Electrical Power and Energy Systems: Sciencedirect

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Electrical Power and Energy Systems 111 (2019) 447–458

Contents lists available at ScienceDirect

Electrical Power and Energy Systems


journal homepage: www.elsevier.com/locate/ijepes

Control strategy for inverters in microgrid based on repetitive and state T


feedback control

Wenjie Ma, Sen Ouyang
School of Electric Power, South China University of Technology, Guangzhou 510641, China

A R T I C LE I N FO A B S T R A C T

Keywords: As for an ac microgrid, it’s important to supply the loads with a sinusoidal voltage. However, due to the majority
Repetitive control of the loads being naturally nonlinear, when the microgrid is operating in the island mode, the output voltage of
State feedback the inverters is always deformed. To improve the total harmonic distortion (THD) of the output voltage, a control
Microgrid inverters strategy based on repetitive and state feedback control is proposed in this paper. Firstly, the state feedback
Total harmonic distortion (THD)
control is used to implement the pole assignment of the controlled object, i.e., the LC filter. By this way, the
resonance of the filter can be well suppressed. And the open-loop gain of the system is also increased in the low
frequency band, which can improve the system dynamics. Combined with this, the repetitive control is adopted
to ensure good steady-state control performance. Based on the sensitivity function and the regeneration spec-
trum theory, a parameter design method is proposed to simplify the design of a repetitive controller. Both
simulations and experiments are provided to demonstrate the good control performance of the proposed strategy
when supplying nonlinear loads in comparison to the PI controller. Moreover, the microgrid simulation results of
two inverters have been presented to validate the effectiveness of the designed control strategy.

1. Introduction been successfully applied to controlling dc-ac power inverters, such as


[12,13]. Based on this, the strategy consisting of a set of resonant
Nowadays, as an important form of power supply networking that controllers is proposed to reduce the THD of the output voltage for the
can give full play to the flexibility and advantages of the distributed uninterruptible power supply when serving nonlinear loads [14]. Al-
generation (DG), the microgrid has attracted much attention in recent though a system equipped with well-tuned multiple resonant con-
years [1–3]. Power electronic inverters are the main interface devices trollers shows perfect performance of rejecting harmonics, the de-
for power exchange between DGs and microgrid. Therefore, ensuring termination of a large number of parameters is a difficult task.
efficient and stable operation of the inverters is of great significance for Moreover, compared to others, this kind of controller requires much
improving the operation of microgrid and promoting its development. more DSP resources [15]. Due to the characteristics of simple structure
The majority of loads in microgrids are nonlinear. Together with the and strong robustness [16], the application of the sliding mode control
voltage at the point of common coupling (PCC), the output voltage of to the control of the inverter output voltage is studied by many re-
the inverters is always deformed by the load harmonic current when the searchers [17], which ensures that the system is well resistant to load
microgrid operates as an island, which may cause serious problems disturbances while maintaining a good dynamic response. Nevertheless,
regarding stability and reliability [4–6]. Therefore, it is of great prac- the chattering problem in the digital implementation of the sliding
tical significance to study the control strategy for reducing the total mode control is unavoidable [18]. A droop control strategy is proposed
harmonic distortion (THD) of the output voltage when supplying the in [19] to share the load harmonic power, which can reduce the THD of
demand of nonlinear loads. the inverter output voltage to a certain extent. However, it is necessary
Among many control technologies, the control strategy based on the to know the impedance type at each harmonic frequency to determine
proportional plus integral (PI) controller is widely used in the output the selected droop control equation. To address this problem, a har-
voltage control of microgrid inverters [7,8]. Though the structure of PI monic droop control strategy is presented in [20]. But the design of the
controller is simple to implement, it has limitations for harmonic sup- control coefficients is more complex.
pression [9,10]. The proportional plus resonant (PR) controller can The repetitive control based on the internal model principle can
realize zero-steady-state error tracking of sinusoidal signals [11]. It has realize the precise tracking of periodic signals, and can effectively


Corresponding author.
E-mail address: ouyangs@scut.edu.cn (S. Ouyang).

https://doi.org/10.1016/j.ijepes.2019.04.002
Received 8 March 2019; Received in revised form 1 April 2019; Accepted 5 April 2019
Available online 23 April 2019
0142-0615/ © 2019 Elsevier Ltd. All rights reserved.
W. Ma and S. Ouyang Electrical Power and Energy Systems 111 (2019) 447–458

