Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

www.fenwal@fenwal.

it

1019-G3 Single Channel Gas Detection Card


Card mod.1019/G3, is a single channel gas detection card which accept 0-20mA input. It is equipped with 3-
digits display and bar-graph to allow the actual reading of the sensors/transmitter output.
It can be used as interface for toxic gas detectors (ppm), combustible gas detectors (%L.E.L.) or oxygen
depletion (%).

MAIN FEATURES
§ Microprocessor technology
§ LED’s for alarms/status indication.
§ 3-digits display with selectable range through INPUTS/OUTPUTS
dip-switches as follws: 0-20 mA Input
ü 0-10 ppm 0-20 mA Output
ü 0-20 ppm
ü 0-25 % O2
ü 0-50 ppm FRONT PANEL
ü 0-100 ppm or % L.E.L. Led’s indication (F= steady, I= intermmittent).
ü 0-200 ppm
ü 0-500 ppm SET + and – push buttons
ü 0-999 ppm
§ 0-100% end-of-scale bargraph By simultaneously depressing
§ On board self-checking functions the two push button for:
§ Std. 19” 3HE mounting with locking screw. less than 5 sec’s
§ Dip switches address setting. lamp test
§ Different working modes selectable through Dip more than 5 sec’s
switches. alarm thresholds set.
By using the push buttons +
and – the alarm’s set point
OPERATION will be increased/decreased.
The 1019 G3 controls one 0-20mA input from gas ALARM
detectors/transmitters. I Alarm threshold visualisation
It is equipped with 3-digits display and bar-graph to during setting phase.
allow the actual reading of the sensors/transmitter F Alarm (2nd threshold)
output. A further 0-20mA output is also provided PREALARM
which corresponds to the sensor/transmitter I Alarm threshold visualisation
reading. during setting phase.
Two alarm thresholds can be set in the whole F Alarm (1st threshold)
reading range (prealarm, alarm); both of them are RESET
visulised on card front panel by means of LED’s. Card working mode
The alarms can be used by the 1019 CPU to I During thresholds set
activate other system’s outputs through the F Card disabled or during
configuration software. remote programming

A MEMBER OF KIDDE PLC


FENWAL IS A REGISTERED TRADE MARK OF KIDDE FENWAL INC.
TECHNICAL CHARACTERISTICS WIRING
The card is equipped with terminal’s
Model 1019 G3 board connected to the 1019 I/O rack
Part Number SCH 1019/G3-XX (*) by means of a flat cable.
Customized further terminal strip can
Voltage 22-28 Vdc also be provided.
Stand-by: 70 mA

Current Consumption In test: 90 mA


Alarm: 80 Ma

Input 0-20 mA
Output (2-wires) 0-20 mA
Outputs activation Programmable
Working temperature -10°C +50
Storage temperature -30° C + 70° C
Humidity (UR%) 95% non condensata
Color Ral 9002
Weight 90 g
Dimensions (height std. 19” rack
L. 25 mm P. 150 mm
3HE)
(*)NOTE: Indicates revision index

TYPICAL WIRING DIAGRAM

You might also like