Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

3TB AC Contactors

Selection and ordering data

AC operation

3TB40 3TB41 3TB42 3TB43 3TB44

Auxiliary contacts
NO NC
NO - NC NO - NC NO - NC NO - NC NO - NC
3TB40 10 - 0X 1 - 3TB41 10 - 0X 1 -
Order No. 3TB40 01 - 0X - 1 3TB41 01 - 0X - 1
3TB40 22 - 0X 2 2 3TB41 22 - 0X 2 2 3TB42 22 - 0X 2 2 3TB43 22 - 0X 2 2 3TB44 22 - 0X 2 2
Rated insulation voltage (V) 660 660 660 660 660
Rated operational current (A) AC - 3 9 12 16 22 32
(380V)
AC - 4 3.3 4.3 7.7 8.5 15.6
Rated outputs of 230/220V 2.4 3.3 4 6.1 8.5
three-phase motors 400/380V 4 5.5 7.5 11 15
at 50Hz (kW) AC - 3 500 V 5.5 7.5 10 11 21
690/660V 5.5 7.5 11 11 23
1000 V -- -- -- -- --
AC - 4 400/380V
690/660V
1.4
2.4
1.9
3.3
3.5
6
4
6.6
7.5
13
Mechanical endurance (x10 )
6
10 10 10 10 10
Electrical endurance (x106) AC - 3 1.0 1.0 1.0 1.0 1.0
AC - 4 0.2 0.2 0.2 0.2 0.2
Switching frequency (1/h) AC - 3 1000 1000 750 750 750
AC - 4 250 250 250 250 250
Coil voltage tolerance (AC) (0.8~1.1)Us
Order No. suffixes for rated Coils for 50Hz Coils for 50/60Hz
control voltages for coils V AC V AC
24 B0 24 C2
3TB40 -0X 42 D0 42 D2
110 F0 110 G2
~

3TB44 -0X 220 M0 220 N2


240 U0 240 P2
380 Q0
Closed (VA) 10 10 10 10 10
Power consumption
of coil (50Hz) p.f. 0.29 0.29 0.29 0.29 0.29
Closing (VA) 68 68 68 68 69
p.f. 0.82 0.82 0.82 0.82 0.86
Conventional thermal current (A) 20 20 30 30 45
Conventional thermal current of auxiliary contacts 10 10 10 10 10
(A)
Rated insulation voltage of auxiliary contacts
(V) 660 660 660 660 660
Rated operational current of AC - 15 6/10 6/10 6/10 6/10 4/6
auxiliary contacts (A) 380/220V
DC - 13 0.9/0.45 0.9/0.45 0.9/0.45 0.9/0.45 1.8/0.9
110/220V
Weight (kg) 0.43 0.43 0.49 0.49 0.7