Professional Documents
Culture Documents
1 IntroductiontoProtectionv1
1 IntroductiontoProtectionv1
net/publication/339460150
CITATIONS READS
0 10,383
1 author:
Francisco Gonzalez-Longatt
University of South-Eastern Norway
406 PUBLICATIONS 2,972 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Francisco Gonzalez-Longatt on 24 February 2020.
Introduction
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The word “protection” is used here to describe the whole concept of
protecting a power system.
1 The Buchholz relay is used as a protective device sensitive to the effects of dielectric failure inside the equipment.
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 2/121
Definitions
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The definitions that follow are generally used in relation to power
system protection:
• Protection System: a complete arrangement of protection
equipment and other devices required to achieve a specified
function based on a protection principle (IEC 60255-20).
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The objectives of electrical system protection and coordination are to
• Limit the extent and duration of service interruption whenever
equipment failure, human error, or adverse natural events occur on any
portion of the system
• Minimize damage to the system components involved in the failure
• The circumstances causing system malfunction are usually unpredictable
[1] IEEE, IEEE std 242-2001. IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems. .
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 4/121
Safety
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Prevention of human injury is the most important objective when
designing electrical systems.
[1] IEEE, IEEE std 242-2001. IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems. .
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 5/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Minimizing the risk of equipment damage or preserving service
continuity is the more important objective depends upon the
operating philosophy of the particular industrial.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The cost of system protection determines the degree of protection
that can be feasibly designed into a system.
Relaying: Definition
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Relaying is the branch of electric power engineering concerned with
the principles of design and operation of equipment (called “relays”
or “protective relays”) that detects abnormal power system conditions
and initiates corrective action as quickly as possible in order to
return the power system to its normal state.
• Radial
• Mesh
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The manner in which the power apparatus is connected together,
system topology, in substations and switching stations, and the
general layout of the power network, has a profound influence on
protective relaying.
1 Circuit 2
breakers TRX
TRX1 1 2 3 4 5
From
Load transmission
network
SW1 SW2 SW3 SW4
Main F1 Load2 Load3 Load4
TRX2 Transformer
Power
G2 transformer
Load LEYEND Load1
SW: Switch
F: Fuse
3
Load
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• A radial system is a single-source arrangement with multiple loads,
and is generally associated with a distribution system (defined as a
system operating at voltages below 100 kV, depend on the country)
or an industrial complex.
• Such a system is most economical to build; but from the reliability
point of view, the loss of the single source will result in the loss of
service to all of the users
TRX
1 2 3 4 5
From
transmission
network
SW1 SW2 SW3 SW4
Main F1 Load2 Load3 Load4
Transformer
Power
transformer
LEYEND Load1
SW: Switch
F: Fuse
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 11/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The network has multiple sources
and multiple loops between the
sources and the loads.
• Subtransmission and transmission TRX1
1 Circuit
breakers
2
systems. Load
G2
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The load at bus 2 has secure service for the loss of a single power
system element.
Typical Transmission System
V1 1.00 pu V3 1.00 pu
1 3 Network
j0.1 system
2
j0.1 j0.1 Radial system
4 5 6 7 8 9
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The fault current for a fault at bus 2 is Icc2 = −j20.0 p.u. when all
lines are in service. V 1.00 pu V 1.00 pu 1 3
1 j0.1 3
Vf 10
I cc 2 20 j + 2 +
Z EQ 0.1 j 0.1 j j0.1 j0.1
• If lines 2–3 go out of service, the fault current changes to Icc2 =−j10.0
p.u. V3 1.00 pu
V1 1.00 pu
1 j0.1 3
Vf 10
I cc 2 10 j + 2 +
Z EQ 0.1 j j0.1 j0.1
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• All the loads on the feeder will lose their source of power if
transformers 2–4 are lost.
1 3
j0.1
2
j0.1 j0.1
4 5 6 7 8 9
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The fault current at bus 9 on the distribution feeder with system
normal is Icc9 = −j0.22988 pu,
V1 1.00 pu V3 1.00 pu
1 j0.1 3
+ 2 +
j0.1 j0.1
4 5 6 7 8 9
Vf 10
I cc 9 0.22988 j
Z EQ 0.1 j 0.1 j 4.3 j
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 16/121
Example: Effect of Topology in Fault currents
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• If one of the two generators on the transmission system is lost is Icc
Icc9= −j0.22900 pu.