suppress the periodic disturbance [21], so it is widely used in control of


inverters [9,12]. In [22], the repetitive controller is applied to the
voltage harmonic mitigation of the inverters in island microgrid, and a
design method of the lead unit in repetitive controllers is proposed to
take comprehensive consideration of control accuracy and the system
stability margin. However, due to the inherent hysteresis property of
repetitive control, the response speed of the system is slow. In order to
further enhance the robustness of the system, a combined controller of
repetitive control and sliding mode control is presented in [23], assisted
by feedforward control to improve dynamics. Nevertheless, to get good
tracking accuracy and resonance suppression of the LC filter, the design
of the phase advance unit and the low-pass filters is more complex. In
order to reduce the number of parameters to be considered in the de-
sign, a method based on the H∞ control theory is proposed in [24,25]
to obtain the stabilizing compensator, which can guarantee the ex-
ponential stability of the repetitive control system. But the compensator
with excellent performance is always higher-order and its im-
plementation is complicated. Also, in [15], an approach based on the
mixed sensitivity is used to design the repetitive controller. But the
selection of the weighting functions is not easy. It should be noted that
the condition [9,26] employed for the system stabilization design in
[22,23] is a sufficient condition, which means that the stability margin
Fig. 1. Architecture of an islanded low-voltage microgrid.
of the designed system cannot be evaluated. It’s pointed out in [27] that
the regeneration spectrum is suitable for simplifying the system stabi-
lization design and analyzing the stability margin of the repetitive 2. Basic control structure of the microgrid inverter
control system. On this basis, a design method for the repetitive con-
troller based on regeneration spectrum is shown in [28], and the ef- An islanded microgrid composed of multiple DG units is shown in
fectiveness of the method is verified by simulation and experimental Fig. 1. The DG is usually equipped with an energy storage device to
results in an active power filter system. It is worth to point out that supply high-quality power to loads. Therefore, it is assumed that the
there are few experiment results available in literature showing cases of DC-side voltage of the inverter, denoted as vdc , remains a constant in
regeneration spectrum applied to the output voltage repetitive control this paper.
of microgrid inverters. Usually, the control system of microgrid inverters can be divided
The inverters are always connected to the microgrid via LC filters. into a power layer, a control layer and a PWM hardware layer [32]. The
At the resonance frequency, the controlled object, i.e., the LC filter, common algorithms used to generate the voltage reference in the power
with a phase lag nearly 180 degrees shows a large resonance peak, layer mainly include the droop control and the virtual synchronous
which leads to the poor stability of the system [29]. Therefore, a good generator (VSG) control. The control loop, which regulates the output
suppression of the filter resonance is important for improving the voltage with no steady-state errors, and the virtual output impedance
control performance of the repetitive control system. The passive loop together constitute the control layer. In the low-voltage microgrid,
damping method of series resistor in the circuit is adopted in [24,25], the P-U and Q-f droop control can better achieve the decoupling control
thereby increasing the power loss [30,31]. To avoid this problem, the between active power and reactive power [33].
way of adding digital filters into the control loop is used in [22,23] to Based on the aforementioned discussion, the overall control block
suppress the resonance peak. However, the active damping method of diagram of the inverter designed in this paper is shown in Fig. 2.
adding low-pass filters and notch filters requires accurate information In Fig. 2, vx (x = a, b, c) represents the inverter-side output voltage.
of the system parameters (such as the filter resonant frequency). Thus, The measured signals ix and vox are the inductor current and the output
it’s sensitive to the parameters changes. voltage, respectively. iox is the current injected into the microgrid. The
To mitigate the output voltage harmonics when serving nonlinear LC filter inductance and capacitance are denoted as L and C. Rl is the
loads, a control strategy based on the repetitive and state feedback equivalent series resistance of the filter inductor, and Rc is that of the
control is proposed in this paper. Firstly, the inductor current and ca- filter capacitor. P and Q are the measured average active power and
pacitor voltage of the LC filter are selected as state variables to perform reactive power respectively. E∗ and ω∗ are the nominal voltage and
pole assignment of the controlled object, namely, the LC filter. Through frequency. The droop coefficients are defined as kp and kq, respectively.
the state feedback, the resonance of the filter can be well-suppressed The state feedback coefficients are represented as k1 and k2. Rfi and Lfi
without extra power loss. And this way is relatively insensitive to the are the resistance and inductance of the feeder, and their values are
parameter perturbations. Combined with the state feedback control, a generally small.
voltage repetitive controller with good steady-state control accuracy As shown in Fig. 2, the pole assignment implemented by state
and stability is designed based on the sensitivity function and re- feedback of the controlled object, i.e., the LC filter, is carried out to
generation spectrum. Both simulation and experimental results are change its frequency characteristics. The repetitive control is used to
given to demonstrate the excellent performance of the proposed control achieve high steady-state control accuracy and enhance the ability to
strategy of reducing the inverter output voltage THD when supplying resist the harmonic interference. And the dynamic response speed of the
nonlinear loads. Furthermore, a microgrid simulation model is built to system is further ensured by the feedforward control. Because the
verify its effectiveness in parallel operation of inverters. control model in each coordinate α or β is the same and decoupled [34],
The rest of this paper is structured as follows. The basic control the single-phase control model of the LC filter is taken as an example for
structure of microgrid inverter is introduced in Section 2. And the de- explanation in the following design process. In this work, the design of
sign of the proposed control strategy and the analysis of stability and voltage control is mainly concerned. Details about the droop control
robustness are illustrated in Sections 3 and 4, respectively. Section 5 and the virtual impedance technique can be found in [32,33,35].
gives the simulation and experiment results.

448
W. Ma and S. Ouyang Electrical Power and Energy Systems 111 (2019) 447–458

Fig. 2. Control block diagram of the microgrid inverter.

