Professional Documents
Culture Documents
98533118-Factory Configuration of Hydro Multi-E - SaVer - 2014-04
98533118-Factory Configuration of Hydro Multi-E - SaVer - 2014-04
FACTORY CONFIGURATION
OF HYDRO MULTI-E
(From 2,2kW and below)
1 History
Version Date / Initials Comments
00.00.01 05-08-2013/KRJ Document created
00.00.02 05-09-2013/KRJ Appendix 1 added, Firmware check added.
00.00.03 11-09-2013/KRJ Unlocking GO added.
00.00.04 09-04-2014/KKA GSC files added. Use motor SW 02.01.00 or newer. Use PC-Tool
15.00.00 or newer. Clean up in appendix 1.
Drawing No:
FACTORY CONFIGURATION
1133609
1119206
10-04-2014 KKA
07-08-2013 PHO
OF HYDRO MULTI E From
Page :
98533118
of
Chg.note Date – Init. 2,2kW and below. 1 10
FACTORY CONFIGURATION OF HYDRO MULTI-E (From 2,2 and Below)
2 Table of contents
1 History ................................................................................................................................................................................................1
2 Table of contents .............................................................................................................................................................................2
3 Purpose ..............................................................................................................................................................................................2
4 Necessary equipment ....................................................................................................................................................................2
5 Checking the Firmware version ...................................................................................................................................................3
5.1 Checking firmware version on the Motor ......................................................................................................................3
5.2 Checking the firmware using PC-tool E-products. .......................................................................................................3
6 Factory configuration of Hydro Multi-E ....................................................................................................................................4
6.1 Download Multi-Pump GSC files to the pumps............................................................................................................4
6.2 Setup the Multi-Pump system with GO. ........................................................................................................................7
6.3 Setup tank size with GO......................................................................................................................................................8
Appendix 1 .................................................................................................................................................................................................9
How to acquire GO equipment ........................................................................................................................................................9
Unlocking the advanced menu in the application (GENI parameters) ..................................................................................9
How to acquire PC-Tool E-Products, version 15.00 or later ................................................................................................... 10
3 Purpose
The purpose of this document is to describe the configuration procedure for Hydro Multi-E from 2,2 kW and be-
low.
4 Necessary equipment
The following equipment is needed:
1. Grundfos GO version 2.0.7 or newer (Planned release May)
2. PC-Tool E-Products, version 15.00 or later – And updated Configuration files
3. PC-Tool Link adapter
Drawing No:
FACTORY CONFIGURATION
1133609
1119206
10-04-2014 KKA
07-08-2013 PHO
OF HYDRO MULTI E From
Page :
98533118
of
Chg.note Date – Init. 2,2kW and below. 2 10
FACTORY CONFIGURATION OF HYDRO MULTI-E (From 2,2 and Below)
5 Checking the Firmware version
Only firmware version V02.01.00 or newer can be used for configuring a Hydro Multi-E. The firmware version can
be checked on the Motor nameplate or on using PC-tool E-products
If the motor was produced before week 01 2014 it must be updated. The updating procedure is described in “Pro-
cedure for updating existing SaVer motors with new SW versions” which can be downloaded from Insite:
“Select site”-> “Global Product Management” -> “Systems” -> “Hydro Boosters” -> “Hydro Multi-E” -> “Production
Documents”
4. Go to “Monitor” and “Information” and read out the “software version – front end”
Drawing No:
FACTORY CONFIGURATION
1133609
1119206
10-04-2014 KKA
07-08-2013 PHO
OF HYDRO MULTI E From
Page :
98533118
of
Chg.note Date – Init. 2,2kW and below. 3 10
FACTORY CONFIGURATION OF HYDRO MULTI-E (From 2,2 and Below)
6 Factory configuration of Hydro Multi-E
The configuration of Hydro Multi-E set consists of the following steps:
5.1 Download Multi-Pump GSC files to the pumps.
5.2 Setup the Multi-Pump system with GO.
5.3 Setup tank size with GO.
8. Go to ”Standard Configuration” select ”number” and type the number according to tabel 1 and press
“search now”.