V1 1.00 pu
1 j0.1 3
+ 2
j0.1 j0.1
4 5 6 7 8 9
Vf 10
I cc 9 0.22900 j
Z EQ 0.1 j 0.2 j 4.3 j
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 17/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
Symbols: ANSI/IEC
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
ANSI IEC
Overhead Transmission Line
Undergroudn Cable
Fault X
Current Transformer
Voltage transformer
Current I I
IEC
Symbols: ANSI/IEC ANSI
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
Normally open contact
Form “C”
Breaker X
Disconnect Switch
Motor disconnect switch
Circuit Switcher C
S
Transformer 3 windings
Autotransformer
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 20/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
BUS ARRANGEMENT IN SUBSTATIONS
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Substations are designed for reliability of service and flexibility in
operation and to allow for equipment maintenance with a minimum
interruption of service.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• A single bus configuration consists of one main bus that is energized
at all times and to which all circuits are connected.
• This arrangement is the simplest, but provides the least amount of
system reliability.
• Bus faults or failure of circuit breakers to operate under fault
conditions results in complete loss of the substation.
Single Bus
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
Advantages Disadvantages
• Lowest cost • High-profile arrangement equipped with
• Small land area required circuit breaker bypass facilities does not
provide for circuit protection when
• Easily expandable bypass facilities are being used inside the
• Simple in concept and operation substation.
• Relatively simple for the application of • A single bus arrangement has the lowest
protective relaying reliability.
• Failure of a circuit breaker or a bus fault
causes loss of the entire substation.
• Maintenance switching can complicate
and disable some of the protective relay
scheme and overall relay coordination.
• Maintenance at the upper elevations of
high-profile arrangements necessitates
de-energization or protection of the lower
equipment.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• It allows the breakers to be
maintained without de-energizing the
associated line.
• For system flexibility, and
particularly to prevent a bus fault
from splitting the system too
drastically, some of the lines are
connected to bus 1 and some to bus 2
(the transfer bus).
• When maintaining a breaker, all of
the lines that are normally connected
to bus 2 are transferred to bus 1, the
breaker to be maintained is bypassed
by transferring its line to bus 2 and
the bus tie breaker becomes the line
breaker.
• Only one breaker can be maintained
at a time.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• It allows any bus or breaker to be
removed from service, and the lines can
be kept in service through the companion
bus or breaker.
• A line fault requires two breakers to trip
to clear a fault.
• A bus fault must trip all of the breakers
on the faulted bus, but does not affect
the other bus or any of the lines.
• This station arrangement provides the
greatest flexibility for system
maintenance and operation; however,
this is at a considerable expense: the
total number of breakers in a station
equals twice the number of the lines
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 27/121
Ring Bus
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• A ring bus configuration is an extension of the sectionalized bus
arrangement and is accomplished by interconnecting the two open
ends of the buses through another sectionalizing breaker.
• This results in a closed loop or ring with each bus section separated
by a circuit breaker.
• For maximum reliability and operational flexibility, each section
should supply only one circuit.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
Plan View – Typical Bay
Ring Bus
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
Advantages Disadvantages
• Flexible operation • Ring may be split by faults on two
• High reliability circuits or a fault during breaker
maintenance to leave possibly
• Isolation of bus sections and circuit undesirable circuit combinations
breakers for maintenance without (supply/load) on the remaining bus
disrupting circuit operation sections. Some consider this,
• Double feed to each circuit however, to be a second contingency
• No main buses factor.
• Expandable to breaker-and-a-half • Each circuit has to have its own
configuration potential source for relaying.
• Economic design • This configuration is usually limited
to four circuit positions, although
larger rings are in service, including
10-position ring buses. A 6-position
ring bus is usually considered as a
maximum limit for the number of
terminals in a ring bus.
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 30/121
Breaker-and-a-Half
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The breaker-and-a-half
configuration consists of two
main buses, each normally
energized.