3. The voltage control strategy

3.1. Design of the state feedback control

The SVPWM block together with the inverter can be modeled by


using an average voltage approach. So the SVPWM block and the in-
verter bridge can be ignored when designing the controller [25]. Con-
sidering a balanced three-phase system, the controlled object P of the
single-phase model of the LC filter is shown in Fig. 3.
From Fig. 3, the transfer function from vx to vox can be expressed as

vox (s ) CR c s + 1
G0 (s ) = =
vx (s ) LCs 2 + (Rl + R c ) Cs + 1 (1)

On the basis of the system parameters, the Bode plot of G0 (s ) is


shown in Fig. 4.
It’s obvious in Fig. 4 that the underdamped system exhibits a large
resonance peak at the resonant frequency with a lag phase close to Fig. 4. Bode plots of G0 (s ) and Gp (s ) .
180 degrees, which means the stability of the system is very poor. In
order to improve the frequency characteristics of the controlled object,
the filter inductor current i x and the output voltage vox are selected as
the state feedback variables, and the designed state feedback control is

Fig. 5. Diagram of the controlled object with state feedback control.


Fig. 3. Diagram of the controlled object P.

449
W. Ma and S. Ouyang Electrical Power and Energy Systems 111 (2019) 447–458

shown in Fig. 5. 5
Td ⩾
Then, the transfer function from vx to vox can be rewritten as |α max | (8)

vox sCR c + 1 ln(R (ωi ))


Gp (s ) = = αi ≅
vx LCs 2 + (Rl + R c + k1 R c + k2 ) Cs + 1 + k1 (2) Td (9)

Assume the poles of the controlled object with state feedback con- in which α max is the zero point’s real part of P (s ) , and αi is the real part
trol be of dominant pole of the system.
Therefore, the dominant poles can be expressed as
s1,2 = −ξωr ± jωr 1 − ξ 2 (3)
ln(R (ωi ))/ Td ± jω (10)
where ξ and ωr are the desired damping ratio and natural angular where ω ∈ (0, ∞) .
frequency. Thus, some conclusions can be derived:
Combining the system characteristic equation determined by (3)
with (2), the corresponding expressions of the two state feedback (a) To design a stable system, the condition that R (ω) < 1 should be
coefficients can be obtained as satisfied.
2 (b) If (8) is met, the stability margin of the system can be estimated by
⎧ k1 = ωr LC − 1
the degree of between R (ω) and 1.
⎨ k2 = 2ξωr L − ωr2 LCR c − Rl (4)

In this paper, the desired damping ratio and natural angular fre- More details are provided in [27,36,37].
quency are set to ξ = 0.6 and ωr = 6600 . Then, according to (4), the The unity feedback closed-loop system only with pole assignment is
state feedback coefficients are as follows shown in Fig. 6(a). The system sensitivity function is defined as
1
S0 (s ) =
⎧ k1 = −0.78725 1 + Gp (s ) (11)
⎩ k2 = 5.7502
⎨ (5)
The characteristic equation of the system in Fig. 6(b) is given by
The Bode plot of the controlled object after pole assignment, i.e., the
frequency characteristic of Gp (s ) , is shown in Fig. 4. From Fig. 4, the 1 + Gp (s ) − K q (s ) e−(T − τ1) s = 0 (12)
advantages of the state feedback control can be concluded as follows: Based on the aforementioned discussion, the regeneration spectrum
function of the system in Fig. 6(b) is defined as
(1) Eliminate the resonance peak completely and improve the phase
margin of the system; R (ω) = |K q (jω) S0 (jω)| (13)
(2) Increase the system open-loop gain in the low-frequency band, Let ‖S0 (s )‖∞ = Ms and |S0 (jωs )| = 1(‖·‖∞ denotes the H∞ norm of the
thereby, improving the dynamics and the steady-state tracking ac- transfer function) as shown in Fig. 7.
curacy. Since ‖K q (s )‖∞ = 1, a condition to ensure R (ω) < 1 is given by
|K q (jωs )| < 1/ Ms (14)
3.2. The repetitive control
In this paper, K q (s ) is selected as a second-order low-pass filter with
Usually, the load current iox contains a large number of harmonic the transfer function as follows
components. As shown in Fig. 6(b), in order to further enhance the
ωq2
ability to reject harmonic interference, the repetitive controller is K q (s ) =
adopted to improve the steady-state control performance of the system. s2 + 2ξq ωq s + ωq2 (15)
In Fig. 6, K q (s ) is a low-pass filter to ensure the system stability. e−sT where ωq is the cut-off frequency of the filter and ξq is the damping
is a delay link, and Tis the base period of the reference vref . e sτ1 is the
coefficient, which is set to ξq = 2 /2 . Therefore, according to (14), the
lead link.
upper limit of ωq can be calculated by
2
3.2.1. Design of the low-pass filter K q (s ) 2 2 2
⎛ ωs − 2ξq ωs ⎞ ωs 4 ωs 2 − 2ξq2 ωs2
Firstly, a brief introduction of the regeneration spectrum theory ωq < ⎜ M −1 ⎟
2
+ 2

