series of tests confirms
4000
the fact that steel fibres and higher steel contribution
ratio help to improve the strength and ductility of
2000 composite columns.

3.5.3. Series 3: performance of NSC and UHSC


0 filled double-tube columns
0 20 40 60 80
For concrete-filled double-tube specimens in Series 3,
Axial shortening (mm)
the axial load shortening curves are shown in two groups
Figure 16. Axial load-shortening curves for specimens in Group as Group S3-1 in Figure 17 and Group S3-2 in Figure 18.
S2-2 of Series 2 Group S3-1 specimens consisted of an external steel tube

Table 10. Comparison of test results with Eurocode 4 for test Series 2

Eurocode 4 predictions Test results Ntest,u Ntest,u Ntest,r Ntest,r


No. Npl,Rk1 (kN) Npl,Rk2 (kN) Ntest,u (kN) Ntest,r (kN) N pl,Rk 1 N pl,Rk 2 N pl,Rk 1 Ntest,u

S2-1-1 1238 1190 0.961


S2-1-2 2999 3535 3118 1.040 0.882
S2-1-3 7316 7710 7837 3803 1.071 1.017 0.520 0.485
S2-1-4 7592 7978 8664 5691 1.141 1.086 0.750 0.657
S2-2-1 2433 3050 1.254
S2-2-2 4036 5060 5241 1.299 1.036
S2-2-3 7965 8775 9085 7353 1.141 1.035 0.923 0.809
S2-2-4 8216 9014 9187 7479 1.118 1.019 0.910 0.814
Mean* 1.118 1.039
Standard Deviation* 0.033 0.032
* Only for S2-1-3, S2-1-4, S2-2-3 and S2-2-4 which contain UHSC

1496 Advances in Structural Engineering Vol. 15 No. 9 2012


J.Y. Richard Liew and D.X. Xiong

10000
S3-1-1
developed much higher ultimate strengths than the NSC
S3-1-2 filled specimens S3-1-1 and S3-2-1. However, they
S3-1-3 unloaded sharply after the peak load due to the
8000 S3-1-4 brittleness of UHSC core. The other four specimens
were infilled with NSC in between the external and
6000 internal tubes and with UHSC in the internal tubes. They
Load (kN)

demonstrated significant ductility after the peak load.


The drop in load after the peak was not too abrupt and it
4000 recovered soon. The second peak load was even higher
than the first peak load, as shown for specimens S3-2-3
and S3-2-4 in Figure 18.
2000
Loud cracking/crushing noise emanating from the
specimens was heard around the peak load during the
0 testing of the specimens with UHSC. A sharp drop in
0 20 40 60 80 the load-displacement curves after the peak load was
Axial shortening (mm) observed as shown in Figures 10–16. Soon after the
Figure 17. Axial load-shortening curves for specimens in Group load drop, visual inspection was carried out on the
S3-1 of Series 3 specimens and no visible deformation was observed.
Therefore, the noise is thought to be originated from
10000
the cracking/crushing of the UHSC core. The external
steel tubes of the failed specimens were removed to
reveal the inner UHSC core as shown in Figure 19.
8000 For S1-2-1(a) which was loaded only on the UHSC
core, its UHSC core remained intact, showing some
form of structural integrity. For specimens S1-3-1(a)
6000
and S1-3-2(b), which were loaded simultaneously on
Load (kN)

both of steel tubes and the UHSC cores, their UHSC


4000
cores were cracked apart, showing brittleness of the
concrete core. Figure 20 shows all the test specimens
S3-2-1 after the tests.
2000 S3-2-2
S3-2-3
S3-2-4
0
0 20 40 60 80
Axial shortening (mm)