• Electrically connected between
the buses are three circuit
breakers and, between each
two breakers,
• Three circuit breakers are used
for two independent circuits;
hence, each circuit shares the
common centre circuit breaker,
so there are one-and-a-half
circuit breakers per circuit.
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 31/121
Breaker-and-a-Half
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
Advantages Disagventages
• Flexible operation • One-and-a-half breakers are
• High reliability required per circuit.
• It can isolate either main bus • Relaying is involved, since the
for maintenance without center breaker has to respond
disrupting service to faults of either of its
associated circuits.
• It can isolate any circuit
breaker for maintenance • Each circuit should have its
without disrupting service own potential source for
relaying.
• Double feed to each circuit
• Bus fault does not interrupt
service to any circuits
• All switching done with
circuit breakers
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 33/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The double breaker–double bus configuration consists of two main
buses, each normally energized.
• Electrically connected between the buses are two circuit breakers
and, between the breakers, one circuit.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
Plan View – Typical Bay
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
Advantages Disadvantages
• Flexible operation • This configuration carries a high
• Very high reliability cost.
• Isolation of either main bus for • Two circuit breakers are required
maintenance without disrupting for each circuit
service
• Isolation of any circuit breaker for
maintenance without disrupting
service
• Double feed to each circuit
• No interruption of service to any
circuits from bus fault
• Loss of only one circuit for breaker
failure
• All switching with circuit breakers
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The function of protective relaying is to promptly remove from
service any element of the power system that starts to operate in an
abnormal manner.
• Relays do not prevent damage to equipment! they operate after
some detectable damage has already occurred.
• Their purpose is
• (1) to limit, to the extent possible, further damage to equipment, to
minimize danger to people, to reduce stress on other equipments and,
above all,
• (2) to remove the faulted equipment from the power system as
quickly as possible so that the integrity and stability of the remaining
system are maintained.
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 38/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
FUNCTIONAL CHARACTERISTICS OF
PROTECTIVE RELAYING
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Sensitivity: Any relaying equipment must be sufficiently sensitive so
that it will operate reliably, when required, under the actual
condition that produces the least operating tendency.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Sensitivity is a term frequently used when referring to the minimum
operating level (current, voltage, power etc.) of relays or complete
protection schemes.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Note about speed. Applied to a relay, high speed indicates that the
operating time usually does not exceed 50 ms (three cycles on a 60-
Hz base).
[1] Walter A. Elmore, Protective Relaying Theory and Applications, Second Edi. New York. USA: Marcel Dekker, Inc., 1397.
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 42/121
Note about speed (2)
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The function of protection systems is to isolate faults on the power
system as rapidly as possible.
[1] ALSTOM, Network Protection & Automation Guide. Protective relays, measurement and control. 2011.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The shorter the time a fault is allowed to remain in the system, the
greater can be the loading of the system.
Curves illustrating the relation between relay-plus-breaker time and the maximum amount of power that can be
transmitted over one particular system without loss of synchronism when various faults occur [1], [2].
[1] ALSTOM, Network Protection & Automation Guide. Protective relays, measurement and control. 2011.
[2] C. Russell Mason, The Art & Science of Protective Relaying. GE Grid Solutions, 1956.
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 44/121
Sensitivity, Selectivity, And Speed
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The ultimate goal of protective relaying is to disconnect a faulty
system element as quickly as possible.
[1] C. Russell Mason, The Art & Science of Protective Relaying. GE Grid Solutions, 1395.
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 45/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• When a fault occurs, the protection scheme is required to trip only
those circuit breakers whose operation is required to isolate the
fault.
[1] ALSTOM, Network Protection & Automation Guide. Protective relays, measurement and control. 2011.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Reliability: It is generally understood to measure the degree of
certainty that a piece of equipment will perform as intended.
[1] IEEE, “The Authoritative Dictionary of IEEE Standards Terms,” IEEE Std 100-2000, pp. 1–1362, 2000.
[2] S. H. Horowitz and A. G. Phadke, Power System Relaying, Fourth Edi. John Wiley and Sons Ltd, 2014.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Dependability is defined as the measure of the certainty that the
relays will operate correctly for all the faults for which they are
designed to operate.