s Ms − 1 Ms2 − 1
[27,28] is presented to help understand the design method. ⎝ ⎠ (16)
Considering the continuous time-invariant system with a single-
delay, assume its characteristic equation is
3.2.2. Design of the lead link e sτ1
P (s ) + Q (s ) e−sTd =0 (6) Based on the sensitivity function, the parameter design can take into
the trade-off among the control accuracy and stability of the control
where Td is the delay time. system [15,28]. So this paper adopts the sensitivity function in the
Accordingly, the regeneration spectrum function of the system is design of the lead link e sτ1.
defined as From Fig. 6(b), the sensitivity function of the system is expressed as
Q (s ) Sγ (s ) = S0 (s ) X (s ) (17)
R (ω) =
P (s ) (7)
in which
The closed-loop system keeps stable on the condition that R (ω) < 1 1 − K q (s ) e sτ1 e−sT
and all the zero points of P (s ) are in the left half part of the complex X (s ) =
1 − S0 (s ) K q (s ) e sτ1 e−sT (18)
plane. This is a sufficient but non-essential condition, which means the
regeneration spectrum function cannot be used to estimate the absolute Lemma 1 gives a sufficient condition for choosing the parameter τ1
stability margin of the system. Fortunately, this issue was addressed in to reduce the magnitude of the sensitivity function at the harmonic
[27]. frequency of kωn (ωn is the base angular frequency of the reference)
Systems satisfying (8) have the characteristic stated as (9) [38].

450
W. Ma and S. Ouyang Electrical Power and Energy Systems 111 (2019) 447–458

Fig. 6. Control Block diagrams. (a) The unity feedback closed-loop system only with pole assignment. (b) A repetitive controller is plugged in the system in (a). (c)
The proposed voltage control strategy in this paper.

|Sγ (jkωn )| ⩽ |S0 (jkωn )||X (jkωn )| ⩽ |S0 (jkωn )|, ∀ kωn < ωq (22)

It can be derived from (22) that the magnitude of the sensitivity


function defined in (17) can be reduced by the reasonable design of τ1 at
all harmonic frequencies within the bandwidth of K q (s ) . Thereby, the
ability of the system to reject harmonic interference can be improved.

3.2.3. Design of the phase advance compensator e sτ2


According to the above analysis, the bandwidth of K q (s ) is limited to
ensure the system stability. In order to further improve the tracking
performance for the signals with frequencies smaller than ωq , a phase
Fig. 7. The frequency response of K q (s ) and S0 (s ) . advance compensator is plugged into the system in Fig. 6(b).
The characteristic equation of the system in Fig. 6(c) is as follows
Lemma 1. For a ωq satisfying (16), if there exists a positive constant τ1 such 1 + Gp (s ) + K q (s ) e sτ1 [e sτ2 Gp (s ) − Gp (s ) − 1] e−sT = 0 (23)
that θl (kωn ) ⩽ δ1 (kωn ) ⩽ θu (kωn ), ∀ kωn < ωq , then |X (jkωn )| ⩽
1, ∀ kωn < ωq , where and the regeneration spectrum function is

δ1 (ω) = arg[K q (jω) e jωτ1] (19) R (̂ ω) = |K q (jω) S0̂ (jω)| (24)

where
Im[S0 (jkωn )]
θu (kωn ) = tan−1
1 − Re[S0 (jkωn )] e sτ2 Gp (s )
S0̂ (s ) = 1 −
1 + Gp (s ) (25)
⎡ (1 − |S0 (jkωn )|2 )/2 ⎤
+ cos−1 ⎢
1 2Re[ ( )] | ( )|2 ⎥
⎣ − S0 jkω n + S 0 jkωn ⎦ (20) Then the sensitivity function of the system in Fig. 6(c) is given by

Sγ̂ (s ) = S0 (s ) X ̂(s ) (26)


Im[S0 (jkωn )]
θl (kωn ) = tan−1
1 − Re[S0 (jkωn )] in which
⎡ (1 − |S0 (jkωn )|2 )/2 ⎤ 1 − K q (s ) e sτ1 e−sT
− cos−1 ⎢
2 ⎥ X ̂(s ) =
⎣ 1 − 2Re[S0 (jkω n )] + |S 0 (jkωn )| ⎦ (21) 1 − S0̂ (s ) K q (s ) e sτ1 e−sT (27)

Lemma 2 gives a sufficient condition for choosing the parameter τ2


[38].
Therefore, according to Lemma 1, for a positive constant τ1 sa-
tisfying the condition, there is Lemma 2. If there exists a constant τ2 satisfying that

451
W. Ma and S. Ouyang Electrical Power and Energy Systems 111 (2019) 447–458

θl2 (kωn ) ⩽ ωτ2 (defined as δ2 (ω)) ⩽ θu2 (kωn), ∀ kωn < ωq , then Table 1
Parameters of the inverter.
‖K q (s ) S0̂ (s )‖∞ < 1 (28)
Parameters Value
and
LC-filter inductance, L/mH 0.75
LC-filter inductance, C/ μ F 6.6
1 − K q (jkωn ) e jkωn τ1 e−jkωn T
|X ̂(jkωn )| = <1 Equivalent resistance, Rl /Ω 0.1
1 − S0̂ (jkωn ) K q (jkωn ) e jkωn τ1 e−jkωn T (29) Equivalent resistance, R c /Ω 0.05
Switching and sampling frequency, f/kHz 20
where DC voltage, vdc /V 400

θl2 (kωn ) = −arg[T0 (jkωn )] (30)

|T0 (jkωn )| ⎤
θu2 (kωn ) = cos−1 ⎡ − arg[T0 (jkωn )]
⎣ 2 ⎦ (31)

T0 (s ) = 1 − S0 (s ) (32)

It can be derived from (29) that

|Sγ̂ (jkωn )| = |S0 (jkωn ) X ̂(jkωn )| ⩽ |S0 (jkωn )||X ̂(jkωn )| ⩽ |S0 (jkωn )| (33)

Then, from (24), (28), and (33), it can be concluded that the closed-
loop system in Fig. 6(c) is not only stable, but also the tracking error is
lower than that of the system in Fig. 6(b).
Consequently, the design procedure of the proposed voltage control
strategy shown in Fig. 6(c) is presented in Fig. 8.
Fig. 9. Frequency response of S0 (s ) .