Figure 18. Axial load-shortening curves for specimens in Group


S3-2 of Series 3

CHS219 mm × 5.0 mm and an internal steel tube (a) S1-2-1(a) loaded only on UHSC core
CHS114 mm × 3.6 mm, and Group S3-2 specimens
consisted of an external steel tube CHS219 mm × 10 mm
and an internal steel tube CHS114 mm × 6.3 mm. The
NSC filled specimen S3-1-1 developed significant plastic
plateau as shown in Figure 17, although both the external
and internal steel tubes were of large diameter-to-
thickness ratios. The other NSC filled specimen S3-2-1
in Series 3 developed higher plastic resistance and
hardening effect, since the external and internal tubes
were of smaller diameter-to-thickness ratios. (b) S1-3-1(a) without SF (b) S1-3-2(b) with 1% SF
Comparison between Figures 17 and 18 shows that Figure 19. Failure modes of UHSC core
the UHSC filled specimens S3-1-2 and S3-2-2

Advances in Structural Engineering Vol. 15 No. 9 2012 1497


Ultra-High Strength Concrete Filled Composite Columns for Multi-Storey Building Construction

S2-1-2 by 11.8% and S3-1-1 by 7.9%. It should be noted


that these two NSC filled specimens had Class 3 cross-
sectional steel tubes. The comparison of test results with
predictions is also shown in Figure 21 and Figure 22 for
all the composite specimens except the hollow steel tube
specimens. In conclusion, the Eurocode 4 approach can be
safely extended to predict the resistance of UHSC filled
steel tubular columns. On average for all the composite
specimens involving UHSC, Eurocode 4 approach
underestimated the resistance by 14.6% if confinement
effect was not considered and by 3.5% if confinement
effect was considered. However, it may over-predict the
confinement effect for NSC filled steel tubes with Class 3
sections and thus the confinement effect should be
ignored. Furthermore, for composite specimens only
involving UHSC, it is recommended that the confinement
effect should also be ignored, since the ultimate strengths
Figure 20. Failure of specimens after tested
were reached almost at elastic stage and thus no significant
confinement effect should have developed.
4. EVALUATION OF TEST RESULTS
4.1. Comparison with Eurocode 4’s Predictions
12000
Eqns 2 and 3 were used to predict the resistances and they
were compared with the test results as shown in Tables 9
10000
to 11. It should be noted that the values of fck,100, instead of
fck, were used in both equations for all the composite
Test results, Ntest,u (kN)

specimens in Series 1, because the concrete cores in these 8000


specimens were almost of the same size as the standard
concrete cylinder of 100 mm diameter and 200 mm height. 6000
Comparison with test results indicates that Eqn 2, without
considering the confinement enhancement, conservatively 4000
predicted the compression resistance of hollow steel tubes
S1-1-2(a), S1-1-2(b) and S2-2-1 and all the composite
2000 Series 1
specimens, but it slightly overestimated the compression Series 2
resistance of hollow steel tubes S1-1-1(a) by 3.1% and Series 3
S2-1-1 by 3.9%. Eqn 3, considering the confinement 0
0 2000 4000 6000 8000 10000 12000
effect, conservatively predicted the resistance for most of Predictions by eurocode 4, Npl,Rk1 (kN)
the composite specimens, but it overestimated the
resistance for some UHSC filled tubes in Series 1 by less Figure 21. Comparison of test results with predictions without
than 5%, and for two NSC filled composite specimens confinement effect

Table 11. Comparison of test results with Eurocode 4 for test Series 3

Eurocode 4 predictions Test results Ntest,u Ntest,u Ntest,r Ntest,r


No. Npl,Rk1 (kN) Npl,Rk2 (kN) Ntest,u (kN) Ntest,r (kN) N pl,Rk 1 N pl,Rk 2 N pl,Rk 1 Ntest,u

S3-1-1 3438 3939 3626 1.055 0.921


S3-1-2 7300 7684 8529 5069 1.168 1.110 0.694 0.594
S3-1-3 4492 4931 4968 4830 1.106 1.008 1.075 0.972
S3-1-4 4647 5077 5239 4171 1.127 1.032 0.898 0.796
S3-2-1 4821 5678 6300 1.307 1.110
S3-2-2 8226 8928 9817 6951 1.193 1.100 0.845 0.708
S3-2-3 5844 6627 7022 7022 1.201 1.060 1.201 1.000
S3-2-4 5909 6687 7160 7160 1.212 1.071 1.212 1.000
Mean* 1.168 1.063
Standard Deviation* 0.043 0.039
*S3-1-1 and S3-2-1, which do not contain UHSC, are not considered.