Protection Systems
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Most protection systems are designed for high dependability: A fault
is always cleared by some relay.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The need for a high degree of reliability has already been discussed
briefly. Reliability is dependent on the following factors:
a) incorrect design/settings
b) incorrect installation/testing
c) deterioration in service
• Design: Due consideration must be given to the nature, frequency
and duration of faults likely to be experienced, all relevant
parameters of the power system and the type of protection
equipment used.
• Settings: The characteristics of power systems change with time, due
to changes in loads, location, type and amount of generation, etc.
[1] ALSTOM, Network Protection & Automation Guide. Protective relays, measurement and control. 2011.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Installation: The complexity of the interconnections of many systems and
their relationship to the remainder of the system may make checking the
installation difficult. Site testing is therefore necessary. Since it will be
difficult to reproduce all fault conditions correctly, these tests must be
directed towards proving the installation itself.
• Testing: Using recognised standards is carried out during design and
production and this fulfils many of these requirements, but it will still be
necessary to test the complete protection scheme (relays, current
transformers and other ancillary items).
• Deterioration of the service: The time between operations of protection
relays may be years rather than days. During this period, defects may
have developed unnoticed until revealed by the failure of the protection to
respond to a power system fault. For this reason, relays should be
periodically tested in order to check they are functioning correctly.
[1] ALSTOM, Network Protection & Automation Guide. Protective relays, measurement and control. 2011.
B1
R1
Circuit breaker
Relay
Reliability of Protections
Line
Transmission
R2
Example: Reliability of Protections
B2
1. Introduction to Protections V1
1. Introduction to Protections V1
Busbar
B4
B3
R4
R3
• Consider the following transmission system.
R5
B5
54/121
53/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
Example: Reliability of Protections
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• If a fault happens in the point “F” on the transmission line.
• In normal operation, this fault should be cleared by the two relays
R1 and R2 through the CBs B1 and B2.
Normal operation
R3 R5
R1 R2
B3 B5
B1 “F” B2 B4
Open Open
R4
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• If R2 does not operate for this fault, it has become unreliable through
a loss of dependability.
R3 R5
R1 R2
B3 B5
B1 “F” B2 B4
Open
FAIL
TO
R4
UNRELIABLE OPEN
LOSS OF DEPENDABILITY
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 56/121
Example: Reliability of Protections
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• If relay R5 operates through breaker B5 for the same fault, and
before breaker B2 clears the fault, it has become unreliable through
a loss of security.
R3 R5
R1 R2
B3 B5
B1 “F” B2 B4
Open
UNRELIABLE
Open
FAIL
TO
R4 LOSS OF SECURITY
OPEN
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 57/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The property of security of relays, that is, the requirement that they
not operate for faults for which they are not designed to operate, is
defined in terms of regions of a power system – called zones of
protection – for which a given relay or protective system is
responsible.
• From the power system point of view, to limit the extent of the power
system that is disconnected when a fault occurs, protection is
arranged in zones.
Zones of Protection
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
SG ZONE 1
• Ideally, the zones of protection
should overlap, so that no part of
ZONE 2
the power system is left
unprotected.
ZONE 3
ZONE 4
ZONE 6
ZONE 5 ZONE 7
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The relay will be considered to be secure if it responds only to faults
within its zone of protection.
• The CTs provide a window through which the associated relays “see”
the power system inside the zone of protection.
• While the CTs provide the ability to detect a fault inside the
zone of protection, the CBs provide the ability to isolate the fault
by disconnecting all of the power equipment inside the zone.
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 61/121
Zones of Protection
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
SG ZONE 1
• A zone boundary is usually
defined by a CT and a CB.
ZONE 2
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The figure shows a
system of power 5 5
• Some form of
backup protection is
provided to trigger 2
the adjacent
switches or areas
3
3 3
adjacent to the
3
2
problem area. 1 2
4
4
• The protection of 4 4 2
each zone is 1
2
superimposed to
eliminate the 3
possibility of
unprotected areas
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 63/121
Zone of protections
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The overlapping of protection zones is carried out by connecting the
relays to the current transformers (CT) as shown.
