Building J Renovation-Plans
Building J Renovation-Plans
PROJECT:
RENOVATION OF BUILDING J
A.7.00 GYPSUM BOARD PARTITION SCHEDULE AND JM.1.10 BUILDING J - OVERALL MECHANICAL PLAN -
DETAILS LEVEL 1
A.7.01 FINISH SCHEDULES JM.1.11 BUILDING J - AREA A MECHANICAL PLAN - LEVEL 1
JAD.1.10 BUILDING J - OVERALL DEMO PLAN - LEVEL 1 JM.1.12 BUILDING J - AREA B MECHANICAL PLAN - LEVEL 1
JAD.1.11 BUILDING J - AREA A DEMO PLAN -LEVEL 1 JM.1.20 BUILDING J - OVERALL MECHANICAL PLAN -
JAD.1.12 BUILDING J - AREA B DEMO PLAN - LEVEL 1 LEVEL 2
JAD.1.20 BUILDING J - OVERALL DEMO PLAN - LEVEL 2 JM.1.21 BUILDING J - AREA A MECHANICAL PLAN - LEVEL 2
JAD.1.21 BUILDING J - AREA A - DEMO PLAN - LEVEL 2 JM.1.22 BUILDING J - AREA B MECHANICAL PLAN - LEVEL 2
JA.1.10 BUILDING J - OVERALL FLOOR PLAN- LEVEL 1 JM.1.30 BUILDING J - OVERALL ROOF PLAN
JA.1.11 BUILDING J - AREA A FLOOR PLAN - LEVEL 1 JM.3.01 ENLARGED MECH ROOM PLAN AND SECTIONS
2015 INTERNATIONAL MECHANICAL CODE AT A MINIMUM, SPECIFIC ACM MAY INCLUDE THE FOLLOWING. REFER TO RELEVANT SCOPE IN TEXAS REGISTERED ENGINEERING FIRM F-2966
DEMOLITION DRAWINGS FOR ADDITIONAL NOTES:
2017 NATIONAL ELECTRICAL CODE 777 Main Street, Suite B-101
BUILDING J:
2012 TEXAS ACCESSIBILITY STANDARDS - WATERPROOFING BENEATH MORTAR BED IN ALL RESTROOMS/LOCKER ROOM Fort Worth, TX 76102
- WATERPROOFING BEHIND BRICK ON EXTERIOR WALLS
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN 817-735-6000
IN THE EVENT ASSUMED UNABATED HAZARDOUS MATERIALS ARE SUSPECTED, UNCOVERED,
OR ENCOUNTERED, STOP WORK IMMEDIATELY. THESE MATERIALS MUST BE TREATED AS ACM
UNTIL SAMPLED AND REBUTTED. NOTIFY THE OWNER'S REPRESENTATIVE FOR FURTHER
DIRECTION.
ARCHITECT OF RECORD
ENGINEER OF RECORD
4/9/2020 15:04:59
R
Texas
Department
of Transportation
I-20
F WY THIS DRAWING CREATED
FOR PRODUCTION ON
22"x34" SHEET SIZE.
DO NOT SCALE PRINTS.
SW L
OOP
820
TEXAS REGISTERED ENGINEERING
FIRM F-2966
777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
BUILDING J 1
JA.1.10
SD
(N )
DW
REF
.
DN
DN
TARRANT COUNTY
DN
DN
DW
REF .
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
DN
DN
MC CART. AVE
J ISSUED: 04-09-2020
EDGECLIFF RD. DRAWN BY: NR
REVISIONS:
L
U
NORTH
N
02470420015
NOT TO SCALE
SHEET NO:
A. BUILDING AND DESIGN CODES: A. THE OWNER WILL EMPLOY THE SERVICES OF ONE OR MORE SPECIAL INSPECTORS TO PROVIDE SPECIAL INSPECTIONS
DURING CONSTRUCTION FOR THE ITEMS IN THE SPECIAL INSPECTION TABLE BELOW IN ACCORDANCE WITH THE A. DESIGN, DETAIL AND ERECT STRUCTURAL STEEL ELEMENTS IN ACCORDANCE WITH THE LATEST VERSION OF THE FOLLOWING:
1. INTERNATIONAL BUILDING CODE 2015 WITH APPLICABLE MODIFICATIONS AND ORDINANCES. INTERNATIONAL BUILDING CODE, 2015 EDITION. NOT APPLICABLE TO SLABS ON GROUND OR SITE CONCRETE FULLY Texas
SUPPORTED ON EARTH. 1. AISC SPECIFICATION FOR THE DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS.
Department
2. ASCE 7-10 MINIMUM DESIGN LOADS BUILDING AND OTHER STRUCTURES. of Transportation
B. THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO SHALL DEMONSTRATE COMPETENCE, TO THE SATISFACTION 2. AISC MANUAL OF STEEL CONSTRUCTION, ALLOWABLE STRESS DESIGN.
3. FACTORY MUTUAL PUBLICATION 1-2 FOR EARTHQUAKE LOADS AND 1-7, 1-28 AND 1-28S FOR WIND LOADS. OF THE BUILDING OFFICIAL FOR INSPECTION OF THE PARTICULAR TYPE OF CONSTRUCTION OR OPERATION REQUIRING
SPECIAL INSPECTION. 3. AWS STRUCTURAL WELDING CODE, D1.1.
4. AISC MANUAL OF STEEL CONSTRUCTION, 14TH EDITION.
C. DUTIES AND RESPONSIBILITIES OF THE SPECIAL INSPECTOR: B. PROVIDE STRUCTURAL STEEL OF THE FOLLOWING ASTM DESIGNATIONS UNLESS NOTED OTHERWISE: THIS DRAWING CREATED
FOR PRODUCTION ON
5. ACI 318 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE, THE LATEST EDITION. 22"x34" SHEET SIZE.
1. THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK ASSIGNED FOR CONFORMANCE WITH THE APPROVED DESIGN 1. CHANNELS DO NOT SCALE PRINTS.
6. ACI 530 BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES, THE LATEST EDITION. DRAWINGS AND SPECIFICATIONS. THE INSPECTOR MAY NOT ALTER, MODIFY, ENLARGE OR WAIVE ANY OF THE
REQUIREMENTS OF THE DOCUMENTS. 2. COLD FORMED STEEL TUBING (HSS)
B. DESIGN LOADS:
2. THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE BUILDING OFFICIAL, THE PROFESSIONAL OF 3. BASE PLATES, MISCELLANEOUS STEEL PLATES, AND RODS
1. LIVE LOADS: UNIFORM LOAD RECORD, AND THE CONTRACTOR. ALL DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
a. FLAT ROOF 20 PSF CONTRACTOR FOR CORRECTION. 4. HIGH STRENGTH BOLTS
TEXAS REGISTERED ENGINEERING
b. PITCHED ROOF 20 PSF FIRM F-2966
3. THE SPECIAL INSPECTOR SHALL SUBMIT A FINAL SIGNED REPORT STATING WHETHER THE WORK REQUIRING SPECIAL 5. HARDENED STEEL WASHERS 777 MAIN ST. STE B-101
LIVE LOAD REDUCTION ON SUPPORTING ELEMENTS IN ACCORDANCE WITH 2015 IBC. INSPECTION WAS, TO THE BEST OF THE INSPECTOR'S KNOWLEDGE, IN CONFORMANCE WITH THE APPROVED PLANS FORT WORTH, TEXAS 76102
AND SPECIFICATIONS AND THE APPLICABLE WORKMANSHIP PROVISIONS OF THE CODE. C. WELD MINIMUM SIZE AND STRENGTH
LOADING FOR MECHANICAL AND ELECTRICAL ROOMS ARE BASED ON THE WEIGHTS OF ASSUMED EQUIPMENT, AS INDICATED
ON THE MECHANICAL DRAWINGS (INCLUDING THE WEIGHT OF CONCRETE PADS WHERE INDICATED ON THE MECHANICAL E. INSPECTION OF FABRICATORS IS NOT REQUIRED WHERE THE WORK IS DONE ON THE PREMISES OF A FABRICATOR 1. PROVIDE MINIMUM SIZE OF FILLET WELDS AS SPECIFIED IN TABLE J2.4 OF THE AISC MANUAL.
DRAWINGS). ANY CHANGES IN TYPE, SIZE, LOCATION, OR NUMBER OF PIECES OF EQUIPMENT SHOULD BE REPORTED TO THE REGISTERED AND APPROVED BY THE BUILDING OFFICIAL TO PERFORM SUCH WORK WITHOUT SPECIAL INSPECTION
ARCHITECT FOR VERIFICATION OF THE ADEQUACY OF SUPPORTING MEMBERS PRIOR TO PLACEMENT OF EQUIPMENT. PROVIDED AN AISC CERTIFICATE OF COMPLIANCE. THE APPROVED FABRICATOR SHALL SUBMIT AN AISC CERTIFICATE OF 2. DEVELOP THE FULL TENSILE STRENGTH OF THE MEMBER ELEMENT JOINED, ON ALL SHOP AND FIELD WELDS,
COMPLIANCE THAT THE WORK WAS PERFORMED IN ACCORDANCE WITH THE APPROVED PLANS AND SPECIFICATIONS TO UNLESS NOTED OTHERWISE ON THE DRAWINGS.
2. DEAD LOADS: THE BUILDING OFFICIAL AND TO THE ARCHITECT OF RECORD.
3. WHERE CONNECTIONS ARE NOTED ON DRAWINGS AS MOMENT CONNECTIONS, PROVIDE WELDS TO DEVELOP FULL
DESIGN DEAD LOADS INCLUDE THE WEIGHT OF STRUCTURAL COMPONENTS AND PERMANENT FIXTURES. FLEXURAL CAPACITY OF THE LESSER MEMBER.
3. WIND LOADS: 4. PROVIDE ELECTRODES FOR FIELD OR SHOP WELDING THAT CONFORM TO AWS D1.1 CLASS E70.
a. ULTIMATE WIND SPEED (3 SECOND GUST) - 115 MPH SPECIAL INSPECTION FREQUENCY D. PROVIDE MINIMUM OF TWO BOLTS PER CONNECTION. MINIMUM BOLT DIAMETER TO BE 3/4-INCH.
b. IMPORTANCE FACTOR - lw = 1.0
STEEL:
c. EXPOSURE - B
d. COMPONENT AND CLADDING DESIGN PRESSURE - 20.2 PSF 1. HIGH-STRENGTH BOLTING (A325 AND A490 BOLTS) E. PROVIDE BOLTS, NUTS AND WASHERS THAT ARE HOT DIP GALVANIZED ACCORDING TO ASTM A 153, CLASS C WHEN USED TO
e. DESIGN UPLIFT - 12 PSF (NET) CONNECT STEEL ELEMENTS THAT ARE HOT DIP GALVANIZED AFTER FABRICATION.
A. WHILE THE WORK IS IN PROGRESS, DETERMINE THAT THE PERIODIC
REQUIREMENTS FOR BOLTS, NUTS, WASHERS, AND PAINT: BOLTED
4. SEISMIC LOADS F. STEEL FABRICATION
PARTS: AND INSTALLATION AND TIGHTENING ARE IN ACCORDANCE
a. SEISMIC OCCUPANCY CATEGORY - II WITH APPROVED NATIONALLY RECOGNIZED STANDARDS
b. SPECTRAL RESPONSE COEFF. - Sds = 0.094, Sd1 = 0.078 1. FABRICATE AND ASSEMBLE STRUCTURAL MEMBERS/ASSEMBLIES IN SHOP TO GREATEST EXTENT POSSIBLE. 04/09/2020
c. SITE CLASS - D B. MONITOR THE INSTALLATION OF BOLTS TO DETERMINE THAT ALL PILES CONTINUOUS
d. DESIGN CATEGORY - B OF CONNECTED MATERIALS HAVE BEEN DRAWN TOGETHER AND THAT 2. SPLICING OF STRUCTURAL STEEL MEMBERS IS PROHIBITED WITHOUT PRIOR APPROVAL BY THE A/E.
e. BASIC FORCE RESISTING SYSTEM - STEEL ORDINARY CONCENTRICALLY BRACED FRAMES THE SELECTED PROCEDURE IS PROPERLY USED TO TIGHTEN ALL BOLTS.
f. RESPONSE MODIFICATION FACTOR - R = 3.25 3. BE RESPONSIBLE FOR ALL ERRORS OF DETAILING ON THE SHOP DRAWINGS, ERRORS IN FABRICATION, AND THE
g. DESIGN BASE SHEAR - V = 0.012W STRUCTURAL WELDING: CORRECT FITTING OF STRUCTURAL STEEL MEMBERS.
h. ANALYSIS PROCEDURE - EQUIVALENT LATERAL FORCE PROCEDURE 1. FOR WELDS WHERE THE PROVIDED MATERIALS, QUALIFICATIONS OF
G. CONFORM TO THE AISC CODE OF STANDARD PRACTICE, FOR ERECTION TOLERANCES. FIELD MODIFICATION TO STRUCTURAL
WELDING PROCEDURES AND WELDERS ARE VERIFIED IN ADVANCE: AND A
5. SNOW LOADS: STEEL IS PROHIBITED WITHOUT PRIOR APPROVAL BY THE A/E.
VISUAL INSPECTION OF ALL WELDS IS MADE PRIOR TO COMPLETION
a. GROUND SNOW LOAD - Pg = 5 PSF
b. IMPORTANCE I - 1.00 H. CLEAN STEEL OF RUST, LOOSE MILL SCALE AND OTHER FOREIGN MATERIALS WHERE REQUIRED FOR FABRICATION, FITTING
A. SINGLE PASS FILLET WELDS NOT EXCEEDING 5/16 INCH IN SIZE PERIODIC
c. THERMAL FACTOR Ct - 1.0 UP, OR WELDING.
d. EXPOSURE Ce - 1.1 B. WELDED SHEET STEEL FOR COLD-FORMED STEEL FRAMING PERIODIC
U:\BLDG\TxDOT Fort Worth District\700 Working Documents\730 Models\730.03 Structural\CAD\WFXO4202 S101 S102.dwg
e. RAIN ON SNOW - 5 PSF MEMBERS SUCH AS STUDS AND JOISTS. I. DO NOT CUT STRUCTURAL STEEL MEMBERS FOR THE WORK OF OTHER TRADES WITHOUT PRIOR REVIEW AND APPROVAL OF
CONCRETE FOUNDATIONS: (NOT APPLICABLE TO SLABS ON GROUND) THE A/E.
BUILDING J RENOVATIONS
2. VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO BEGINNING SHOP DRAWINGS OR FABRICATING MATERIALS.
NOTIFY A/E OF DISCREPANCIES BEFORE PROCEEDING WITH ANY PHASE WORK. SUBMIT THE APPROPRIATE PLANS AND K. MILL STEEL COLUMN ENDS TO FIT FLUSH WITH BASE PLATE, CAP PLATE AND END PLATES. FIELD ASSEMBLY OF THESE STEEL
ELEMENTS TO THE COLUMNS IS PROHIBITED.
3. VERIFY THE LOCATION OF CHASES, INSERTS, OPENINGS, SLEEVES, FINISHES, DEPRESSIONS, PADS, AND WALL OPENINGS. L. PROVIDE TEMPORARY SHORING OR BRACING DURING CONSTRUCTION PHASE, PRIOR TO COMPLETING CONNECTIONS.
4. DO NOT SCALE DRAWINGS FOR THE PURPOSE OF ESTABLISHING DIMENSIONS. M. ALL STEEL SHALL BE PAINTED WITH FABRICATOR'S STANDARD PRIMER.
TARRANT COUNTY
5. DETAILS LABELED "TYPICAL DETAILS" ON DRAWINGS APPLY TO SITUATIONS OCCURRING ON THE PROJECT THAT ARE THE
SAME OR SIMILAR TO THOSE SPECIFICALLY DETAILED. SUCH DETAILS APPLY WHETHER OR NOT DETAILS ARE REFERENCED
EPOXY ANCHORED DOWELS AND BOLTS
AT EACH LOCATION. NOTIFY ENGINEER OF CONFLICTS REGARDING APPLICABILITY OF "TYPICAL DETAILS".
A. EPOXY ANCHORS USED FOR FIELD REPAIRS OR SUBSTITUTIONS SHALL BE MANUFACTURED BY HILTI OR SIMPSON STRONG-TIE.
6. DO NOT LOAD THE SLAB ON GRADE OR SUPPORTED SLAB WITH ERECTION CRANES OR ERECTION EQUIPMENT. THE SLABS
B. INSTALL BOLTS AND DOWELS IN ACCORDANCE WITH CURRENT ICC-ES REPORT FOR THE BOLT, AND RECOMMENDATIONS OF
HAVE NOT BEEN DESIGNED FOR CRANE LOADS AND WILL REQUIRE AN INCREASE IN THICKNESS AND/OR REINFORCEMENT.
THE MANUFACTURER. FOLLOW MANUFACTURER'S INSTRUCTIONS EXPLICITLY.
OBTAIN A/E APPROVAL ON PROPOSED CRANE SUPPORT PLAN FOR SLABS PRIOR TO COMMENCING WORK.
C. INSTALL BOLTS AND DOWELS PERPENDICULAR TO THE FACE OF CONCRETE, UNLESS OTHERWISE INDICATED IN THE
7. DO NOT STORE OR STACK CONSTRUCTION MATERIALS ON POURED OR ERECTED FLOORS/ROOFS IN EXCESS OF 80 PERCENT
DRAWINGS.
OF LIVE LOAD. GENERAL CONTRACTOR WILL ENSURE THAT ALL SUB-CONTRACTORS ARE INFORMED OF LOADING
RESTRICTIONS. AVOID IMPACT WHEN PLACING MATERIALS ON POURED OR ERECTED FLOORS OR ROOF. D. DIAMETER OF DRILLED HOLES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. DO NOT REDIRECT
HOLES ALONG LENGTH OF BOLT.
8. THE CONTRACT STRUCTURAL DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THE CONTRACTOR IS RESPONSIBLE FOR
THE MEANS AND METHODS OF CONSTRUCTION. PROVIDE ALL MEASURES REQUIRED TO PROTECT THE STRUCTURE, E. DRILL HOLES IN CONTINUOUS OPERATION. BLOW DUST FROM THE HOLE USING COMPRESSED AIR.
WORKMEN, AND OTHER PERSONS DURING CONSTRUCTION; INCLUDING BRACING, SHORING FOR CONSTRUCTION EQUIPMENT,
SHORING FOR THE BUILDING, FORMS AND SCAFFOLDING, SHORING OF RETAINING WALLS AND OTHER TEMPORARY F. FILL ABANDONED HOLES WITH EPOXY GROUT.
SUPPORTS AS REQUIRED.
G. INSTALLATION OF EPOXY ANCHORED DOWELS AND BOLTS SHALL BE CONTINUOUSLY INSPECTED BY THE TESTING
9. PRINCIPAL OPENINGS THROUGH THE FRAMING ARE SHOWN ON DRAWINGS. EXAMINE THE ARCHITECTURAL AND MECHANICAL LABORATORY TO ENSURE THAT HOLES ARE OF THE PROPER DIAMETER AND LENGTH, ARE PROPERLY CLEANED, AND THAT
DRAWINGS FOR THE REQUIRED OPENINGS AND PROVIDE FOR REQUIRED OPENINGS WHETHER SHOWN ON THE STRUCTURAL BOLTS ARE INSTALLED CORRECTLY.
DRAWINGS OR NOT, VERIFY SIZE AND LOCATION OF OPENINGS WITH THE MECHANICAL CONTRACTOR. DEVIATIONS FROM
THE OPENINGS SHOWN ON THE STRUCTURAL DRAWINGS MUST BE APPROVED PRIOR TO IMPLEMENTING THE CHANGES.
10. THE STRUCTURAL ENGINEER'S REVIEW OF THE SHOP DRAWINGS SHALL NOT RELIEVE THE CONTRACTOR FROM
RESPONSIBILITY FOR DEVIATIONS FROM THE CONTRACT DOCUMENTS, NOR FROM ANY ERRORS IN THE SHOP DRAWINGS.
ISSUED: 04-09-2020
REVISIONS:
10/1/2018 4:31:54 PM
PROJECT NO.
02470420015
SHEET NO:
GENERAL NOTES
JS.1.01
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
12 11 10 9 8 7 6 5 4 3 2 1 R
275'-9"
Texas
1'-0" Department
34'-5" 20'-4" 20'-4" 20'-4" 20'-4" 25'-0" 25'-0" 25'-0" 25'-0" 25'-0" 16'-0" 18'-0" of Transportation
4'-1021" 15'-3" 4'-1021" 4'-10 21" 15'-3" 4'-1021" 4'-1021" 15'-3" 4'-1021"
THIS DRAWING CREATED
FOR PRODUCTION ON
2
JS.1.02
6"
TEXAS REGISTERED ENGINEERING
FIRM F-2966
A 777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
20'-0"
EXISTING COLUMNS
PLAN NOTES TO REMAIN, TYP.
1. REFER TO SHEET S.101 FOR GENERAL NOTES & SHEETS S.102 FOR
DETAILS NEW HSS4x4x1/4 ROLL-UP
DOOR COLUMNS, TYP.
2. GC SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS
PRIOR TO CONSTRUCTION. IF THERE ARE ANY DISCREPANCIES BETWEEN
THE EXISTING FIELD CONDITIONS AND THE STRUCTURAL CONSTRUCTION B
DOCUMENTS, THE GC SHALL NOTIFY THE STRUCTURAL E.O.R
IMMEDIATELY PRIOR TO CONSTRUCTION.
20'-0"
STRUCTURAL INTEGRITY OF THE EXISTING BUILDING DURING
CONSTRUCTION.
NORTH 04/09/2020
T/ EXIST STEEL
BUILDING J RENOVATIONS
TO REMAIN TYP. TYP. LOCATE EXISTING REBAR PRIOR TO INSTALLING THE
HSS6x6x1/2 BEAM 5 HSS6x6x1/2 BEAM 4 HSS6x6x1/2 BEAM EXIST. TRUSS NEW BASE PLATE.
2. THE GC SHALL MAINTAIN THE INTEGRITY OF THE
B/ STEEL
HSS COLUMN
EL = 14'-2"
PL21"x10"x0'-10"
TARRANT COUNTY
ATTACHED w/ (4) 5 8" DIA.
EQ. 15'-0" CLEAR OPENING EQ. EQ. 15'-0" CLEAR OPENING EQ. EQ. 15'-0" CLEAR OPENING EQ. HILTI HAS (7" SPACING E.W.)
AND HILTI HIT-HY 200 EPOXY EXIST. GRADE BEAM/SLAB
14'-2" CLEAR OPENING
HSS4x4x1/2 NEW
COLUMN, TYP.
T/ EXIST SLAB
EL = 0'-0"
TO REMAIN, TYP.
PROJECT NO.
0 1' 2' 4' 0 1' 2' 4' 5 DETAIL 0 1' 2' 4' 4 DETAIL
0 1' 2' 4'
SHEET NO:
4"
EXIST CMU WALL EXTENTS OF OPENING
TO BE REMOVED
EXISTING BRICK: REMOVE, TYP.
3/16
RAMP DN
B TYP
3/16
REINSTALL AND NOTCH AS
PL 3/8"x0'-5"xCONT
TEXAS REGISTERED ENGINEERING
FIRM F-2966
REQ'D FOR INSTALLATION
4"
B/ STEEL 777 MAIN ST. STE B-101
2 PL 3/8"x0'-5"xCONT OF NEW LINTEL.
JS.1.03 L2x2x3/16x0'-3" @ 32" O.C. ATTACHED FORT WORTH, TEXAS 76102
18'-0" MAX.
1'-0" +/-
TO CMU w/ (1) 58" DIA. HAS AND HILTI
WT12x51.5
FULLY GROUTED CELL WT12x51.5 CONT.
L8x4x1
HIT-HY 70 EPOXY, TYP. TYP.
RE: NOTE '1' 4/JS.1.03 3/16
TYP T/ EXIST. OPNG.
3/16 2-12
HSS COL BEYOND, RE: PLAN EDGE OF CMU
WALL OPENING L2x2x3/16x0'-3" EF BEYOND @ 32" O.C.
RE: 6/JS.1.03 FOR BASE CONNX. EXIST STEEL LINTEL AND CONT.
RE: 7/JS.1.02 FOR TOP CONNX. 3 CUT INSIDE FLANGE
NOTES: PLATE TO BE REMOVED
ATTACHED TO CMU w/ (1) 58" DIA. HAS
AND HILTI HIT-HY 70 EPOXY, TYP.
JS.1.03
C 1. ALL STEEL SHALL BE GALVANIZED. EXIST WALL BEYOND
HSS4x4x41 COL. TO BE REMOVED
2 PARTIAL CMU WALL OPENING ELEVATION 0 1' 2' 4' 3 CMU WALL OPENING SECTION 0 1' 2' 4'
H
TYP.
IT
B 1. GC SHALL SCAN THE EXISTING SLAB/GRADE BEAM TO
.W
UR 1/4
D
IT C
OR
L4x4x3/8 LOCATE EXISTING REBAR PRIOR TO INSTALLING THE
UN
CO
SCALE: 3/32" = 1'-0" NEW BASE PLATE.
2. THE GC SHALL MAINTAIN THE INTEGRITY OF THE
EXISTING STRUCTURE DURING CONSTRUCTION.
U:\BLDG\TxDOT Fort Worth District\700 Working Documents\730 Models\730.03 Structural\CAD\WFXO4202 S101 S102.dwg
NOTCH HORIZ
LEG OF ANGLE 1
TARRANT COUNTY
CMU CELLS. CONTRACTOR SHALL VERIFY LOCATIONS OF FULLY GROUTED CELLS
AND ADJUST THE LOCATION OF OPENINGS ACCORDINGLY. NOTE:
1. ANGLES SHALL BE LOCATED UNDER EQUIPMENT PER MANUFACTURER'S
2. PROPERLY SUPPORT AND PROTECT MASONRY INDICATED TO REMAIN. RECOMMENDATION. REFERENCE MECHANICAL DRAWINGS AND
MANUFACTURER DRAWINGS FOR OPENING AND CURB DIMENSIONS.
2. SHIM ANGLES TIGHT TO DECK AND FASTEN DECK TO ANGLES WITH #10
3. LOCATE AND DRILL THE THRU BOLT HOLES ON THE MASONRY WALL. INSTALL TEK SCREWS @ 12" O.C. PRIOR TO CUTTING DECK.
THE THRU BOLTS WITH HILTI HIT HY 70 EPOXY SYSTEM. WAIT UNTIL THRU BOLTS
AND HILTI EPOXY SYSTEM FULLY CURES.
5. SAW CUT THE WALL HORIZONTALLY ABOVE PROPOSED NEW OPENING. THE FIRST
SCALE: 3/4" = 1'-0" SCALE: 3/4" = 1'-0"
SAW CUT SHALL ONLY BE DEEP ENOUGH TO ALL0W FOR INSTALLATION OF
THE FIRST OF TWO ANGLES. INSTALL FIRST ANGLE INTO CUT PRIOR TO SAW
CUTTING THE HORIZONTAL JOINT ON THE OPPOSITE SIDE OF THE WALL. INSTALL
SECOND ANGLE INTO SECOND CUT AND TIGHTEN ALL THRU BOLTS. REF. MECH. FOR EMBEDDED ELECTRICAL
AND GROUNDING REQUIREMENTS
2'-6"
6. AFTER COMPLETE INSTALLATION OF BOTH ANGLES, CONTRACTOR MAY BEGIN
REMOVAL OF REMAINING EXISTING MASONRY WALL BELOW NEW STEEL LINTEL
3
(I.E., DOUBLE ANGLES). INSTALL 8" PLATE BELOW.
7. AFTER COMPLETE INSTALLATION OF NEW LINTEL AND ITS SUPPORTING #3 DWLS @ 12" O.C.
COMPONENTS, AND THE REMOVAL OF EXISTING MASONRY; LOWER THE TEMPORARY SLOPE 1:12 MAXIMUM TO MATCH SLAB REINF.
RE: ARCH PROVIDE 1/2 TIE
SHORING AND BRACING GRADUALLY TO VERIFY THAT THE ASSEMBLY IS PROPERLY ATTACHED W/ HILTI
SPACING ABOVE GRADE
HIT HY 200 EPOXY
SUPPORTING THE REMAINING EXISTING MASONRY ABOVE THE NEWLY CREATED #4 DWL x 1'-6"
#3 x @ 12" O.C. E.W. (MIN. EMBED = 6")
@ 12" O.C. (3 MIN)
OPENING.
ATTACHED w/ HILTI HIT-HY 200
EPOXY (MIN. EMBED = 4") #3 x @ 12" O.C. E.W.
8'-0" MIN.
T/ SLAB
RE: PLAN 24" Ø PIER
T/ SLAB REF. W 6-#6 VERTICAL W/
#3 TIES @ 18" O.C. (LAP 18") ISSUED: 04-09-2020
PROJECT NO.
TYPICAL CURB RAMP DETAIL 8 TYPICAL LIGHTPOLE FOUNDATION DETAIL
02470420015
7 0 1' 2' 4' 0 1' 2' 4' SHEET NO:
Texas
12 Department
of Transportation
UP
4'-3" 4'-4" 4'-3"
#4 X 2'-6"X2'-6" #4 @ 12" OC EA
5'-4" 11'-8" 5'-4" @ 12" OC, TYP WAY AT TOP, THIS DRAWING CREATED
FOR PRODUCTION ON
AT CORNERS TYP SLAB REINF 22"x34" SHEET SIZE.
6"
RE: PLAN, TYP EXISTING
6 RAMP
4'-3"
JS.1.04
CONTRUCTION
TEXAS REGISTERED ENGINEERING
4'-4"
6"
TYP FILLER AND
FORT WORTH, TEXAS 76102
4'-3"
5 SEALANT
JS.1.04
6"
T/SLAB EL = 0'-0" EXISTING ASPHALT
PAVING, TYP
HORIZONTAL AND
C
BELOW LOWEST
1'-0" MIN
SHALL BE
10"
TYP
04/09/2020
NORTH
#4 @ 12" OC EXISTING
1'-0"
MIN
1
1'-0"
1 DOCK
REPLACE SLAB
AND CONNECT
6" (2)#5 TO EXISTING
TYP 1'-6" PER 3/JS.1.04
EXISTING VAPOR RETARDER RECOMPACT SUBGRADE
WHERE PRESENT TO REMAIN PRIOR TO REPLACING SLAB 10" 1'-0"
CAPILLARY WATER BARRIER LAP VAPOR RETARDER 6"
TO MATCH EXISTING w/ EXIST VAPOR RETARDER
WHERE PRESENT AT ALL INTERFACES w/
EXIST SLAB
NOTE:
ROUGHEN SURFACE OF EXISTING CONCRETE
TO 1/4" AMPLITUDE AND APPLY BONDING AGENT
PRIOR TO PLACEMENT OF NEW CONCRETE.
3 TYPICAL SECTION 4 TYPICAL SECTION AT STAIR 5 SECTION 0 1' 2' 4' 6 SECTION
0 1' 2' 4'
ISSUED: 04-09-2020
SCALE: 3/4" = 1'-0" SCALE: 3/4" = 1'-0"
DRAWN BY: JDE
REVISIONS:
10/1/2018 4:31:54 PM
PROJECT NO.