1498 Advances in Structural Engineering Vol. 15 No. 9 2012


J.Y. Richard Liew and D.X. Xiong

12000 500 1

10000 400 0.8


σa
Test results, Ntest,u (kN)

Poisson's ratio
Stress (MPa)
8000
300 0.6

νa
6000
200 0.4

4000 Stress (test)


100 Stress (FEM) 0.2
Poisson's ratio (test)
2000 Series 1
Poisson's ratio (FEM)
Series 2 0 0
Series 3 0 0.004 0.008 0.012 0.016 0.02
0
Longitudinal compressive strain
0 2000 4000 6000 8000 10000 12000
Predictions by eurocode 4, Npl,Rk2 (kN) Figure 23. Variation of Poisson’s ratio with longitudinal stresses
Figure 22. Comparison of test results with predictions with for steel tube S2-2-1
confinement effect
60 2
Stress (test)
4.2. Interaction Mechanics between Concrete Stress (FEM)
Poisson's ratio (test)
Core and Steel Tube 48 σc Poisson's ratio (FEM) 1.6
4.2.1. Effect of Poisson’s ratio
Poisson’s ratio, defined as the absolute value of the ratio

Poisson's ratio
Stress (MPa)

36 1.2
of transverse strain to longitudinal strain under uniaxial
loading, plays a significant role in analyzing the load νc
sharing mechanism between the concrete core and the 24 0.8
steel tube.
For mild steel, the Poisson’s ratio value is about 0.3 12 0.4
before yielding, and then it increases rapidly
approaching to 0.5 after yielding. For NSC, it is at about
0.2 under low compressive stress level and it increases 0 0
0 0.004 0.008 0.012 0.016 0.02
rapidly after reaching 80% to 90% of the ultimate Longitudinal compressive strain
strength due to the initiating of micro-cracks, and finally
approaches a value of about 0.5 at the ultimate strength. Figure 24. Variation of Poisson’s ratio with longitudinal stresses
The value exceeds 0.5 after the ultimate strength due to for NSC
dilation effect. The Poisson’s ratio for the UHSC used in 200 2
this study was about 0.25, slightly higher than that of
NSC, under low compressive stress level. σc
The longitudinal stress-strain curve for the hollow 160 1.6
steel tube S2-2-1 is plotted in Figure 23, together with Stress (test)
the Poisson’s ratio measured as the ratio of Stress (FEM)
Poisson's ratio
Stress (MPa)

120 1.2
circumferential strain to longitudinal strain. The Poisson's ratio (test)
Poisson's ratio (FEM)
measured Poisson’s ratio value was decreasing instead
of increasing right after yielding, mainly due to the 80 0.8
influence of the hoop ring stiffeners and imperfections.
Figure 24 and Figure 25 show the variations of νc
Poisson’s ratios for NSC and UHSC, respectively, 40 0.4
derived from the concrete cylinder tests. Unlike NSC,
the stress-strain curve for UHSC was almost linearly
0 0
elastic up to the maximum load. Once the ultimate load 0 0.005 0.01 0.015 0.02
was reached, the concrete cylinder was cracked and Longitudinal compressive strain
fractured into pieces. However, in composite columns,
macro cracks may be delayed or even prevented due to Figure 25. Variation of Poisson’s ratio with longitudinal stresses
the confinement stress offered by the steel tube showing for UHSC

Advances in Structural Engineering Vol. 15 No. 9 2012 1499


Ultra-High Strength Concrete Filled Composite Columns for Multi-Storey Building Construction