Busbar Busbar
Protection Protection
B1
CT1
B1
CT1
CT2 CT2
Feeder Feeder
Protection Protection
CTs on both sides of circuit breaker CTs on circuit side of circuit breaker
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 64/121
Zones of protection: Measurement locations
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
CT Zone B
Zone A Zone B
CT Zone B
Zone A Zone B
CT Zone A
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 65/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Example of multiple protection Zones
Bus 2
Bus 1
Line 1 Line 2
Gen+Transf
Transformer
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Generator Protection
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Busbar protection
• Busbar protection
Fault location
Fault location
• Transmission line protection
1. Introduction to Protections V1
1. Introduction to Protections V1
Breakers responsible
Breakers responsible
M
M
70/121
69/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
Zones of protection: Transformer protection
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Transformer protection
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Busbar protection
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Distribution line protection
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Load protection (MOTOR)
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• All equipment's must be inside at least one protection zone.
Zones overlapping
surrounding the circuit
breaker.
Zones of protection
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The book [1] established a zone of protection may be closed or
open.
• Zone is closed, if all power apparatus entering the zone is monitored
at the entry points of the zone.
• Such a zone of protection is also known as “differential,” “unit,” or
“absolutely selective.”
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
(or ‘reach’) will depend on measurement of the system quantities and
Unit type protection will therefore be subject to variation, owing to changes in system
results in the conditions and measurement errors.
boundary being a Close Zone
clearly defined
closed loop.
Open Zone
Open Zone
Zones overlapping
surrounding
Open Zone
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
EXAMPLE
Zones of protection
[1] S. H.F.Horowitz
Professor and A. G. Phadke, Power System Relaying, Fourth Edi. John Wiley and Sons Ltd, 2014.
Gonzalez-Longatt 1. Introduction to Protections V1 78/121
Example Zones of protection
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Consider the following power system
Zone 1
Zone 3 Zone 5
1
Zone 4 Zone 6
Zone 2 2 3 4 5
B2
B1
B4 B5 B6
B3
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Consider the fault at F1, as shonw in the following Figure.
Zone 1
Zone 3 Zone 5
1
Zone 4 Zone 6
F1 Zone 2 2 3 4 5
B2
B1
Close zone B4 B5 B6
B3
Fault location
Breakers responsible
for the operation
• This fault lies in a closed zone, and will cause CBs B1 and B2 to trip.
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 80/121
Example Zones of protection
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Consider the fault at F2, as shown in the following Figure.
Zone 1
Zone 3 Zone 5
1
Zone 4 Zone 6
F2 Zone 2 2 3 4 5
B2
B1
Overlapping
zone B4 B5 B6
Fault location
Overlapping
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Consider the fault at F3, as shown in the following Figure. Overlapping
zone
Zone 1
Zone 3 Zone 5
1
Zone 4 Zone 6
Zone 2 2 3 4 5
F3
B2
B1
B4 B5 B6
Fault location
Breakers responsible B3 Overlapping
Open zone
zone
for the operation
[1] S. H. Horowitz and A. G. Phadke, Power System Relaying, Fourth Edi. John Wiley and Sons Ltd, 2014.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• It is desirable to remove a fault from the power system as quickly as
possible.
• The relay must make its decision based upon voltage and current
waveforms that are severely distorted due to transient phenomena
which must follow the occurrence of a fault.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
CA CB
Primary Primary
protection protection
• It operates in the fastest time possible and removes the least amount
of equipment from service.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The reliability of a power system includes the use of more than one
primary (or ‘main’) protection system operating in parallel.
CA CB
Protected Zone
[1] The Electricity Training Association, Power System Protection Vol.1: Principles and Components, vol. 1. The Institution of Engineering and Technology, Michael Faraday House, Six Hills Way, Stevenage SG1 2AY, UK: IET, 1995.
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 88/121
Primary and Backup Protection
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• On lower voltage systems, even the relays themselves may not be
duplicated. In such situations, only backup relaying is used.
• In the event of failure or non-availability of the primary protection
some other means of ensuring that the fault is isolated must be
provided.
• The secondary systems are referred to as ‘back-up protection
schemes’.