02470420015
SHEET NO:
ALUM ALUMINUM HORIZ HORIZONTAL OPQ OPAQUE 777 MAIN ST. STE B-101
ANOD ANODIZE HT HEIGHT OWSJ OPEN WEB STEEL JOIST FORT WORTH, TEXAS 76102
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
HYDR HYDRAULIC OPR
ORD
ORIG
OPERABLE
OVERFLOW ROOF DRAIN
ORIGINAL
JA.1.01 EXISTING PARTITION TO REMAIN
AR AS REQUIRED F ---------------------
ARCH ARCHITECT FA FIRE ALARM
ASC ABOVE SUSPENDED CEILING FAAP FIRE ALARM ANNUNCIATOR PANEL P -------------------- MATERIALS EXISTING PARTITION TO BE REMOVED
ASSY ASSEMBLY FAS BD FASCIA BOARD P PAINT
ATC ACOUSTICAL TILE CEILING FC BRK FACE BRICK PAR PARAPET
PAT PATTERN CONCRETE/ PRECAST
AVG AVERAGE FCO FLOOR CLEANOUT
CONCRETE GYPSUM BOARD
EXISTING TO BE REMOVED
AW ARCHITECTURAL WOODWORK FD FLOOR DRAIN PB PULL BOX
AWT ACOUSTICAL WALL TREATMENT FDTN FOUNDATION PBD PARTICLEBOARD
FE FIRE EXTINGUISHER PCC PRECAST CONCRETE SOIL EXTERIOR GYPSUM
FEC FIRE EXTINGUISHER CABINET PCF POUNDS PER CUBIC FOOT SHEATHING
B ---------------------
B LABEL CLASS B DOOR FED FEDERAL PCT PERCENT REMOVE EXIST. DOOR AND DOOR
FF FINISH FACE PERF PERFORATED SAND, EIFS FINISH COAT, FRAME SYSTEM
BALC BALCONY EXTERIOR CEMENT
FF EL FINISH FLOOR ELEVATION PERIM PERIMETER OR CEMENT PLASTER
BB BASEBOARD BOARD
BC BOOKCASE FF INSUL FOIL BACKED INSULATION PH PHASE
FGL FIBERGLASS PIL PILASTER BRICK
BD BOARD
BDRY BOUNDARY FH FIRE HOSE PL PROPERTY LINE AREA OF EXISTING MASONRY WALL TO BE REMOVED;
FHP FULL HEIGHT PARTITION PL GL PLATE GLASS COATED GLASS MAT
BFF BELOW FINISH FLOOR
CMU WATER RESISTANT REFER TO STRUCTURAL FOR NEW LINTELS
BHMA BUILDER'S HARDWARE MANUFACTURER'S FIN FINISH PLAM PLASTIC LAMINATE
FIN BS FINISH BOTH SIDES PLAS PLASTER GYP BD
ASSOCIATION
BLDG BUILDING FIN FLR FINISH FLOOR PLBG PLUMBING
BLKG BLOCKING FIN GR FINISH GRADE PLG PILING STONE APPROX. LOCATION AND SIZE OF EXIST. CONC. FLOOR
PLYWD PLYWOOD PLYWOOD
BLT IN BUILT-IN FIXT FIXTURE SLAB TO BE REMOVED FOR NEW WORK. RE: MEP AND
BN BULLNOSE FLDG FOLDING PNL PANEL STRUCTURAL FOR BACK-FILL AND PATCHING
BOS BOTTOM OF STEEL FLEX FLEXIBLE PP PL PUSH/PULL PLATE FIBERGLASS BATT
FLG FLOORING PR PAIR INSULATION COVER BOARD
BOT BOTTOM
BP BUILDING PAPER FLMT FLUSH MOUNT PRCST PRECAST
BRKT BRACKET FLR FLOOR PRKG PARKING FIRE RATED WALL SYMBOLS:
PS CONC PRESTRESSED CONCRETE FIBERGLASS SEMI RIGID
BSMT BASEMENT FM FACTORY MUTUAL
INSULATION 1 HR FIRE
BTWN BETWEEN FOC FACE OF CONCRETE PSF POUNDS PER SQUARE FOOT
BUR BUILT-UP ROOFING FOM FACE OF MASONRY PSI POUNDS PER SQUARE INCH 2 HR FIRE
PT PRESSURE TREATED MINERAL WOOL SEMI
FR FIRE RESISTANT
PTD PAPER TOWEL DISPENSER RIGID INSULATION 3 HR FIRE
C --------------------- FRG FIBER REINFORCED GYPSUM
C CONC CAST CONCRETE FRMG FRAMING PTDR PAPER TOWEL DISPENSER AND RECEPTACLE
EXPANDED 4 HR FIRE
C LABEL CLASS C DOOR FRP FIBERGLASS REINFORCED PLASTIC PTN PARTITION
POLYSTYRENE RIGID
CAB CABINET FRTW FIRE RETARDANT TREATED WOOD PWR POWER S 1 HR FIRE/SMOKE WALL
INSULATION
CATW CATWALK FS FEDERAL SPECIFICATION
FSTNR FASTENER Q -------------------- EXTRUDED S 2 HR FIRE/SMOKE WALL
CAV CAVITY POLYSTYRENE RIGID
CBB CEMENTITIOUS (BACKER) BOARD FT FEET QT QUARRY TILE S 3 HR FIRE/SMOKE WALL
BUILDING J RENOVATIONS
INSTALLED GB GRAB BAR RC REINFORCED CONCRETE
CFE CONTRACTOR FURNISHED EQUIPMENT GFCI GOVERNMENT FURNISHED CONTRACTOR RCP REFLECTED CEILING PLAN
Ref
CFMF COLD-FORMED METAL FRAMING INSTALLED BY GOVERNMENT REC RECESSED PLATE NUMBER WHERE 101 ROOM NAME/NUMBER
CFS CUBIC FEET PER SECOND GFRG GLASS-FIBER-REINFORCED GYPSUM REF REFERENCE SECTION/DETAIL IS
CG CORNER GUARD GLZ GLAZING REM REMOVABLE 1 A101 1
REP REPAIR
DRAWN
CI CAST IRON GR FL GROUND FLOOR 01 WINDOW TYPE
Ref
TARRANT COUNTY
CIP CAST-IN-PLACE GUT GUTTER REPL REPLACE
CJ CONTROL JOINT GYP BD GYPSUM BOARD REQ REQUIRE Ref
CL CENTER LINE GYP PLAS GYPSUM PLASTER REQD REQUIRED 1 ELEVATION NUMBER 1i
RESIL RESILIENT WALL TYPE
CLG CEILING
CLG DIFF CEILING DIFFUSER H --------------------- REST RESTROOM
CLG HT CEILING HEIGHT HB HOSE BIBB RF RESILIENT FLOORING
GRID / COLUMN
CLL COLUMN LINE HDPE HIGH DENSITY POLYETHYLENE RFG ROOFING
1 EXTERIOR ELEVATION 0 LINE
CLO CLOSET HDW HARDWARE RH ROOF HATCH
HDWD HARDWOOD RHR RIGHT HAND REVERSE A101 DESIGNATOR
CLR COLOR
CLRM CLASSROOM HEPA HIGH EFFICIENCY PARTICULATE AIR (FILTER) RL ROOF LEADER PLATE NUMBER WHERE
RLG RAILING 1i EQUIPMENT NUMBER
HM HOLLOW METAL
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
101
COL COLUMN 1 SECTION
COMM COMMUNICATION RVL REVEAL
I --------------------- A101
CONC CONCRETE
CONC FLR CONCRETE FLOOR IBC INTERNATIONAL BUILDING CODE S --------------------
INSUL INSULATION SB SPLASH BLOCK PLATE NUMBER WHERE
CONF CONFERENCE
INT INTERIOR SCHED SCHEDULE SECTION/DETAIL IS
CONT CONTINUE
COORD COORDINATE ILO IN LIEU OF SD SMOKE DETECTOR DRAWN
CORR CORRIDOR SF SQUARE FOOT (FEET) 1
SFTWD SOFTWOOD 1 ENLARGEMENT, REVISION TAG
CP CONCRETE PIPE J ---------------------
JAN JANITOR SGL SINGLE DETAIL
CPT CARPET A-101
CR CONTROL ROOM SHT MTL FLASH SHEET METAL (FLASHING)
CS CAST STONE K --------------------- SHTHG SHEATHING PLAN NORTH
CSWK CASEWORK KPD KEYPAD SHV SHELVING PLATE NUMBER WHERE
CT CERAMIC TILE KIT KITCHEN SIM SIMILAR SECTION/DETAIL IS
CTB CERAMIC TILE BASE KPL KICKPLATE SJ SCORED JOINT DRAWN
CTF CERAMIC TILE FLOOR SKLT SKYLIGHT
SLNT SEALANT NORTH ARROW w/
CTR CENTER L ---------------------
SMK SMOKE TRUE NORTH
CU FT CUBIC FEET LAM LAMINATE
SPOT ELEVATION INDICATION
CW CASEMENT WINDOW LAV LAVATORY SMLS SEAMLESS
LBR LUMBER SP EL SPOT ELEVATION
SPEC SPECIFICATION
D --------------------- LBS POUND
SQ SQUARE
Name
D DEPTH LDG LANDING FLOOR LEVEL & NAME Room
D LABEL CLASS D DOOR LF LINEAR FEET (FOOT) SQ IN SQUARE INCH Elevation Rm_Occupancy
DBL DOUBLE LIB LIBRARY SQ YD SQUARE YARD
DEMO DEMOLITION LIN LINEAR SST STAINLESS STEEL 101
ST STAIRS ROOM OCCUPANCY
DEPT DEPARTMENT LKR LOCKER SHEET KEYNOTE
010
? & AREA
DET DETAIL LOC LOCATION STD STANDARD 150 SF
DIA DIAMETER LT LIGHT STN STAINED
DIR DIRECTION LVDR LOUVER DOOR STL JST STEEL JOIST EGRESS :Egress_ID
LVR LOUVER STL RF DK STEEL ROOF DECK EGRESS ROUTE ID
DIST DISTANCE SHEET KEYNOTE Egress_Length
DOC DOCUMENT STOR STORAGE 010 DEMOLITION
AND SECTION
M --------------------- STR STRINGERS LENGTH
DR DOOR
DS DOWNSPOUT MACH RM MACHINE ROOM STRB/HRN STROBE/HORN
MATL MATERIAL SUB FL SUBFLOOR
ISSUED: 04-09-2020
E --------------------- MAX MAXIMUM SV SHEET VINYL
E LABEL CLASS E DOOR MC MOISTURE CONTENT SW SIDEWALK CEILING SYMBOLS DRAWN BY: NR
EA EACH MD METAL DECK
EF EACH FACE MECH MECHANICAL T --------------------
MECH RM MECHANICAL ROOM T TREAD REVISIONS:
EIFS EXTERIOR INSULATION AND FINISH SYSTEM
EJ EXPANSION JOINT MEMB MEMBRANE T/S TUB/SHOWER RETURN AIR GRILLE
2' x 2' ACT CEILING
ES EACH SIDE MF MILL FINISH TC TERRA COTTA
EL ELEVATION MFR MANUFACTURER TD TRENCH DRAIN
ELEV ELEVATOR MID MIDDLE TEL TELEPHONE
SUPPLY AIR GRILLE
ENTR ENTRANCE MIL STD MILITARY STANDARD TEMP TEMPORARY
EPS EXPANDED POLYSTYRENE BOARD MIN MINIMUM, MINUTE TER TERRAZZO 4' x 4' ACT CEILING
(INSULATION) MIRR MIRROR TFF TOP OF FINISH FLOOR
EQ EQUAL MISC MISCELLANEOUS THK THICKNESS EXHAUST AIR GRILLE
EWC ELECTRIC WATER COOLER MLDG MOLDING (MOULDING) TK BD TACKBOARD PROJECT NO.
4/9/2020 15:04:49
A.0.01
GFCI GOVERNMENT FURNISHED CONTRACTOR MVBL MOVABLE TOPO TOPOGRAPHY 2 x 2 LIGHT FIXTURE
MWP MEMBRANE WATERPROOFING TOS TOP OF SLAB
2 X 4 LIGHT FIXTURE
TRANS TRANSOM
TRTD
TV
TREATED
TELEVISION
SUSP. FLUORESCENT
LIGHT GENERAL NOTES, ABBREVIATIONS
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
R
STANDARD DOOR OPENING LOCATIONS ADA DOOR CLEARANCES ADA MOUNTING HEIGHTS ADA CLEARANCES
Texas
Department
3'-3" MIN of Transportation
3'-0" MIN
BLOCKING, REQUIRED HEIGHT TO
32" MIN 1'-0" 3'-6" MIN SPAN FROM STUD TO STUD OPERABLE
4" TYP. 1'-0" MIN
60" MIN
PARTS
1'-6"
18" MIN
THIS DRAWING CREATED
17" - 19"
24" PREFERED FOR PRODUCTION ON
3'-8" MAX
22"x34" SHEET SIZE.
3'-3" MIN
3-10"
DO NOT SCALE PRINTS.
33"-36"
1'-6"
2'-6"
MIN.
MAX
18"
MIN
17"
32" MIN 4" MAX 32" MIN
42"
TYPICAL DOOR PLACEMENT TYPICAL DOOR PLACEMENT 16"-18" ADULT TOILET TISSUE ADULT SANITARY NAPKIN/ ALTERNATE
MAX
PULL SIDE (UON) (UON) ACCESSIBLE DISPENSER ACCESSIBLE NAPKIN TAMPON DOOR LOCATION
7"-9" TEXAS REGISTERED ENGINEERING
WATER CLOSET NAPKIN/TAMPON URINAL DISPOSAL VENDOR FIRM F-2966
Y
24" MAX
DISPOSAL 777 MAIN ST. STE B-101
EQ. EQ. X FORT WORTH, TEXAS 76102
32" MIN
4" MAX
1'-0" MIRROR FULL
60" MIN
MIN. WIDTH OF COUNTER
36" MIN
ALUMINUM PIPE
BOTTLE FILLING 8" MAX
NOTE: X=36" MIN. IF Y=60", OR COVER
16"-18"
STATION
X=42" MIN. IF Y=54"
4'-0"
MEN DOOR
6" MAX
54" MIN X
B.O. REFLECTIVE
12"
74" MIN
38 - 43" MAX
SURFACE
MAX
STANDING
60"
40" MAX
PERSONS
54" MIN
36" MAX
MAX
2'-10"
34"
42" MIN (Y)
ADA
48" MIN
TYPICAL DOOR PLACEMENT TYPICAL DOOR PLACEMENT 60" MIN
PUSH SIDE (UON) (UON) NOTE: X=12" IF DOOR
HAS BOTH A CLOSER 42" MIN LATCH APPROACH
AND A LATCH HI-LO SIGNAGE WALL MOUNTED RESTROOM ONLY, OTHER APPROACHES 48" MIN
REFRIGERATED LAVATORY COUNTER
NOTE: Y=48" MIN. IF
DRINKING FOUNTAIN
ADA NOTES DOOR HAS BOTH A
CLOSER AND A LATCH NOTE: HANDLE 36" MIN
16"-18"
MUST BE BELOW
48"
1. NOT ALL DRAWINGS OR CONDITIONS MAY APPLY TO THIS PROJECT. 24" MIN (X)
48" TO HANDLE
24" MIN (X)
56" MIN
48" MAX
48" MAX
60" MIN
48" MIN (Y)
48"
48"
48"
48"
30" MAX
CLEAR FLOOR
SPACE CLEAR FLOOR
36"
18"
SPACE
MIN
8"
42" MIN 16"-18"
56" MIN
NOTE: Y=54" MIN. IF NOTE: Y=48" MIN. IF 60" MIN WALL MOUNTED W.C.
FIRE FIRE BABY CHANGING PAPER TOWEL OUTLET LIGHT FIRE COAT HOOK HAND PAPER TOWEL
DOOR HAS CLOSER DOOR HAS CLOSER EXTINGUISHER EXTINGUISHER STATION DISPOSAL SWITCH PULL DRYER DISPENSER & WASTE 59" MIN
TARRANT COUNTY
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
ISSUED: 04-09-2020
DRAWN BY: NR
REVISIONS:
ADA - RAMP
2 12" = 1'-0"
PROJECT NO.
4/9/2020 15:04:51
02470420015
SHEET NO:
ADA GUIDELINES
A.0.02
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
GENERAL DEMOLITION NOTES R
BUILDING J RENOVATIONS
HARDWARE, HANGERS, ANCHOR SYSTEMS, MISC METAL
ATTACHMENTS, ETC. PATCH AND FINISH TO MATCH ADJACENT
TARRANT COUNTY
PROVIDE A CLEAN SPACE TO INITIATE NEW CONSTRUCTION.
19 COORDINATE WITH STRUCTURAL FOR AREAS OF EXISTING
CONCRETE FLOOR AND ROOF THAT NEED TO BE OPENED FOR NEW
UTILITY INSTALLATIONS.
20 REPAIR AND FINISH ALL HOLES IN WALLS, UNDERSIDE OF
CONCRETE DECKS AND FLOORS LEFT FROM REMOVAL OF
HARDWARE, FASTENERS, DUCTS, PIPES, CONDUIT, ETC AND
RESTORE TO ORIGINAL INTEGRITY; RE: STRUCTURAL, MECHANICAL,
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
PLUMBING, ELECTRICAL
21 ALL MATERIALS REMOVED BY CONTRACTOR SHALL BE DISPOSED
OF BY CONTRACTOR AT AN OFF-SITE LOCATION, UNLESS
OTHERWISE NOTED BY PROJECT MANAGER.
22 PATCH AND REPAIR ALL HOLES IN WALLS, CEILINGS, CONCRETE
COLUMNS, AND FLOORS PRODUCED DURING DEMOLITION. PATCH
TO MATCH ADJACENT CONSTRUCTION.
23 AT SAW CUTS OF EXISTING CONCRETE FLOOR SLAB; COORDINATE
WITH PROJECT MANAGER FOR SCHEDULING OF CUTTING OF FLOOR
SLAB. CONTRACTOR TO OVERSEE CONCRETE FLOOR CUTTING
PROCESS AND CONTROL / MITIGATE FLYING DUST. USE VACUUM
CLEANER DURING CUTTING EXERCISE. NEW INFILL TO ALIGN WITH
EXISTING ADJACENT FACE OF SLAB.
24 CONTRACTOR TO EXERCISE CARE DURING DEMOLITION OF AREAS
LIKELY TO CONTAIN HIDDEN OR OBSCURED SYSTEMS BEYOND
FINISHED SURFACES.
25 THE CONTRACTOR SHALL VERIFY CONSTRUCTION LAYOUT PRIOR
TO COMMENCEMENT OF CONSTRUCTION.
26 CONTRACTOR SHOULD FIELD MEASURE ALL EXISTING OPENINGS
WHERE DOORS AND WINDOWS WILL BE INSTALLED.
27 COORDINATE ALL NEW MEP OPENINGS REQUIRED IN THE
HORIZONTAL ASSEMBLIES WITH OTHER DISCIPLINES.
28 IN FILL HOLES IN EXISTING SLAB AND FINISH AT LOCATIONS OF
REMOVED PLUMBING DRAINS, VENTS, PIPES, ETC. PATCH TO MATCH
ADJACENT SURFACE
29 REFER TO HAZARDOUS MATERIAL ADVISORY ON COVER SHEET,
AND SPECIFIC NOTES REGARDING ACM ON DEMOLITION PLANS.
ISSUED: 04-09-2020
DRAWN BY: NR
REVISIONS:
PROJECT NO.
4/9/2020 15:04:52
02470420015
SHEET NO:
2'-6" (U-2)
B1 3 5/8" 18 GAUGE
1' - 6"
Texas
2' - 1"
MTL RUNNER EQ EQ
Department
AROUND SNTD - 1 of Transportation
MAX
COUNTER
6"
1' - 0"
LK-1 SD-1 COUNTER TOP HD-1
2'-6"x4'-0" AND BACKSPLASH PTWR-1
CLEAR FLOOR AS SCHEDULED
THIS DRAWING CREATED
RECOMMENDED MOUNTING
REFER TO PLAN FOR QUANTITIES SPACE U1 FOR PRODUCTION ON
22"x34" SHEET SIZE.
U2 SC1 DO NOT SCALE PRINTS.
AND ORIENTATION OF LOCKERS
RECOMMENDED MOUNTING
4'-0"
5"
SD-1
.
AS INDICATED TEXAS REGISTERED ENGINEERING
4'-0" MAX
FIRM F-2966
MAX
2"
PIPE WRAP
8"
8". 8". FORT WORTH, TEXAS 76102
-
U1 U2
3'-0"
5"
1'-6"-
2' - 10" 4"
REQUIRED KNEE
1' - 5"
2' - 0"
B-1 ACCESSIBLE SHOWER NAPKIN/TAMPON VENDOR,
1' - 5"
9"-
BENCH; 1 1/4" THICK RED BOBRICK: B - 282 25
OAK SEAT, ROUNDED
3'-0"
-
6" -
10" -
8" TSCD - 1 RECESSED TOILET SEAT-COVER
EDGES, WITH BRUSHED L1 ACCESSIBLE UNDER COUNTER
CHROME PEDESTALS DISPENSER, BOBRICK: B - 301 U1 STANDARD URINAL
MOUNTED LAVATORY 2'-0"
MG- 1 MIRROR, BOBRICK B-165, 24" X 36" OR
4"
HD-1 EXCEL XLERATOR XL-SB WITH U2 ACCESSIBLE URINAL
AS NOTED RECESS KIT 40502
SD- 1 WALL MOUNTED SOAP DISPENSER, PTWR-1 SEMI-RECESSED PAPER TOWEL SC1 URINAL SCREEN
STOKO REFRESH 4 IN 1 DISPENSER, BOBRICK B-3949
CONC. BASE, CFCI
U1 STANDARD URINAL
ACCESSIBLE MISCELLANIOUS TOILET ROOM
B1 STANDARD SHOWER BENCH LK-1 STANDARD LOCKERS L1 COUNTER MOUNTED LAVATORY MOUNTING HEIGHTS U2 ACCESSIBLE URINAL
1' - 6" 1" 3' - 0" 1" 3' - 0" 3'-0" SHOWER STALL NOTES:
16"-18" 3' - 0" 3' - 0"
1. FLOOR SLOPES TO BE A MAX
1' - 6" 1' - 6" 16"-18" MAX CONTROL WALL
OF 1:50 IN ANY DIRECTION.
SC1
MAX
3' - 6"
MAX
TSCD-1 TO BE NO HIGHER THAN 1/2"; TP-1
9"
MAX
2' - 6"
WC-2
9"
3' - 0"
REFER 1/A.5.0101 GB-2
4' - 6"
GB-1
MAX
WC-1
9"
4' - 0"
5' - 0"
TTD-1
4' - 6"
TTD-1 HAVE A HOSE 60" LONG THAT
SND-1 WC-2 GB-1
2"
CAN BE USED FIXED OR HAND
BUILDING J RENOVATIONS
4. SHOWER FLOOR TO BE NON- CLEAR FLOOR SPACE
TARRANT COUNTY
CH-1 5'-0" TP-1 1' - 6"
2' - 0".
TLT-2
4' - 10"
7' - 0"
HANDLE ON SIDE
GB-1 CONTROLS
6' - 0"
OPPOSITE WALL
4' - 0"
MAX
3'-8"
DB-1
GB-2 GB-2
MAX
3'-0"
3' - 8"
3' - 4".
TTD-1
MAX
FSS-1
3'-8"
1/2" MAX
3' - 0"
2'-0"
MIN
ENTRY
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
1' - 4"
MAX
3'-0"
1' - 0"
CURB
1' - 6"
1' - 7"
WC-2 WC-2
PRT-1 1" THICK SOLID PHENOLIC DB-1 DOOR BUMPER; BOBRICK: CH-1 COAT HOOK BUMPER; SOLID CAST GB-1 GRAB BAR L-SHAPE; BOBRICK: B-68137
TOILET PARTITION B-687 ALUMINUM; BOBRICK: B- 211 TTD-1 SURFACE MOUNTED WC-2 ACCESSIBLE TOILET FSS-1 FOLDING SHOWER SCR HEAVY DUTY CURTAIN
WC-2 ACCESSIBLE TOILET
WC-1 STANDARD TOILET TOILET PAPER SEAT; BOBRICK B-5181 ROD,BOBRICK B-6107
TOILET STALL NOTES: TSCD-1 SURFACE MOUNTED TOILET SEAT DISPENSER, BOBRICK VINYL SHOWER CURTAIN,
SC1 1" THICK SOLID PHENOLIC TSCD-1 SURFACE MOUNTED TOILET HSD-1 HEAVY DUTY SOAP
1. REFER TO PLAN FOR COVER DISPENSER; BOBRICK; B-4221 B-2840 GB-1 GRAB BAR L SHAPE BOBRICK 204-3
URINAL SCREEN SEAT COVER DISPENSER; DISH; BOBRICK B-4390
QUANTITIES AND TTD-1 SURFACE MOUNTED TOILET PAPER CH-1 COAT HOOK BUMPER; BOBRICK: B-68137 NOT SHOWN - (12) CURTAIN HOOKS
BOBRICK; B-4221
ORIENTATION DISPENSER, BOBRICK B-2840 SOLID CAST ALUMINUM; GB-2 GRAB BAR L-SHAPE,
CH-1 CLOTHES HOOK AND OF TOILET PARTITIONS AND TTD-1 SURFACE MOUNTED TOILET BOBRICK: B- 211
PAPER DISPENSER, BOBRICK TSCD-1 SURFACE MOUNTED BOBRICK B6816.99,
BUMPER CENTER ON URINAL SCREENS
B-2840 DB-1 SURFACE MOUNTED TOILET SEAT COVER B-5897 AT 5'-0"
DOOR; BOBRICK: B-212
DOOR BUMPER, DISPENSER; WIDE SHOWERS
SND-1 SANITARY NAPKIN DISPOSAL CENTER ON DOOR, BOBRICK; B-4221
(UNISEX/WOMEN'S RR ONLY) TP-1 TOWEL PIN,BOBRICK B-
BOBRICK: B-687
677
STANDARD FLOOR MOUNTED STANDARD ACCESSIBLE END OF ROW ACCESSIBLE SHOWER
P1 TOILET PARTITIONS S1 STALL S2 TOILET S3 ACCESSIBLE STALL SH1 STALL
3' - 0" FINISH AS TILE AS TOILET ACCESSORIES NOTES
SCHEDULED SCHEDULED A MANUFACTURER PRODUCTS INDICATED ESTABLISHES A PALLETE OF COLORS AND
2" STL STUDS WATERPROOFING MORTAR BED
A MINIMUM LEVEL OF ACCEPTABLE QUALITY. IT IS NOT INTENDED TO LIMIT THE
SLOPE TO SLOPE TO AT 16" OC
SELECTION OF APPROVED EQUIVALENT PRODUCTS.
1
1
MEMBRANE B REFER TO PLAN FOR QUANTITIES AND ORIENTATION OF TOILET PARTITIONS AND
DRAIN DRAIN
2 5/8"CEMENTITIOUS ACCESSORIES
BACKER BD C CONTRACTOR IS RESPONSIBLE FOR FURNISHING AND INSTALLING ALL
MAX
HEIGHT FLASHING
1
ACCESSIBLE SHOWER DETAIL
3" = 1'-0"
2
SHOWER FLASHING DETAIL
NOT TO SCALE
RESTROOM ACCESSORIES AND DETAILS
A.5.01
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
R
PROVIDE
PROVIDE
EPOXY PAINT
EPOXY PAINT
FINISH BEHIND Texas
FINISH BEHIND Department
ALL 2' - 1"
ALL of Transportation
COUNTERTOPS
COUNTERTOPS
1/2"
THIS DRAWING CREATED
COUNTER & BACKSPLASH: FOR PRODUCTION ON
22"x34" SHEET SIZE.
SOLID SURFACE SS-1 COUNTER & BACKSPLASH: DO NOT SCALE PRINTS.
4"
SOLID SURFACE SS-1
APRON: FLUSH WITH
1 1/2"
ADJACENT CABINET DRAWER BOX: 1/2" WHITE
4"
DOOR, 3/4" PARTICLE MELAMINE SIDES. 1/4" WHITE
5"
BOARD WITH HPLAM MELAMINE BOTTOM WITH PVC
EDGEBAND TO MATCH PL-#
REQUIRED KNEE SPACE: TEXAS REGISTERED ENGINEERING
2"
FIRM F-2966
DASHED LINE SHOWN FOR DRAWER FRONT: 3/4" PARTICLE
3/8"
1' - 8"
5"
4"
REFERENCE ONLY 777 MAIN ST. STE B-101
BAORD WITH HPLAM TO MATCH
FORT WORTH, TEXAS 76102
PL-1 AND PVC EDGEBAND TO
REMOVABLE PANEL: 3/4" MATCH PL-1
PLYWOOD WITH PLAM TO
MATCH PL-1, TO BE CASE: 3/4" PARTICLE BOARD
ATTACHED TO CABINET WITH PLAM FINISH
AND WALL WITH HANGING
1' - 6"
2' - 10"
CLEATS ADJ. SHELF: 3/4" PARTICLE
2' - 4 1/2"
BOARD WITH PLAM TO MATCH
BACK WALL: PAINT AND
2' - 10"
PL-1 AND OAK EDGEBAND
BASE AS SCHEDULED
BACK: 1/4" WHITE VINYL BOARD
9"
3"
4"
6"
PROVIDE PROVIDE
BUILDING J RENOVATIONS
TARRANT COUNTY
1 1/2"
PL-1
4"
1 1/2"
1/2"
4"
ADJ. SHELF: 3/4" PARTICLE
BOARD WITH PLAM TO
MATCH PL-1 AND OAK
EDGEBAND
3/8"
5"
3/8"
EQ.
1' - 8"
BACK: 1/4" WHITE VINYL
BOARD
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
1/8"
2"
DOOR: 3/4" PBD WITH
HPLAM
EQ.
5"
1' - 8"
PULL: 4" WIRE BRUSHED
2' - 4 1/2"
2' - 4 1/2"
CHROME
2"
2' - 10"
2' - 10"
TOEKICK: BASE TO MATCH
1/8"
BASE SCHEDULED IN
5"
EQ.
2"
1/8"
5"
EQ.
1' - 8"
1/2"
4"
3"
4"
3"
ISSUED: 04-09-2020
DRAWN BY: NR
REVISIONS:
PROJECT NO.
4/9/2020 15:04:55
02470420015
SHEET NO:
0 6" 1' 2'
1 1/2" = 1'-0"
MILLWORK DETAILS
A.5.03
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
PARTITION TYPE KEY R
TYPE
TYPE
TYPE
A B E 2. PARTITIONS IN HIGH MOISTURE AREAS SHALL USE
MOISTURE RESISTANT GYPSUM BOARD WHICH
IND STUD SIZE TOTAL WIDTH IND STUD SIZE TOTAL WIDTH IND STUD SIZE TOTAL WIDTH INCLUDE TOILET ROOM(S), LOCKER ROOM(S),JANITOR
INDICATOR
INDICATOR
INDICATOR
2 2 1/2" 3 3/4" 2 2 1/2" 5" 2 2 1/2" 3 1/8" CLOSET(S), MECHANICAL ROOM(S), AND WITHIN 4'-0"
OF WATER FOUNTAIN.