a gradual softening of post peak stress-strain behaviour. Considering the displacement compatibility at point
The corresponding idealized true stress strain curves “P”, urp,c ≤ urp,a, it further implies that
with softening portions are also shown in Figures 23–25
as references. It should be noted that the true stress and  v < v : separationor tensile debodingoccurs
 c a
strain values from the tests are converted from the  vc = va : concreteandsteel tube are in contact but no int eraction
nominal values and they are shown in the three figures 
 vc > va : concrete core is confined bysteel tube
for comparison. (9)
Figure 26 shows a simplified model for a concrete
filled tube subjected to longitudinal compressive strain Thus, confinement effect can be produced only if the
εz. Assuming that there is no interaction at the interface Poisson’s ratio value of concrete is greater than that of
which means that the concrete core and steel tube are steel, unless effective transverse restraints are imposed
free to expand, the tensile strains at a point “P” at the on steel tubes.
interface in circumferential and radial directions are For axially loaded concrete filled composite columns
with steel materials between S275 and S460, the steel
tube will yield first before the concrete achieves its
 εθp,c = ε rp,c = vc ε z ( based on the propertiesof concreete )
(7) ultimate strength. Therefore, the effective concrete
 p p
εθ ,a = ε r ,a = va ε z ( based on the propertiesof steel ) confinement stresses can only start before the concrete
reaches its ultimate strength. Before that, tensile stresses
or separation may occur at the steel and concrete
The displacements at point “P” in the radial direction
interface since νc<νa. Figure 27 shows the general
of the concrete and steel materials are p
variations of longitudinal stresses and εθ / ε zp at point
“P” of the model shown in Figure 26. The values are
 p d  p d  compared with the variations of uniaxial stresses and
 ur ,c =  2 − t  ε r ,c = vc  2 − t  ε z urp,c vc Poisson’s ratios of mild steel and NSC. Initially, the
 ⇒ p = (8)
ur ,a va Poisson’s ratio value of concrete is less than that of
u p =  d − t  ε p = v  d − t  ε
 r ,a  2  r ,a a
 2  z steel. The concrete core and steel tube are transversely
expanding freely and hence the ratios of circumferential
strain to longitudinal strain are respectively equal to
d
their Poisson’s ratios. After that, the Poisson’s ratio
value of concrete is increasing and exceeds that of steel.
The concrete core will be confined by steel tube. Values
p p
of εθ ,c / ε z will be less than the Poisson’s ratio values of
θ r p p
0 concrete and values of εθ ,a / ε z will be greater than the
P
Poisson’s ratio values of steel. To ensure compatibility,
εθP,c εθP,a
≈ P . The confinement effect improves the
ε zP εz

500 1.5
Debonding Bonding

Z t 400 σa 1.2
εz
Longitudinal stress (MPa)

σ pa
ε pθ,c/εz
300 ε pθ,a/εz 0.9
νc
ε θ /εz

P r
0
200 0.6

νa
100 σ pc 0.3

σc
0 0
0 0.004 0.008 0.012 0.016 0.02
Longitudinal compressive strain

Figure 26. A concrete filled tube subjected to uniaxial compression Figure 27. Variation of stresses and εθ/εz in composite columns