CA CB
Protected Zone
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Thus faults that occur between the current transformers and circuit
breaker (CA and CB) are outside the zone of the circuit protection and
can be dealt with either by the busbar protection (which is usual in
the transmission system, but less so in the distribution systems), or
by back-up protection.
CA CB
Fault location
Protected Zone
Breakers responsible
for the operation Protected zone of a “unit” system of protection
CA CB X Y
Fault location R R
Breakers responsible Back-up Zone
for the operation
Protected and back-up zones of a non-unit system of
protection (distance protection)
[1] The Electricity Training Association, Power System Protection Vol.1: Principles and Components, vol. 1. The Institution of Engineering and Technology, Michael Faraday House, Six Hills Way, Stevenage SG1 2AY, UK: IET, 1995.
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 91/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Backup relaying may be installed locally, that is, in the same
substation as the primary protection, or remotely.
• Remote backup relays are completely independent of the relays,
transducers, batteries, and CBs of the protection system they are
backing up.
[1] The Electricity Training Association, Power System Protection Vol.1: Principles and Components, vol. 1. The Institution of Engineering and Technology, Michael Faraday House, Six Hills Way, Stevenage SG1 2AY, UK: IET, 1995.
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 92/121
Substation Local Backup Protection
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The HV-transformer T feeds Back-up Protection Primary
the busbar 1 in a non- 1 2
effectively earthed radial C2
network without any other Fault location
sources. Breakers responsible
• It is assumed that a short for the operation
circuit occurs at F on the feeder R2
to 4 and that the feeder Back-up
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
Remote backup cannot always detect all
• A shunt fault occurs at F on the power faults on the adjacent power lines.
line between bus 2 and 3 and that the
line protection C2 in substation 2 fails to
operate. 1 2 3
“F”
• The line protections C5, C7 and C8 have C5 C1 C2 C6
to detect the shunt fault.
• The intermediate infeed at 2 will enlarge
C7 C3 C4 C8
the impedances seen by the distance
protections at 1, 4 and 5.
4 5
• This enlargement may prevent the use of
remote backup protection.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Remote backup cannot always detect all faults on the adjacent power
lines.
1 R2 R2 2
R1 R1
Fault location
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
Example:
Primary, Local backup and Remote
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Consider the following transmission system
2 3
CB6 CB4
1
R4 4
R5 “F” 5 R9
CB8 CB10
R1
R2 R10
R3
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 97/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Consider a fault “F” inside the zone of protection of transmission line
-. 2 3
CB6 CB4
1
R4 4
R5 “F” 5 R9
CB8 CB10
R1
Fault location R2 R10
Breakers responsible
for the operation R3
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 98/121
Example: Primary, Local backup and Remote
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Primary relays R1 and R5 will clear this fault by acting through
breakers CB1 and CB5. 2 3
CB6 CB4
1
R4 4
R5 “F” 5 R9
CB8 CB10
Primary
R1
Fault location Primary
R2 R10
Breakers responsible
for the operation R3
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 99/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• At substation , a duplicate primary relay R2 may be installed to
trip the breaker CB1 to cover the possibility that the relay R1 may
fail to trip. 2 3
CB6 CB4
1
R4 4
R5 “F” 5 R9
CB8 CB10
Primary R1
R2 will operate in the same time
Fault location Duplicate
R2 R10 as R1 and may use the same or
relay
different elements of the
Breakers responsible R3 protection chain.
for the operation
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 100/121
Example: Primary, Local backup and Remote
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• The local backup relay R3 is designed to operate at a slower speed
than R1 and R2; it is probably set to see more of the system.
2 3
CB6 CB4
1
R4 4
R5 “F” 5 R9
CB8 CB10
Primary R1
Fault location
R2 R10
Breakers responsible Local R3
back up
for the operation
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 101/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• R3 will first attempt to trip breaker CB1 and then its breaker failure
relay will trip breakers CB5, CB6, CB7, and CB8.
2 3
CB6 CB4
1
R4 4
R5 “F” 5 R9
CB8 CB10
Primary R1
Fault location
R2 R10
Breakers responsible Local R3
back up
for the operation
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 102/121
Example: Primary, Local backup and Remote
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• R3 is local backup relaying, often known as breaker failure
protection, for CB CB1.