SIZE
SIZE
SIZE
3 3 5/8" 4 7/8" 3 3 5/8" 6 1/8" 3 3 5/8" 4 1/4"
3. PARTITIONS BEHIND TILE FINISHES SHALL USE
4 4" 5 1/4" 4 4" 6 1/2" 4 4" 4 5/8" CEMENT ITIOUS BACKER BOARD WITH A MOISTURE
6 6" 7 1/4" 6 6" 8 1/2" 6 6" 6 5/8" BARRIER.
8 8" 9 1/4" 8 8" 10 1/2" 8 8" 8 5/8" 4. ALL GYP BD LOCATED IN CORRIDORS UP TO 8'-6" AFF
NO RATING - NO INSULATION NO RATING - NO INSULATION NO RATING - NO INSULATION SHALL BE IMPACT RESISTANT.
RATING
RATING
RATING
1 1 HR FIRE RATED - UL# U419 2 2 HR FIRE RATED - UL# U419 A ACOUSTICAL E. SEALANT:
1. FIRE RESISTANT RATED PARTITIONS SHALL USE FIRE
A ACOUSTICAL - STC 45 A ACOUSTICAL - STC 55 S SMOKE STOP SEALANT SYSTEM.
S SMOKE S SMOKE 2. NON - RATED PARTITIONS AND SMOKE RATED
PARTITIONS SHALL USE ACOUSTICAL SEALANT.
F. INSULATION - HEAD CONDITION AT STRUCTURE ABOVE:
1. FIRE RATED RESISTANT PARTITIONS SHALL USE FIRE
LINE OF STRUCTURE SAFING INSULATION.
ABOVE 2. NON - RATED PARTITIONS SHALL USE SOUND
ATTENUATION BLANKET.
THERMAL
DO NOT ATTACH GYP BD OR
INSULATION - RATING G. FIRE AND / OR SMOKE RESISTANT RATINGS ARE TO
STUDS TO TOP TRACK
'T'
BUILDING J RENOVATIONS
WIDTH
TARRANT COUNTY
PLATE AND DECK AT FRAMING
CONT 18 GAGE X 3" J. STC RATING IS BASED ON THE USE OF A 3 5/8" METAL
EACH SIDE STUD OR GREATER.
LEG TRACK, FLOOR
ANCHOR TO DECK CONT 14" WIDE 20
GAGE CLOSURE K. INSTALL HORIZONTAL STUD FRAMING BRACING AT 4'- 0"
WITH S-12 SCREWS
TYPE
PLATE
SEALANT WITH BOND ON CENTER.
AT 12" OC
STAGGERED BREAKER TAPE L L. CMU INFILL WALLS ARE TO BE A THICKNESS TO MATCH
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
GYP BD PARTITION PERPENDICULAR TO TOP RUNNER IND STUD SIZE TOTAL WIDTH EXISTING ADJACENT WALL.
AS SCHED METAL DECK FLUTES CAPTURED WITHIN
INDICATOR
DEEP LEG TRACK 1 7/8" 1 1/2"
SIZE
2 2 1/2" 3 1/8"
TYP TOP OF GYP BD WALL CONNECTION 3 3 5/8" 4 1/4"
1 3" = 1'-0"
NO RATING - NO INSULATION
RATING
T THERMAL
A ACOUSTICAL
S SMOKE
COMPRESSED SOUND
ATTENUATION
BLANKETS
ACOUSTICAL SEALANT
3/8"
GYP BD PARTITION AS SCHED AND BACKER ROD ZINC CONTROL JOINT
BASE AS SCHED AT BOTH SIDES
1/2"
GALV U-SHAPED
METAL RUNNER STEEL CASING METAL STUD
SEALANT AND BACKER ROD METAL STUD
GYP BD PARTITION ISSUED: 04-09-2020
FLR FIN AS AS SCHED DRAWN BY: NR
SCHED GYP BD PARTITION
AS SCHED REVISIONS:
TYP BOTTOM OF WALL CONNECTION TYP WALL-WALL CONNECTION TYP CONTROL JOINT
2 3" = 1'-0"
3 3" = 1'-0"
4 3" = 1'-0"
PROJECT NO.
4/9/2020 15:04:56
02470420015
SHEET NO:
CPT-1 CARPET TILE CARPET 096810 MEETING ROOM MOHAWK GOUP, ONE FIRST HAPPENING 8989
24"X24"
PTF-1 FLOOR TILE PORCELAIN TILE 096620 RESTROOMS DALTILE D200 DESERT GRAY 2" X 2"
SPECKLE
PAINT
PT-1 WALL PAINT PAINT 099000 RESTROOMS SHERWIN WILLIAMS SW 7006 EXTRA WHITE 257-C1 PROVIDE EPOXY PAINT BEHIND ALL COUNTERTOPS AND IN WET LOCATIONS
SATIN/EGGSHELL SHEEN
PT-2 WALL PAINT PAINT 099000 OFFICE SHERWIN WILLIAMS SW7005 PURE WHITE 255-C1 PROVIDE EPOXY PAINT BEHIND ALL COUNTERTOPS AND IN WET LOCATIONS
SATIN/EGGSHELL SHEEN
PT-3 RAILING PAINT PAINT 099000 STEEL PIPE RAILS, SHERWIN WILLIAMS TRAFFIC / SAFETY YELLOW
BOLLARDS
VINYL FLOORING
LVT -1 FLOOR TILE VINYL TILE 096620 OFFICE METROFLOR SMOOTH CONCRETE / DN123813 24" X 24"
ANTHRACITE
COUNTER TOPS
PL-1 PLASTIC LAMINATE CABINET FACES 064110 KITCHEN NEVAMAR JUTE S2086T
BASE
BUILDING J RENOVATIONS
ISSUED: 04-09-2020
DRAWN BY: NR
REVISIONS:
PROJECT NO.
4/9/2020 15:04:57
02470420015
SHEET NO:
FINISH SCHEDULES
A.7.01
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
GENERAL NOTES - DEMOLITION R
AREA A: 1/JAD.1.11
AREA B: 1/JAD.1.12
IMMEDIATELY IF WATERPROOFING IS OBSERVED UNDER TILE FOR PRODUCTION ON
MORTAR BEDS. ASBESTOS TESTING FOR THIS MATERIAL WILL BE 22"x34" SHEET SIZE.
DO NOT SCALE PRINTS.
REQUIRED PRIOR TO CONTINUATION OF WORK IN THIS AREA. ALSO
REFER TO HAZARDOUS MATERIAL ADVISORY ON COVER SHEET.
F CONTRACTOR TO STOP WORK AND NOTIFY ARCHITECT
IMMEDIATELY IF WATERPROOFING IS OBSERVED WITHIN EXTERIOR
WALL ASSEMBLY IN AREAS WHERE WALL IS BEING DEMOLISHED OR
OTHERWISE MANIPULATED DUE TO PROJECT WORK. ASBESTOS
A TESTING FOR THIS MATERIAL WILL BE REQUIRED PRIOR TO TEXAS REGISTERED ENGINEERING
FIRM F-2966
CONTINUATION OF WORK IN THIS AREA. ALSO REFER TO
HAZARDOUS MATERIAL ADVISORY ON COVER SHEET. 777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
BREAKROOM
105
BAY 1
MENS WOMENS 109
104 103
C
MEETING ROOM
107
UP
D
LOBBY
108
(N)
E
BUILDING J RENOVATIONS
111 102
110
TARRANT COUNTY
H
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
AREA A AREA B
BUILDING J
J ISSUED: 04-09-2020
DRAWN BY: NR
REVISIONS:
L
NORTH
U
N
PROJECT NO.
4/9/2020 15:05:45
02470420015
SHEET NO:
0 8' 16' 32' 48'
1/16" = 1'-0"
AREA B: 1/JAD.1.12
NOTED. COVER AND PROTECT DURING CONSTRUCTION Texas
C REFER TO STRUCTURAL DRAWINGS FOR ANY AND ALL Department
UP 053 of Transportation
PENETRATIONS AND SAW CUTS THROUGH SLABS AND EXTERIOR
WALLS, COORDINATE WITH STRUCTURAL ENGINEER PRIOR TO ANY
DRILLING OR SAW CUTTING
D EXISTING FIRE SPRINKLER SYSTEMS TO REMAIN AS IS.
E CONTRACTOR TO STOP WORK AND NOTIFY ARCHITECT THIS DRAWING CREATED
IMMEDIATELY IF WATERPROOFING IS OBSERVED UNDER TILE FOR PRODUCTION ON
A MORTAR BEDS. ASBESTOS TESTING FOR THIS MATERIAL WILL BE 22"x34" SHEET SIZE.
DO NOT SCALE PRINTS.
REQUIRED PRIOR TO CONTINUATION OF WORK IN THIS AREA. ALSO
030 REFER TO HAZARDOUS MATERIAL ADVISORY ON COVER SHEET.
F CONTRACTOR TO STOP WORK AND NOTIFY ARCHITECT
030 IMMEDIATELY IF WATERPROOFING IS OBSERVED WITHIN EXTERIOR
025 WALL ASSEMBLY IN AREAS WHERE WALL IS BEING DEMOLISHED OR
OTHERWISE MANIPULATED DUE TO PROJECT WORK. ASBESTOS
030 TESTING FOR THIS MATERIAL WILL BE REQUIRED PRIOR TO TEXAS REGISTERED ENGINEERING
FIRM F-2966
CONTINUATION OF WORK IN THIS AREA. ALSO REFER TO
HAZARDOUS MATERIAL ADVISORY ON COVER SHEET. 777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
090
030 KEYNOTES
025 REMOVE EXISTING CASEWORK.
098
030 REMOVE AIR HANDLER; REF. MECH.
053 REMOVE EXISTING CONDENSER. REF. MECH.
B 054 REMOVE EXISTING PLUMBING FIXTURES, REF. PLUMBING
030 058 REMOVE EXISTING STEEL PIPE RAILING. PATCH, AND REPAIR
DAMAGED CONCRETE.
BREAKROOM 059 REMOVE EXISTING WALL FINISH, BASE, TRIM, AND CHAIR RAIL.
105 CLEAN AND PREP WALL TO RECEIVE NEW PAINT.
061 REMOVE EXISTING FREIGHT ELEVATOR EQUIPMENT. SALVAGE AND
RETURN TO OWNER.
069 SALVAGE NEWER MECHANICAL UNIT AND RETURN TO OWNER.
BAY 1 071 REMOVE EXISTING CHAIR LIFT FROM STAIR.
109 075 REMOVE EXISTING WALL MOUNTED TOILET ACCESSORIES. PATCH
MENS WOMENS AND PREP WALL TO RECEIVE NEW FINISH.
104 103 076 REMOVE EXISTING TILE FLOORING; REMOVE EXCESS MORTAR,
GROUT, AND ANY MUD BEDS DOWN TO SLAB TO ACCOMMODATE
NEW FLOORING.
061
078 REMOVE EXISTING FRP PANELING; PREP WALL FOR NEW FINISH
C
090 REMOVE EXISTING ELECTRIC RANGE. RETURN TO OWNER.
076 076 098 REMOVE EXISTING EXHAUST HOOD.
054 054
058
BUILDING J RENOVATIONS
LOBBY
TARRANT COUNTY
108
030
UP
E
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
053 069
098
025 075
075 BUILDING J
054
054 J ISSUED: 04-09-2020
DRAWN BY: NR
025 REVISIONS:
L
NORTH
076 U
076
N
PROJECT NO.
4/9/2020 15:05:48
02470420015
AREA A: 1/JAD.1.11
R
8 7 6 5 4 3 2 1.9 1 A ALL ITEMS THAT ARE NOT DASHED OR BOLD ARE EXISTING TO
REMAIN
B ALL LIFE SAFETY DEVICES AND EQUIPMENT TO REMAIN UNLESS
062 062 062 NOTED. COVER AND PROTECT DURING CONSTRUCTION Texas
044 044 044 C REFER TO STRUCTURAL DRAWINGS FOR ANY AND ALL Department
PENETRATIONS AND SAW CUTS THROUGH SLABS AND EXTERIOR of Transportation
WALLS, COORDINATE WITH STRUCTURAL ENGINEER PRIOR TO ANY
A DRILLING OR SAW CUTTING
D EXISTING FIRE SPRINKLER SYSTEMS TO REMAIN AS IS.
E CONTRACTOR TO STOP WORK AND NOTIFY ARCHITECT THIS DRAWING CREATED
IMMEDIATELY IF WATERPROOFING IS OBSERVED UNDER TILE FOR PRODUCTION ON
MORTAR BEDS. ASBESTOS TESTING FOR THIS MATERIAL WILL BE 22"x34" SHEET SIZE.
DO NOT SCALE PRINTS.
REQUIRED PRIOR TO CONTINUATION OF WORK IN THIS AREA. ALSO
REFER TO HAZARDOUS MATERIAL ADVISORY ON COVER SHEET.
F CONTRACTOR TO STOP WORK AND NOTIFY ARCHITECT
IMMEDIATELY IF WATERPROOFING IS OBSERVED WITHIN EXTERIOR
WALL ASSEMBLY IN AREAS WHERE WALL IS BEING DEMOLISHED OR
OTHERWISE MANIPULATED DUE TO PROJECT WORK. ASBESTOS
TESTING FOR THIS MATERIAL WILL BE REQUIRED PRIOR TO TEXAS REGISTERED ENGINEERING
FIRM F-2966
CONTINUATION OF WORK IN THIS AREA. ALSO REFER TO
HAZARDOUS MATERIAL ADVISORY ON COVER SHEET. 777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
B
KEYNOTES
023 REMOVE EXISTING CEILING, LIGHTING, DIFFUSERS, AND
ASSOCIATED CEILING MOUNTED EQUIPMENT IN THIS AREA. REF.
MECHANICAL AND ELECTRICAL
024 REMOVE EXISTING LOCKER SYSTEM AND CONCRETE CURB AND
ASSOCIATED MASONRY; PATCH, REPAIR, CLEAN, AND PREP
WALL/FLOOR TO RECEIVE NEW FINISHES.
030 REMOVE AIR HANDLER; REF. MECH.
BAY 1
109 044 REMOVE EXISTING WINDOW SYSTEM; PATCH AND PREP OPENING
FOR OVERHEAD DOOR INSTALLATION
054 REMOVE EXISTING PLUMBING FIXTURES, REF. PLUMBING
062 SAW-CUT EXISTING MASONRY WALL TO INSTALL NEW
DOOR/OPENING. RE: STRUCT FOR INFORMATION REGARDING THE
INSTALLATION OF NEW LINTEL ABOVE.
063 REMOVE EXISTING FLOOR DRAIN. PATCH, REPAIR, CLEAN AND
PREP AREA TO RECEIVE NEW FINISH.
C
072 EXISTING FLOOR DRAIN TO REMAIN; CLEAN, PATCH AND PREP FOR
NEW FLOOR FINISH.
074 REMOVE EXISTING SHOWER TUB, CURB AND ASSOCIATED
FIXTURES. SEE PLUMBING
075 REMOVE EXISTING WALL MOUNTED TOILET ACCESSORIES. PATCH
AND PREP WALL TO RECEIVE NEW FINISH.
076 REMOVE EXISTING TILE FLOORING; REMOVE EXCESS MORTAR,
GROUT, AND ANY MUD BEDS DOWN TO SLAB TO ACCOMMODATE
NEW FLOORING.
085 EXISTING ROUND SINK TO BE REMOVED. PATCH, REPAIR, AND PREP
AREA TO RECEIVE NEW FLOOR FINISH.
086 REMOVE EXISTING TOILET PARTITIONS.
054 086
D
BUILDING J RENOVATIONS
S
102
TARRANT COUNTY
(N)
OFFICE
111 076 085
S
075 E
023
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
024
AREA B
075
BAY 2
110
024
086
G BUILDING J
085 075
Site Key Plan:
054
028
J ISSUED: 04-09-2020
DRAWN BY: NR
REVISIONS:
L
076 NORTH
076 U
N
PROJECT NO.
4/9/2020 15:05:50
H 02470420015
1/8" = 1'-0"
AREA A: 1/JAD.1.21
REFER TO HAZARDOUS MATERIAL ADVISORY ON COVER SHEET.
F CONTRACTOR TO STOP WORK AND NOTIFY ARCHITECT
IMMEDIATELY IF WATERPROOFING IS OBSERVED WITHIN EXTERIOR
WALL ASSEMBLY IN AREAS WHERE WALL IS BEING DEMOLISHED OR
OTHERWISE MANIPULATED DUE TO PROJECT WORK. ASBESTOS
TESTING FOR THIS MATERIAL WILL BE REQUIRED PRIOR TO TEXAS REGISTERED ENGINEERING
FIRM F-2966
CONTINUATION OF WORK IN THIS AREA. ALSO REFER TO
HAZARDOUS MATERIAL ADVISORY ON COVER SHEET. 777 MAIN ST. STE B-101
A FORT WORTH, TEXAS 76102
B
DOCK WAREHOUSE
201
OFFICE
205
OPEN TO C
DN BELOW
RESTROOM
204
TARRANT COUNTY
BELOW G
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
AREA A AREA B
BUILDING J
J ISSUED: 04-09-2020
DRAWN BY: NR
REVISIONS:
L
NORTH
U
N
PROJECT NO.
4/9/2020 15:05:52
02470420015
SHEET NO:
0 8' 16' 32' 48'
1/16" = 1'-0"
A
KEYNOTES
010 REMOVE EXISTING DOOR. SALVAGE DOOR FOR REUSE.
011 REMOVE PORTION OF EXISTING WALL FOR NEW DOOR, REF. FLOOR
060 PLAN
021 EXISTING WINDOW TO REMAIN
052 039 SAWCUT CONCRETE STAIR AT FACE OF EXISTING BEAM
087 052 DISCONNECT AND REMOVE EXISTING RACK. REF. ELEC.
054 REMOVE EXISTING PLUMBING FIXTURES, REF. PLUMBING
058 REMOVE EXISTING STEEL PIPE RAILING. PATCH, AND REPAIR
092 DAMAGED CONCRETE.
060 REMOVE EXISTING MAILBOX; SALVAGE AND RETURN TO OWNER
FOR RELOCATION
075 REMOVE EXISTING WALL MOUNTED TOILET ACCESSORIES. PATCH
AND PREP WALL TO RECEIVE NEW FINISH.
078 REMOVE EXISTING FRP PANELING; PREP WALL FOR NEW FINISH
REMOVED
B 084 REMOVE EXISTING STAIR RAILING.
6' - 0"
011 086 REMOVE EXISTING TOILET PARTITIONS.
087 REMOVE EXISTING WIRE MESH CAGE; RETURN TO OWNER.
092 REMOVE EXISTING DOCK BUMPER AND ASSOCIATED ACCESSORIES
FIELD VERIFY
WAREHOUSE 021
12' - 0"
010 201
OFFICE
087 205
039
2'-2" V.I.F.
C
BUILDING J RENOVATIONS
054
TARRANT COUNTY
D
DN
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
E
Building Key Plan:
AREA A
BUILDING J
DRAWN BY: NR
REVISIONS:
L
NORTH
U
N
PROJECT NO.
4/9/2020 15:05:54
02470420015
SHEET NO:
0 4' 8' 16' 24'
1/8" = 1'-0"
12 11 10 9 8 7 6 5 4 3 2 1.9 1
AREA A: 1/JA.1.11
AREA B: 1/JA.1.12
TEXAS REGISTERED ENGINEERING
UP
FIRM F-2966
777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
BREAKROOM
105
MATCHLINE
MATCHLINE
BAY 1
109
MENS WOMENS
104 103
C
MEETING ROOM
107
UP
D
STAIR
106
LOBBY
108
UP E
TARRANT COUNTY
G
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
AREA A AREA B
BUILDING J
J ISSUED: 04-09-2020
DRAWN BY: NR
REVISIONS:
L
NORTH
U
N
PROJECT NO.
4/9/2020 15:05:03
02470420015
SHEET NO:
0 8' 16' 32' 48'
1/16" = 1'-0"
AREA B: 1/JA.1.12
153 NEW CONDENSER, REF. MECHANICAL
153 153 231 REPLACE EXISTING GLASS WINDOW LITE WITH NEW COMPOSITE
231 METAL PANEL SPANDREL; CUT OAL-A LOUVER INTO PANEL AS
232 SCHEDULED BY MECHANICAL. TEXAS REGISTERED ENGINEERING
FIRM F-2966
232 REPLACE EXISTING SPANDREL AT UPPER LITE WITH NEW 777 MAIN ST. STE B-101
COMPOSITE METAL PANEL SPANDREL; COORDINATE OPENING FOR
FORT WORTH, TEXAS 76102
EXHAUST FLUE PASSING THROUGH SPANDREL WITH MECHANICAL.
DISCONNECT AND REROUTE ANY UTILITIES THROUGH NEW
A SPANDREL. ENSURE ALL PENETRATIONS ARE WATERTIGHT.
104
BREAKROOM
105
1
JA.4.03 104
104
1
2
JA.4.01
JA.4.01
J103
MEETING ROOM
BUILDING J RENOVATIONS
TARRANT COUNTY
STAIR
106
UP
D
J106
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
104
LOBBY
108
E
UP Building Key Plan:
AREA A
153
BUILDING J
DRAWN BY: NR
REVISIONS:
L
NORTH
U
N
PROJECT NO.
4/9/2020 15:05:05
02470420015
SHEET NO:
0 4' 8' 16' 24'
1/8" = 1'-0"
AREA A: 1/JA.1.11
EQ. EQ. WHILE RENOVATION WORK IS UNDERWAY. CONTRACTOR SHALL
COORDINATE WITH PROJECT MANAGER TO IDENTIFY SECURE
AND/OR "OFF-LIMITS" AREAS IN THE BUILDING. Texas
2 REFER TO SHEET A.7.00 FOR PARTITION TYPES. Department
2 of Transportation
1 3 DO NOT SCALE DRAWINGS FOR CONSTRUCTION PURPOSES.
J109C
J109B
J109A
____________________________________________________
____________________________________________________
BAY 1
109
UP
D
TARRANT COUNTY
JA.4.02
J102B
E
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
MENS LOCKER
OFFICE ROOM
111 102
AREA B
BAY 2
110 BUILDING J
G
BUILDING J - AREA B FLOOR PLAN - LEVEL 1 Site Key Plan:
1 1/8" = 1'-0"
J ISSUED: 04-09-2020
DRAWN BY: NR
REVISIONS:
L
NORTH
U
N
PROJECT NO.
4/9/2020 15:05:07
02470420015
H SHEET NO:
0 4' 8' 16' 24'
1/8" = 1'-0"
AREA A: 1/JA.1.21
TEXAS REGISTERED ENGINEERING
FIRM F-2966
777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
A
TELECOM ROOM
203
DN
102
B
OFFICE
WAREHOUSE 202
201
OFFICE
205
OPEN TO C
DN
BELOW
RESTROOM
204
DN
D
DN
AREA A AREA B
BUILDING J
J ISSUED: 04-09-2020
DRAWN BY: NR
REVISIONS:
L
NORTH
U
N
PROJECT NO.
4/9/2020 15:05:09
02470420015
SHEET NO:
0 8' 16' 32' 48'
1/16" = 1'-0"
AREA A: 1/JA.1.21
UP
TEXAS REGISTERED ENGINEERING
1
TELECOM ROOM FIRM F-2966
JA.5.02 203 777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
A
J203
6' - 0"
PAINT INTERIOR OF
12' - 9"
ROOM AND BOTH A3
J201
DN SIDES OF ALL NEW
PARTITIONS PT-1.
PROVIDE RB-1 AT ALL
NEW PARTITIONS. 236
A3
8' - 0"
B
RAMP DN
J201B OFFICE 2
202
DOCK JA.4.21
18' - 0"
WAREHOUSE
201
J202
MATCHLINE
MATCHLINE
1
____________________________________________________
JA.5.05 2
JA.5.01 OFFICE
205
BUILDING J RENOVATIONS
RESTROOM
JA.4.21
TARRANT COUNTY
D
DN
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
E
Building Key Plan:
AREA A
ROOF BELOW
BUILDING J
DRAWN BY: NR
REVISIONS:
L
NORTH
U
N
PROJECT NO.
4/9/2020 15:05:11
02470420015
SHEET NO:
0 4' 8' 16' 24'
1/8" = 1'-0"
0' - 0"
062 062 062
2
____________________________________________________
1
JA.5.04 ____________________________________________________
JA.5.04
1 1.9 2 3 4 5 6 7
EQ. 15' - 0" EQ. EQ. 15' - 0" EQ. EQ. 15' - 0" EQ. 217
TYP.
LEGEND
LEVEL 2
BUILDING J RENOVATIONS
EXISTING WINDOWS, DOORS, AND OTHER
TARRANT COUNTY
EXISTING CORRUGATED METAL WALL PANAEL
SYSTEM
EXTERIOR ELEVATION AT OVERHEAD DOORS
2 1/8" = 1'-0"
A B C D E
6' - 0" 12' - 0"
087
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
REMOVE V.I.F
LEVEL 2
10' - 10"
DOCK LEVEL
092 011 010 087 7' - 1"
A B C D E
1
____________________________________________________
JA.5.05
18' - 0" Site Key Plan:
J ISSUED: 04-09-2020
LEVEL 2 N
10' - 10"
PROJECT NO.
4/9/2020 15:05:14
02470420015
DOCK LEVEL
SHEET NO:
406 102 206 7' - 1" 0 4' 8' 16' 24'
EXTERIOR ELEVATION @ DOCK
4 1/8" = 1'-0"
1/8" = 1'-0"
ELEVATIONS
JA.2.01
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
ENLARGED PLAN GENERAL NOTES R
J104
129 TILE FLOOR
REF.
3 129
J103
7 133 SEMI-RECESSED PAPER TOWEL DISPENSER AND WASTE THIS DRAWING CREATED
129 PTF-1 RECEPTACLE PTWR-1; REF. A.5.01 FOR PRODUCTION ON
22"x34" SHEET SIZE.
137 MIRROR WITH FRAME MG-1, REF. A.5.01
5 JA.4.01 6 PTF-1 DO NOT SCALE PRINTS.
9 JA.4.01 10 142 WALL MOUNTED SOAP DISPENSER SD-1; REF. A.5.01
143 143 RECESSED HAND DRYER HD-1; REF. A.5.01
144 143
4 144 144 TOILET PAPER DISPENSER TTD-1; REF. A.5.01
8 149 TOILET SEAT-COVER DISPENSER TSCD-1; REF. A.5.01
CT-1 WALL TILE
CTB-1 CERAMIC TILE BASE TEXAS REGISTERED ENGINEERING
142 FIRM F-2966
PT-1 PAINTED WALL COLOR 777 MAIN ST. STE B-101
142 PTF-1 PORCELAIN TILE FLOORING FORT WORTH, TEXAS 76102
PT-1
133 PT-1
143 149
142
PT-1 CT-1
137 PT-1
144
CT-1 CT-1
CT-1
3' - 10"
CTB-1 CTB-1
3' - 3"
3' - 3"
3' - 3"
3' - 3"
CTB-1
LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1
0' - 0" 0' - 0" 0' - 0" 0' - 0"
9 9
TARRANT COUNTY
PT-1
133 PT-1
PT-1
137
143
PT-1 149
142
CT-1
CT-1
144 CT-1
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
CT-1
CTB-1
3' - 3"
3' - 3"
3' - 3"
3' - 3"
CTB-1 CTB-1 CTB-1
LEVEL 1 LEVEL 1 LEVEL 1 LEVEL 1
0' - 0" 0' - 0" 0' - 0" 0' - 0"
WOMENS NORTH WALL WOMENS SOUTH WALL WOMENS WEST WALL WOMENS EAST WALL
7 1/4" = 1'-0"
8 1/4" = 1'-0"
9 1/4" = 1'-0"
10 1/4" = 1'-0"
J ISSUED: 04-09-2020
DRAWN BY: NR
REVISIONS:
L
NORTH
U
N
PROJECT NO.
4/9/2020 15:05:18
02470420015
SHEET NO:
0 2' 4' 8' 12'
E3
REFLECTED CEILING PLAN NOTES
A REFER TO ELECTRICAL FOR PLACEMENT OF NEW LIGHT FIXTURES.
L1 B REINSTALL, REPAIR, RE-LEVEL, AND/OR RE-FINISH ANY CEILINGS THIS DRAWING CREATED
144 REMOVED, MODIFIED, OR DAMAGED DURING ABOVE-CEILING FOR PRODUCTION ON
UTILITY WORK. CEILINGS SHALL BE RETURNED TO ORIGINAL 22"x34" SHEET SIZE.
116 CONDITION; RE: MECHANICAL, PLUMBING, AND ELECTRICAL FOR
DO NOT SCALE PRINTS.
S
132 SHELVING
2' - 6"
5
A3 TYP. 133 SEMI-RECESSED PAPER TOWEL DISPENSER AND WASTE
173 148 RECEPTACLE PTWR-1; REF. A.5.01
7
129 138 LARGE FRAME MIRROR
L1 4 JA.4.02 3
147 PTF-1 E3 140 ACCESSIBLE SHOWER STALL; REF. SH1/A.5.01
142 141 STANDARD SHOWER STALL; REF. SH2/A.5.01
JA.4.02 6' - 5" 197
142 WALL MOUNTED SOAP DISPENSER SD-1; REF. A.5.01
143 RECESSED HAND DRYER HD-1; REF. A.5.01
244 144 TOILET PAPER DISPENSER TTD-1; REF. A.5.01
129 172
8' - 6"
JA.4.02 147 ACCESSIBLE URINAL; REF. U2/A.5.01
J102B A3 190
PTF-1 148 URINAL SCREEN SC1; REF. A.5.01
L1 104 151 OPEN TO STRUCTURE ABOVE
6 E E 154 CURTAIN ROD SCR; REF. A.5.01
142 151 159 STANDARD TOILET STALL; REF. S1/A.5.01
L1 A3
A3
A6 143 160 ACCESSIBLE TOILET STALL; REF. S3/A.5.01
172 EXPOSED DUCTWORK; REF. MECHANICAL. PAINT DUCTWORK,
132 ANCHORS, AND HANGERS TO MATCH SCHEDULED CEILING COLOR.
5' - 6 1/2" A3 3' - 2" 8
173 STONE THRESHOLD
L1 189 NEW PAINTED GYP BD CEILING ON METAL FRAMING.
121 190 EXTEND WALL TO FULL HEIGHT; MATCH FRAMING AND FINISH.
JA.4.02
L1 197 PREP DRYWALL CEILING, HEADERS, AND TRIM FOR NEW PAINT
FINISH. REMOVE ALL LOOSE PAINT, SCALE, OR OTHER
DETERIORATED FINISHES AND ALL UNUSED ANCHORS OR
SUPPORTS. PATCH ALL HOLES AND PAINT AS SCHEDULED.