4. Solution of control parameters and system performance


analysis derived that ωs = 12, 100 rad/s and Ms = 1.97 . Then, calculated by (16),
the upper band of ωq is 9210 rad/s. In this paper, the value of ωq is set to
4.1. Solution of control parameters 9000 rad/s.
For the sake of simplicity, both τ1 and τ2 are selected as integer
Parameters of the inverter are listed in Table 1. Based on these multiples of the sampling period τ0 (50 μs in this paper). Suppose
parameters, the frequency response of S0 (s ) is plotted in Fig. 9. It can be τ1 = a1 τ0 and τ2 = a2 τ0 . The plots of δ1 (ω) with different values of a1 and
those of δ2 (ω) with different values of a2 are shown in Figs. 10 and 11,
respectively.
From Fig. 10, when a1 is taken as 2, 3, 4, 5, 6, and 7, respectively,
the phase plot of δ1 (ω) satisfies the condition described in Lemma 1. In
order to choose a better value of a1, a simulation model of the system in
Fig. 6(b) is built. For a sinusoidal input signal with a frequency of 50 Hz
and an amplitude of 1, several tests are carried out with different values
of a1. According to the tracking performance, the value of a1 is finally set
to 4. Similarly, the simulation model of the system in Fig. 6(c) is also
built, and a2 = 2 is finally determined by the same method.

4.2. Analysis of system stability and control performance

Assuming continuous values for L and C inside the range 0.54 mH to


0.94 mH and 4.6 μF to 8.6 μF, the changes in values of R ̂(ω) , which is
the regeneration spectrum function of the system in Fig. 6(c), is shown

Fig. 8. The design flow of the proposed voltage control strategy. Fig. 10. The plots of δ1 (ω) with different values of a1.

452
W. Ma and S. Ouyang Electrical Power and Energy Systems 111 (2019) 447–458

Fig. 11. The plots of δ2 (ω) with different values of a2 .

Fig. 13. Bode plots of G (s ) and Gd (s ) .

Fig. 14. Schematic diagram of the simulation model.

Fig. 12. System stability analysis.

in Fig. 12.
It can be observed from Fig. 12 that when the parameters of the
inverters vary in a large range, the maximum value of R ̂(ω) is always
less than 0.5, which proves that the designed voltage repetitive control
system has a large stability margin.
The transfer function from vref to vox in Fig. 6(c) and that from iox to
Fig. 15. Circuit topologies of loads used in the simulation.
vox are denoted as G (s ) and Gd (s ) , respectively. Fig. 13 shows the Bode
plots of them.

453
W. Ma and S. Ouyang Electrical Power and Energy Systems 111 (2019) 447–458

Fig. 16. Simulation results of Strategy I.

Fig. 17. Simulation results of Strategy II.

Fig. 18. Microgrid simulation model consisting of two inverters.

Fig. 13(a) shows that the magnitude of G (s ) at the fundamental, 5th, 5. Simulation and experiment
and 7th harmonics is close to 0 dB, and the phase angle is also close to
0, which means that the control system can realize zero-steady-state 5.1. Simulations
error tracking of the voltage reference. And it can be concluded from
Fig. 13(b) that the magnitude of Gd (s ) at the fundamental frequency and As shown in Fig. 14, a PSCAD simulation model is built to verify the
low-order harmonics, e.g., the 5th and 7th, is far less than 0 dB. effectiveness of the designed control strategy. Referring to [15], con-
Therefore, the designed control system has a good ability to reject trast tests with the conventional PI controller (Strategy I) have been
harmonic interference. carried out to demonstrate the outstanding performance of the designed
control strategy (Strategy II) of improving the inverter output voltage

454
W. Ma and S. Ouyang Electrical Power and Energy Systems 111 (2019) 447–458

Fig. 22. THD of the output voltage in experiments.

Fig. 19. Harmonic analysis of the output voltage in simulations.

Fig. 23. The experiment setup.

Table 2
Parameters of the droop control.
Parameters Values

Nominal frequency and voltage E ∗ = 105 V, ω∗ = 313.8 rad/s


Droop coefficient kp = 0.0026, kq = 0.0028
Power filter cut-off frequency ωf 1 = 300 rad/s, ωf 2 = 135 rad/s

Fig. 20. Experiment result with PI controller.