1500 Advances in Structural Engineering Vol. 15 No. 9 2012


J.Y. Richard Liew and D.X. Xiong

longitudinal compression strength of concrete, but occurred, which means that inelastic local buckling
reduces the longitudinal compression strength of steel occurred. On the contrary, S2-2-1 could develop the full
tube since the tensile stress is produced in the plastic resistance with subsequent strain hardening effect.
circumferential direction of the tube section. For concrete filled tubes of Class 3 sections, separation
The model presented so far considers the worst case or tensile stresses may occur at the interface even after
scenario. In practice, there may be some initial yielding, which means that the concrete core cannot
confinement stresses before loading due to self- provide effective restraint to prevent local buckling of the
expanding of concrete, circumferential restraint boundary steel tube. Figure 29 shows the history curves of the
conditions and so on. Some of the initial confinement measured vertical strains at the middle height of columns,
stresses could be released at the initial stage of loading applied load and axial shortening of NSC filled tubes S2-
when the Poisson’s ratio of concrete is less than that of 1-2 of Class 3 section and S2-2-2 of Class 1 section.
steel; however, if they are not released completely, tensile Better than the pure steel specimen S2-1-1, the vertical
debonding stresses may not occur and the effective strain of S2-1-2 was increasing after yielding, but local
confinement stress could start earlier. On the other hand, buckling of the tube occurred at vertical displacement less
initial imperfections, such as loading eccentricity, than 20 mm, which was much smaller than that of the
geometrical imperfections and concrete shrinkage may pure steel specimen S2-2-2 which occurred at about
also affect the performance of confined concrete. 40 mm. Therefore, Eqn 3 should be used only to calculate
the compression capacity of concrete filled columns with
4.2.2. Effect of Class 3 section on composite Class 1 and Class 2 sections, and only Eqn 2, without the
stub column strength consideration of confinement effect, is applicable to
Specimen S2-1-1, which was a Class 3 steel tube section columns with Class 3 section.
according to Eurocode 3, developed an axial resistance
which was 4% less than the estimated squash load. This 4.3. Ductility Requirements
is probably due to some difference in the tensile strength Structures members are usually required to have
of the tube and that from the coupon tests and also due to sufficient ductility to undergo large deformations
some initial imperfections which led to eccentricity of without collapse when subjected to accidental actions.
load. For Class 3 sections, once yielding occurs, they are For axially loaded composite columns, an axial
susceptible to inelastic local buckling. Figure 28 shows shortening limit similar to the value of the structural
the history curves of the measured vertical strains at the steel ultimate strain is defined in Eurocode 3 as
middle height of columns, the applied load and axial ∆Llim fy
shortening of steel tubes S2-1-1 of Class 3 section and ϕ lim = = 15 (10)
S2-2-1 of Class 1 section. If there is no local buckling, the L Ea
vertical strains should keep increasing as long as the axial Deformations beyond the limit are significant, and
shortening displacements are increasing. However, the the remaining strength beyond this limit is regarded as
vertical strain of S2-1-1 decreased once yielding the residual strength. To meet ductility requirements,

0.04 500 0.06 6000

0.05 5000
0.032 400
Measured vertical strain
Measured vertical strain

0.04 4000
Load (MPa)

0.024 300
Load (kN)

0.03 3000
0.016 200
0.02 2000
S2-1-1 strain S2-1-2 strain
0.008 Yielding 100
S2-2-1 strain S2-2-2 strain 1000
point 0.01
S2-1-1 load S2-1-2 load
S2-2-1 load Yielding
S2-2-2 load
0 0 0 0
0 15 30 45 60 0 20 40 60 80
Axial shortening (mm) Axial shortening (mm)

Figure 28. Measured strains and load-shortening curves for hollow Figure 29. Measured strains and load-shortening curves for NSC
tubes S2-1-1 and S2-2-1 filled tubes S2-1-2 and S2-2-2

Advances in Structural Engineering Vol. 15 No. 9 2012 1501


Ultra-High Strength Concrete Filled Composite Columns for Multi-Storey Building Construction

1 of concrete, can be used with confidence for the


S1-3-3 design of concrete filled steel tubular sections.
S2-2-4 (a, b) However, the equation may overestimate the
S1-3-2
Residual strength ratio Ntest,r /Ntest.u