216 L-SHAPE GRAB BAR GB-2; REF. A.5.01
244 NEW 3 STATION ACCESSIBLE WALL MOUNTED SINK WITH TUBULAR
SUPPORTS. ELECTRONIC OPERATED
402 FOLDING SHOWER SEAT FSS-1; REF. A.5.01
CT-1 WALL TILE
CTB-1 CERAMIC TILE BASE
BUILDING J RENOVATIONS
1/4" = 1'-0" 1/4" = 1'-0"
TARRANT COUNTY
CT-1 PT-1
CT-1
160
PT-1 CT-1
121 121
CT-1
7' - 0"
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
3' - 3"
3' - 3"
2' - 10"
CTB-1
LEVEL 1 LEVEL 1
0' - 0" 0' - 0"
244 148 CTB-1 144
4 4 132
PT-1
133 OPEN 154 154 OPEN
CT-1 143
7' - 0"
7' - 0"
140 141 121
CT-1 CT-1 Site Key Plan:
CT-1 OPEN OPEN
216
CTB-1
3' - 3"
3' - 3"
3' - 3"
CTB-1 J ISSUED: 04-09-2020
MENS LOCKER ROOM NORTH WALL MENS LOCKER ROOM SOUTH WALL MENS LOCKER ROOM SHOWER MENS LOCKER ROOM U
5 6 7 1/4" = 1'-0"
8 1/4" = 1'-0"
1/4" = 1'-0" 1/4" = 1'-0"
N
PROJECT NO.
4/9/2020 15:05:22
02470420015
SHEET NO:
0 2' 4' 8' 12'
A.5.03 A.5.03
1
____________________________________________________ TEXAS REGISTERED ENGINEERING
FIRM F-2966
A.5.03
777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
3
____________________________________________________
A.5.03 4
3 JA.4.03
TARRANT COUNTY
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
B A
119
PT-1
TO NEAREST INSIDE 119
CORNER
2' - 6"
1' - 8"
PT-1
TO NEAREST INSIDE
CORNER
2' - 10"
2' - 10"
LEVEL 1 LEVEL 1
0' - 0" 0' - 0"
180 120 RB-1 120 RB-1
J ISSUED: 04-09-2020
DRAWN BY: NR
REVISIONS:
L
NORTH
U
N
PROJECT NO.
4/9/2020 15:05:25
02470420015
SHEET NO:
0 2' 4' 8' 12'
11' - 0"
8 JA.4.21 10
KEYNOTES
188 021 EXISTING WINDOW TO REMAIN
RESTROOM
079 REMOVE EXISTING CEILING GRID AND TILE SYSTEM AS INDICATED TEXAS REGISTERED ENGINEERING
J204 204 FIRM F-2966
FLOORING BY DASHED LINES. REMOVE EXISTING LIGHT FIXTURES
777 MAIN ST. STE B-101
TERMINATION / OFFICE 113 HI-IMPACT XP GYPSUM BOARD
FORT WORTH, TEXAS 76102
TRANSITION 202 114 ALIGN WALLS
J202 114 116 LIGHT FIXTURE; REF. ELECTRICAL
STRIP
127 LVT FLOORING; CFCI
143
114 133 SEMI-RECESSED PAPER TOWEL DISPENSER AND WASTE
RECEPTACLE PTWR-1; REF. A.5.01
137 MIRROR WITH FRAME MG-1, REF. A.5.01
143 RECESSED HAND DRYER HD-1; REF. A.5.01
ENLARGED PLAN - RESTROOM 204 ENLARGED PLAN - OFFICE 202 144 TOILET PAPER DISPENSER TTD-1; REF. A.5.01
1 1/4" = 1'-0"
2 1/4" = 1'-0" 145 ACCESSIBLE TOILET; REF. S2/A.5.01
149 TOILET SEAT-COVER DISPENSER TSCD-1; REF. A.5.01
169 NEW 2x2 CEILING TILE AND GRID
RESTROOM RESTROOM 181 42" MINIMUM GRAB BAR
204 204 B 182 36" MINIMUM GRAB BAR
079 188 NEW ACCESSIBLE SINK; REF. PLUMBING
116 TYP. OFFICE 8' - 0" 191 MATCH EXISTING WALL HEIGHT
202 116 TYP. CT-1 WALL TILE
CTB-1 CERAMIC TILE BASE
LVT-1 LVT FLOORING
169 169 PT-1 PAINTED WALL COLOR
PT-2 PAINTED WALL COLOR
RB-1 RUBBER WALL BASE
8' - 0"
BUILDING J RENOVATIONS
TARRANT COUNTY
143
181 133
182
CT-1
144 CT-1
CT-1 CTB-1
3' - 3"
3' - 3"
3' - 3"
3' - 3"
CTB-1
CTB-1
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
AREA A
B C 9 10 B
18' - 9 1/4" V.I.F.
J ISSUED: 04-09-2020
9' - 2" V.I.F.
DRAWN BY: NR
REVISIONS:
L
U
LEVEL 2 LEVEL 2 LEVEL 2
N
10' - 10" 10' - 10" 10' - 10"
RB-1 PT-2 113 RB-1 113 PT-2 PROJECT NO.
021
4/9/2020 15:05:30
4"
1 1/2" DIA. PAINTED STEEL 1' - 0"
P)
22"x34" SHEET SIZE.
INTERMEDIATE RAIL BRACKET
(TY
DO NOT SCALE PRINTS.
HANDRAIL
1' - 6"
EQUALLY SPACED RETURN HANDRAIL
1" O.D. STEEL PIPE BACK TO POST
1 1/2" O.D. STEEL INTERMEDIATE RAIL,
PIPE POST, WELD TO EQUALLY SPACED 1 1/2" OD STEEL PIPE
4"
4"
(TY
STRINGER
(TY
TEXAS REGISTERED ENGINEERING
POST, WELD TO
1' - 6"
FIRM F-2966
1 1/2" O.D. STEEL PIPE
P)
P)
RETURN HANDRAIL POST, WELD TO STRINGER STRINGER 777 MAIN ST. STE B-101
1" O.D. STEEL PIPE FORT WORTH, TEXAS 76102
BACK TO POST
STEEL CHANNEL STRINGER, INTERMEDIATE RAIL
2' - 10"
UP
RAILING AT STAIR BOTTOM RAILING AT STAIR RUN TYP RLG AT TOP OF STAIR RUN D
3 1" = 1'-0"
4 1" = 1'-0"
5 1" = 1'-0" A3
21
/2"
STEEL CHANNEL STRINGER OF EXISTING BEAM TO A3
RESIST TOTAL APPLIED
CONCRETE FILLED STEEL STRINGER REACTION CONCRETE
2 1/2" PAN TREADS FILLED STEEL STAIR PLAN LEVEL 1
EXISTING 52" WORKING REF LINE PAN TREADS 1
BUILDING J RENOVATIONS
FLOOR AS 1/4" PLATE STRINGER STEEL CHANNEL
TARRANT COUNTY
STRINGER ATTACH TO FLR CONCRETE
NOSING
W/ 5/8" DIA EXP BOLT FILLED
STEEL PAN
TREADS
DN
STAIR TO CONCRETE SLAB CONNECTION FLOOR TO STAIR CONNECTION CONCRETE FILLED STEEL PAN TREAD
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
6 1 1/2" = 1'-0"
7 1 1/2" = 1'-0"
8 1 1/2" = 1'-0"
406
408
1 1/2" O.D.STEEL
1 1/2" O.D. STEEL 1 1/2" O.D. STEEL
PIPE RAIL
5"
5"
1' - 9"
5/8" DIA STEEL 1" O.D. STEEL PIPE
BAR BRACKET INTERMEDIATE RAIL 1 1/2" O.D. STEEL
EQ
EQ
INTERMEDIATE RAIL
1 1/2" O.D. STEEL
EQ
EQ
2' - 10"
1/4" = 1'-0"
EQ
STEEL CHANNEL
EQ
CHANNEL
FINISH FLOOR AS J ISSUED: 04-09-2020
SCHEDULED FINISH FLOOR
4"
AS SCHEDULED
4"
U
2 1/2"
2 1/2"
N
PROJECT NO.
4/9/2020 15:05:32
ALIGN
KEYNOTES
406 102 406 102 NEW ACCESSIBLE CONC RAMP AND LANDINGS; REF. ALSO
STRUCTURAL
THIS DRAWING CREATED
184 EXISTING LOADING RAMP FOR PRODUCTION ON
22"x34" SHEET SIZE.
4' - 3" 205 INSULATED HOLLOW METAL DOOR, AS SCHEDULED DO NOT SCALE PRINTS.
206 INSULATED OVERHEAD COILING DOOR, AS SCHEDULED
9' - 5 1/2" 205
406 1 1/2" PAINTED STEEL GUARDRAIL WITH HANDRAIL; REF. JA.5.01
10' - 10" 407 1 1/2" PAINTED STEEL GUARDRAIL; REF. JA.5.01
411 PAINT EXISTING GUARD RAIL PT-3
3 V.I.F.
4' - 4" V.I.F.
3
JA.5.05
411
B
7' - 1"
206
V.I.F.
J201B
184 411
4
JA.5.02
TARRANT COUNTY
205 206 406
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
407
406 411
102 102
EXISTING EXISTING
DOCK DOCK
EXISTING EXISTING
GRADE GRADE
J ISSUED: 04-09-2020
DRAWN BY: NR
REVISIONS:
L
NORTH
U
N
PROJECT NO.
4/9/2020 15:05:36
02470420015
SHEET NO:
0 2' 4' 8' 12'
1/4" = 1'-0"
Texas
Department
of Transportation
E3
3' - 0"
TARRANT COUNTY
PLAN DETAIL- MENS LOCKER ROOM
1 1 1/2" = 1'-0"
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
TYPICAL PORCELAIN TILE BASE TYPICAL DRAIN AT TILE FLOOR THIN-SET DETAIL TYPICAL LOCKER BASE DETAIL
2 3" = 1'-0"
3 3" = 1'-0"
5 3" = 1'-0" 0 3" 6" 1' PROJECT NO.
4/9/2020 15:05:37
02470420015
3" = 1'-0"
SHEET NO:
0 6" 1' 2'
1 1/2" = 1'-0"
INTERIOR DETAILS
JA.5.03
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
KEYNOTES R
A A A 107 14'-2" X 15'-0" W MOTOR OPERATED OVERHEAD DOOR
193 EXISTING STRUCTURAL STEEL COLUMN
217 EXISTING TRANSLUCENT WALL PANEL SYSTEM
Texas
315 PREFINISHED METAL FLASHING TO MATCH EXISTING
Department
343 EXISTING BRICK VENEER of Transportation
EXISTING 344 MTL STUD FRAMING
345 7/8" FURRING HAT CHANNELS
TRANSLUCENT WALL
346 METAL WALL PANEL, MATCH EXISTING
SYSTEM ASSEMBLY
347 BACKER ROD AND SEALANT
THIS DRAWING CREATED
348 EXISTING METAL WALL PANEL SYSTEM FOR PRODUCTION ON
22"x34" SHEET SIZE.
351 INSULATION DO NOT SCALE PRINTS.
MTL STUD
FRAMING
3 SEALANT JOINT
JA.5.04
PREFINISHED
METAL FLASHING
WITH DRIP EDGE
7
JA.5.04
TARRANT COUNTY
INSULATED DOOR
C10X15.3 GALV AS SCHEDULED
PTD STL CHANNEL
GALVANIZED STEEL DOUBLE
ANGLE BOTTOM BAR
5 1/2"
GUIDE TRACK SEAL
.
FINISH FLOOR
DOOR WIDTH AS
LEVEL 1
LEVEL 1 LEVEL 1
SEALANT; TYP 0'-0"
SHEDULED
0' - 0" 0' - 0"
INSULATED DOOR
PAVING BY OTHERS
5 AS SCHEDULED
JA.5.04 PREFINISHED MTL
JAMB EXTRUSION
WALL SECTION @ GARAGE WALL SECTION @ WINDOW FILL OH DR JAMB - EXT MTL PNL OH COILING DOOR SILL
1 1/2" = 1'-0"
2 1/2" = 1'-0"
4 1 1/2" = 1'-0"
5 3" = 1'-0"
A
344
345
348
351
DRAWN BY: NR
347
REVISIONS:
L
344 U
343
346 N
02470420015
3" = 1'-0"
SHEET NO:
0 6" 1' 2'
WINDOW FILL - SILL DETAIL WINDOW FILL HEAD DETAIL
6 3" = 1'-0"
7 3" = 1'-0"
EXTERIOR DETAILS & WALL SECTIONS
1 1/2" = 1'-0"
JA.5.04
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
R
Texas
Department
of Transportation
EXISTING CMU
TEXAS REGISTERED ENGINEERING
FIRM F-2966
777 MAIN ST. STE B-101
BOLT; REFER STRUCTURAL FORT WORTH, TEXAS 76102
2
JA.5.05
STEEL LINTEL; REFER
STRUCTURAL
OVERHEAD DOOR AS
SCHEDULED
LEVEL 2
TARRANT COUNTY
C:\Users\sangercd\Documents\TXDOT_FW-A-BldgJ-R18-Central_SangerCD.rvt
EXISTING CMU
SEALANT; TYP
STEEL PLATE
GUIDE TRACK
THERMAL/AIR SEAL
J ISSUED: 04-09-2020
DRAWN BY: NR
REVISIONS:
L
02470420015
3" = 1'-0"
SHEET NO:
0 1' 2' 4' 6'
1/2" = 1'-0"
2"
BADGE READER (COORDINATE WITH OWNER'S EXISTING SYSTEM)
5"
ELECTRIC STRIKE (FAIL SECURE, COORDINATE WITH OWNER'S EXISTING SYSTEM)
1' - 6"
WALL BUMPER
AS SCHEDULED
4"
FRAME SILENCERS
AS SCHEDULED
AS SCHEDULED
AS SCHEDULED
AS SCHEDULED
3' - 0"
AS SCHED
3 PAIR HINGES (VERIFY QUANTITY AND SIZE IF REUSING EXISTING FRAME)
ACCESSIBLE LOCKSET - STOREROOM FUNCTION (ACTIVE LEAF)
TOP AND BOTTOM FLUSH BOLTS (INACTIVE LEAF)
4' - 0"
2X CLOSER
2X FLOOR BUMPER
2X FLOOR STOP
SPLIT ASTRAGAL WEATHERSTRIPPING
2X BRUSH SWEEP
SINGLE FLUSH SINGLE FLUSH SINGLE FLUSH PAIR FLUSH OVERHEAD COILING THRESHOLD
NARROW LITE HALF LITE DOOR/GRILLE STEEL DOOR STD FRAME WEATHERSTRIPPING AT FRAME
TYPE A TYPE B TYPE C TYPE D TYPE E TYPE A HARDWARE SET 5 - TYPICAL UTILITY ROOM
1 1/2 PAIR HINGES (VERIFY QUANTITY AND SIZE IF REUSING EXISTING FRAME)
ACCESSIBLE LOCKSET - STOREROOM FUNCTION
RE: PLANS FURRING CHANNEL CLOSER
HAT -SHAPED WALL BUMPER
PARTITION AS CONT. INSULATION FRAME SILENCERS
CONT. MTL FLASHING W/
SCHEDULED WEEP HOLES @ 24" O.C.; HARDWARE SET 6 - TYPICAL LOCKER ROOM
BUILDING J RENOVATIONS
CMU VENEER AS INSTALLED IN EXISTING FRAME SILENCERS
METAL STUD
3/8"
CMU WALL AS SCHEDULED; HOLLOW METAL
DOOR HEIGHT AS SCHED 2"
TARRANT COUNTY
5/8" GYP. BD.
SCHEDULED
DOOR HEIGHT
HOLLOW METAL SHIM, BACKER ROD, AND
SHIM, BACKER ROD,
AS SCHED
NEOPRENE DOOR
1/4"
4"
AND SEALANT BOTH SWEEP
4"
AS SCHEDULED
AS SCHED
DOOR AS SCHEDULED
DOOR HEIGHT
1 15/16" 1 15/16" WITH GROUT FINISH FLOOR, AS SCHEDULED
1 15/16" 1 15/16"
DOOR AS
V.I.F.
1 15/16" 1 15/16" SCHEDULED
5 3/4"
5 3/4"
5 3/4" DOOR AS N
1 15/16" 5 3/4" 1 15/16" SCHEDULED PROJECT NO.
4/9/2020 15:05:43
02470420015
SHEET NO:
0 3" 6" 1'
DR JAMB AT GYP BD WALL EXTERIOR JAMB DETAIL JAMB DETAIL - CMU WALL
7 3" = 1'-0"
8 3" = 1'-0"
9 3" = 1'-0"
BLDG BUILDING 4. CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL PIPING, DRAINS, AND CLEANOUTS WITH
BLW BELOW N2 NITROGEN ALL TRADES AND DRAWINGS PRIOR TO COMMENCING INSTALLATION. NO ADDITIONAL COST TO THE
BMS BUILDING MANAGEMENT SYSTEM NC NORMALLY CLOSED BALANCING VALVE (SEE SPEC FOR TYPE) OWNER WILL BE ALLOWED IF ATTRIBUTED TO A FAILURE TO COORDINATE.
BOP BOTTOM OF PIPE NEG NEGATIVE
BOT BOTTOM NFGH-X NON-FREEZE GROUND HYDRANT
BSMT BASEMENT 5. PLUMBING CONTRACTOR SHALL REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION
NFWH-X NON-FREEZE WALL HYDRANT OF SINKS AND FIXTURES. TEXAS REGISTERED ENGINEERING
BTU BRITISH THERMAL UNIT NIC NOT IN CONTRACT GAS COCK FIRM F-2966
BWV BACKWATER VALVE NG NATURAL GAS 777 MAIN ST. STE B-101
No NUMBER 6. ALL PIPING INCLUDING WATER, SANITARY, AND VENT INDICATED ON THE PLANS SHALL BE LOCATED FORT WORTH, TEXAS 76102
C DEGREES CENTIGRADE NO NORMALLY OPEN ABOVE FINISHED CEILING, IN CHASES, SHAFTS, OR WALL CAVITIES UNLESS SHOWN OR NOTED
CHECK VALVE - (SEE SPEC FOR TYPE)
CA COMPRESSED AIR NPW NON-POTABLE WATER OTHERWISE.
CAF COMPRESSED AIR FILTER NTS NOT TO SCALE
CBV CIRCUIT BALANCING VALVE 7. ALL STORM, SANITARY WASTE PIPING 3" AND LARGER SHALL SLOPE 1/8" PER FOOT. ALL STORM, SANITARY, AND WASTE PIPING
NOM NOMINAL
CFH CUBIC FEET PER HOUR SAFETY/RELIEF VALVE WASTE PIPING 2" AND LESS SHALL SLOPE 1/4" PER FOOT.
CFM CUBIC FEET PER MINUTE O2 OXYGEN
CI CAST IRON OD OUTSIDE DIAMETER 8. ALL VENTS THAT CONNECT TO HORIZONTAL DRAINAGE PIPES SHALL HAVE ITS INVERT TAKEN OFF
CIP CLEAN IN PLACE OFD OVERFLOW DRAIN ABOVE THE DRAINAGE CENTER LINE. ALL VENT PIPING SHALL HAVE A POSITIVE SLOPE TOWARDS THE
PRESSURE REGULATING VALVE DRAINS THAT THEY SERVE.
CL CENTER LINE OPG OPENING
CLG CEILING OS OPEN SITE DRAIN
OS&Y OUTSIDE SCREW & YOKE 9. ALL NATURAL GAS PIPING SHALL BE INSTALLED IN CONFORMANCE WITH THE NATIONAL FUEL CODE (NFPA-54), E O F T EX
CO CLEAN OUT P PRESSURE GAUGE W/ GAUGE COCK AT A
COL COLUMN GOVERNING MECHANICAL AND PLUMBING CODE, AND THE REQUIREMENTS OF THE GAS UTILITY COMPANY. ST S
(SEE SPEC FOR RANGE)
CONC CONCRETE P PUMP
CONN CONNECTION P/LW PUMPED LAB WASTE 10. NATURAL GAS EQUIPMENT SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER RECOMMENDATIONS.
T PROVIDE DIRT LEGS AT THE BASE OF THE RISERFOR ALL EQUIPMENT CONNECTIONS.
CONT'D CONTINUATION P/SAN PUMPED SANITARY WASTE THERMOMETER-STEM - (SEE SPEC FOR RANGE) PHILLIP K. DEWOLFE
CONTR CONTRACTOR PC PUMPED CONDENSATE
102003
PH PHASE
R
11. RISER DIAGRAMS SHALL BE USED PRIMARILY FOR THE SIZING OF PIPING AND NOT NECESSARILY FOR
PR
EE
LI
DCW DOMESTIC COLD WATER PI PRESSURE INDICATOR PIPING ARRANGEMENT. FE C ENS ED
O
IN
DD DESICCANT AIR DRYER PRESS PRESSURE SS G
PUMP IO NA L E N
DEG DEGREE PRV PRESSURE REDUCING VALVE
DET DETAIL PS PRESSURE SWITCH 12. CONTRACTOR SHALL PROVIDE AND INSTALL DIELECTRIC UNIONS WHEN CONNECTING PIPING AND/OR
DFU DRAINAGE FIXTURE UNIT PSI POUNDS PER SQUARE INCH EQUIPMENT OF DISSIMILAR MATERIALS. 04/09/2020
PSIG POUNDS PER SQUARE INCH GAUGE DEMOLISHED PIPING
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN PSIA POUNDS PER SQUARE INCH ABSOLUTE
DIA DIAMETER PT PRESSURE TRANSMITTER 13. ALL DIMENSIONS, ELEVATIONS, AND EXISTING CONDITIONS SHALL BE CHECKED AND
VB
DIS DEIONIZED WATER SUPPLY PVC POLYVINYL CHLORIDE VERIFIED BY CONTRACTOR AT THE SITE BEFORE PROCEEDING WITH WORK.
VACUUM BREAKER
DIR DEIONIZED WATER RETURN
DISCH DISCHARGE QC QUICK CONNECT COUPLING 14. VALVES, SHOCK ABSORBERS, AND TRAP PRIMERS ARE TO BE LOCATED IN ACCESSIBLE LOCATION,
DIV DIVISION QD QUICK DISCONNECT OR PROVIDED WITH AN ACCESS PANEL. LOCATIONS OF ANY ACCESS PANELS ARE TO BE
DIW DOWN IN WALL QTY QUANTITY HB HOSE BIBB COORDINATED WITH ARCHITECTURAL AND INTERIOR DRAWINGS AND VERIFIED BY CONTRACTOR AT
DN DOWN THE SITE BEFORE PROCEEDING WITH WORK
DWG DRAWING RAC RUN ABOVE CEILING
DWV DRAINAGE, WASTE & VENT RAF RUN ABOVE FLOOR WATERHAMMER ARRESTER (TYPE AS NOTED) 15. A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH SANITARY WASTE STACK, RAINWATER
RBC RUN BELOW CEILING CONDUCTOR AND EXTERIOR CAST IRON STORM BOOTS.
(E) EXISTING RBF RUN BELOW FLOOR
BUILDING J RENOVATIONS
EQUIP EQUIPMENT RM ROOM 18. CLEAN THE JOB SITE DAILY AND REMOVE FROM THE PREMISES ANY DIRT AND DEBRIS
TARRANT COUNTY
20. COORDINATE ALL VENTS THROUGH THE ROOF WITH DUCT WORK.
EXP EXPANSION SS/EW SAFETY SHOWER / EYE WASH
EXT EXTERNAL SA-X SHOCK ABSORBER
EWH ELECTRIC WATER HEATER SAN SANITARY 21. PROVIDE CHROME PLATED ESCUTCHEONS ON FINISHED SIDES WHERE EXPOSED PIPING
RISE OR DROP
SE SEWAGE EJECTOR PENETRATES ALL FINISHED SPACES AND ROOMS.
F DEGREES FAHRENHEIT SH SHOWER
22. REFER TO AND COORDINATE FINISH ROOM SCHEDULE FOR FLOORING TYPES BEFORE
C:\Users\greenwko\Documents\TXDOT_FW-P-BldgJ-R18-Central_keith.greenwade.rvt
AREA A: 1/JPD.1.11
AREA A: 1/JPD.1.12
ABANDONED ABOVE CEILING OR IN WALL CHASES THAT WILL NOT
BE REUSED.
E ALL PIPING TO BE REMOVED SHALL BE TAKEN BACK TO ABOVE
CEILING OR BELOW SLAB. DO NOT LEAVE PIPE ABANDONED IN
12 11 10 9 8 7 6 5 4 3 2 1.9 1 WALLS, COORDINATE REPAIR OF WALL SURFACES WITH FINISHES
PER ARCHITECT. TEXAS REGISTERED ENGINEERING
FIRM F-2966
F PRIOR TO STARTING ANY WORK, CONTRACTOR SHALL INSPECT
EXISTING UNDERGROUND SANITARY SYSTEM WITH CAMERA FROM 777 MAIN ST. STE B-101
CLEANOUT OUTSIDE OF BUILDING THROUGHOUT PIPING UNDER FORT WORTH, TEXAS 76102
A SLAB. PROVIDE VIDEO COPY OF RESULTS TO OWNER.
DW
B
REF.
E O F T EX
AT A
ST S
PHILLIP K. DEWOLFE
102003
R
PR
C
EE
LI
REF.
FE C ENS ED
O
IN
SS G
IO NA L E N
REF.
04/09/2020
DW
D
(N)
E
TARRANT COUNTY
G
C:\Users\greenwko\Documents\TXDOT_FW-P-BldgJ-R18-Central_keith.greenwade.rvt
AREA A AREA B
BUILDING J
J ISSUED: 04-09-2020
N
4/9/2020 2:22:15 PM
PROJECT NO.
02470420015
BUILDING J - OVERALL DEMO PLUMBING PLAN - LEVEL 1
1 1/16" = 1'-0" SHEET NO:
0 8' 16' 32' 48'
1/16" = 1'-0"
AREA B: 1/JPD.1.12
CEILING OR BELOW SLAB. DO NOT LEAVE PIPE ABANDONED IN
12 11 10 9 8 WALLS, COORDINATE REPAIR OF WALL SURFACES WITH FINISHES
PER ARCHITECT. TEXAS REGISTERED ENGINEERING
FIRM F-2966
F PRIOR TO STARTING ANY WORK, CONTRACTOR SHALL INSPECT
EXISTING UNDERGROUND SANITARY SYSTEM WITH CAMERA FROM 777 MAIN ST. STE B-101
CLEANOUT OUTSIDE OF BUILDING THROUGHOUT PIPING UNDER FORT WORTH, TEXAS 76102
SLAB. PROVIDE VIDEO COPY OF RESULTS TO OWNER.
A
KEYNOTES
102 DISCONNECT AND REMOVE EXISTING URINAL. REMOVE EXISTING
SANITARY, DOMESTIC WATER, AND VENT PIPING BACK TO MAINS AND
CAP.
104 DISCONNECT AND REMOVE EXISTING WATER CLOSET. MODIFY
EXISTING SANITARY, DOMESTIC WATER, AND VENT PIPING IN CHASE
AND SLAB AS REQUIRED FOR NEW WATER CLOSET THAT WILL BE E O F T EX
AT A
109 INSTALLED IN SAME GENERAL LOCATION. ST S
DW
109 DISCONNECT AND REMOVE EXISTING SINK. MODIFY EXISTING
SANITARY, DOMESTIC WATER, AND VENT PIPING IN WALL AS
REQUIRED FOR NEW SINK THAT WILL BE INSTALLED IN SAME PHILLIP K. DEWOLFE
GENERAL LOCATION.
102003
R
110 DISCONNECT AND REMOVE EXISTING LAVATORY. MODIFY EXISTING
PR
EE
LI
SANITARY, DOMESTIC WATER, AND VENT PIPING IN CHASE AS FE C ENS ED
O
IN
SS G
REQUIRED FOR NEW LAVATORY THAT WILL BE INSTALLED IN SAME IO NA L E N
GENERAL LOCATION.
B 111 EXISTING ELECTRIC WATER COOLER TO REMAIN.
04/09/2020
REF.
117 EXISTING SERVICE SINK TO REMAIN.
118 EXISTING SINK TO REMAIN.
119 EXISTING ELECTRIC WATER HEATER TO REMAIN.
123 EXISTING WATER CLOSET TO REMAIN.
118
BUILDING J RENOVATIONS
110
117 118
110 102
REF.
104
TARRANT COUNTY
DW
118
C:\Users\greenwko\Documents\TXDOT_FW-P-BldgJ-R18-Central_keith.greenwade.rvt
D
123
111
BUILDING J
J ISSUED: 04-09-2020
N
4/9/2020 2:22:16 PM
PROJECT NO.
02470420015
BUILDING J - AREA A DEMO PLUMBING PLAN - LEVEL 1
1 1/8" = 1'-0" SHEET NO:
0 4' 8' 16' 24'
AREA A: 1/JPD.1.11
A THESE DRAWINGS WERE PRODUCED BASED ON SURVEYED
8 7 6 5 4 3 2 1.9 1 CONDITIONS. CONTRACTOR SHALL BECOME THOROUGHLY
FAMILIAR WITH THE SITE PRIOR TO BID. ANY DEVIATIONS FROM
DRAWINGS SHALL BE REPORTED TO THE ENGINEER PRIOR TO Texas
BEGINNING CONSTRUCTION. Department
B ALL EQUIPMENT AND MATERIAL WITHIN AREAS IDENTIFIED TO BE of Transportation
DEMOLISHED SHALL BE DISCONNECTED AND REMOVED, UNLESS
NOTED OTHERWISE. CONTRACTOR SHALL PROPERLY DISPOSE ALL
DEMOLISHED EQUIPMENT AND MATERIAL.
A C COORDINATE WITH OWNER BEFORE DISPOSAL OF ITEMS TO VERIFY
THIS DRAWING CREATED
IF THEY WANT TO KEEP CERTAIN FIXTURES. FOR PRODUCTION ON
D IN ADDITION TO MATERIAL SPECIFICALLY NOTED TO BE REMOVED, 22"x34" SHEET SIZE.
DO NOT SCALE PRINTS.
THE CONTRACTOR SHALL REMOVE ANY ITEMS OBSERVED
ABANDONED ABOVE CEILING OR IN WALL CHASES THAT WILL NOT
BE REUSED.
E ALL PIPING TO BE REMOVED SHALL BE TAKEN BACK TO ABOVE
CEILING OR BELOW SLAB. DO NOT LEAVE PIPE ABANDONED IN
WALLS, COORDINATE REPAIR OF WALL SURFACES WITH FINISHES
PER ARCHITECT. TEXAS REGISTERED ENGINEERING
FIRM F-2966
F PRIOR TO STARTING ANY WORK, CONTRACTOR SHALL INSPECT
EXISTING UNDERGROUND SANITARY SYSTEM WITH CAMERA FROM 777 MAIN ST. STE B-101
CLEANOUT OUTSIDE OF BUILDING THROUGHOUT PIPING UNDER FORT WORTH, TEXAS 76102
SLAB. PROVIDE VIDEO COPY OF RESULTS TO OWNER.
B KEYNOTES
102 DISCONNECT AND REMOVE EXISTING URINAL. REMOVE EXISTING
SANITARY, DOMESTIC WATER, AND VENT PIPING BACK TO MAINS AND
CAP.
103 DISCONNECT AND REMOVE EXISTING SHOWER. REMOVE EXISTING
SANITARY, DOMESTIC WATER, AND VENT PIPING BACK TO MAINS AND
CAP. E O F T EX
AT A
104 DISCONNECT AND REMOVE EXISTING WATER CLOSET. MODIFY ST S
EXISTING SANITARY, DOMESTIC WATER, AND VENT PIPING IN CHASE
AND SLAB AS REQUIRED FOR NEW WATER CLOSET THAT WILL BE
INSTALLED IN SAME GENERAL LOCATION. PHILLIP K. DEWOLFE
115 DISCONNECT AND REMOVE EXISTING URINAL. MODIFY EXISTING 102003
R
SANITARY, DOMESTIC WATER, AND VENT PIPING IN CHASE AS
PR
EE
LI
REQUIRED FOR NEW URINAL THAT WILL BE INSTALLED IN SAME FE C ENS ED
O
IN
SS G
GENERAL LOCATION. IO NA L E N
130 EXISTING FLOOR DRAIN TO REMAIN.
C
131 DEMO EXISTING FLOOR DRAIN ALONG WITH ASSOCITATED SS AND 04/09/2020
VENT PIPING.
