Point of ● Run CPU ● DI120~150

TCD - 144 Power Failure Detection (By 5V Power) ○ Speed CPU


Application
Detection ● DI180~420

[Meaning] Power failure is detected when DC +5[V], power is applied [Actions to take]
from SMPS to DOC-200 PCB, falls down to +4.8[V] or below. 1. If DOC-200 PCB is in Down and +4.8[V] or less voltage is applied,
not +5[V], TCD 144 is judged to result from normal power failure.

2. Check the voltage applied to DOC-200 PCB,


if TCD 144 occurs even when the voltage is normal(+4.8[V]+0.05[V] or more),
or TCD 144 does not occur even when the voltage is abnormal(+4.8[V]-0.05[V]
or less), error is judged to result from a DOC-200 PCB error.
[Explanation] Check the +5[V] voltage of DOC-200 PCB again after powering OFF and then
ON the control panel to see if TCD 144 does occur or not.
1) If TCD 144 exists even though the voltage is normal,
try replacing DOC-200 PCB.
2) Also, if TCD 144 does not occur though the voltage is abnormal,
try replacing DOC-200 PCB.

3. Check the voltage of +5[V] output terminal of SMPS’ +5[V], ±15[V]


to see if it is within +5[V]±0.1[V] or not while the control panel is applied by
normal power.
1) f the voltage measured is too low, set the voltage to be +5[V]±0.1[V] by
adjusting the variable resistance of SMPS.
2) If the voltage of SMPS’ +5[V] output terminal is not adjustable or TCD 144
occurs 2~3 consecutive times, replace SMPS.

[Figure] DOC-200 PCB′s +5V Power Failure Detecting Circuit

When DC +5[V] power(MG/1, MG/6) P5 applied from SMPS to DOC-200 PCB falls
down to +4.8[V] or below, +5[V] Down detecting signal LL# (LOW LINE #) is diverted
into “Low” by U2(MAX791) element in DOC-200 PCB. And then this “Low” signal develops
Power Fail Interrupt(PF-INT#) in U1(80960KB) CPU.(Then, CPU carries out Power
Failure Interrupt Handler).