0.8
(a, b)
S2-2-3 strength of NSC filled steel tubes with Class 3
S1-3-1
cross-sections. For such cases, Eqn 2, which does
S2-1-4
(a, b)
not consider the confinement effect, should be
0.6
used.
S2-1-3
(3) Material Poisson’s ratio is one of the important
0.4
parameters that affect the load distribution in
concrete filled column. Before cracks are
developed in the concrete core under the applied
0.2 UHSG
compression force, the value of Poisson’s ratio for
UHSG + 0.5%SF UHSC is found to be higher than NSC and thus the
UHSG + 1%SF concrete confinement effect for UHSC filled tubes
0 should be higher than NSC filled tubes for the
0 0.2 0.4 0.6
same stress ratio. The ductility and strength of
Steel contribution ratioδ
UHSC core, as well as NSC core, can be enhanced
Figure 30. Residual strength ratios for UHSC filled due to the effective confinement of the steel tube.
single-tube columns (4) The ductility and strength of UHSC filled
composite columns can be further improved if
the residual strength should not be less than the actions the load is imposed only on the concrete core
under serviceability limit state. For concrete filled tubes, where tri-axial confinement effect is the
the service load should be less than 70% of the column maximum or by adding at least 1% volume of
ultimate strength. Therefore, to ensure a conservative steel fibres into the core materials.
design, the residual strength should be at least equal to (5) UHSC filled steel tubular columns can achieve
70% of the column ultimate strength. ultra-high compression capacities, but their post
The test results of residual strength for composite peak load behaviour is quite brittle, in
columns with UHSC are shown in Tables 9–11. Most of particularly when the steel contribution ratio is
the composite columns achieved their ultimate strengths low. To ensure sufficient ductility, the limitation
at quite small deformations, especially for the UHSC on minimum steel contribution ratio should be
filled single-tube columns loaded simultaneously on the increased to 0.30 or a minimum of 1% volume
top of tubes and concrete cores. The residual strength of steel fibres should be added to the UHSC.
ratios are plotted against the steel contribution ratios for
all the specimens as shown in Figure 30. It is observed ACKNOWLEDGEMENT
that higher steel contribution ratio and higher steel fibre The research is sponsored by Densit Asia, Yongnam
volume increase the residual strength ratio. To meet the Holdings Ltd and Continental Steel Pte Ltd, and funded
ductility requirements and to ensure residual strength by A*STAR (Grant No. P0820166). Their financial
ratio of at least 0.7, the steel contribution ratio should be supports are gratefully acknowledged.
at least 0.30, or steel fibre volume of at least 1% should
be added to UHSC filled tubes. REFERENCES
Eurocode 3 (2005). Eurocode 3: Design of Steel Structures - Part 1-1:
5. CONCLUSIONS General Rules and Rules for Buildings, European Committee for
Based on the test results and analyses, some significant Standardization, Brussels, Belgium.
conclusions can be drawn as follows: Eurocode 4 (2004). Eurocode 4: Design of Composite Steel and
(1) Limited test evidence indicates that the Concrte Structures - Part 1.1: General Rules and Rules for
Eurocode 4 limitation on concrete cylinder Buildings, European Committee for Standardization, Brussels,
strength could be safely extended to 200 N/mm2 Belgium.
(cylinder strength). The circular column sections Gho, W.M. and Liu, D.L. (2004). “Flexural behaviour of high-strength
with ultra high strength concrete of 200 N/mm2 rectangular concrete-filled steel hollow sections”, Journal of
compression strength were safe though more Constructional Steel Research, Vol. 60, No. 11, pp. 1681–1696.
tests with such high strength concrete for longer Han, L.H. and Yao, G.H. (2003). “Behaviour of concrete-filled
column length are needed to justify this. hollow structural steel (HSS) columns with pre-load on the steel
(2) For concrete filled steel tubes with Class 1 or tubes”, Journal of Constructional Steel Research, Vol. 59, No. 12,
Class 2 sections, Eqn 3, considering confinement pp. 1455–1475.