Fig. 19 shows the harmonic analysis results of the output voltage in


each case. It can be observed from Fig. 19 that under the linear load,
both the PI controller and the repetitive controller exhibit good per-
formance of tracking the voltage reference with a low THD of the
output voltage. The performance of the PI controller under highly
nonlinear load is shown in Fig. 16(c), where the harmonic effect of
nonlinear current with THD of 28.32% almost deforms the output
voltage with THD of 3.91%. The result with repetitive controller is
shown in Fig. 17(c). Here, it can be easily observed that the THD in
voltage waveforms is almost negligible (THD = 2.11%) despite of
highly nonlinear load current with THD of 28.64%. Therefore, it can be
concluded that the harmonic voltage is reduced more effectively with
the efforts of the repetitive controller.

5.2. Experiments

To further verify the feasibility of the proposed scheme, three ex-


Fig. 21. Experiment result with repetitive controller.
periment tests have been carried out in a laboratory setup (based on the
TMS320F28335, as shown in Fig. 23) to demonstrate the effectiveness
THD when serving nonlinear loads. In this part, the voltage reference is of the designed control strategy. The experimental conditions are the
fixed at 100 V (the amplitude). same as that of simulations. The waveforms of the output voltage in
Three kinds of loads are used in the tests, and the circuit topologies load case 3 are shown in Fig. 20 and 21, and the THD of the output
of loads are shown in Fig. 15. voltage is presented in Fig. 22.
The simulation results are shown in Figs. 16 and 17. In each wa- Based on the experiment results, the THD of the output voltage with
veform, the red line is for the phase A output voltage, and the black line PI controller and repetitive controller is 2.35% and 4.22% (the voltage
is for the load current. THD needs to be maintained below 5% [20]), respectively. It can be

455
W. Ma and S. Ouyang Electrical Power and Energy Systems 111 (2019) 447–458

Fig. 24. Simulation results of the proposed strategy in parallel operation. (a–g) Are the results under load condition A, and others are the results under load condition
B.

concluded that the designed repetitive controller shows better perfor-


mance of rejecting harmonic interference, which is nearly accordance
with the simulation results. It should be pointed out that the THD of the
output voltage in the experiment is slightly larger than that in simu-
lation due to the influence of some factors such as the digital control
delay and the dead time in the PWM module.

5.3. Parallel operation simulations with repetitive controller

In microgrid, during parallel operation, the voltage loop of the in-


verter must maintain synchronism and keep stability with the re-
maining system. Therefore, the proposed control strategy is tested for
Fig. 25. Circuit topologies of the load used in the parallel operation simulation. parallel operation. A microgrid consisting of two inverters is shown in
Fig. 18, where the parameters of the two inverters are the same (listed