REF.
BUILDING J RENOVATIONS
TARRANT COUNTY
103
MOUNTED HANDWASH SINK. REFER TO JP.1.12
FOR NEW SINK LOCATION.
(N)
SD
103
115
E
C:\Users\greenwko\Documents\TXDOT_FW-P-BldgJ-R18-Central_keith.greenwade.rvt
AREA B
BUILDING J
G
Site Key Plan:
N
4/9/2020 2:22:17 PM
PROJECT NO.
02470420015
H SHEET NO:
0 4' 8' 16' 24'
1/8" = 1'-0"
AREA A: 1/JPD.1.21
12 11 10 9 8 7 6 5 4 3 2 1.9 1
E O F T EX
AT A
ST S
A
PHILLIP K. DEWOLFE
102003
R
PR
EE
LI
FE C ENS ED
O
IN
SS G
IO NA L E N
B
04/09/2020
TARRANT COUNTY
JPD.1.21
C:\Users\greenwko\Documents\TXDOT_FW-P-BldgJ-R18-Central_keith.greenwade.rvt
BUILDING J
J ISSUED: 04-09-2020
N
4/9/2020 2:22:18 PM
PROJECT NO.
02470420015
BUILDING J - OVERALL DEMO PLUMBING PLAN - LEVEL 2
1 1/16" = 1'-0" SHEET NO:
0 8' 16' 32' 48'
1/16" = 1'-0"
A
KEYNOTES
102 DISCONNECT AND REMOVE EXISTING URINAL. REMOVE EXISTING
SANITARY, DOMESTIC WATER, AND VENT PIPING BACK TO MAINS
AND CAP.
104 DISCONNECT AND REMOVE EXISTING WATER CLOSET. MODIFY
EXISTING SANITARY, DOMESTIC WATER, AND VENT PIPING IN CHASE
AND SLAB AS REQUIRED FOR NEW WATER CLOSET THAT WILL BE E O F T EX
AT A
INSTALLED IN SAME GENERAL LOCATION. ST S
110 DISCONNECT AND REMOVE EXISTING LAVATORY. MODIFY EXISTING
SANITARY, DOMESTIC WATER, AND VENT PIPING IN CHASE AS
REQUIRED FOR NEW LAVATORY THAT WILL BE INSTALLED IN SAME PHILLIP K. DEWOLFE
GENERAL LOCATION.
102003
R
PR
EE
LI
FE C ENS ED
O
IN
SS G
IO NA L E N
B
04/09/2020
BUILDING J RENOVATIONS
102
TARRANT COUNTY
C:\Users\greenwko\Documents\TXDOT_FW-P-BldgJ-R18-Central_keith.greenwade.rvt
BUILDING J
J ISSUED: 04-09-2020
N
4/9/2020 2:22:20 PM
PROJECT NO.
02470420015
BUILDING J - AREA A DEMO PLUMBING PLAN - LEVEL 2
1 1/8" = 1'-0" SHEET NO:
0 4' 8' 16' 24'
1/8" = 1'-0"
AREA A: 1/JP.1.11
AREA A: 1/JP.1.12
G. SLOPE 3" AND LARGER HORIZONTAL SANITARY WASTE PIPING AT
1/8" PER FOOT.
12 11 10 9 8 7 6 5 4 3 2 1.9 1
TEXAS REGISTERED ENGINEERING
FIRM F-2966
777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
A
BREAKROOM
105
REF.
E O F T EX
AT A
ST S
BAY 1
109
MENS WOMENS PHILLIP K. DEWOLFE
R
PR
C
EE
LI
REF.
FE C ENS ED
O
IN
SS G
IO NA L E N
MEETING ROOM
REF.
04/09/2020
107
DW
D
LOBBY
108
BUILDING J RENOVATIONS
1 MENS LOCKER
TARRANT COUNTY
G
C:\Users\greenwko\Documents\TXDOT_FW-P-BldgJ-R18-Central_keith.greenwade.rvt
AREA A AREA B
BUILDING J
J ISSUED: 04-09-2020
N
4/9/2020 2:22:08 PM
PROJECT NO.
02470420015
BUILDING J - OVERALL PLUMBING PLAN - LEVEL 1
1 1/16" = 1'-0" SHEET NO:
0 8' 16' 32' 48'
AREA A: 1/JP.1.12
12 11 10 9 8
TEXAS REGISTERED ENGINEERING
FIRM F-2966
777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
113
KEYNOTES AT
E O F T EX
A
106 NEW FLOOR MOUNTED WATER CLOSET WC-1. FURNISH AND INSTALL ST S
1" DCW LINE TO FLUSH VALVE, 4" SS, AND 2" V LINE FROM WATER
CLOSET TO EXISTING MAINS.
107 NEW WALL MOUNTED LAVATORY L-1. FURNISH AND INSTALL 1/2" DCW, PHILLIP K. DEWOLFE
BREAKROOM 1/2" DHW, 1-1/2" SS, AND 1-1/2" V FROM LAVATORY TO EXISTING MAINS. 102003
105
R
PR
111 EXISTING ELECTRIC WATER COOLER TO REMAIN.
EE
LI
FE C ENS ED
O
113 NEW SINK SK-1. FURNISH AND INSTALL 1/2" DCW, 1/2" DHW, 1-1/2" SS, IN
SS G
IO NA L E N
1-1/2" V AND GARBAGE DISPOSAL FROM SINK TO EXISTING MAINS.
117 EXISTING SERVICE SINK TO REMAIN.
B
118 EXISTING SINK TO REMAIN. 04/09/2020
REF.
119 EXISTING ELECTRIC WATER HEATER TO REMAIN.
123 EXISTING WATER CLOSET TO REMAIN.
MENS WOMENS
104 118 103
BUILDING J RENOVATIONS
107
REF.
TARRANT COUNTY
107
DW
118
123
C:\Users\greenwko\Documents\TXDOT_FW-P-BldgJ-R18-Central_keith.greenwade.rvt
111
LOBBY
108
BUILDING J
J ISSUED: 04-09-2020
N
4/9/2020 2:22:09 PM
PROJECT NO.
02470420015
BUILDING J - AREA A PLUMBING PLAN - LEVEL 1
1 1/8" = 1'-0" SHEET NO:
0 4' 8' 16' 24'
1/8" = 1'-0"
AREA A: 1/JP.1.11
8 7 6 5 4 3 2 1.9 1
B. REFER TO SHEET P.5.01 FOR DETAILS.
Texas
C. REFER TO SHEET P.6.01 FOR SCHEDULES. Department
of Transportation
D. REFER TO SHEET P.7.01 FOR RISER DIAGRAMS.
BAY 1
109
KEYNOTES AT
E O F T EX
A
106 NEW FLOOR MOUNTED WATER CLOSET WC-1. FURNISH AND INSTALL ST S
1" DCW LINE TO FLUSH VALVE, 4" SS, AND 2" V LINE FROM WATER
CLOSET TO EXISTING MAINS.
112 NEW SHOWER SH-1. FURNISH AND INSTALL 1/2" DCW, 1/2" DHW, 2" SS, PHILLIP K. DEWOLFE
AND 1-1/2" V FROM SHOWER TO EXISTING MAINS. 102003
R
PR
116 NEW URINAL U-1. FURNISH AND INSTALL 3/4" DCW LINE TO FLUSH
EE
LI
FE C ENS ED
O
VALVE, 2" SS, AND 1-1/2" V FROM URINAL TO EXISTING MAINS. IN
SS G
IO NA L E N
120 NEW FLOOR MOUNTED WATER CLOSET WC-2. FURNISH AND INSTALL
C 1" DCW LINE TO FLUSH VALVE, 4" SS, AND 2" V LINE FROM WATER
CLOSET TO EXISTING MAINS. 04/09/2020
121 NEW URINAL U-2. FURNISH AND INSTALL 3/4" DCW LINE TO FLUSH
VALVE, 2" SS, AND 1-1/2" V FROM URINAL TO EXISTING MAINS.
122 NEW SHOWER SH-2. FURNISH AND INSTALL 1/2" DCW, 1/2" DHW, 2" SS,
AND 1-1/2" V FROM SHOWER TO EXISTING MAINS.
128 NEW WALL MOUNTED SINK SK-2. FURNISH AND INSTALL 3/4" DCW, 3/4"
DHW, 1-1/2" SS, AND 1-1/2" V FROM SINK TO EXISTING MAINS.
129 NEW FLOOR DRAIN FD-1. FURNISH AND INSTALL 2" SS AND 2" VENT
FROM FLOOR DRAIN TO EXISTING MAINS. INSTALL 1/2" PIPE FROM TAIL
PIECE ON SK-2 TO FLOOR DRAIN TRAP PRIMER.
132 ROUTE 1/2" TRAP PRIMER PIPE FROM FLUSH VALVE ON URINAL TO
EXISTING FLOOR DRAIN.
BUILDING J RENOVATIONS
122
121
5
TARRANT COUNTY
132 112
P.5.01
116
OFFICE 128
111
E
C:\Users\greenwko\Documents\TXDOT_FW-P-BldgJ-R18-Central_keith.greenwade.rvt
4
129
P.5.01
MENS LOCKER
ROOM
102 Building Key Plan:
AREA B
BAY 2
110
BUILDING J
G
Site Key Plan:
N
4/9/2020 2:22:09 PM
PROJECT NO.
02470420015
H SHEET NO:
0 4' 8' 16' 24'
1/8" = 1'-0"
AREA A: 1/JP.1.21
AREA A: 1/JP.1.22
1/8" PER FOOT.
12 11 10 9 8 7 6 5 4 3 2 1.9 1
TEXAS REGISTERED ENGINEERING
FIRM F-2966
777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
A
TELECOM ROOM
203
B
OFFICE E O F T EX
AT A
202 ST S
WAREHOUSE
201
PHILLIP K. DEWOLFE
OFFICE
102003
205
R
PR
C
EE
LI
FE C ENS ED
O
IN
SS G
IO NA L E N
04/09/2020
RESTROOM
204
D
BUILDING J RENOVATIONS
1
TARRANT COUNTY
G
C:\Users\greenwko\Documents\TXDOT_FW-P-BldgJ-R18-Central_keith.greenwade.rvt
AREA A AREA B
BUILDING J
J ISSUED: 04-09-2020
N
4/9/2020 2:22:11 PM
PROJECT NO.
02470420015
BUILDING J - OVERALL PLUMBING PLAN - LEVEL 2
1 1/16" = 1'-0" SHEET NO:
0 8' 16' 32' 48'
AREA A: 1/JP.1.22
12 11 10 9 8
TEXAS REGISTERED ENGINEERING
FIRM F-2966
777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
KEYNOTES AT
E O F T EX
A
106 NEW FLOOR MOUNTED WATER CLOSET WC-1. FURNISH AND INSTALL ST S
1" DCW LINE TO FLUSH VALVE, 4" SS, AND 2" V LINE FROM WATER
CLOSET TO EXISTING MAINS.
PHILLIP K. DEWOLFE
107 NEW WALL MOUNTED LAVATORY L-1. FURNISH AND INSTALL 1/2" DCW,
1/2" DHW, 1-1/2" SS, AND 1-1/2" V FROM LAVATORY TO EXISTING 102003
R
MAINS.
PR
TELECOM ROOM
EE
LI
FE C ENS ED
O
IN
203 SS G
IO NA L E N
B
04/09/2020
OFFICE
202
WAREHOUSE
201
OFFICE
BUILDING J RENOVATIONS
TARRANT COUNTY
RESTROOM
204
C:\Users\greenwko\Documents\TXDOT_FW-P-BldgJ-R18-Central_keith.greenwade.rvt
EXISTING NATURAL
GAS LINE
BUILDING J
J ISSUED: 04-09-2020
N
4/9/2020 2:22:12 PM
PROJECT NO.
02470420015
BUILDING J - AREA A PLUMBING PLAN - LEVEL 2
1 1/8" = 1'-0" SHEET NO:
0 4' 8' 16' 24'
1/8" = 1'-0"
AREA A: 1/JP.1.21
8 7 6 5 4 3 2 1.9 1
B. REFER TO SHEET P.5.01 FOR DETAILS.
Texas
C. REFER TO SHEET P.6.01 FOR SCHEDULES. Department
of Transportation
D. REFER TO SHEET P.7.01 FOR RISER DIAGRAMS.
EXISTING NATURAL GAS LINE G. SLOPE 3" AND LARGER HORIZONTAL SANITARY WASTE PIPING AT
1/8" PER FOOT.
B
2
127
CORAYVAC GAS P.5.01
CORAYVAC GAS
HEATER (100 CFH)
HEATER (100 CFH)
REFER TO
MECHANICAL
REFER TO
MECHANICAL
KEYNOTES AT
E O F T EX
A
124 ROUTE NEW NATURAL GAS PIPING FROM EXISTING VALVE ON MAIN ST S
2 EXISTING NATURAL THAT SERVED UNIT HEATER G-13 THAT HAS BEEN REMOVED,
CORAYVAC GAS GAS LINE REFER TO MECHANICAL.
P.5.01 PHILLIP K. DEWOLFE
HEATER (100 CFH) 125 ROUTE NEW NATURAL GAS PIPING FROM EXISTING VALVE ON MAIN
REFER TO THAT SERVED UNIT HEATER G-14 THAT HAS BEEN REMOVED, 102003
R
MECHANICAL REFER TO MECHANICAL.
PR
EE
LI
FE C ENS ED
O
126 ROUTE NEW NATURAL GAS PIPING FROM EXISTING VALVE ON MAIN IN
SS G
THAT SERVED UNIT HEATER G-15 THAT HAS BEEN REMOVED, IO NA L E N
C REFER TO MECHANICAL.
127 INSTALL TEE AND ISOLATION VALVE IN EXISTING GAS MAIN. 04/09/2020
3/4" NG
BUILDING J RENOVATIONS
REFER TO REFER TO
124 2
2 3/4" NG P.5.01
EXISTING NATURAL GAS LINE
TARRANT COUNTY
P.5.01
3/4" NG
125 126
E
C:\Users\greenwko\Documents\TXDOT_FW-P-BldgJ-R18-Central_keith.greenwade.rvt
AREA B
EXISTING NATURAL GAS NEW NATURAL GAS
EQUIPMENT TO BE REMOVED EQUIPMENT TO BE ADDED
EXISTING UNIT HEATER G-13 THAT WILL BE REMOVED - 160 CFH NEW CORAYVAC HEATER - 100 CFH
EXISTING UNIT HEATER G-14 THAT WILL BE REMOVED - 160 CFH NEW CORAYVAC HEATER - 100 CFH
EXISTING UNIT HEATER G-15 THAT WILL BE REMOVED - 160 CFH NEW CORAYVAC HEATER - 100 CFH
TOTAL 480 CFH NEW CORAYVAC HEATER - 100 CFH
NEW CORAYVAC HEATER - 100 CFH BUILDING J
TOTAL 500 CFH
G
ADDITIONAL 20 CFH WILL BE ADDED
TO THE BUILDING TOTAL OF 3550 CFH Site Key Plan:
PER EXISTING DRAWINGS
N
4/9/2020 2:22:13 PM
PROJECT NO.
02470420015
H SHEET NO:
0 4' 8' 16' 24'
1/8" = 1'-0"
R
D 1 1/4" 61-113 COUNTER SINK 1.5 1.5
PR
PIPE (TYP.)
EE
LI
DOUBLE NUTS OR LOCK FE C ENS ED
O
IN
SS G
NUTS (TYP. FOR ALL IO NA L E N
SUPPORTS) FLAT E 1-1/2" 114-154 LAVATORY 1.5 1.5
WASHERS UNION
04/09/2020
F 2" 155-330 MOP BASIN 3 3
GALVANIZED STEEL MSS-SP58
TYPE 40 INSULATION SHIELD 6" DIRT LEG, FULL LINE IF STATIC PRESSURE IS GREATER 0.5
WATER COOLER (2 HEADS) --
(TYPICAL) SIZE. PROVIDE 3" MINIMUM THAN 55 PSIG, USE NEXT LARGER
UNISTRUT OR SIMILAR CLEARANCE TO REMOVE CAP SIZE.
CHANNEL GAS-FIRED EQUIPMENT SHOWER 2 3
NOTES: GAS SUPPLY MAIN - PROVIDE PIPE
1. INSULATION INSERT LENGTH SHALL BE 6" LONGER THAN INSULATION SHIELD. SUPPORTS PER SPECIFICATIONS OR
2. INSULATION SYSTEM SHALL MAINTAIN CONTINUITY OF THERMAL INSULATION, VAPOR RETARDER, AND PROVIDE WATER HAMMER ARRESTERS BY WADE, OR APPROVED EQUAL WITH SHOCKSTOPS OF WELDED NESTED BELLOWS
8'-0" ON CENTER MINIMUM
SPECIFIED JACKETING THROUGH ALL PIPE SUPPORTS. CONSTRUCTION, HAVING PDI #WH-201, ASSE #1010 AND ANSI #A112.26.1M CERTIFICATION. INSTALL IN HORIZONTAL OR VERTICAL
(CONTRACTOR TO USE MORE
POSITION, BUT NEVER UPSIDE DOWN. INSTALL INLINE WITH WATER FLOW DIRECTION IF POSSIBLE. SIZE UNITS PER TABLES ABOVE.
STRINGENT OF THE TWO) AND AT
EACH ELBOW AND TEE
BUILDING J RENOVATIONS
TARRANT COUNTY
MANUFACTURER AS FLUSH
VALVE
C:\Users\greenwko\Documents\TXDOT_FW-P-BldgJ-R18-Central_keith.greenwade.rvt
URINAL
PROVIDE PROTECTIVE
SLEEVE AT FLOOR
PENETRATION
FINISHED FLOOR FLOOR DRAIN AND
P-TRAP FLOOR DRAIN FINISHED FLOOR
AND P-TRAP
ISSUED: 04-09-2020
TRAP PRIMER - TAILPIECE FLUSH VALVE TRAP PRIMER DETAIL PROJECT NO.
4 NTS
5 NTS
02470420015
SHEET NO:
PLUMBING DETAILS
P.5.01
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
R
FD-1 FLOOR DRAIN ZURN Z415S CAST IRON FLOOR DRAIN, INVERTIBLE FLASHING COLLAR, BOTTOM OUTLET, ADJUSTABLE 6" X 6" RECTANGULAR NICKEL BRONZE TOP, 1/2" TRAP PRIMER. 2" 2" - -
THIS DRAWING CREATED
FOR PRODUCTION ON
HB-1 INDOOR HOSE BIBB ZURN Z1341-BFP-P34 ALL BRONZE, EXPOSED, ANTI-SIPHON, WALL FAUCET WITH HOSE CONNECTION CONFORMING TO ASSE 1052, BRONZE FINISH, 3/4" FPT CONNECTION WITH STANDARD HANDLE. - - 3/4" - 22"x34" SHEET SIZE.
DO NOT SCALE PRINTS.
ADA COMPLIANT WALL MOUNTED, 20-7/8" X 18" VITREOUS CHINA WITH SELF DRAINING DECK AREA WITH BACK AND SIDE SPLASH SHIELDS, FAUCET LEDGE AND CONCEALED
BOWL TOTO LT307
ARM SUPPORT.
DECK MOUNTED, POLISHED CHROME BRASS BODY WITH INTEGRAL SPOUT, MOTION SENSOR ACTIVATED, PROVIDE ONE 120VA/12VAC, 400 MA TRANSFORMER FOR EACH BANK
FAUCET SLOAN SF-2400
OF LAVATORIES.
TEXAS REGISTERED ENGINEERING
L-1 STRAINER MCGUIRE 155WC CAST BRASS CHROME PLATED OFFSET WHEELCHAIR PERFORATED FIXED STRAINER WITH TAILPIECE. 1-1/2" 1-1/2" 1/2" 1/2" 1 FIRM F-2966
777 MAIN ST. STE B-101
ACCESSORIES MCGUIRE ANGLE STOPS, P-TRAP WITH CLEANOUT, AND ADA INSULATED COVERS FOR STOPS AND P-TRAP. FORT WORTH, TEXAS 76102
BOWL AMERICAN STANDARD 0490 COUNTERTOP, DROP-IN, 19-1/8" DIAMETER ROUND, VITREOUS CHINA, SELF-RIMMING SINK.
DECK MOUNTED, POLISHED CHROME BRASS BODY WITH INTEGRAL SPOUT, MOTION SENSOR ACTIVATED, PROVIDE ONE 120VA/12VAC, 400 MA TRANSFORMER FOR EACH BANK
FAUCET SLOAN SF-2400
OF LAVATORIES.
L-2 1-1/2" 1-1/2" 1/2" 1/2"
STRAINER MCGUIRE 155WC CAST BRASS CHROME PLATED OFFSET WHEELCHAIR PERFORATED FIXED STRAINER WITH TAILPIECE. E O F T EX
AT A
ST S
ACCESSORIES MCGUIRE ANGLE STOPS, P-TRAP WITH CLEANOUT, AND ADA INSULATED COVERS FOR STOPS AND P-TRAP.
NON-ADA SHOWER SYSTEM, CHROME PLATED SWIVEL BALL HEAD, 1.5 GPM FLOW CONTROL WITH 2-1/2" DIAMETER ESCUTCHEON AND CHROME PLATED FIXED SHOWER ARM. 102003
1905-VOCCP WITH
R
PR
SH-1 SHOWER VALVE CHICAGO 2" 2" 1/2" 1/2"
EE
CHROME PLATED PRESSURE BALANCING VALVE WITH INTEGRAL SERVICE AND CHECK STOPS. ASSE 1016 COMPLIANT FOR SCALD PROTECTION, NSF 61 NO LEAD COMPLIANT. LI
620-LCP FE C ENS ED
O
IN
SS G
IO NA L E N
SHOWER DRAIN KOHLER K9132-CP 2" BRASS SHOWER DRAIN WITH FIXED PERFORATED POLISHED CHROME STRAINER, SHOWER DRAIN KIT WITH GASKETS AND CONNECTOR JOINT.
ADA COMPLIANT SHOWER SYSTEM, 1/2" CHROME PLATED HAND SHOWER WITH NON POSITIVE SHUT-OFF, CHROME PLATED ELBOW WITH IN-LINE VACUUM BREAKER, STD 60"
1905-VOCCP WITH 2" 2" 1/2" 1/2"
SH-2 SHOWER VALVE CHICAGO FLEXIBLE METAL HOSE, 36" SLIDE BAR, AND 1.5 GPM FLOW CONTROL WITH 2-1/2" DIAMETER ESCUTCHEON. CHROME PLATED PRESSURE BALANCING VALVE WITH INTEGRAL
154-ALCP
SERVICE AND CHECK STOPS. ASSE-1016 COMPLIANT FOR SCALD PROTECTION. NSF 61 NO LEAD COMPLIANT.
SHOWER DRAIN KOHLER K9132-CP 2" BRASS SHOWER DRAIN WITH FIXED PERFORATED POLISHED CHROME STRAINER, SHOWER DRAIN KIT WITH GASKETS AND CONNECTOR JOINT.
BOWL ELKAY LRAD291855 29" X 18" TOP-MOUNT STAINLESS STEEL SINK, COUNTERTOP DROP-IN, SELF-RIMMING SINK WITH (2) 12" X 12" X 5-1/2" DEEP BOWL.
DECK-MOUNTED, POLISHED CHROME, 8" CENTERS FAUCET, 9-1/2" L TYPE SWING SPOUT, 4" WRISTBLADE HANDLES, WITH FLEX HOSE AND VEGETABLE SPRAY, NSF 61 NO-LED
FAUCET CHICAGO 200-AE35-317AB CP
COMPLIANT.
BUILDING J RENOVATIONS
GARBAGE DISPOSAL INSINKERATOR BADGER 5 DISPOSAL WITH QUICK LOCK MOUNTING SYSTEM, 1/2 HP, 120 VOLT, 6.3 AMPS, INLET FOR DISHWASHER, MANUAL RESET OVERLOAD, WRENCH.
FAUCET ADVANCE TABCO K-175 (3) SINGLE HOLE, SPLASH MOUNTED 3-1/2" ELECTRONIC FAUCET, K-08 AERATOR, NSF 61 NO-LED COMPLIANT, PROVIDE ONE 120VA/12VAC, 400 MA TRANSFORMER.
TARRANT COUNTY
SK-2 STRAINER ADVANCE TABCO K-6 STRAINER PLATE FOR 3-1/2" DRAIN. 1-1/2" 1-1/2" 1/2" 1/2" 1
MIXING VALVE WATTS LFUSG-B-M2 LEAD-FREE, ASSE 1070 THERMOSTATIC MIXING VALVE.
BOWL KOHLER K-5016 ADA-COMPLIANT BOWL HEIGHT, 0.5 GPF WALL MOUNTED URINAL, WHITE VITREOUS CHINA, 3/4" TOP SPUD, INTEGRAL P-TRAP AND 2" OUTLET.
VALVE: EXPOSED, AUTOMATIC INFRARED FLUSH VALVE WITH VACUUM BREAKERS AND MANUAL OVERRIDE FLUSH CAPABILITY. FLUSH VALVE DESIGN SHALL BE ADA COMPLIANT, 3/4"
U-1 FLUSHOMETER SLOAN SOLIS 8186 2" 1-1/2" - 1
0.5 GALLONS PER FLUSH - 30 TO 90 PSIG OPERATING PRESSURE. BATTERY POWERED, FURNISH WITH (4) AA BATTERIES.
BOWL KOHLER K-5016 0.5 GPF WALL MOUNTED URINAL, WHITE VITREOUS CHINA, 3/4" TOP SPUD, INTEGRAL P-TRAP AND 2" OUTLET.
VALVE: EXPOSED, AUTOMATIC INFRARED FLUSH VALVE WITH VACUUM BREAKERS AND MANUAL OVERRIDE FLUSH CAPABILITY. FLUSH VALVE DESIGN SHALL BE ADA COMPLIANT, 3/4"
U-2 FLUSHOMETER SLOAN SOLIS 8186 2" 1-1/2" - 1
0.5 GALLONS PER FLUSH - 30 TO 90 PSIG OPERATING PRESSURE. BATTERY POWERED, FURNISH WITH (4) AA BATTERIES.
BOWL KOHLER K-96057 ADA-COMPLIANT BOWL HEIGHT, 1.28 GPF FLOOR MOUNTED WATER CLOSET, ELONGATED BOWL, WHITE VITREOUS CHINA, 1-1/2" TOP SPUD.
VALVE: EXPOSED, AUTOMATIC INFRARED FLUSH VALVE WITH VACUUM BREAKERS AND MANUAL OVERRIDE FLUSH CAPABILITY. FLUSH VALVE DESIGN SHALL BE ADA COMPLIANT,
WC-1 FLUSHOMETER SLOAN SOLIS 8111 4" 2" 1" -
1.28 GALLONS PER FLUSH - 30 TO 90 PSIG OPERATING PRESSURE. BATTERY POWERED, FURNISH WITH (4) AA BATTERIES.
SEAT BEMIS OLSONITE 10CT WHITE, INJECTION MOLDED SOLID PLASTIC SEAT, OPEN FRONT, NO COVER, WITH SERIES 300 STAINLESS STEEL POSTS AND PINTLES.
BOWL KOHLER K-96053 1.28 GPF FLOOR MOUNTED WATER CLOSET, ELONGATED BOWL, WHITE VITREOUS CHINA, 1-1/2" TOP SPUD.
VALVE: EXPOSED, AUTOMATIC INFRARED FLUSH VALVE WITH VACUUM BREAKERS AND MANUAL OVERRIDE FLUSH CAPABILITY. FLUSH VALVE DESIGN SHALL BE ADA COMPLIANT,
WC-2 FLUSHOMETER SLOAN SOLIS 8111 4" 2" 1" -
1.28 GALLONS PER FLUSH - 30 TO 90 PSIG OPERATING PRESSURE. BATTERY POWERED, FURNISH WITH (4) AA BATTERIES.
SEAT BEMIS OLSONITE 10CT WHITE, INJECTION MOLDED SOLID PLASTIC SEAT, OPEN FRONT, NO COVER, WITH SERIES 300 STAINLESS STEEL POSTS AND PINTLES.
GENERAL NOTES:
PROJECT NO.
02470420015
SHEET NO:
PLUMBING SCHEDULES
P.6.01
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
R
EXTEND TO EXISTING MAIN
AND INSTALL ISOLATION VALVE
AT POINT OF CONNECTION. INSTALL
WATER HAMMER ARRESTER PER
DETAIL 3/P.5.01 Texas
Department
EXTEND TO EXISTING MAIN of Transportation
EXTEND TO EXISTING MAINS 3/4" DCW
AND INSTALL ISOLATION VALVE
EXTEND TO EXISTING MAIN
AT POINT OF CONNECTION.
AND INSTALL ISOLATION VALVE
INSTALL WATER HAMMER EXTEND TO EXISTING MAIN AT POINT OF CONNECTION.
ARRESTER PER DETAIL 3/P.5.01 EXTEND TO EXISTING MAIN
THIS DRAWING CREATED
INSTALL WATER HAMMER FOR PRODUCTION ON
3/4" DHW AND INSTALL ISOLATION VALVE ARRESTER PER DETAIL 3/P.5.01 EXTEND TO EXISTING MAIN 22"x34" SHEET SIZE.
EXTEND TO EXISTING MAIN DO NOT SCALE PRINTS.
3/4" DCW AND INSTALL ISOLATION VALVE AT POINT OF CONNECTION. INSTALL
EXTEND TO EXISTING MAIN
AT POINT OF CONNECTION. WATER HAMMER ARRESTER PER 1" DCW
INSTALL WATER HAMMER DETAIL 3/P.5.01
ARRESTER PER DETAIL 3/P.5.01 TO FLUSH VALVE
1 1/2" V
1 1/2" V
3/4" DHW 3/4" DCW
TEXAS REGISTERED ENGINEERING
FIRM F-2966
1 1/2" V
777 MAIN ST. STE B-101
TO DISHWASHER TO FLUSH VALVE FORT WORTH, TEXAS 76102
2" V
L1 & L2
DISHWASHER DRAIN
R
PR
EE
LI
FE C ENS ED
O
IN
SS G
IO NA L E N
TYPICAL SINK RISER DIAGRAM TYPICAL LAVATORY RISER DIAGRAM TYPICAL WATER CLOSET RISER DIAGRAM TYPICAL URINAL RISER DIAGRAM
1 2 3 4 04/09/2020
2" V
BUILDING J RENOVATIONS
EXTEND TO EXISTING MAIN
TARRANT COUNTY
EXTEND TO EXISTING MAIN
1 1/2" V
3/4" DCW 3/4" DCW
C:\Users\greenwko\Documents\TXDOT_FW-P-BldgJ-R18-Central_keith.greenwade.rvt
MIXING VALVE
2" V
SH-1 & SH-2
2" SS
2" SS
EXTEND TO
EXISTING MAIN FD-1
ISSUED: 04-09-2020
PROJECT NO.