2 3
CB6 CB4
1
R4 4
R5 “F” 5 R9
CB8 CB10
Primary R1
Fault location
R2 R10
Breakers responsible Breaker Failure R3
Protection
for the operation
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 103/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Relays R9, R10, and R4 constitute the remote backup protection
for the primary protection R1.
2 3
R5 “F” 5 R9
CB8 CB10
Primary R1 Remote back-up protection of R1
Fault location
R2 R10
Breakers responsible R3
for the operation
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 104/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• No elements of the protection system associated with R1 are shared
by these protection systems, and hence no common modes of failure
between R1 and R4, R9 and R10 are possible.
2 3
CB6 CB4
1
R4 4
R5 “F” 5 R9
CB8 CB10
R1
R2 R10
R3
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 105/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• USA common practice :
• to trip all three phases of the faulted power system element
for all types of fault. Three-pole tripping (TPT)
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Faults statistic indicates the faults on overhead lines fall into one of
three categories:
• Transient (80-90%)
• Semi-permanent
• Permanent
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• As a large proportion of faults on a power system are of a temporary
nature, the power system can be returned to its pre-fault state if the
tripped CBs are reclosed as soon as possible.
Reclosing Supervision:
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• All reclosing operations should be supervised (i.e., controlled) by
appropriate interlocks to prevent an unsafe, damaging, or
undesirable reclosing operation.
• Voltage Check. Used when good operating practice demands that
a certain piece of equipment be energized from a specific side.
• Synchronizing Check. This check may be used when the
reclosing operation is likely to energize a piece of equipment from
both sides.
• Equipment Check. This check is to ensure that some piece of
equipment is not energized inadvertently.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Automatic reclosing can be high speed, or it may be delayed.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• A protection system may mean only
the relays, the actual protection Electrical Power System
system consists of many other
subsystems that contribute to the Power equipment to be
detection and removal of faults. protected
Protection
Transductors Breakers
Systems
(CT, PT, etc.)
Seccionalizers Communication to
other protection
systems
V,I I/O Intertrip,
Communication,
teleprotection
Power Supply
Protection Relay I/O
I/O
Other logics Communication
management
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Since the primary function of a protection
system is to remove a fault, the ability to
trip a CB through a relay must not be
compromised during a fault, when the AC
voltage available in the substation may
not be of sufficient magnitude.
• For example, a close-in three-phase fault
can result in zero AC voltage at the
substation AC outlets.
• Tripping power, as well as the power
required by the relays, cannot therefore
be obtained from the AC system, and is
usually provided by the station battery.
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 114/121
Circuit Breakers
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Knowledge of CB operation and
performance is essential to an
understanding of protective
relaying.
• It is the coordinated action of both
that results in successful fault
clearing.
• The CB isolates the fault by
interrupting the current at or near
a current zero.
• At the present time, an EHV CB
can interrupt fault currents of the
order of 105 A at system voltages
up to 800 kV.
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 115/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
General Electric type FK, 138-kv, 3500-mva oil A 345 kV SF6 circuit breaker
circuit breakers installed at Murray Gill Station,
Kansas Gas & Electric, Wichita, KA
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 116/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Live Tank - the circuit breaker the switching unit is located in an
insulator bushing which is live at line voltage (or some voltage above
ground).
• Live Tank circuit breakers are cheaper than dead tank and require
less space.
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Zone overlap with different types of CTs and circuit breakers
CT Zone B
CB
Bus F1 F2 Bus
Zone A Zone B
Bus Bus
F1 F2 F3 F4
CB1 CB2
Line
Fault location
Professor F. Gonzalez-Longatt 1. Introduction to Protections V1 118/121
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
Summary
All rights reserved. No part of this publication may be reproduced or distributed in any form without permission of the author. Copyright © 2008-2020. http:www.fglongatt.org
• Fundamentals of protective relaying philosophy.
• Concept of reliability and its two components, dependability and
security
• Selectivity and speed of relay operation has been defined.
• Three-phase tripping, the prevailing practice in the United States,
has been compared to the more prevalent European practice of
single-phase tripping.
• Various reclosing and interlocking practices and the underlying
reasons for a given choice.
• Types of CBs and their impact on the protection system design.