456
W. Ma and S. Ouyang Electrical Power and Energy Systems 111 (2019) 447–458

in Table 1) and the rated power is both set to 2.5 kVA. The standard 2016;169:709–20. https://doi.org/10.1016/j.apenergy.2016.02.053.
feeder impedance in low voltage microgrid is 0.642 + j 0.083 Ω/ km [39]. [4] Somkun S. Unbalanced synchronous reference frame control of singe-phase stand-
alone inverter. Int J Electr Power Energy Syst 2019;107:332–43. https://doi.org/10.
On this basis, the impedance of Feeder 1 is set to 0.1284 + j 0.0166 Ω 1016/j.ijepes.2018.12.011.
(with the length of 200 m) and the same is Feeder 2. [5] Lee T, Cheng P. Design of a new cooperative harmonic filtering strategy for dis-
Initially, only Inverter 1 is connected to loads. At 0.5 s, Inverter 2 is tributed generation interface converters in an islanding network. IEEE Trans Power
Electron 2007;22(5):1919–27. https://doi.org/10.1109/TPEL.2007.904200.
interconnected immediately. As shown in Fig. 25, two kinds of load are [6] Micallef A, Apap M, Spiteri-Staines C, Guerrero JM. Mitigation of harmonics in grid-
used in the simulations. connected and islanded microgrids via virtual admittances and impedances. IEEE
Parameters of the droop control are listed in Table 2. Fig. 24 shows Trans Smart Grid 2017;8(2):651–61. https://doi.org/10.1109/TSG.2015.2497409.
[7] Pereira HA, da Mata GL, Xavier LS, Cupertino AF. Flexible harmonic current com-
the simulation results. The voltage at the PCC is denoted as Upcc . And the pensation strategy applied in single and three-phase photovoltaic inverters. Int J
currents (supplied to loads) of Inverter 1 and Inverter 2 are represented Electr Power Energy Syst 2019;104:358–69. https://doi.org/10.1016/j.ijepes.2018.
as i1 and i2 . The circulating current iH between the two inverters is de- 07.017.
[8] Merritt NR, Chakraborty C, Bajpai P. New voltage control strategies for vsc-based dg
fined as iH = (i1 − i2)/2 .
units in an unbalanced microgrid. IEEE Trans Sustain Energy 2017;8(3):1127–39.
From Fig. 24(g) and (l), it’s obvious that the circulating current https://doi.org/10.1109/TSTE.2017.2657660.
between the two inverters is close to zero in the steady-state whether [9] Gao Y-G, Jiang F-Y, Song J-C, Zheng L-J, Tian F-Y, Geng P-L. A novel dual closed-
the load is linear or nonlinear. The load power is well shared. After loop control scheme based on repetitive control for grid-connected inverters with an
lcl filter. ISA Trans 2018;74:194–208. https://doi.org/10.1016/j.isatra.2018.01.
interconnection to the microgrid, Inverter 2 can keep cooperative op- 029.
eration well with Inverter 1. Due to the sharing of the distorted load [10] Rocabert J, Luna A, Blaabjerg F, Rodríguez P. Control of power converters in ac
current, the THD of Upcc has decreased. Fig. 24(i) shows that the PCC microgrids. IEEE Trans Power Electron 2012;27(11):4734–49. https://doi.org/10.
1109/TPEL.2012.2199334.
voltage is nearly sinusoidal (with a THD nearly 1.3% after Inverter 2 [11] Fukuda S, Imamura R. Application of a sinusoidal internal model to current control
put into operation) despite of the nonlinear load current with THD of of three-phase utility-interface converters. IEEE Trans Industr Electron
28.56%. 2005;52(2):420–6. https://doi.org/10.1109/TIE.2005.843914.
[12] Liserre M, Teodorescu R, Blaabjerg F. Multiple harmonics control for three-phase
grid converter systems with the use of pi-res current controller in a rotating frame.
6. Conclusions IEEE Trans Power Electron 2006;21(3):836–41. https://doi.org/10.1109/TPEL.
2006.875566.
[13] Fukuda S, Yoda T. A novel current-tracking method for active filters based on a
In this paper, a control strategy based on repetitive and state feed- sinusoidal internal model [for pwm invertors]. IEEE Trans Ind Appl
back control is designed for inverters in microgrid to improve the THD 2001;37(3):888–95. https://doi.org/10.1109/28.924772.
of the output voltage. Through theoretical analysis and experimental [14] Pereira LFA, Flores JV, Bonan G, Coutinho DF, da Silva JMG. Multiple resonant
controllers for uninterruptible power supplies-a systematic robust control design
verification, the following conclusions can be drawn.
approach. IEEE Trans Industr Electron 2014;61(3):1528–38. https://doi.org/10.
1109/TIE.2013.2259781.
(1) The regeneration spectrum theory is used to design the voltage [15] Trivedi A, Singh M. Repetitive controller for vsis in droop-based ac-microgrid. IEEE
repetitive control system so that not only the system stabilization Trans Power Electron 2017;32(8):6595–604. https://doi.org/10.1109/TPEL.2016.
2619367.
design can be simplified, but also the absolute stability of the [16] Wang B, Ma G, Xu D, Zhang L, Zhou J. Switching sliding-mode control strategy
system can be estimated. Theoretical analysis shows the designed based on multi-type restrictive condition for voltage control of buck converter in
control system has a large stability margin, and the good control auxiliary energy source. Appl Energy 2018;228:1373–84. https://doi.org/10.1016/
j.apenergy.2018.06.141.
performance of the proposed strategy has been demonstrated by [17] Li Z, Zang C, Zeng P, Yu H, Li S, Bian J. Control of a grid-forming inverter based on
simulations and experiments when supplying nonlinear loads in sliding mode and mixed h2/h∞ control. IEEE Trans Industr Electron
comparison to the conventional PI controller. 2017;64(5):3862–72. https://doi.org/10.1109/TIE.2016.2636798.
[18] Abeywardana DBW, Hredzak B, Agelidis VG. A fixed-frequency sliding mode con-
(2) The adoption of state feedback control can reduce system power troller for a boost-inverter-based battery-supercapacitor hybrid energy storage
loss when compared with the passive damping method. And it in- system. IEEE Trans Power Electron 2017;32(1):668–80. https://doi.org/10.1109/
creases the design flexibility of assigning the poles of the controlled TPEL.2016.2527051.
[19] Baghaee HR, Mirsalim M, Gharehpetan GB, Talebi HA. Nonlinear load sharing and
object at the desired position to suppress the resonance of the LC
voltage compensation of microgrids based on harmonic power-flow calculations
filter and improve the control performance. using radial basis function neural networks. IEEE Syst J 2018;12(3):2749–59.
(3) The presented simulation results of a microgrid have demonstrated https://doi.org/10.1109/JSYST.2016.2645165.
[20] Zhong Q. Harmonic droop controller to reduce the voltage harmonics of inverters.
the effectiveness of the proposed strategy in parallel operation of
IEEE Trans Industr Electron 2013;60(3):936–45. https://doi.org/10.1109/TIE.
inverters. 2012.2189542.
[21] Francis B, Wonham W. The internal model principle for linear multivariable reg-
Declaration of interests ulators. Appl Math Optimiz 1975;2:170–94. https://doi.org/10.1007/BF01447855.
[22] Yang S, Wang P, Tang Y, Zhang L. Explicit phase lead filter design in repetitive
control for voltage harmonic mitigation of vsi-based islanded microgrids. IEEE
The authors declare that they have no known competing financial Trans Industr Electron 2017;64(1):817–26. https://doi.org/10.1109/TIE.2016.
interests or personal relationships that could have appeared to influ- 2570199.
[23] Zheng L, Jiang F, Song J, Gao Y, Tian M. A discrete-time repetitive sliding mode
ence the work reported in this paper. control for voltage source inverters. IEEE J Emerg Sel Top Power Electron
2018;6(3):1553–66. https://doi.org/10.1109/JESTPE.2017.2781701.
Acknowledgement [24] Hornik T, Zhong Q. A current-control strategy for voltage-source inverters in mi-
crogrids based on h∞ and repetitive control. IEEE Trans Power Electron
2011;26(3):943–52. https://doi.org/10.1109/TPEL.2010.2089471.
This work was supported by the Natural Science Foundation of [25] Hornik T, Zhong Q. H∞ repetitive voltage control of gridconnected inverters with a
Guangdong Province, project number 2016A03-0313476. frequency adaptive mechanism. IET Power Electron 2010;3(6):925–35. https://doi.
org/10.1049/iet-pel.2009.0345.
[26] Franklin GF, Powell J, Emami-Naeini A. Feedback control of dynamic systems;
References 1994.
[27] Srinivasan K, Shaw F. Analysis and design of repetitive control systems using the
regeneration spectrum. In: 1990 American control conference; 1990. p. 1150–55.
[1] Hossain MA, Pota HR, Hossain MJ, Blaabjerg F. Evolution of microgrids with con-
https://doi.org/10.23919/ACC.1990.4790923.
verter-interfaced generations: challenges and opportunities. Int J Electr Power
[28] Sun J, Gong J, Chen B, Zha X. Analysis and design of repetitive controller based on
Energy Syst 2019;109:160–86. https://doi.org/10.1016/j.ijepes.2019.01.038.
regeneration spectrum and sensitivity function in active power filter system. IET
[2] Petreus D, Etz R, Patarau T, Cirstea M. An islanded microgrid energy management
Power Electron 2014;7(8):2133–40. https://doi.org/10.1049/iet-pel.2013.0614.
controller validated by using hardware-in-the-loop emulators. Int J Electr Power
[29] Guan Y, Wang Y, Xie Y, Liang Y, Lin A, Wang X. The dual-current control strategy of
Energy Syst 2019;106:346–57. https://doi.org/10.1016/j.ijepes.2018.10.020.
grid-connected inverter with lcl filter. IEEE Trans Power Electron 2018:1. https://
[3] Sreedharan P, Farbes J, Cutter E, Woo C, Wang J. Microgrid and renewable gen-
doi.org/10.1109/TPEL.2018.2869625.
eration integration: University of California, San Diego. Appl Energy
[30] Dahono PA, Bahar YR, Sato Y, Kataoka T. Damping of transient oscillations on the