02470420015
SHEET NO:
PLUMBING RISERS
P.7.01
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
DUCTWORK SYMBOLS PIPING SYMBOLS VALVE SYMBOLS (CON'T) CONTROLS SYMBOLS HVAC DESIGN CRITERIA R
XX/XX PITCH DOWN IN DIRECTION OF ARROW T ROOM THERMOSTAT OR SENSOR TXDOT FORTWORTH DISTRICT HEADQUARTERS
DUCT WITH ACOUSTICAL LINING PRESSURE REDUCING VALVE (PRV)
Texas
MANUAL VOLUME DAMPER DIRECTION OF FLOW BUTTERFLY VALVE H ROOM HUMIDISTAT DESIGN CONDITIONS FROM ASHRAE FUNDAMENTALS 2013 Department
(SEE BELOW FOR OTHER TYPES) of Transportation
PIPE ANCHOR BALL VALVE WEATHER STATION - DALLAS/FORT WORTH INT AP; STATION 722590
T TEMPERATURE SENSOR/TRANSMITTER
VERTICAL DAMPER IN DUCT (OR OPENING) PIPE GUIDE NEEDLE VALVE
AT FIRE-RATED PARTITION H HUMIDITY SENSOR/TRANSMITTER ELEVATION: 560 FEET; LATITUDE: 32.898°N; LONGITUDE: 97.019°W
CONCENTRIC REDUCER VENTURI FLOW METER
HORIZONTAL FIRE DAMPER AT FLOOR PENETRATION WINTER: 23.3°F DRY BULB (99.6%) THIS DRAWING CREATED
FOR PRODUCTION ON
ECCENTRIC REDUCER VALVE IN DROP S DUCT SMOKE DETECTOR 22"x34" SHEET SIZE.
CONNECT NEW DUCT TO EXISTING SUMMER: 101.4°F DRY BULB / 74.2°F MEAN COINCIDENT WET BULB (0.4%) DO NOT SCALE PRINTS.
R
PR
SP STATIC PRESSURE SENSOR/TRANSMITTER
EE
LI
A. REFER TO SPECIFICATIONS FOR MATERIALS AND METHODS FOR CONSTRUCTION. F C ENS ED
O
ES IN
STANDARD ECCENTRIC DUCT TRANSITION FLANGED CONNECTION ANGLE GATE VALVE S IO
NA L E
N G
BUILDING J RENOVATIONS
PATTERN. NO PATTERN SHOWN EQUALS
4-WAY PS THESE STANDARDS WHETHER OR NOT INDICATED ON THE DRAWINGS.
TARRANT COUNTY
AUTOMATIC AIR VENT R STRUCTURE WILL BE AVOIDED.
REFRIGERANT DETECTOR/SENSOR
CHWS CHILLED WATER SUPPLY
SIDEWALL SUPPLY OR RETURN AIR REGISTER OR GRILLE MANUALLY ACTIVATED SWITCH
PUMP HS H. PROVIDE THE ENTIRE SYSTEM AND ITS COMPONENT ITEMS OF EQUIPMENT IN
CHWR CHILLED WATER RETURN (PULL STAT., PUSH STAT., ETC) OPERATING CONDITION WITHOUT OBJECTIONABLE VIBRATION OR NOISE.
SUPPLY OR OUTSIDE AIR DUCT UP HWS HEATING WATER SUPPLY
WELDED CONNECTION NORMAL NORMAL I. PROVIDE ALL WIRING AND ELECTRICAL CONTROLS IN ACCORDANCE WITH NFPA 70
OPEN CLOSED
SUPPLY OR OUTSIDE AIR DUCT DOWN HWR HEATING WATER RETURN (NEC).
FLANGED CONNECTION GATE VALVE
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
CWS CONDENSER WATER SUPPLY J. DO NOT SCALE THESE DRAWINGS FOR CONSTRUCTION PURPOSES.
RETURN AIR DUCT UP SOLDERED CONNECTION VALVE W/ REDUCERS (GATE VALVE SHOWN)
CWR CONDENSER WATER RETURN
K. ALL DUCTWORK SIZES ARE FREE AIR STREAM DIMENSIONS.
RETURN AIR DUCT DOWN THREADED OR "PRESS" CONNECTION CD AHU CONDENSATE DRAIN GLOBE VALVE
L. INSTALL DUCTWORK AND PIPING TO PROVIDE THE MAXIMUM CLEAR HEIGHT
BELL & SPIGOT CONNECTION D DRAIN BUTTERFLY VALVE UNDERNEATH.
RELIEF OR EXHAUST AIR DUCT UP
SOLVENT CONNECTION PCWR PROCESS CHILLED WATER RETURN NEEDLE VALVE/INSTRUMENT VALVE M. REFER TO STRUCTURAL DRAWINGS FOR FRAMING REQUIRED AROUND PIPES AND
RELIEF OR EXHAUST AIR DUCT DOWN PCWS PROCESS CHILLED WATER SUPPLY DUCTS PENETRATING ROOFS, WALLS, AND FLOORS.
3-WAY VALVE
IN-LINE 90 DEGREE DROP (RISE) IN DUCT
ABBREVIATIONS RL REFRIGERANT LIQUID N. REFER TO ARCHITECTURAL ELEVATION DRAWINGS, WHERE THE ARCHITECT HAS
BALL VALVE
BCWP - BUILDING CONDENSER WATER PUMP RS REFRIGERANT SUCTION DRAWN SUCH ELEVATIONS, FOR THE LOCATION OF ALL WALL MOUNTED DEVICES.
UP INCLINED RISE IN DUCT BCW - BUILDING CONDENSER WATER PLUG VALVE
MU MAKE-UP WATER O. ALL TAPS TO DIFFUSERS SHALL BE SAME SIZE AS DIFFUSER NECK OPENING
CPVC - CHLORINATED POLYVINYL CHLORIDE
ANGLE VALVE UNLESS OTHERWISE NOTED
DN HDPE - HIGH DENSITY POLYETHYLENE X X AAA X X PIPE TO BE REMOVED, "AAA" DENOTES TYPE
INCLINED DROP IN DUCT
HWP - HOT WATER PUMP CONTROL VALVE SYMBOLS: P. PAINT ANY ABOVE CEILING ITEMS, WHICH CAN BE SEEN THROUGH AIR SLOTS OR
HX - HEAT EXCHANGER AAA EXISTING PIPE, "AAA" DENOTES TYPE
FLEXIBLE DUCT, SIZE AS SHOWN M GRILLES, FLAT BLACK.
PCW - PLANT COOLING WATER ELECTRIC ACTUATOR
AAA UNDERGROUND PIPE, "AAA" DENOTES TYPE
VFD - VARIABLE SPEED DRIVE P Q. PROVIDE PLENUM RATED CABLE, DEVICES, PIPING, ETC. IN PLENUM SPACE.
1 2 DUCT PRESSURE CLASS. DTS DUAL TEMPERATURE SUPPLY PNEUMATIC ACTUATOR
POINT OF CHANGE IN DUCT CONSTRUCTION
DTR DUAL TEMPERATURE RETURN S R. PROVIDE TEMPORARY 30% EFFICIENT, 2" THICK FILTERS OVER RETURN AIR
DAMPER TYPE: FD - FIRE DAMPER SOLENOID ACTUATOR
OPENINGS OF ANY AHU'S WHICH ARE PLACED IN SERVICE PRIOR TO COMPLETION
SD - SMOKE DAMPER VALVE SYMBOLS OF CONSTRUCTION. REMOVE FILTERS FOR TEST & BALANCE.
FSD - COMBINATION FIRE/SMOKE DAMPER EQUIPMENT TAG SYMBOLS ISSUED: 04-09-2020
BD - GRAVITY BACKDRAFT DAMPER GATE VALVE MISCELLANEOUS S. DUCT AND PIPE HANGARS IN UNCONDITIONED SPACE OR EXTERIOR TO BUILDING DRAWN BY: D. REILLY
CD - CONTROL DAMPER GLOBE VALVE SHALL BE GALVANIZED STEEL.
24/12 INDICATES A 24"x10" RECTANGULAR REVISIONS:
*NO MARK INDICATES MANUAL VOLUME DAMPER 1 DRAWING NOTE REFERENCE DUCT (NET FREE AREA)
CHECK VALVE (NON SLAM) T. PROVIDE ACCESS PANELS FOR ALL DAMPER ACTUATORS AND MOTORS LOCATED
EQUIPMENT SYMBOLS PLUG VALVE POINT OF CONNECTION - NEW TO EXISTING 20"ø INDICATES A 20" ROUND DUCT (NET FREE AREA) INSIDE DUCT OR FAN HOUSING.
46/30 Ө INDICATES A 46"/30" DIA OVAL DUCT (NET FREE AREA) U. ALL TAPS TO BE CONICAL BELL MOUTH SPIN-IN TAPS WITH2" RAISED REGULATOR
NEW EQUIPMENT DRAWING/DETAIL REFERENCE KEY VOLUME DAMPER.
4/9/2020 1:17:45 PM
M-XXX
SHEET NUMBER ON WHICH
DETAIL IS DRAWN
(CFM)
R
THERMOSTAT. ALL THERMOSTATS TO BE MOUNTED 48" AFF.
PR
EE
LI
C ENS ED
A F
O
ES IN
G
K INSTALL NO2/CO SENSORS BASED ON MANUFACTURER'S S IO
NA L E
N
RECOMMENDATION
DW
04/09/2020
B
REF.
REF.
BUILDING J RENOVATIONS
D
J ISSUED: 04-09-2020
N
4/9/2020 1:18:17 PM
PROJECT NO.
02470420015
BUILDING J - OVERALL DEMO MECHANICAL PLAN - LEVEL 1
1 1/16" = 1'-0" SHEET NO:
0 8' 16' 32' 48'
DW
PHILLIP K. DEWOLFE
J PROVIDE COMMERCIAL PROGRAMMABLE NETWORK CAPABLE 102003
R
THERMOSTAT. ALL THERMOSTATS TO BE MOUNTED 48" AFF.
PR
EE
LI
F C ENS ED
O
ES IN
G
K INSTALL NO2/CO SENSORS BASED ON MANUFACTURER'S S IO
NA L E
N
RECOMMENDATION
001 04/09/2020
KEYNOTES
REF. B Key Keynote Text
001 AIR HANDLER UNIT AND ASSOCIATED DUCTWORK TO BE
052 DEMOLISHED.
002 CONDENSER TO BE DEMOLISHED.
040 RETURN NEWER UNIT TO OWNER
051 DEMOLISH SUPPLY DIFFUSER (TYPICAL FOR ALL SHOWN).
052 DEMOLISH RETURN GRILLE (TYPICAL FOR ALL SHOWN).
054 DEMOLISH DUCTWORK AND PATCH TO MATCH EXISTING.
BUILDING J RENOVATIONS
REF.
040
001
AREA A
E
054
002 040
BUILDING J
J ISSUED: 04-09-2020
N
4/9/2020 1:18:19 PM
PROJECT NO.
02470420015
BUILDING J - AREA A DEMO MECHANICAL PLAN - LEVEL 1
1 1/8" = 1'-0" SHEET NO:
0 4' 8' 16' 24'
R
THERMOSTAT. ALL THERMOSTATS TO BE MOUNTED 48" AFF.
PR
EE
LI
F C ENS ED
O
ES IN
G
K INSTALL NO2/CO SENSORS BASED ON MANUFACTURER'S S IO
NA L E
N
B RECOMMENDATION
04/09/2020
KEYNOTES
Key Keynote Text
001 AIR HANDLER UNIT AND ASSOCIATED DUCTWORK TO BE
DEMOLISHED.
004 EXHAUST FLUE DUCTWORK TO BE DEMOLISHED.
051 DEMOLISH SUPPLY DIFFUSER (TYPICAL FOR ALL SHOWN).
052 DEMOLISH RETURN GRILLE (TYPICAL FOR ALL SHOWN).
053 DEMOLISH SUPPLY GRILLE (TYP).
TARRANT COUNTY
052
D
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
001
051
(N)
053
E Building Key Plan:
AREA B
004
BUILDING J
J ISSUED: 04-09-2020
N
4/9/2020 1:18:20 PM
PROJECT NO.
02470420015
BUILDING J - AREA B DEMO MECHANICAL PLAN - LEVEL 1
1 1/8" = 1'-0" SHEET NO:
0 4' 8' 16' 24'
R
THERMOSTAT. ALL THERMOSTATS TO BE MOUNTED 48" AFF.
PR
EE
LI
F C ENS ED
O
ES IN
G
K INSTALL NO2/CO SENSORS BASED ON MANUFACTURER'S S IO
NA L E
N
RECOMMENDATION
B 04/09/2020
TARRANT COUNTY
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
J ISSUED: 04-09-2020
N
4/9/2020 1:18:22 PM
PROJECT NO.
02470420015
BUILDING J - OVERALL DEMO MECHANICAL PLAN - LEVEL 2
1 1/16" = 1'-0" SHEET NO:
0 8' 16' 32' 48'
R
THERMOSTAT. ALL THERMOSTATS TO BE MOUNTED 48" AFF.
PR
EE
LI
F C ENS ED
O
ES IN
G
K INSTALL NO2/CO SENSORS BASED ON MANUFACTURER'S S IO
NA L E
N
RECOMMENDATION
04/09/2020
B KEYNOTES
Key Keynote Text
001 AIR HANDLER UNIT AND ASSOCIATED DUCTWORK TO BE
DEMOLISHED.
051 DEMOLISH SUPPLY DIFFUSER (TYPICAL FOR ALL SHOWN).
051 052 DEMOLISH RETURN GRILLE (TYPICAL FOR ALL SHOWN).
BUILDING J RENOVATIONS
052
001
TARRANT COUNTY
D
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
AREA A
E
BUILDING J
J ISSUED: 04-09-2020
N
4/9/2020 1:18:23 PM
PROJECT NO.
BUILDING J - AREA A DEMO MECHANICAL PLAN - LEVEL 2 02470420015
1 1/8" = 1'-0" SHEET NO:
0 4' 8' 16' 24'
R
THERMOSTAT. ALL THERMOSTATS TO BE MOUNTED 48" AFF.
PR
EE
LI
F C ENS ED
O
ES IN
G
057 057 057 K INSTALL NO2/CO SENSORS BASED ON MANUFACTURER'S S IO
NA L E
N
RECOMMENDATION
04/09/2020
KEYNOTES
Key Keynote Text
005 UNIT HEATER TO BE DEMOLISHED WITH ASSOCIATED
DUCTWORK. ROOF PENETRATION TO BE PATCHED. GAS LINE TO
BE CAPPED.
B 056 DUCTWORK AND GRILLES EXISTING TO REMAIN (TYP).
057 EXISTING UNIT HEATER TO REMAIN.
057
TARRANT COUNTY
056 057
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
005
D
056
005 005
056
057
J ISSUED: 04-09-2020
057 DRAWN BY: D. REILLY
057
REVISIONS:
L
N
4/9/2020 1:18:24 PM
PROJECT NO.
02470420015
BUILDING J - AREA B DEMO MECHANICAL PLAN - LEVEL 2
1 1/8" = 1'-0" SHEET NO:
R
THERMOSTAT. ALL THERMOSTATS TO BE MOUNTED 48" AFF.
PR
EE
LI
F C ENS ED
O
ES IN
G
K INSTALL NO2/CO SENSORS BASED ON MANUFACTURER'S S IO
NA L E
N
RECOMMENDATION
A KEYNOTES
04/09/2020
B
002
(E)
TARRANT COUNTY
(E)
CU-8
E
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
J ISSUED: 04-09-2020
N
4/9/2020 1:18:26 PM
PROJECT NO.
02470420015
BUILDING J - OVERALL ROOF DEMO MECHANICAL PLAN
1 1/16" = 1'-0" SHEET NO:
0 8' 16' 32' 48'
121.1 125
TEXAS REGISTERED ENGINEERING
FIRM F-2966
3 MAIN ROOM 3 OFFICE 481 2 5 .06 38.86 777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
STORAGE AREA 2 DRY STORAGE 320 0 5 .06 29.2
116.1 120
102003
LOWER NORTH OFFICE 8 OFFICE 105 1 5 .06 11.00
R
PR
EE
LI
F C ENS ED
O
ES IN
NORTH CORRIDOR CORRIDOR 250 0 0 .06 15 S IO N G
NA L E
84.4 90
04/09/2020
5 LOWER NORTH OFFICE 1 OFFICE 100 1 5 .06 11
BUILDING J RENOVATIONS
TARRANT COUNTY
141.4 150
124.7 130
62 65
86.8 220
44.84 85
118.4 120
ISSUED: 04-09-2020
OA CALCULATIONS
1 NTS
4/9/2020 1:17:46 PM
PROJECT NO.
02470420015
SHEET NO:
OA/EA CALCULATIONS
JM.0.02
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
GENERAL NOTES R
T
H PROVIDE TURNING VANES IN ALL SQUARE THROAT ELBOWS.
I PROVIDE SPLITTER DAMPER AND TURNING VANES AT ALL TEES PHILLIP K. DEWOLFE
J PROVIDE COMMERCIAL PROGRAMMABLE NETWORK CAPABLE 102003
R
THERMOSTAT. ALL THERMOSTATS TO BE MOUNTED 48" AFF.
PR
EE
LI
F C ENS ED
B
O
ES IN
G
A1
K INSTALL NO2/CO SENSORS BASED ON MANUFACTURER'S S IO
NA L E
N
JM.3.02
RECOMMENDATION
04/09/2020
T
REF.
REF.
DW
T D
TARRANT COUNTY
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
J ISSUED: 04-09-2020
N
4/9/2020 1:17:49 PM
PROJECT NO.
02470420015
BUILDING J - OVERALL MECHANICAL PLAN - LEVEL 1
1 1/16" = 1'-0" SHEET NO:
0 8' 16' 32' 48'
1/16" = 1'-0"
R
10"x10"
90 CFM 120 CFM THERMOSTAT. ALL THERMOSTATS TO BE MOUNTED 48" AFF.
PR
SD-B
EE
RG-C RG-A F
LI
C ENS ED
O
100 CFM RG-A ES IN
75 CFM
10"x10"
640 CFM G
100 CFM K INSTALL NO2/CO SENSORS BASED ON MANUFACTURER'S S IO
NA L E
N
T RG-B
360 CFM
SD-B
90 CFM
SD-B
90 CFM
B RECOMMENDATION
3 16"x12" 04/09/2020
JM.3.01 KEYNOTES
14"ø
14"ø
14"ø
SD-B SD-B
20"ø
10"x10"
90 CFM 90 CFM SD-B SD-C EG-C A1 Key Keynote Text
90 CFM 120 CFM
JM.3.02 010 8" EXHAUST DUCT UP TO 2ND FLOOR.
SR-B SR-B
300 CFM 300 CFM SR-B RG-A 014 1" CONDENSATE LINE UP TO 2ND FLOOR TO AHU-9
RG-C
300 CFM 640 CFM T
SD-C 100 CFM 017 CONDENSATE LINE UP TO 2ND FLOOR TO EP-2.
120 CFM
12"x10"
SD-C RG-A RG-A RG-A
018 PROVIDE MANUAL BALANCING DAMPER ON RETURN DUCT TAP.
10"x10"
062 120 CFM 75 CFM 75 CFM 75 CFM
TYPICAL FOR ALL RETURN GRILLES.
061
SD-C 022 CONDENSATE LINE UP TO 2ND FLOOR FCU-1.
059 060 RG-C 16"x12" 10"x10"
1"ø
120 CFM 030 COMBUSTION AIR AND EXHAUST FLUE FOR FURNACE UP
18"ø
RG-B SD-A 031 ROUTE CONDENSATE LINE SOUTH TO OUTSIDE DRAIN
BUILDING J RENOVATIONS
300 CFM 300 CFM 40 CFM
70 CFM
6"ø 70 CFM
032 ROUTE CONDENSATE LINE NORTH TO GROUND OUTSIDE. AVOID
GANGING LINES AND AVOID DISCHARGING ONTO CONCRETE
10"x12"
640 CFM 350 CFM
1"ø SD-E
010 500 CFM
041 VERTICAL DUCT TAP WITH MANUAL BALANCING DAMPER (TYP.
14"x12"
SD-A
REF.
EG-A FOR ALL GRILLES ASSOCIATED WITH AHU-2).
SD-D
6"ø
40 CFM 50 CFM
SD-D
10"ø
12"ø
TARRANT COUNTY
350 CFM 047 NEW CONDENSING UNIT. REFERENCE DETAIL 1 ON SHEET
DW
340 CFM
10"ø
10"ø
EG-A
RG-C
RG-B 70 CFM
SD-E JM.6.01. (TYPICAL).
640 CFM 500 CFM
SR-B 480 CFM 059 AHU-1 DUCTWORK TO BE A60 GALVANEALED STEEL.
SR-B 300 CFM SD-A
SR-B
16"x8"
300 CFM T
060 AHU-2 DUCTWORK TO BE A60 GALVANEALED STEEL.
300 CFM
T8"ø
SD-B
100 CFM 12"x12"
40 CFM RG-B
400 CFM
D 061 AHU-3 DUCTWORK TO BE A60 GALVANEALED STEEL.
041 8"ø 12"x14"
10"x10"
062 RETURN DUCTWORK FOR AHU-1/2/3 TO BE A60 GALVANNEALED
T
STEEL.
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
SD-E SD-B
100 CFM 065 SUPPLY AND RETURN DUCTWORK IN LOBBY AREA TO BE A60
10"x10"
500 CFM SD-C T
BUILDING J
J ISSUED: 04-09-2020
N
4/9/2020 1:17:52 PM
PROJECT NO.
BUILDING J - AREA A MECHANICAL PLAN - LEVEL 1 02470420015
1 1/8" = 1'-0" SHEET NO:
0 4' 8' 16' 24'
1/8" = 1'-0"
R
THERMOSTAT. ALL THERMOSTATS TO BE MOUNTED 48" AFF.
PR
EE
LI
F C ENS ED
O
ES IN
G
K INSTALL NO2/CO SENSORS BASED ON MANUFACTURER'S S IO
NA L E
N
RECOMMENDATION
04/09/2020
B KEYNOTES
Key Keynote Text
016 18" X 12" OUTSIDE AIR VENT TO RETURN AIR. PROVIDE
EG-C MOTORIZED DAMPER.
019 16" X 8" EXHAUST DUCT UP TO EF-2 ON ROOF.
030 COMBUSTION AIR AND EXHAUST FLUE FOR FURNACE UP
THROUGH ROOF. PROVIDE WITH CONCENTRIC VENT.
058 FURNISH DUCTWORK WITH DUCT WRAP INSULATION WITH
WHITE VINYL FINISH EQUAL TO FORPLAX AD-363. TYPICAL FOR
BUILDING J RENOVATIONS
064 EXHAUST DUCTWORK TO BE A60 GALVANNEALED STEEL.
TARRANT COUNTY
REF.
063
35 CFM
SR-A SD-A
275 CFM SD-A 25 CFM
12"x6"
058 25 CFM SD-A 063
100 CFM
12"x6" 10"x8"
058
058 EG-A
100 CFM EG-B
T
RG-D 140 CFM
500 CFM
SD-A
EG-C 100 CFM
14"x8"
12"x6" 064
E AREA B
16"x8"
SR-A SD-A
275 CFM 100 CFM 7
JM.3.01
058 EG-B
M 115 CFM
OAL-C
030 019 BUILDING J
016
J ISSUED: 04-09-2020
N
4/9/2020 1:17:54 PM
PROJECT NO.
02470420015
BUILDING J - AREA B MECHANICAL PLAN - LEVEL 1
1 1/8" = 1'-0" SHEET NO:
0 4' 8' 16' 24'
R
THERMOSTAT. ALL THERMOSTATS TO BE MOUNTED 48" AFF.
PR
EE
LI
F C ENS ED
O
ES IN
G
K INSTALL NO2/CO SENSORS BASED ON MANUFACTURER'S S IO
NA L E
N
RECOMMENDATION
04/09/2020
B
EP-1
T
C
BUILDING J RENOVATIONS
J ISSUED: 04-09-2020
N
4/9/2020 1:17:56 PM
PROJECT NO.
BUILDING J - OVERALL MECHANICAL PLAN - LEVEL 2 02470420015
1 1/16" = 1'-0" SHEET NO:
0 8' 16' 32' 48'
1/16" = 1'-0"
22"x22"
I PROVIDE SPLITTER DAMPER AND TURNING VANES AT ALL TEES PHILLIP K. DEWOLFE
J PROVIDE COMMERCIAL PROGRAMMABLE NETWORK CAPABLE 102003
R
THERMOSTAT. ALL THERMOSTATS TO BE MOUNTED 48" AFF.
PR
EE
LI
C ENS ED
007 F
O
ES IN
G
K INSTALL NO2/CO SENSORS BASED ON MANUFACTURER'S S IO
NA L E
N
B RECOMMENDATION
SD-C SD-C
04/09/2020
120 CFM 120 CFM KEYNOTES
A1 Key Keynote Text
JM.3.02
10"x10" 006 10" EXHAUST DUCT UP THROUGH ROOF TO EF-1.
012 007 12" X 24" OUTSIDE AIR DUCT UP THROUGH ROOF DOWN TO
RG-A RETURN AIR. PROVIDE MOTORIZED DAMPER.
018
26
SD-C 190 CFM SD-C 008 8" EXHAUST DUCT DOWN TO 1ST FLOOR.
"x
26
12"x12"
120 CFM 120 CFM
"
009 6" OUTSIDE AIR DUCT UP THROUGH ROOF. PROVIDE
MOTORIZED DAMPER.
009
12"x10" 011 CONDENSATE LINE DOWN TO 1ST FLOOR MOP SINK IN
BUILDING J RENOVATIONS
EG-A
030 70 CFM 020 AHU-9 TO BE RELOCATED ABOVE CEILING OF SECOND FLOOR
012
TARRANT COUNTY
032 ROUTE CONDENSATE LINE NORTH TO GROUND OUTSIDE. AVOID
033 GANGING LINES AND AVOID DISCHARGING ONTO CONCRETE
PATH.
D 033 ROUTE CONDENSATE LINE TO JANITOR CLOSET MOP SINK ON
1ST FLOOR.
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
NO2/CO
E
AREA A
BUILDING J
J ISSUED: 04-09-2020
N
4/9/2020 1:17:58 PM
PROJECT NO.
02470420015
BUILDING J - AREA A MECHANICAL PLAN - LEVEL 2
1 1/8" = 1'-0" SHEET NO:
0 4' 8' 16' 24'
T
A J PROVIDE COMMERCIAL PROGRAMMABLE NETWORK CAPABLE 102003
R
NO2/CO NO2/CO NO2/CO NO2/CO
THERMOSTAT. ALL THERMOSTATS TO BE MOUNTED 48" AFF.
PR
EE
LI
F C ENS ED
O
ES IN
G
NO2/CO K INSTALL NO2/CO SENSORS BASED ON MANUFACTURER'S S IO
NA L E
N
RECOMMENDATION
04/09/2020
T KEYNOTES
Key Keynote Text
044
22"x22"
M
012 CONDENSATE LINE DOWN TO 1ST FLOOR.
023 023 4" OUTSIDE AIR DUCT UP THROUGH ROOF.
023 030 COMBUSTION AIR AND EXHAUST FLUE FOR FURNACE UP
IRH-2 IRH-1 THROUGH ROOF. PROVIDE WITH CONCENTRIC VENT.
B 039 36" X 36" EXHAUST AIR DUCT UP TO EF-3.
043 BIG ASS FAN EXISTING TO REMAIN
044 24" X 36" DUCT UP THROUGH ROOF TO INTAKE HOOD WITH
BUILDING J RENOVATIONS
023 045
26
043 043
"
039
T NO2/CO
TARRANT COUNTY
22"x22"
C
012
1"ø CD
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
EP-2
22"x22"
045
T
D
NO2/CO
NO2/CO
M
044 NO2/CO
023 023
AREA B
IRH-5 IRH-4
NO2/CO
E BUILDING J
J ISSUED: 04-09-2020
N
4/9/2020 1:18:00 PM
PROJECT NO.
02470420015
BUILDING J - AREA B MECHANICAL PLAN - LEVEL 2
1 1/8" = 1'-0" SHEET NO:
R
A THERMOSTAT. ALL THERMOSTATS TO BE MOUNTED 48" AFF.
PR
EE
LI
F C ENS ED
O
ES IN
G
K INSTALL NO2/CO SENSORS BASED ON MANUFACTURER'S S IO
NA L E
N
048 RECOMMENDATION
024 IH-1
04/09/2020
024 KEYNOTES
026 Key Keynote Text
B 021 14" EXHAUST DUCT DOWN TO 2ND FLOOR.
CU-9 024 4" OUTSIDE AIR DUCT DOWN TO IRH. PROVIDE INTAKE HOOD.
024
025 4" EXHAUST AIR DUCT DOWN TO EP.
025 026 12" X 24" OUTSIDE AIR DUCT DOWN TO AHU 4 & 5. PROVIDE
027 INTAKE HOOD EQUAL TO COOK MODEL 12X24 GR.
030
C 027 6" DIA OUTSIDE AIR DUCT DOWN TO AHU-9 RETURN DUCT.
PROVIDE INTAKE HOOD EQUAL TO COOK MODEL 8 PR. PROVIDE
BUILDING J RENOVATIONS
024
IH-2
D 050 NEW EXHAUST FAN. REFERENCE DETAIL 6 ON SHEET JM.6.02.
TARRANT COUNTY
E
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
J ISSUED: 04-09-2020
N
4/9/2020 1:18:02 PM
PROJECT NO.
02470420015
BUILDING J - OVERALL ROOF PLAN
1 1/16" = 1'-0" SHEET NO:
0 8' 16' 32' 48'
4"ø
THIS DRAWING CREATED
M A 4
JM.3.01 FOR PRODUCTION ON
22"x34" SHEET SIZE.
DO NOT SCALE PRINTS.
24"x14" JM.3.01
14"x12"
16"x8"
16"x16"
12"x12"
AHU-4
16"x14"
AHU-1 TEXAS REGISTERED ENGINEERING
FIRM F-2966
777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
AHU-7
16"x12"
4"ø
4"ø
16"x16"
8"ø
AHU-2 12"x14"
12"x12"
B AHU-10
16"x16"
16"x12" T E O F T EX
TA A
S
S
8"ø
20"x14"
12"x14" AHU-6 PHILLIP K. DEWOLFE
16"x16"
102003
R
PR
EE
LI
F C ENS ED
O
AHU-3 AHU-8 ES IN
S IO N G
NA L E
12"x8"
4"ø
4"ø
04/09/2020
20"x20" 16"x12"
AHU-5 8"ø E
16"x8"
4"ø
4"ø
8
JM.3.01
TARRANT COUNTY
E
12"x12"
4"ø 4"ø 4"ø 8"x16" 12"x12" 4"ø 4"ø
8"ø
8"ø
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
20"x14"
4"ø
12"x14"
16"x16"
16"x12"
16"x12"
12"x14"
3"ø
3"ø
M
3"ø
3"ø
3"ø
3"ø
3"ø
3"ø
AHU-8
3"ø
3"ø
3"ø
3"ø
3"ø
3"ø
OAL-A 14"x24"
8"x12"
16"x12"
16"x12"
AHU-2 AHU-3
AHU-1
AHU-4 AHU-5
AHU-7 AHU-10 AHU-6
12"ø
055
055 055 055 055
12"x12"
8"x16"
8"x16"
055
19"x22"
19"x22"
19"x20"
16"x20"
16"x20"
20"x20"
16"x20"
ISSUED: 04-09-2020
055 055
DRAWN BY: D. REILLY
REVISIONS:
SECTION SECTION SECTION SECTION
1 4 6 8
1/2" = 1'-0" 1/2" = 1'-0" 1/2" = 1'-0" 1/2" = 1'-0"
4/9/2020 1:18:05 PM
PROJECT NO.