Drawing No:
FACTORY CONFIGURATION
1133609
1119206
10-04-2014 KKA
07-08-2013 PHO
OF HYDRO MULTI E From
Page :
98533118
of
Chg.note Date – Init. 2,2kW and below. 4 10
FACTORY CONFIGURATION OF HYDRO MULTI-E (From 2,2 and Below)
TABEL 1
Sensor range Inlet protection GSC file
0-10 Bar Switch 98523060
0-16 Bar Switch 98523071
0-10 Bar None 98566796
0-16 Bar None 98566797
0-10 Bar 0-1 Bar 98523074
0-10 Bar 0-6 Bar 98523075
0-16 Bar 0-1 Bar 98523076
0-16 Bar 0-6 Bar 98523077
Master Pumps
0-145 PSI Switch 98523072
0-232 PSI Switch 98523073
0-145 psi None 98566798
0-232 psi None 98566799
0-145 psi 0-14,5 psi 98523078
0-232 psi 0-14,5 psi 98523079
0-145 psi 0-87 psi 98523080
0-232 psi 0-87 psi 98523081
No sensor Switch 98523082
Slave Pumps
No Sensor No Switch 98523083
*Slave pumps are the pumps that does not have a discharge sensor connected.
9. Mark the number under ”configuration files” and press “send”.
10. Stop the pump by pressing the “on/off” button on the pump.
11. Repat step 1-6 for all the pumps in the system.
Drawing No:
FACTORY CONFIGURATION
1133609
1119206
10-04-2014 KKA
07-08-2013 PHO
OF HYDRO MULTI E From
Page :
98533118
of
Chg.note Date – Init. 2,2kW and below. 5 10
FACTORY CONFIGURATION OF HYDRO MULTI-E (From 2,2 and Below)
12. After all pumps have been configured, power the complete system off and replace the terminals connect-
ing the pumps.
Drawing No:
FACTORY CONFIGURATION
1133609
1119206
10-04-2014 KKA
07-08-2013 PHO
OF HYDRO MULTI E From
Page :
98533118
of
Chg.note Date – Init. 2,2kW and below. 6 10
FACTORY CONFIGURATION OF HYDRO MULTI-E (From 2,2 and Below)
6.2 Setup the Multi-Pump system with GO.
1. Power the complete system on.
2. Press connect on GO and press the connect button on pump one.
3. When the pump have been initialized on GO, select “Assist”-> “Multi-Pump setup” -> “Cascade”-> “Bus
cable”
4. Press ”Select pump 2” and a list of available pumps occours. By pressing the “wink icon” the pumps can be
identified. Press on a pump in the list to configure it as pump number 2. Continue doing this until all the
pumps in the system have been paired. Press “>” and “Send”.
Drawing No:
FACTORY CONFIGURATION
1133609
1119206
10-04-2014 KKA
07-08-2013 PHO
OF HYDRO MULTI E From
Page :
98533118
of
Chg.note Date – Init. 2,2kW and below. 7 10
FACTORY CONFIGURATION OF HYDRO MULTI-E (From 2,2 and Below)
6.3 Setup tank size with GO.
1. Power the complete system on.
2. Press connect on GO and press the connect button on any of the pumps.
3. When prompted “connect to system or pump”, choose “Pump”.
4. Choose “Settings” -> “Stop Function” -> “Diaphragm tank volume” set the volume according to the
connected tank and press “OK”
Drawing No:
FACTORY CONFIGURATION
1133609
1119206
10-04-2014 KKA
07-08-2013 PHO
OF HYDRO MULTI E From
Page :
98533118
of
Chg.note Date – Init. 2,2kW and below. 8 10
FACTORY CONFIGURATION OF HYDRO MULTI-E (From 2,2 and Below)
Appendix 1
Hardware:
There are several options that can be used for GO.
MI 301 – Universal bluetooth dongle for Android and Apple devices. PN: 98046408
MI 204 with iPod touch kit – iPod touch 5th generation with protective cover. PN: 98612711
http://wiki.grundfos.com/pages/viewpage.action?title=Grundfos+GO&spaceKey=datacom
Software:
1. Open the GO application.
2. “Slide” to the right and scroll down and select “settings”.
3. Select “Personal Info” and type in “wei” in the notes field. Reboot the GO app.
4. GO is now unlocked.
Drawing No:
FACTORY CONFIGURATION
1133609
1119206
10-04-2014 KKA
07-08-2013 PHO
OF HYDRO MULTI E From
Page :
98533118
of
Chg.note Date – Init. 2,2kW and below. 9 10
FACTORY CONFIGURATION OF HYDRO MULTI-E (From 2,2 and Below)
How to acquire PC-Tool E-Products, version 15.00 or later
Hardware:
PC-Tool link box is available at this PN: 96705378
Note: it is the same hardware as used for programming Multi-E and MPC earlier.
Software:
Latest version of PC-Tool E-products is available on insite under “groupportal” -> “Toolbox” -> “GTI – Grundfos
technical information” -> “service and support tools” -> “Grundfos PC-tools\ Pc-Tool E products.
Drawing No:
FACTORY CONFIGURATION
1133609
1119206
10-04-2014 KKA
07-08-2013 PHO
OF HYDRO MULTI E From
Page :
98533118
of
Chg.note Date – Init. 2,2kW and below. 10 10