457
W. Ma and S. Ouyang Electrical Power and Energy Systems 111 (2019) 447–458

output lc filter of pwm inverters by using a virtual resistor. In: 4th IEEE interna- [35] Matas J, Castilla M, Vicuña LGd, Miret J, Vasquez JC. Virtual impedance loop for
tional conference on power electronics and drive systems. IEEE PEDS 2001 – droop-controlled single-phase parallel inverters using a second-order general-in-
Indonesia. Proceedings (Cat. No.01TH8594); 2001. p. 403–7. https://doi.org/10. tegrator scheme. IEEE Trans Power Electron 2010;25(12):2993–3002. https://doi.
1109/PEDS.2001.975347. org/10.1109/TPEL.2010.2082003.
[31] Liserre M, Blaabjerg F, Hansen S. Design and control of an lcl-filter-based three- [36] Tomizuka M, Tsao T, Chew K. Discrete-time domain analysis and synthesis of re-
phase active rectifier. IEEE Trans Ind Appl 2005;41(5):1281–91. https://doi.org/ petitive controllers. In: 1988 American control conference; 1988. p. 860–6. https://
10.1109/TIA.2005.853373. doi.org/10.23919/ACC.1988.4789842.
[32] Vasquez JC, Guerrero JM, Savaghebi M, Eloy-Garcia J, Teodorescu R. Modeling, [37] Hara S, Omata T, Nakano M. Synthesis of repetitive control systems and its appli-
analysis, and design of stationary-reference-frame droop-controlled parallel three- cation. In: 1985 24th IEEE conference on decision and control; 1985. p. 1387–92.
phase voltage source inverters. IEEE Trans Industr Electron 2013;60(4):1271–80. https://doi.org/10.1109/CDC.1985.268739.
https://doi.org/10.1109/TIE.2012.2194951. [38] Tsai M-C, Yao W-S. Design of a plug-in type repetitive controller for periodic inputs.
[33] Guerrero JM, de Vicuna LG, Matas J, Castilla M, Miret J. Output impedance design IEEE Trans Control Syst Technol 2002;10(4):547–55. https://doi.org/10.1109/
of parallel-connected ups inverters with wireless load-sharing control. IEEE Trans TCST.2002.1014674.
Industr Electron 2005;52(4):1126–35. https://doi.org/10.1109/TIE.2005.851634. [39] Li C, Chaudhary SK, Savaghebi M, Vasquez JC, Guerrero JM. Power flow analysis
[34] Koch GG, Maccari LA, Oliveira R, Montagner VF. Robust H∞ state feedback con- for low-voltage ac and dc microgrids considering droop control and virtual im-
trollers based on LMIs applied to grid-connected converters. IEEE Trans Industr pedance. IEEE Trans Smart Grid 2017;8(6):2754–64. https://doi.org/10.1109/TSG.
Electron 2018:1. https://doi.org/10.1109/TIE.2018.2870406. 2016.2537402.

458

You might also like