02470420015
SHEET NO:
Texas
Department
of Transportation
T E O F T EX
TA A
S
S
PHILLIP K. DEWOLFE
102003
R
PR
EE
LI
F C ENS ED
O
ES IN
S IO N G
NA L E
04/09/2020
E D C B A
EF-3
MD
T.O.P
23' - 4"
22"x22"
22"x22"
J ISSUED: 04-09-2020
MEZZANINE
LEVEL
LEVEL 2
22"x22"
EG-C U
(TYP 4)
LEVEL 1 N
-0' - 1 13/16"
4/9/2020 1:18:07 PM
PROJECT NO.
02470420015
SHEET NO:
A1
WAREHOUSE EXHAUST DUCTWORK SECTION VIEW
1/8" = 1'-0"
SECTION VIEWS
JM.3.02
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
R
INTAKE/RELEIF HOOD
Texas
Department
of Transportation
RS
RL
REFRIGERANT LINES
AIR COOLED
CONDENSING UNIT
REFRIGERANT VALVE
(TYP)
FILTER DRYER
T E O F T EX
METAL ROOF CONC. DECK TA A
S
NEOPRENE PADS SIGHT GLASS S
WOOD NAILER (BASE)
INSULATION
CONCRETE PHILLIP K. DEWOLFE
HOUSEKEEPING PAD SLAB MOTORIZED DAMPER 102003
R
TOP OF PAD MINIMUM
PR
EE
GRADE LI
C ENS ED
4" ABOVE GRADE F
O
METAL DECK CONCRETE DECK ES IN
S IO N G
NA L E
04/09/2020
NOTE:
REFRIGERANT LINE ACCESSORIES SHOWN ARE MINIMUM REQUIRED. PROVIDE
ADDITIONAL ACCESSORIES AS REQUIRED BY MANUFACTURER.
BUILDING J RENOVATIONS
HANGER STRAPS
ROD
TARRANT COUNTY
40" MAX
SIZE BOLTS
FOR LOAD
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
SCREWS
1" MIN
STRAP
HANGER RODS,
WIRES OR
STRAPS
NUTS
BAND OF SAME
HANGERS SIZE AS HANGER
ANGLES
MUST NOT STRAP
DEFORM
DUCT
SHAPE
LOAD RATED
FASTENERS
ALTERNATE LOCATION
(VERIFY UPPER TRAPEZE
LOAD CAPACITY)
ISSUED: 04-09-2020
PROJECT NO.
02470420015
TYPICAL DUCTWORK SUPPORT DETAILS SHEET NO:
3 NTS
DETAILS
JM.6.01
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
R
ROUND DUCT
CONNECTION
R
PR
EE
LI
NOTE: STEEL SLEEVE F C ENS ED
O
ES IN
SUPPLY OR S IO N G
NOTES : NA L E
RETURN
FLEXIBLE DUCT 1. PROVIDE YOUNG, OR EQUIVALENT, LOCKING TYPE REGULATOR FOR BALANCING AIR 1. PACK SPACES BETWEEN OPENING AND DUCT INSULATION WITH
5'-0" MAX. DEVICE IN NON-REMOVABLE CEILINGS OR IN FURRINGS. MINERAL FIBER CONFORMING WITH ASTM C553. 04/09/2020
LENGTH 2. WALL IS INTERIOR AND NOT FIRE RATED.
TYPICAL BRANCH DUCT CONNECTION DETAIL TYPICAL DIFFUSER CONNECTION DETAIL TYPICAL DUCTWORK INTERIOR WALL PENETRATION
1 NTS
2 NTS
3 NTS
EQUAL TO REQ'D
AIRFLOW
BRANCH DUCT
EXHAUST FAN
DIMENSIONS
SEAL ALL
AROUND
SECURE FAN TO ROOF
CURB, RE: SPECIFICATIONS
PROJECT NO.
02470420015
SHEET NO:
DETAILS
JM.6.02
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
R
AHU-4 SPLIT SYSTEM NORTH OFFICES TRANE TEM4A0C48S41 145 21.1 21.75 51.25 R-410A 1400 90 0.5 40.3 34.9 76.7/62.1 55.0/52.6 ELECTRIC 10.8 KW 1 3/4 208 1 60 83 90 1,2,3,4,7
AHU-5 SPLIT SYSTEM INTERIOR OFFICES TRANE TEM4A0C48S41 145 21.1 21.75 51.25 R-410A 1400 150 0.5 46 33.8 77.4/62.8 55.0/52.5 ELECTRIC 7.2 KW 1 3/4 208 1 60 58 60 1,2,3,4,7
AHU-6 SPLIT SYSTEM SOUTH OFFICES TRANE 4TXC+S9V2C 144 28.8 21.1 34 R-410A 1475 130 0.5 41.3 35.8 77.0/62.7 55.0/52.9 NATURAL GAS 96 1 3/4 120 1 60 10.8 15 1,2,3,4,6
AHU-7 SPLIT SYSTEM CONFERENCE ROOM TRANE 4TXC+S9V2C 144 28.8 21.1 34 R-410A 700 65 0.5 20.5 15.9 77.2/63.3 55.0/53.0 NATURAL GAS 96 1 1/2 120 1 60 8 15 1,2,3,4,6
TEXAS REGISTERED ENGINEERING
AHU-8 SPLIT SYSTEM MAINTENANCE TRANE 4TXC+S9V2C 114 28.8 21.1 34 R-410A 1000 220 0.5 30.5 23.6 77.1/61.7 55.0/51.2 NATURAL GAS 39 1 1/2 120 1 60 7.9 15 1,2,3,4,6 FIRM F-2966
777 MAIN ST. STE B-101
AHU-9 SPLIT SYSTEM SECOND FLOOR TRANE 4TXC+S9V2B 114 28.8 17.6 34 R-410A 525 85 0.5 16.0 12.2 77.2/62.7 55.0/52.6 NATURAL GAS 39 1 1/2 120 1 60 7.9 15 1,2,3,4,5,6,7 FORT WORTH, TEXAS 76102
AHU-10 SPLIT SYSTEM CENTRAL BREAKROOM TRANE 4TXC+S9V2B 114 28.8 17.6 34 R-410A 1000 120 0.5 29.4 23.7 77.8/63.8 55.0/53.2 NATURAL GAS 39 1 1/2 120 1 60 7.9 15 1,2,3,4,6
NOTES:
1. ELECTRICAL TO PROVIDE UNIT DISCONNECT.
2. PROVIDE WITH A PROGRAMMABLE ELECTRONIC ROOM THERMOSTAT.
3. PROVIDE WITH 2" PLEATED DISPOSABLE FILTERS, MERV 8.
4. PROVIDE FACTORY INSTALLED LIQUID AND SUCTION LINE SERVICE VALVES.
5. UNIT SHALL BE IN HORIZONTAL CONFIGURATION.
6. PROVIDE WITH COMBUSTION AIR CONCENTRIC VENT KIT.
T E O F T EX
7. PROVIDE WITH CONDENSATE PUMP TA A
S
S
102003
NOMINAL
R
PR
EE
LI
C ENS ED
CAPACITY OUTSIDE AMBIENT OPERATING SEER @ F
O
ES IN
S IO N G
(TONS) NA L E
MARK MANUFACTURER MODEL AREA SERVED TEMPERATURE REFRIGERANT TYPE WEIGHT (LBS) AHRI VOLTAGE PHASE FREQUENCY MCA MOCP NOTES
CU-1 TRANE 4TTA3048D4 MAIN FLOOR 4 110 R-410A 197 14.25 460 3 60 8 15 1,2 04/09/2020
CU-2 TRANE 4TTA3048D4 MAIN FLOOR 4 110 R-410A 197 14.25 460 3 60 8 15 1,2
CU-3 TRANE 4TTA3048D4 MAIN FLOOR 4 110 R-410A 197 14.25 460 3 60 8 15 1,2
CU-4 TRANE 4TTA4048A3 NORTH OFFICES 4 110 R-410A 189 14.5 208 3 60 18 30 1,2
CU-5 TRANE 4TTA4048A3 CENTRAL OFFICES 4 110 R-410A 189 14.5 208 3 60 18 30 1,2
CU-6 TRANE 4TTA3048D4 SOUTH OFFICES 4 110 R-410A 197 14.25 460 3 60 8 15 1,2
CU-7 TRANE 4TTR3024H1 CENTRAL CONFERENCE 2 110 R-410A 169 14.75 208 1 60 18 30 1,2
CU-8 TRANE 4TTA4036A4 MAINTENANCE 3 110 R-410A 147 14.75 460 3 60 8 15 1,2
CU-9 TRANE 4TTR3018H1 SECOND FLOOR 1.5 110 R-410A 165 14.5 208 1 60 12 20 1,2
CU-10 TRANE 4TTA3036A4 CENTRAL KITCHEN 3 110 R-410A 147 14.75 460 3 60 8 15 1,2
BUILDING J RENOVATIONS
TARRANT COUNTY
OPERATING EXHAUST PRESSURE (IN
MARK AREA SERVED MANUFACTURER MODEL TYPE ELEVATION WEIGHT CFM W.C.) FAN RPM FAN DRIVE MOTOR HP VOLTAGE PHASE FREQUENCY NOTES
EF-1 HR OFFICE RR LOREN COOK 80 ACE-B CENTRIFUGAL 182 36 330 .5 1318 BELT 1/6 115 1 60 1, 2, 3, 4
EF-2 MAINTENANCE RR LOREN COOK 100 ACE-B CENTRIFUGAL 182 38 585 .67 1627 BELT 1/6 115 1 60 1, 2, 3, 4
EF-3 SHOPS LOREN COOK 365 ACE-B CENTRIFUGAL 182 324 10000 0.75 505 BELT 3 460 3 60 1, 3, 4, 5
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
NOTES:
1. ELECTRICAL TO PROVIDE APPROPRIATELY SIZED DISCONNECT FOR VOLTAGE SPECIFIED AND REQUIRED MOTOR HORSEPOWER.
2. POWER TO EXHAUST FAN SHALL BE INTERLOCKED WITH THE HVAC EQUIPMENT SUPPLYING THE SPACE.
3. MANUFACTURER TO PROVIDE ROOF MOUNTED EXHAUST FANS WITH CURB TO MATCH THE SLOPE OF THE ROOF
4. PROVIDE WITH MOTORIZED ISLOATION DAMPER
5. PROVIDE VFD WITH FAN.
IRH SCHEDULE
INPUT TUBE
MOUNTING CAPACITY DIAMETER GAS CONN. GAS PRESS. (IN
MARK HEIGHT (FT) FUEL TYPE (MBH) FLUE DIAMETER (IN.) (IN.) (IN.) H20) VOLTS/PHASE FLA MANUFACTURER MODEL NOTES
EP-1 18 N/A N/A 4.5 4.5 N/A N/A 115/1 8 ROBERTS GORDON EP-201 4
EP-2 18 N/A N/A 4.5 4.5 N/A N/A 120/1 5.2 ROBERTS GORDON EP-100 4
IRH-1 15 NAT. GAS 100 N/A 4.5 1/2 NPT 4.5 120/1 .3 ROBERTS GORDON CRVB-10 1,2,3
IRH-2 15 NAT. GAS 100 N/A 4.5 1/2 NPT 4.5 120/1 .3 ROBERTS GORDON CRVB-10 1,2,3
IRH-3 15 NAT. GAS 100 N/A 4.5 1/2 NPT 4.5 120/1 .3 ROBERTS GORDON CRVB-10 1,2,3
IRH-4 15 NAT. GAS 100 N/A 4.5 1/2 NPT 4.5 120/1 .3 ROBERTS GORDON CRVB-10 1,2,3
IRH-5 15 NAT. GAS 100 N/A 4.5 1/2 NPT 4.5 120/1 .3 ROBERTS GORDON CRVB-10 1,2,3
NOTES:
1. INSTALL WITH PORCELAIN COATED TAILPIPES AND HIGH EFFICIENCY RELFECTORS.
2. IINSTALL WITH 40' BETWEEN BURNERS.
3. INSTALL HEATER TUBES 15' AFF.
4. PROVIDE WITH CONDENSATE PUMP AND CONDENSATE NEUTRALIZATION TUBE PER MANUFACTURER.
ISSUED: 04-09-2020
PROJECT NO.
02470420015
SHEET NO:
MECHANICAL SCHEDULES
JM.7.01
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
R
PHILLIP K. DEWOLFE
102003
R
PR
EE
LI
F C ENS ED
O
ES IN
S IO N G
NA L E
BUILDING J RENOVATIONS
MARK MANUFACTURER MODEL SYSTEM SERVED EER@ARI VOLTAGE PHASE FREQUENCY MCA MOCP NOTES
FCU CU-1 DAIKIN RKN24NMVJU FCU-1 2 110 R-410A 97 9.2 208 1 60 18.3 20
TARRANT COUNTY
GROSS AREA FREE AREA PERCENT VELOCITY
MARK MANUFACTURER MODEL TYPE AIRFLOW (CFM) WIDTH (IN.) HEIGHT (IN.) (SQ FT) (SQ FT) FREE AREA (FPM) NOTES
OAL-A RUSKIN ELF375DX DRAINABLE STATIONARY 390 14 14 1.36 .52 38% 755 1
OAL-B RUSKIN ELF375DX DRAINABLE STATIONARY 315 16 12 1.33 .48 36% 663 1
OAL-C RUSKIN ELF375DX DRAINABLE STATIONARY 220 12 12 1 .31 31% 711 1
NOTES:
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
ISSUED: 04-09-2020
PROJECT NO.
02470420015
SHEET NO:
MECHANICAL SCHEDULES
JM.7.02
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
R
Texas
Department
of Transportation
AI
SMK
T E O F T EX
TA A
S
S
DI
N.O. PHILLIP K. DEWOLFE
102003
M
R
PR
EE
LI
F C ENS ED
AI
O
AI ES IN
AI S IO N G
NA L E
04/09/2020
SUPPLY AIR
OUTSIDE AIR FLTR TS-02 MIXED AIR TEMP SF TS-03
TS-01 TEMP
TEMP M
N.C.
OUTSIDE AIR SUPPLY AIR
BUILDING J RENOVATIONS
FAN START/STOP DO
TARRANT COUNTY
THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND STAGE
THE FOLLOWING MODES: THE COOLING TO MAINTAIN ITS COOLING SETPOINT. PROGRAMMABLE THERMOSTAT
• OCCUPIED MODE: THE UNIT SHALL MAINTAIN
• A 75°F (ADJ.) COOLING SETPOINT THE COOLING SHALL BE ENABLED WHENEVER:
• A 70°F (ADJ.) HEATING SETPOINT.
• AND THE ZONE TEMPERATURE IS ABOVE COOLING SETPOINT. T
• UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN • AND THE SUPPLY FAN STATUS IS ON.
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
ISSUED: 04-09-2020
PROJECT NO.
SINGLE ZONE SPLIT-SYSTEM CONTROL DIAGRAM 02470420015
1 NTS
SHEET NO:
Texas
Department
of Transportation
RETURN AIR
TS-04
TEMP TEXAS REGISTERED ENGINEERING
FIRM F-2966
777 MAIN ST. STE B-101
FORT WORTH, TEXAS 76102
RETURN AIR
T E O F T EX
TA A
S
S
PHILLIP K. DEWOLFE
SMK
102003
R
PR
EE
LI
F C ENS ED
O
ES IN
S IO N G
DI NA L E
N.O.
04/09/2020
M
AI AI
AI
SUPPLY AIR
OUTSIDE AIR FLTR TS-02 MIXED AIR TEMP SF TS-03
TS-01 TEMP
TEMP M
TARRANT COUNTY
DO
FAN START/STOP DO
RUN CONDITIONS - SCHEDULED: COOLING STAGE:
THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND STAGE
THE FOLLOWING MODES: THE COOLING TO MAINTAIN ITS COOLING SETPOINT.
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
ISSUED: 04-09-2020
PROJECT NO.
02470420015
SINGLE ZONE SPLIT-SYSTEM CONTROL DIAGRAM
1 NTS SHEET NO:
Texas
Department
of Transportation
T E O F T EX
TA A
S
S
PHILLIP K. DEWOLFE
102003
R
PR
EE
LI
F C ENS ED
O
ES IN
S IO N G
NA L E
04/09/2020
YA-1 YR-1
FV-1
ES-2
M
YC-1
FA-1
BUILDING J RENOVATIONS
MOTORIZED VEHICLE
DAMPER EXHAUST
DI DO
SPACE SENSORS
FAN STATUS FAN START/STOP
C:\_Revit_Local_Models\2018\TXDOT_FW-M-BldgJ-R18-Central_DR.Reilly.rvt
START AND STOP VEHICLE VENTILATION SYSTEM UPON SCHEDULE, OPERATOR ACTIVATION, OR AUTOMATICALLY AFTER POWER
M OUTAGE.
VEHICLE VENTILATION AND EXHAUST FAN OPERATION: VEHICLE VENTILATION AND EXHAUST FAN SYSTEM (APRON AND BASEMENT)
THE VENTILATION INTAKE HOODS (IH-1 & IH-2) AND VEHICLE EXHAUST FAN (EF-3) SHALL OPERATE AS A SINGLE SYSTEM AND SHALL RUN
SYSTEM GRAPHICS
ANALOG OUTPUTS
CONTINUOUSLY (AS SCHEDULED) WITH THE NORMALLY CLOSED DAMPERS IN THE OPEN POSITION AND NORMALLY OPEN DAMPERS
SOFTWARE POINT
DIGITAL OUTPUTS
POINT IDENTIFIER
ANALOG INPUTS
IN THE CLOSED POSITION.
DIGITAL INPUTS
THE EXHAUST FAN SHALL START ONLY AFTER THE RESPECTIVE DAMPER STATUS (INTAKE AND EXHAUST) HAS PROVEN THE DAMPER IS
OPEN. THE INTAKE AND EXHAUST DAMPERS SHALL CLOSE 30 SECONDS (ADJUSTABLE) AFTER THE FAN STOPS.
ON STARTUP, THE FANS SHALL BE ENERGIZED AT THE MINIMUM VFD SPEED. THE FANS WILL REMAIN AT MINIMUM SPEED UNTIL A
ALARM
RISE IN CARBON MONOXIDE (200 PPM, ADJ.) OR NITROGENT DIOXIDE (0.2 PPM, ADJ.) IS DETECTED. UPON DETECTION OF AN
RUN CONDITIONS - CONTINUOUS: ELEVATED LEVEL OF CO OR NO2, THE FAN SHALL RAMP UP TO 100% FLOW. ONCE THE DETECTED LEVELS ARE BELOW THE
THE FAN SHALL RUN CONTINUOUSLY. SETPOINTS FOR 5 MIN (ADJ.), THE FANS WILL RAMP DOWN TO MINIMUM SPEED. GENERATE AN ALARM IF CARBON
MONOXIDE LEVELS ABOVE 400 PPM (ADJ.) OR NITROGEN DIOXIDE ABOVE 1 PPM (ADJ.). INTAKE HOOD
FAN STATUS: FV-1 OUTSIDE AIR DAMPER X X
THE EXHAUST FAN SHALL GENERATE AN ALARM UPON THE FOLLOWING CONDITIONS: ES-1 OUTSIDE AIR DAMPER END SWITCH X X X ISSUED: 04-09-2020
THE CONTROLLER SHALL MONITOR THE FAN STATUS. 1. FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF
2. FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON VEHICLE EXHAUST FAN DRAWN BY: D. REILLY
ALARMS SHALL BE PROVIDED AS FOLLOWS: FV-2 EXHAUST AIR DAMPER X X
ES-2 X REVISIONS:
• FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF. OUTSIDE AIR DAMPER END SWITCH X X
• FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON. PSL-1 VEHICLE EXHAUST FAN LOW PRESSURE SWITCH X X X
YR-1 VEHICLE EXHAUST FAN STATUS X X X
YA-1 VEHICLE EXHAUST FAN ALARM X X
YC-1 VEHICLE EXHAUST FAN VFD ENABLE X X
SC-1 VEHICLE EXHAUST FAN VFD MODULATION X X
PSH-1 VEHICLE EXHAUST FAN HIGH PRESSURE SWITCH X X
4/9/2020 1:18:15 PM
EF CONTROL DIAGRAMS
JM.8.03
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION
R
LIGHTING SYMBOLS ELECTRICAL SYMBOLS ELECTRICAL ABBREVIATIONS ELECTRICAL ABBREVIATIONS PROJECT NOTES - ELECTRICAL
Key Name ABBREVIATION Key Name ABBREVIATION A PERFORM ELECTRICAL WORK IN ACCORDANCE WITH 2017 NFPA 70,
2' X 2' LUMINAIRE ELECTRICAL CONNECTION; SQUARE DENOTES CONNECTION TO A, AMP AMPERE(S) MAX MAXIMUM AMERICANS WITH DISABILITIES ACT (ADA) AND APPLICABLE LOCAL Texas
WALL MOUNTED DEVICE, CIRCLE DENOTES CONNECTION TO STANDARDS. IN THE EVENT OF A CONFLICT BETWEEN STANDARDS, THE Department
E E A/V AUDIO/VISUAL MCB MAIN CIRCUIT BREAKER
CEILING OR FLOOR MOUNTED DEVICE. MORE STRINGENT STANDARD WILL GOVERN. of Transportation
AC ALTERNATING CURRENT MCCB MOLDED CASE CIRCUIT BREAKER
1' X 4' LUMINAIRE B UNLESS OTHERWISE NOTED, ALL CONDUCTORS ARE SIZED FOR COPPER
AF AMPERE FRAME (CIRCUIT BREAKER) MDF MAIN DISTRIBUTION FRAME TYPE THWN, THHN, AND RATED FOR 75 DEGREE C (MINIMUM).
AFF ABOVE FINISHED FLOOR MECH MECHANICAL C SHARED NEUTRALS ARE NOT ALLOWED; PROVIDE ALL 120 AND 277 VOLT
2' X 4' LUMINAIRE INDOOR 27KV METAL CLAD SWITCHGEAR WITH WORKING CLEARANCE AFU AMPERE FUSE MH MANHOLE CIRCUITS WITH A DEDICATED NEUTRAL CONDUCTOR.
THIS DRAWING CREATED
AHU AIR HANDLING UNIT MIN MINIMUM D PROVIDE A DEDICATED EQUIPMENT GROUNDING CONDUCTOR, SIZED PER FOR PRODUCTION ON
22"x34" SHEET SIZE.
AIC AMPERE INTERRUPTING CAPACITY MLO MAIN LUGS ONLY THE NEC, WITH EACH BRANCH CIRCUIT. DO NOT SCALE PRINTS.
WALL MOUNTED LUMINAIRE AL ALUMINUM MV MEDIUM VOLTAGE E UNLESS OTHERWISE NOTED, CIRCUITS ARE SIZED ASSUMING NO MORE
AT AMPERE TRIP (CIRCUIT BREAKER) N NEUTRAL, NORMAL THAN THREE CURRENT CARRYING CONDUCTORS IN A SINGLE CONDUIT. NO
INDOOR UNIT SUBSTATION WITH WORKING CLEARANCE 480V MORE THAN THREE CURRENT CARRYING CONDUCTORS MAY BE INSTALLED
ATS AUTOMATIC TRANSFER SWITCH NC NORMALLY-CLOSED
IN A SINGLE CONDUIT UNLESS OTHERWISE NOTED.
CEILING SURFACE MOUNTED / RECESSED LUMINAIRE AWG AMERICAN WIRE GAUGE NEC NATIONAL ELECTRICAL CODE
F VERIFY ALL REQUIREMENTS FOR OVERCURRENT PROTECTIVE DEVICE
BAS BUILDING AUTOMATION SYSTEM NIC NOT IN CONTRACT
SIZES, DISCONNECT SWITCH SIZES, AND CIRCUIT WIRE AND CONDUIT SIZES
C CONDUIT NO NORMALLY-OPEN WITH THE FINAL APPROVED REQUIREMENTS OF THE MECHANICAL TEXAS REGISTERED ENGINEERING
SWITCHBOARD WITH WORKING CLEARANCE, 480/277V FIRM F-2966
SURFACE MOUNTED LUMINAIRE CAT CATEGORY NTS NOT TO SCALE EQUIPMENT TO BE INSTALLED, AND PROVIDE ALL ELECTRICAL
777 MAIN ST. STE B-101
CC CONTROL COIL OL OVERLOAD(S) COMPONENTS AS REQUIRED. THE ELECTRICAL EQUIPMENT SIZING HEREIN
FORT WORTH, TEXAS 76102
CCTV CLOSED CIRCUIT TELEVISION OS OCCUPANCY SENSOR IS BASED UPON THE SPECIFIED MECHANICAL EQUIPMENT AVAILABLE AT
WALL MOUNTED EMERGENCY FIXTURE WITH INTEGRAL BATTERY BACKUP THE TIME OF DESIGN. SYSTEM CHANGES IN REQUIREMENTS THAT OCCUR
DISTRIBUTION PANELBOARD WITH WORKING CLEARANCE, 480/277V CIB CCTV INTERFACE BOX P POLE AS A RESULT OF OTHER MANUFACTURER'S EQUIPMENT BEING SELECTED
(90 MINUTE MINIMUM).
CT CURRENT TRANSFORMER PA PUBLIC ADDRESS SHALL BE ACCOMMODATED WITHOUT ADDITIONAL COST TO THE OWNER.
DAS DISTRIBUTED ANTENNA SYSTEM PB PUSHBUTTON, PULLBOX G FLUSH MOUNT ALL SWITCHES AND RECEPTACLES IN FINISHED AREAS.
WALL MOUNTED EXIT SIGN, SHADED AREAS INDICATE NUMBER OF FACES, BRANCH PANELBOARD WITH WORKING CLEARANCE, 480/277V DC DIRECT CURRENT PC PHOTOCELL SWITCHES AND RECEPTACLES MAY BE SURFACE MOUNTED IN EXPOSED
DIRECTION ARROWS AS INDICATED
DEMO DEMOLITION PDU POWER DISTRIBUTION UNIT SPACES. UNLESS OTHERWISE NOTED, CONCEAL ALL CONDUIT IN WALLS,
DIA DIAMETER PF POWER FACTOR ABOVE ACCESSIBLE CEILING, OR IN FLOOR SLAB. CONDUIT IN ROOMS WITH
CEILING MTD. EXIT SIGN, SHADED AREAS INDICATE NUMBER OF FACES, BRANCH PANELBOARD WITH WORKING CLEARANCE, 208/120V NO CEILING THAT ARE EXPOSED TO STRUCTURE MAY BE EXPOSED,
DIRECTION ARROWS AS INDICATED DP DISTRIBUTION PANELBOARD PFC POWER FACTOR CORRECTION
MOUNTED TO BUILDING STRUCTURE. DO NOT INSTALL CONDUITS IN
DPM DIGITAL POWER METER PH,Θ PHASE CONCRETE FLOORS WITH TOPPINGS LESS THAN 3” THICK. OTHER THAN
EC ELECTRICAL CONTRACTOR PNL PANEL CONDUITS ORIGINATING FROM OR SERVING THE SITE, AND CONDUITS
SWITCH SYMBOLS MINI POWER ZONE PANELBOARD/TRANSFORMER COMBINATION WITH
WORKING CLEARANCE EF EXHAUST FAN PT POTENTIAL TRANSFORMER FROM THE SWITCHGEAR TO THE UNIT SUBSTATIONS, ALL CONDUITS SHALL
ELEV ELEVATOR PVC POLYVINYL CHLORIDE BE ROUTED ABOVE GRADE LEVEL.
EMT ELECTRICAL METALLIC TUBING PWR POWER H VERIFY ALL FURNITURE AND EQUIPMENT LOCATIONS WITH ARCHITECTURAL
S SINGLE POLE SWITCH, 20A, 120-277VAC AND INTERIORS PLANS AND ELEVATIONS, AS WELL AS FINAL APPROVED
EO ELECTRICALLY OPERATED QTY QUANTITY
SINGLE OR THREE PHASE MOTOR ELECTRICAL CONNECTION SHOP DRAWINGS PRIOR TO MAKING ASSOCIATED ELECTRICAL
EOL END OF LINE RE REFER INSTALLATIONS. MAKE ANY ADJUSTMENTS TO RECEPTACLES, FLOOR
S "X" REFER TO SWITCH NOTES EPO EMERGENCY POWER OFF REC, RECPT RECEPTACLE BOXES, OR CONNECTIONS AS REQUIRED TO ACCOMMODATE FURNITURE
X MOTOR RATED DISCONNECT SWITCH, COORDINATE PHASES AND EQ EQUAL REQ, REQD REQUIRED OR EQUIPMENT.
SWITCH NOTES: SM RATINGS WITH FINAL APPROVED EQUIPMENT SERVED PRIOR TO EWC ELECTRIC WATER COOLER RF RETURN FAN I SEAL ALL CONDUIT PENETRATIONS, USING A LISTED SEALANT (INCLUDING
PURCHASE EX EXISTING TO REMAIN RM ROOM FIRESTOPPING) FOR THE APPROPRIATE APPLICATION, OF WALLS,
"a" = LOWER CASE LETTER INDICATES SWITCHING CIRCUIT ID FA FIRE ALARM RTU ROOFTOP UNIT PARTITIONS, FLOORS, ROOF, ETC.
"3" = THREE-WAY SWITCH 20A, 120-277VAC J THROUGH WALL BOXES ARE NOT ACCEPTABLE; BOXES THAT ARE LOCATED
"4" = FOUR-WAY SWITCH 20A, 120-277VAC NON-FUSED DISCONNECT SWITCH FACP FIRE ALARM CONTROL PANEL SB SWITCHBOARD
ON OPPOSITE SIDES OF FIRE RATED OR HIGH SOUND TRANSMISSION CLASS
"M" = MANUAL MOTOR STARTER SWITCH FCU FAN COIL UNIT SCCR SHORT CIRCUIT CURRENT RATING
WALLS MUST HAVE A MINIMUM HORIZONTAL SEPARATION OF 24".
"T" = SINGLE POLE SWITCH WITH TIMER FDS FUSED DISCONNECT SWITCH SD SMOKE DETECTOR
"LV" = LOW VOLTAGE SWITCH WITH ON/OFF AND DIMMING CONTROL K "PROVIDE" = "FURNISH" = "INSTALL"
FUSED DISCONNECT SWITCH FLA FULL LOAD AMPERES SEC SECONDARY
"OS" = OCCUPANCY/VACANCY SENSOR WALL SWITCH (IR) WITH MANUAL OVERRIDE L BALANCE PANEL LOADS AS EVENLY AS POSSIBLE BETWEEN EACH PHASE.