1502 Advances in Structural Engineering Vol. 15 No. 9 2012


J.Y. Richard Liew and D.X. Xiong

Han, L.H., Yao, G.H. and Zhao, X.L. (2005). “Tests and calculations Yu, Q., Tao, Z. and Wu, Y.X. (2008). “Experimental behaviour of
for hollow structural steel (HSS) stub columns filled with self- high performance concrete-filled steel tubular columns”, Thin-
consolidating concrete (SCC)”, Journal of Constructional Steel Walled Structures, Vol. 46, No. 4, pp. 362–370.
Research, Vol. 61, No. 9, pp. 1241–1269.
Liew, J.Y.R. (2004). “Buildable design of multi-storey and large NOTATION
span steel srtuctures”, Journal of Steel Structures, Vol. 4, No. 2, Αa, Αc cross-sectional areas of steel tube and
pp. 53–70. concrete core respectively
Liew, J.Y.R. and Xiong, D.X. (2009). “Effect of preload on the axial d overall diameter of circular hollow steel
capacity of concrete-filled composite columns”, Journal of section
Constructional Steel Research, Vol. 65, No. 3, pp. 709–722. Ea,Ecm modulus of elasticity of structural steel and
Liew, J.Y.R., Chia, K.S., Kazi, M.A.S. and Xiong, D.X. (2008). secant modulus of elasticity of concrete
“Innovation in composite construction – towards the extreme of fck characteristic value of the cylinder (150 mm
high strength and lightweight”, Proceeding of the 5th × 300 mm) compressive strength of concrete
International Conference on Coupled Instabilities in Metal fck,100 characteristic value of the cylinder (100 mm
Structures, Sydney, Australia, pp. 19–33. × 200 mm) compressive strength of concrete
Liu, D.L. (2006). “Behaviour of eccentrically loaded high-strength fy nominal value of the yield strength of steel
rectangular concrete-filled steel tubular columns”, Journal of tube
Constructional Steel Research, Vol. 62, No. 8, pp. 839–846. fu nominal value of the ultimate tensile
Liu, D.L. (2004). “Behaviour of high strength rectangular concrete- strength of steel tube
filled steel hollow section columns under eccentric loading”, L,∆Llim column length and limit of shortening
Thin-Walled Structures, Vol. 42, No. 12, pp. 1631–1644. displacement
Liu, D.L. (2005). “Tests on high-strength rectangular concrete-filled Npl,Rk design value of the composite sectional
steel hollow section stub columns”, Journal of Constructional plastic resistance to compression
Steel Research, Vol. 61, No. 7, pp. 902–911. Npl,Rk characteristic value of the composite
Liu, D.L. and Gho, W.M. (2005). “Axial load behaviour of high- sectional plastic resistance to compression
strength rectangular concrete-filled steel tubular stub columns”, Npl,Rk1 characteristic value of the concrete filled
Thin-Walled Structures, Vol. 43, No. 8, pp. 1131–1142. sectional plastic resistance to compression
Liu, D.L., Gho, W.M. and Yuan, J. (2003). “Ultimate capacity of Npl,Rk2 characteristic value of the concrete filled
high-strength rectangular concrete-filled steel hollow section sectional plastic resistance with confinement
stub columns”, Journal of Constructional Steel Research, effect
Vol. 59, No. 12, pp. 1499–1515. Ntest,r testing values of the residual strength,
Lue, D.M., Liu, J.L. and Yen, T. (2007). “Experimental study on defined as the maximum load beyond the
rectangular CFT columns with high-strength concrete”, axial shortening limit, ϕlim
Journal of Constructional Steel Research, Vol. 63, No. 1, Ntest,u testing values of the ultim ate resistance
pp. 37–44. t thickness of steel tube
Saw, H.S. and Liew, J.Y.R. (2000). “Assessment of current methods urp the displacement in radial direction at the
for the design of composite columns in buildings”, Journal of point “P”
Constructional Steel Research, Vol. 53, No. 2, pp. 121–147. δ steel contribution ratio, the same as defined
Varma, A.H., Ricles, J.M., Sause, R. and Lu, L.W. (2002). in Eurocode 4
“Experimental behavior of high strength square concrete-filled ε rp , ε zp , εθp strains in radial, longitudinal and
steel tube beam-columns”, Journal of Structural Engineering, circumferential directions respectively at the
ASCE, Vol. 128, No. 3, pp. 309–318. point “P”
Varma, A.H., Ricles, J.M., Sause, R. and Lu, L.W. (2004). “Seismic ηa,ηc factors related to the confinement of concrete

behavior and design of high-strength square concrete-filled steel λ relative slenderness, the same as defined in
tube beam columns”, Journal of Structural Engineering, ASCE, Eurocode 4
Vol. 130, No. 2, pp. 169–179. νa,νc Poisson’s ratio of steel and concrete
Varma, A.H., Ricles, J.M., Sause, R. and Lu, L.W. (2002). “Seismic respectively
behavior and modeling of high-strength composite concrete-filled ϕlim a deformation limit on axial shortening
steel tube (CFT) beam-columns”, Journal of Constructional Steel displacement ratio
Research, Vol. 58, No. 5–8, pp. 725–758. HSC high strength concrete
Xiong, D.X. and Zha, X.X. (2007). “A numerical investigation on LVDT linear varying displacement transducer
the behaviour of concrete-filled steel tubular columns under NSC normal strength concrete
initial stresses”, Journal of Constructional Steel Research, SF steel fibre
Vol. 63, No. 5, pp. 599–611. UHSC ultra-high strength concrete

Advances in Structural Engineering Vol. 15 No. 9 2012 1503

You might also like