FLR, FL FLOOR SF SUPPLY FAN
M WORKING SPACES ABOUT ELECTRICAL EQUIPMENT SHALL BE PER NEC
FPB FAN POWERED BOX SG SWITCHGEAR 110.26, WITH THE EXCEPTION THAT THE ELECTRICAL HEIGHT OF WORKING
OS OCCUPANCY SENSOR MOUNTED IN CEILING IN VACANCY-SENSING MODE, COMBINATION MAGNETIC MOTOR DISCONNECT/STARTER FUT FUTURE SIB SECURITY INTERFACE BOX SPACE SHALL EXTEND FROM THE FLOOR TO THE STRUCTURAL CEILING. NO
WATT STOPPER (DUAL TECHNOLOGY) DT-300 OR APPROVED EQUAL
G GROUND (CONDUCTOR) SPD SURGE PROTECTIVE DEVICE PIPING, DUCTS, OR OTHER EQUIPMENT FOREIGN TO ELECTRICAL SYSTEMS
DISCONNECT SWITCH TAG KEY: (60A) DENOTES DISCONNECT FRAME GCC GENERATOR CONNECTION CABINET SPEC SPECIFICATION SHALL BE PERMITTED IN THE WORKING SPACE ABOUT ELECTRICAL
OCCUPANCY SENSOR NOTES: EQUIPMENT.
SIZE. (3P) DENOTES NUMBER OF POLES. (60AFU) DENOTES DISCONNECT
BUILDING J RENOVATIONS
VARIABLE FREQUENCY DRIVE WITH HORSEPOWER DESIGNATION, GRS GALVANIZED RIGID STEEL TELECOM TELECOMMUNICATIONS CONSTRUCTION PRIOR TO BID TO VERIFY EXISTING CONDITIONS.
REFER TO VFD SCHEDULE ON 2E-604 FOR ADDITIONAL INFORMATION. H, HT HEIGHT TV TELEVISION P MULTI-CONDUCTOR CABLES ARE NOT ACCEPTABLE FOR USE ON THIS
TARRANT COUNTY
HWP HOT WATER PUMP UL UNDERWRITERS LABORATORY OF #10 AWG, ETC.).
QUADRAPLEX RECEPTACLE, 125V, 20A, 2P, 3W EMERGENCY POWER OFF MUSHROOM HEAD BUTTON WITH CLEAR HZ HERTZ UON UNLESS OTHERWISE NOTED R FLEXIBLE CONDUIT MAY ONLY BE USED FOR FINAL EQUIPMENT
EPO
NEMA 5-20R COVER IG ISOLATED GROUND UP UNINTERRUPTIBLE POWER SUPPLY BRANCH CONNECTIONS, AND SHALL BE LIMITED TO 6'-0" IN LENGTH.
IMC INTERMEDIATE METAL CONDUIT PANELBOARD S INSTALL ALL OF THE FOLLOWING SYSTEM'S WIRING IN
SPECIAL PURPOSE RECEPTACLE, J JUNCTION BOX UPS UNINTERRUPTIBLE POWER SUPPLY MANFACTURER-COLORED CONDUIT: FIRE ALARM SYSTEMS - RED,
A 208V, 30A, 3P, 4W, NEMA 6-50R T# TRANSFORMER WITH WORKING CLEARANCE, # DENOTES KVA RATING.
KCM ONE THOUSAND CIRCULAR MILS UTP UNSHIELDED TWISTED PAIR GENERATOR POWER – GREEN, SECURITY – PAINTED TO MATCH
C:\Users\trussecs\Documents\TXDOT_FW-E-BldgJ-R18-Central_ctrussellHNAD3.rvt
PROJECT NO.
4/9/2020 14:42:49
02470420015
SHEET NO:
Texas
Department
of Transportation
AMPERAGE SEEN AT SERVICE ENTRANCE PANEL AMPERAGE SEEN AT SERVICE ENTRANCE PANEL
LOAD TYPE WATTAGE LOAD TYPE WATTAGE
(480V/3PHASE) (480V/3PHASE)
LIGHTING (14
LIGHTING (11
704W 0.85 FIXTURES, 32W EACH) 448W 0.54
FIXTURES, 64W EACH)
(SEE NOTE 3) TEXAS REGISTERED ENGINEERING
FIRM F-2966
CU-1 6568W 7.9 CU-1 5321W 6.4 777 MAIN ST. STE B-101
CU-2 6568W 7.9 CU-2 5321W 6.4 FORT WORTH, TEXAS 76102
CU-3 6568W 7.9 CU-3 5321W 6.4
CU-4 4936W 5.93 CU-4 (SEE NOTE 3) 1310W 1.58
CU-5 4936W 5.93 CU-5 (SEE NOTE 3) 1310W 1.58
CU-6 SEE NOTE 1 CU-6 5321W 6.4
CU-7 SEE NOTE 1 CU-7 1726W 2.08
CU-8 SEE NOTE 1 CU-8 4822W 5.8
CU-9 SEE NOTE 1 CU-9 1394W 1.68
AHU-1 1120W 1.35 CU-10 4822W 5.8
AHU-2 1120W 1.35 AHU-1 (SEE NOTE 3) 1296W 1.56
AHU-3 1120W 1.35 AHU-2 (SEE NOTE 3) 1296W 1.56
AHU-4 14400W 17.32 AHU-3 (SEE NOTE 3) 1296W 1.56
AHU-5 14400W 17.32 AHU-4 (SEE NOTE 3) 17264W 20.77
AHU-6 SEE NOTE 1 AHU-5 (SEE NOTE 3) 9984W 12.01
AHU-7 SEE NOTE 1 AHU-6 (SEE NOTE 3) 1296W 1.56
AHU-8 SEE NOTE 1 AHU-7 (SEE NOTE 3) 960W 1.15
AHU-9 8790W 10.57 AHU-8 (SEE NOTE 3) 948W 1.14
ELEVATOR
SEE NOTE 2 AHU-9 (SEE NOTE 3) 948W 1.14
EQUIPMENT
AHU-10 (SEE NOTE 3) 948W 1.14
FCU CU-1 (SEE NOTE
2496W 3
3)
EF-1 (SEE NOTE 3) 528W 0.64
EF-2 (SEE NOTE 3) 528W 0.64
EF-3 3991W 4.8
EP-1 (SEE NOTE 3) 960W 1.15
EP-2 (SEE NOTE 3) 624W 0.75
IRH-1 THRU 5 (SEE
180W 0.22
NOTE 3
RECEPTACLES (SEE
540W 0.65
BUILDING J RENOVATIONS
TARRANT COUNTY
SCHEDULE NOTES
NOTE 1: EXISTING LOAD IS UNAVAILABLE DUE TO LACK OF INFORMATION GATHERED FROM OWNER-SUPPLIED DOCUMENTS AND SITE PHOTOS.
NOTE 2: EXISTING ELEVATOR EQUIPMENT HAS BEEN ABANDONED AND DOES NOT IMPACT THE EXISTING LOAD OF THE BUILDING.
NOTE 3: AMPERAGE CALCULATED REFLECTS IMPACT ON BUILDING SERVICE ENTRANCE PANEL, REFER TO FLOOR PLAN DRAWINGS FOR ACTUAL CIRCUIT INFORMATION.
C:\Users\trussecs\Documents\TXDOT_FW-E-BldgJ-R18-Central_ctrussellHNAD3.rvt
ISSUED: 04-09-2020
PROJECT NO.
4/9/2020 14:42:50
02470420015
SHEET NO:
DW
* GFI BREAKROOM
105
KEYNOTES
102 DEMOLISH EXISTING LIGHT FIXTURE ABOVE MIRROR. CIRCUIT WILL
* REMAIN FOR RECONNECTION DURING RENOVATION.
106 106 DISCONNECT EXISTING STOVE RANGE FROM EXISTING NEMA 6-50R
A 169 RECEPTACLE. RECEPTACLE AND CIRCUIT TO REMAIN FOR
RECONNECTION TO NEW ELECTRIC STOVE DURING RENOVATION.
* GFI
136 EXISTING GARBAGE DISPOSAL CIRCUIT TO REMAIN DURING
B RENOVATION. REFER TO PLUMBING AND ARCHITECTURAL
DRAWINGS FOR EXTENT OF DEMOLITION.
REF.
169
141 DEMOLISH EXISTING FREIGHT ELEVATOR EQUIPMENT. DEMOLISH
ALL ASSOCIATED CONDUCTORS AND CONDUIT BACK TO SOURCE.
LABEL EXISTING CIRCUIT BREAKER SERVING DEMOLISHED
EQUIPMENT AS SPARE.
146 CONTRACTOR WILL VERIFY RECEPTACLE TYPE AT EXISTING EWC
TO BE REMOVED DURING DEMOLITION. DEMOLISH EXISTING
RECEPTACLE IF IT DOES NOT HAVE GFI PROTECTION, AND
CONDUCTORS WILL REMAIN FOR RECONNECTION DURING
RENOVATION. EXISTING RECEPTACLE WILL REMAIN FOR NEW EWC
DURING RENOVATION IF IT ALREADY HAS GFI PROTECTION.
148 DISCONNECT AND REMOVE EXISTING FIXTURE. CIRCUIT TO REMAIN
FOR RECONNECTION DURING RENOVATION.
EXISTING PANEL PH 169 EXISTING CONDUCTORS, CONDUIT, AND BREAKER TO REMAIN FOR
RECONNECTION DURING RENOVATION.
C
REF.
MEETING ROOM
MENS * GFI 213 DISCONNECT AND DEMOLISH ALL ASSOCIATED DISCONNECT
BUILDING J RENOVATIONS
142
REF.
203
DW
STAIR
TARRANT COUNTY
106
146
C:\Users\trussecs\Documents\TXDOT_FW-E-BldgJ-R18-Central_ctrussellHNAD3.rvt
169
169
ROOM
108
AREA A
213
BUILDING J
N
PROJECT NO.
4/9/2020 14:42:58
02470420015
SHEET NO:
0 4' 8' 16' 24'
1/8" = 1'-0"
BAY 1 KEYNOTES
109 108 DISCONNECT AND REMOVE EXISTING RECEPTACLES ABOVE
LOCKER. DEMOLISH ALL ASSOCIATED CONDUCTORS AND CONDUIT
BACK TO SOURCE AND LABEL EXISTING ASSOCIATED BREAKER AS
'SPARE'.
109 DISCONNECT AND REMOVE EXISTING DOWNLIGHTS. SAVE FIXTURES
FOR RECONNECTION DURING RENOVATION. EXISTING CIRCUIT WILL
C REMAIN FOR RECONNECTION DURING RENOVATION.
148 DISCONNECT AND REMOVE EXISTING FIXTURE. CIRCUIT TO REMAIN
FOR RECONNECTION DURING RENOVATION.
169 EXISTING CONDUCTORS, CONDUIT, AND BREAKER TO REMAIN FOR
RECONNECTION DURING RENOVATION.
184 DISCONNECT EXISTING LIGHT SWITCH AND SAVE FOR RELOCATION
AND RECONNECTION DURING RENOVATION.
REF.
BUILDING J RENOVATIONS
S
184
TARRANT COUNTY
(N)
SD
OFFICE
111
S
E
C:\Users\trussecs\Documents\TXDOT_FW-E-BldgJ-R18-Central_ctrussellHNAD3.rvt
108
AREA B
G BUILDING J
BUILDING J - AREA B DEMO PLAN - LEVEL 1
1 1/8" = 1'-0" Site Key Plan:
J ISSUED: 04-09-2020
N
PROJECT NO.
4/9/2020 14:42:59
H 02470420015
SHEET NO:
0 4' 8' 16' 24'
1/8" = 1'-0"
KEYNOTES
113 EXISTING COMMUNICATIONS PANELS ON WALL TO REMAIN DURING
RENOVATION.
181 176 EXISTING CONDUCTORS, CONDUITS, AND BREAKERS SERVING TWO
DEMOLISHED CONDENSING UNITS AND ONE AHU ON ROOF TO
REMAIN FOR RECONNECTION DURING RENOVATION. REFER TO
MECHANICAL FOR LOCATIONS OF DEMOLISHED UNITS.
B 181 DISCONNECT AND REMOVE EXISTING RACK. SERVERS WILL REMAIN
FOR RECONNECTION AND REINSTALLATION IN NEW WALL-MOUNTED
TELECOM RACK.
191 DISCONNECT, REMOVE, AND CLEAN LIGHT FIXTURE IN THIS AREA.
204 SAVE FIXTURE FOR REINSTALLATION DURING RENOVATION. CIRCUIT
WILL REMAIN FOR RECONNECTION DURING RENOVATION.
WAREHOUSE 193 DISCONNECT AND REMOVE ALL EXISTING LIGHT FIXTURES AND
201 194 SWITCHES WITHIN ROOM. CIRCUIT WILL REMAIN FOR
RECONNECTION DURING RENOVATION.
176 194 DISCONNECT AND REMOVE ALL EXISTING LIGHT FIXTURES IN AREA
OF NEW OFFICE ADDITION. REFER TO ARCHITECTURAL DRAWINGS
FOR OFFICE ADDITION.
ROOM 204 DISCONNECT EXISTING COILING DOOR. CIRCUIT WILL REMAIN FOR
205 RECONNECTION DURING RENOVATION
BUILDING J RENOVATIONS
EXISTING PANEL L SECTION 2 193 RESTROOM
TARRANT COUNTY
D
C:\Users\trussecs\Documents\TXDOT_FW-E-BldgJ-R18-Central_ctrussellHNAD3.rvt
AREA A
BUILDING J
N
PROJECT NO.
4/9/2020 14:43:00
02470420015
SHEET NO:
0 4' 8' 16' 24'
1/8" = 1'-0"
A REFER TO SHEET E.0.01 FOR PROJECT NOTES, SYMBOLS, AND 101 EXISTING 45KVA XFMR IS MOUNTED ON UNISTRUT ABOVE EXISTING
ABBREVIATIONS. 75KVA XFMR IN CLOSET.
B PROVIDE AND INSTALL NEW 600A MAIN BUS, 600A MCB 103 CONNECT NEW ELECTRIC RANGE TO EXISTING NEMA 6-50R
DISTRIBUTION PANELBOARD AT LOCATION OF EXISTING PANEL PH. RECEPTACLE VIA FACTORY-INSTALLED PLUG. Texas
RECONNECT ALL EXISTING LOADS PREVIOUSLY SERVED BY PANEL 105 ADJUST ELEVATION OF EXISTING RECEPTACLE PER NEW Department
PH TO NEW DISTRIBUTION PANELBOARD. COORDINATE BREAKER COUNTERTOP HEIGHT TO ENSURE RECEPTACLE IS 6" ABOVE of Transportation
FRAMES AND TRIP SETTINGS WITH EXISTING CIRCUITS PRIOR TO FINISHED COUNTER. TYPICAL FOR 6 DUPLEX RECEPTACLES IN
PURCHASE OF PANELBOARD. PROVIDE AND INSTALL 2 SETS OF BREAKROOM AREA.
4-350KCMIL AND 1#1G IN 3"C FROM EXISTING PANEL M TO NEW
DISTRIBUTION PANELBOARD. PROVIDE AND INSTALL NEW 129 PROVIDE AND INSTALL NEW 2' X 4' LIGHT FIXTURE (LITHONIA 2TLX4
600AF/600AT/3P BREAKER IN EXISTING PANEL M TO SERVE NEW 40L OR APPROVED EQUAL) IN GRID. EXTEND EXISTING LIGHTING
THIS DRAWING CREATED
DISTRIBUTION PANELBOARD. CIRCUIT FROM DEMOLISHED LIGHT FIXTURE TO NEW LIGHT USING FOR PRODUCTION ON
2#12 AND 1#12G IN 3/4"C. CONNECT NEW LIGHT FIXTURE TO 22"x34" SHEET SIZE.
C CONTRACTOR IS RESPONSIBLE FOR FINAL COORDINATION OF DO NOT SCALE PRINTS.
EXISTING SWITCH IN ROOM.
BREAKER SETTINGS DUE TO NEW ELECTRICAL DISTRIBUTION 143 PROVIDE AND INSTALL NEW 2' X 4' SURFACE MOUNTED LIGHT
INSTALLATION. FIXTURE (LITHONIA 2TLX4 40L OR APPROVED EQUAL). EXTEND
EXISTING LIGHTING CIRCUIT FROM DEMOLISHED LIGHT FIXTURE TO
NEW LIGHT USING 2#12 AND 1#12G IN 3/4"C. CONNECT NEW LIGHT
FIXTURE TO EXISTING SWITCH IN ROOM.
144 PROVIDE NEW CIRCUIT TO NEW EXHAUST FAN ON ROOF TO SERVE TEXAS REGISTERED ENGINEERING
FIRM F-2966
RESTROOMS. COORDINATE WITH MECHANICAL FOR LOCATION OF
EXHAUST FAN. CIRCUIT TO SPARE 20A/1P BREAKER IN PANEL Y1 777 MAIN ST. STE B-101
12 11 10 9 8 USING 2#12 AND 1#12G IN 3/4"C. PROVIDE AND INSTALL 120V/1P FORT WORTH, TEXAS 76102
NEMA 3R MOTOR-RATED SWITCH AT UNIT.
147 PROVIDE NEW GFI RECEPTACLE IF EXISTING RECEPTACLE IS
REMOVED DURING DEMOLITION. CONNECT TO EXISTING CIRCUIT AT
LOCATION.
CU-1 CU-2 CU-3 CU-4 CU-5 161 ADJUST ELEVATION OF EXISTING MOTOR-RATED SWITCH FOR
GARBAGE DISPOSAL TO ENSURE SWITCH IS 6" ABOVE FINISHED
FCU CU-1 COUNTER. CONNECT NEW GARBAGE DISPOSAL, IF REQUIRED BY
214 214 215 220 220 PLUMBING DRAWINGS DUE TO BREAKROOM REVISION, TO EXISTING
30A/2P/NF CIRCUIT, EXTENDING EXISTING CIRCUIT AS REQUIRED. CONDUCTOR
AND CONDUIT SIZE TO MATCH EXISTING.
189 171 EXTEND EXISTING CIRCUIT TO NEW DISCONNECT SWITCH FOR NEW
A AHU UNIT.
172 EXTEND EXISTING CIRCUIT TO NEW 20A/1P MOTOR RATED SWITCH
* AHU-1 FOR NEW AHU UNIT.
* * 105 172
SM SM
189 PROVIDE AND INSTALL NEW NEMA 3R DISCONNECT SWITCH FOR
AHU-2 FCU CU 1. COORDINATE MOUNTING LOCATION WITH MECHANICAL
161 PRIOR TO INSTALLATION. PROVIDE NEW 20A/2P BREAKER IN PANEL
172
L TO SERVE NEW UNIT. BREAKER TYPE TO MATCH EXISTING.
AHU-3 CIRCUIT UNIT TO NEW BREAKER USING 2#12 AND 1#12G IN 3/4"C.
* GFI
172 206 EXTEND NEAREST RECEPTACLE CIRCUIT WITHIN ROOM TO SINK,
SM
EXTENDING CIRCUIT USING 2#12 AND 1#12G IN 3/4"C. CONDUCTOR
BREAKROOM AND CONDUIT TYPE TO MATCH EXISTING.
* 100A/2P/NF 212 PROVIDE AND INSTALL NEW 20A/1P MOTOR RATED SWITCH FOR
103 105
AHU-10. CIRCUIT TO SPARE 20A/1P BREAKER IN PANEL SERVING
A NEARBY AHU UNITS, OTHERWISE PROVIDE NEW 20A/1P BREAKER IN
171
* GFI AHU-4 PANEL. BREAKER TYPE TO MATCH EXISTING. CIRCUIT NEW UNIT TO
PANEL USING 2#12 AND 1#12G IN 3/4"C.
B 214 REPLACE EXISTING 40A/3P BREAKER PREVIOUSLY SERVING
DEMOLISHED AC UNIT IN EXISTING PANEL PH WITH NEW 20A/3P
100A/2P/NF BREAKER. BREAKER TYPE TO MATCH EXISTING. CIRCUIT NEW
AHU-5
CONDENSING UNIT TO NEW BREAKER USING 3#12 AND 1#12G IN
171 3/4"C. PROVIDE AND INSTALL NEW 30A/3P/NF NEMA 3R DISCONNECT
FOR CONDENSING UNIT.
BUILDING J RENOVATIONS
FOR CONDENSING UNIT.
EXISTING 75KVA XFMR EXISTING PANEL Y2 217 PROVIDE AND INSTALL NEW 30A/2P BREAKER IN EXISTING PANEL Y1
REF.
TARRANT COUNTY
WITH NEW 20A/3P BREAKER. BREAKER TYPE TO MATCH EXISTING.
MEETING ROOM * GFI BAY 1 CIRCUIT NEW CONDENSING UNIT TO NEW BREAKER USING 3#12 AND
107 101 109
143 1#12G IN 3/4"C. PROVIDE AND INSTALL NEW 30A/3P/NF NEMA 3R
* GFI DISCONNECT FOR CONDENSING UNIT.
129 WOMENS
220 CIRCUIT NEW CONDENSING UNIT TO EXISTING 20A/3P BREAKER IN
103
MENS EXISTING PANEL Y1 USING 3#12 AND 1#12G IN 3/4"C. PROVIDE AND
206 206 INSTALL NEW 30A/3P/NF NEMA 3R DISCONNECT FOR CONDENSING
C:\Users\trussecs\Documents\TXDOT_FW-E-BldgJ-R18-Central_ctrussellHNAD3.rvt
104
UNIT.
REF.
DW
STAIR 144
106
147
172
S
M
AHU-7
AHU-10 AREA A
Room SS
AHU-6
M M
108 212
172
215
E
217 218
BUILDING J
J ISSUED: 04-09-2020
02470420015
SHEET NO:
0 4' 8' 16' 24'
KEYNOTES
110 INSTALL DOWNLIGHTS REMOVED DURING DEMOLITION AT TEXAS REGISTERED ENGINEERING
LOCATIONS SHOWN. EXTEND EXISTING CIRCUIT TO NEW LOCATIONS FIRM F-2966
USING 2#12 AND 1#12G IN 3/4"C. 777 MAIN ST. STE B-101
177 112 RECONNECT EXISTING LIGHT SWITCH TO RELOCATED DOWNLIGHTS FORT WORTH, TEXAS 76102
IRH-2 IRH-1 OVER THE SHOWERS.
B 143 PROVIDE AND INSTALL NEW 2' X 4' SURFACE MOUNTED LIGHT
FIXTURE (LITHONIA 2TLX4 40L OR APPROVED EQUAL). EXTEND
EXISTING LIGHTING CIRCUIT FROM DEMOLISHED LIGHT FIXTURE TO
NEW LIGHT USING 2#12 AND 1#12G IN 3/4"C. CONNECT NEW LIGHT
FIXTURE TO EXISTING SWITCH IN ROOM.
178
152 PROVIDE AND INSTALL NEW 2' X 2' SURFACE MOUNTED LIGHT
FIXTURE (LITHONIA 2TLX2 40L OR APPROVED EQUAL). EXTEND
EP-1 EXISTING LIGHTING CIRCUIT FROM DEMOLISHED LIGHT FIXTURE TO
IRH-3 NEW LIGHT USING 2#12 AND 1#12G IN 3/4"C. CONNECT NEW LIGHT
BAY 1 FIXTURE TO EXISTING SWITCH IN ROOM.
109 167 PROVIDE NEW 30AF/2P/NF DISCONNECT SWITCH FOR NEW
OVERHEAD COILING DOOR. PROVIDE NEW 20A/2P BREAKER IN
EXISTING 120/208V PANEL NEXT TO PANEL J3 AND CONNECT USING
2#12 AND 1#12G IN 3/4" CONDUIT.
172 EXTEND EXISTING CIRCUIT TO NEW 20A/1P MOTOR RATED SWITCH
FOR NEW AHU UNIT.
C 174 PROVIDE NEW NEMA 3R 30A/3P/NF DISCONNECT SWITCH FOR NEW
221 CONDENSING UNIT CU-8 ON ROOF. PROVIDE AND INSTALL NEW
20A/3P BREAKER IN EXISTING PANEL PJ AND CIRCUIT UNIT USING
3#12 AND 1#12G IN 3/4"C. BREAKER TYPE TO MATCH EXISTING.
REFER TO MECHANICAL DRAWINGS FOR LOCATION OF UNIT.
177 CIRCUIT IRH-1, IRH-2, IRH-3, IRH-4, AND IRH-5 TO SPARE 20A/1P
BREAKER IN EXISTING PANEL J USING 2#12 AND 1#12G IN 3/4"C.
EP-2 178 COORDINATE WITH EQUIPMENT CUTSHEET FOR ELECTRICAL
CONNECTION POINT PRIOR TO INSTALLATION OF CIRCUIT.
REF.
174 178 PROVIDE NEW 20A/1P CIRCUIT FROM EXISTING PANEL J TO NEW EP
USING 2#12 AND 1#12G IN 3/4"C. CONNECT TO AVAILABLE SPARE
BREAKER IF POSSIBLE, OTHERWISE PROVIDE NEW 20A/1P BREAKER
EXISTING PANEL J2 EXISTING PANEL J (BREAKER TYPE TO MATCH EXISTING) IN PANEL.
EXISTING PANEL J3 EXISTING PANEL PJ 185 RECONNECT AND REINSTALL EXISTING LIGHT SWITCH AT LOCATION
EXISTING PANEL SHOWN.
206 EXTEND NEAREST RECEPTACLE CIRCUIT WITHIN ROOM TO SINK,
D
BUILDING J RENOVATIONS
102
IRH-5 IRH-4 DISCONNECT FOR EXHAUST FAN.
S
OS
143
TARRANT COUNTY
(TYP)
206
OS
S
SM 172
E
112
AHU-8
C:\Users\trussecs\Documents\TXDOT_FW-E-BldgJ-R18-Central_ctrussellHNAD3.rvt
OS
AREA B
Room
110
G BUILDING J
BUILDING J - AREA B FLOOR PLAN - LEVEL 1
1 1/8" = 1'-0"
Site Key Plan:
J ISSUED: 04-09-2020
N
PROJECT NO.
H
4/9/2020 14:42:55
02470420015
SHEET NO:
0 4' 8' 16' 24'
S
192 175 PROVIDE NEW NEMA 3R 20A/1P MOTOR RATED SWITCH FOR NEW 777 MAIN ST. STE B-101
AHU-9 ON ROOF. EXTEND EXISTING CIRCUIT TO NEW MOTOR RATED FORT WORTH, TEXAS 76102
SWITCH FOR NEW AHU UNIT. REFER TO MECHANICAL FOR FINAL
LOCATIONS OF UNITS.
211 190 CIRCUIT FCU-1 TO SAME CIRCUIT AS FCU CU 1 IN PANEL L USING
2#12 AND 1#12G IN 3/4"C.
192 REINSTALL EXISTING LIGHT FIXTURE REMOVED DURING
RENOVATION CENTERED IN ROOM, EXTENDING CIRCUIT AS
REQUIRED USING 2#12 AND 1#12G IN 3/4"C. CONNECT LIGHT
FIXTURE TO NEW SWITCH IN ROOM.
196 196 195 PROVIDE AND INSTALL NEW 2' X 4' LIGHT FIXTURE (LITHONIA 2TLX4
40L OR APPROVED EQUAL) IN GRID. EXTEND EXISTING LIGHTING
B CIRCUIT FROM DEMOLISHED LIGHT FIXTURE TO NEW LIGHT USING
OFFICE 2#12 AND 1#12G IN 3/4"C. CONNECT NEW LIGHT FIXTURE TO
205 202 EXISTING SWITCH IN ROOM.
196 PROVIDE NEW 20A/1P BREAKER IN EXISTING PANEL L FOR CIRCUIT.
BREAKER TYPE TO MATCH EXISTING. CIRCUIT RECEPTACLES TO
SOS
NEW BREAKER USING 2#12 AND 1#12G IN 3/4"C.
WAREHOUSE 197 MOUNT NEW GFI RECEPTACLE 42"AFF. EXTEND NEAREST EXISTING
201 RECEPTACLE CIRCUIT TO NEW RECEPTACLE USING 2#12 AND 1#12G
195 IN 3/4"C. VERIFY EXISTING CIRCUIT AMPACITY DOES NOT EXCEED
175 219 16A PRIOR TO CONNECTION AND AFTER CONNECTION.
205 CONNECT NEW COILING DOOR TO EXISTING CIRCUIT AT LOCATION,
EXTENDING EXISTING CIRCUIT AS REQUIRED. CONDUCTOR AND
CONDUIT TYPE AND SIZE TO MATCH EXISTING. COORDINATE WITH
MANUFACTURER REQUIREMENTS FOR EXTENT OF CONTROLS FOR
NEW DOOR.
206 EXTEND NEAREST RECEPTACLE CIRCUIT WITHIN ROOM TO SINK,
C EXTENDING CIRCUIT USING 2#12 AND 1#12G IN 3/4"C. CONDUCTOR
AND CONDUIT TYPE TO MATCH EXISTING.
209 REPLACE EXISTING 100A/3P BREAKER PREVIOUSLY SERVING
RESTROOM DEMOLISHED ELEVATOR EQUIPMENT IN EXISTING PANEL PH WITH
NEW 50A/3P BREAKER. BREAKER TYPE TO MATCH EXISTING.
SOS
EXISTING PANEL L SECTION 1 204
PROVIDE AND INSTALL NEW 30 KVA DELTA-WYE TRANSFORMER AND
EXISTING PANEL L SECTION 2 CIRCUIT TRANSFORMER TO NEW BREAKER USING 3#6 AND 1#10G IN
195 206
T30
NEW 30KVA XFMR 210 PROVIDE AND INSTALL NEW 42 POLE, 100A MAIN BUS, 100A MCB
197
BUILDING J RENOVATIONS
211 INSTALL EXISTING SERVERS IN NEW FLOOR-MOUNTED TELECOM
TARRANT COUNTY
20A/2P BREAKER IN EXISTING PANEL L AND CIRCUIT UNIT USING
2#12 AND 1#12G IN 3/4"C. BREAKER TYPE TO MATCH EXISTING.
REFER TO MECHANICAL DRAWINGS FOR LOCATION OF UNIT.
C:\Users\trussecs\Documents\TXDOT_FW-E-BldgJ-R18-Central_ctrussellHNAD3.rvt
AREA A
BUILDING J
J ISSUED: 04-09-2020
N
PROJECT NO.
4/9/2020 14:42:56
02470420015
SHEET NO:
0 4' 8' 16' 24'
Texas
Department
SCHEDULE FOR: NEW PANEL L2 LOCATION: WAREHOUSE 201 FED FROM: NEW 30KVA XFMR of Transportation
VOLTAGE: 208/120V MCB RATING: 100 A SCCR: 10000
MAINS TYPE: MCB PHASE: 3 ENCLOSURE: Type 1
BUS RATING: 100 A WIRE: 4 MOUNTING: Surface THIS DRAWING CREATED
FOR PRODUCTION ON
MIN. WIRE MIN. WIRE 22"x34" SHEET SIZE.
SIZE SIZE DO NOT SCALE PRINTS.
CKT CIRCUIT DESCRIPTION P TRIP LEGEND A B C LEGEND TRIP P CIRCUIT DESCRIPTION CKT
1 SPARE 1 20 A -- -- 0 VA 0 VA -- -- 20 A 1 SPARE 2
3 SPARE 1 20 A -- -- 0 VA 0 VA -- -- 20 A 1 SPARE 4
5 SPARE 1 20 A -- -- 0 VA 0 VA -- -- 20 A 1 SPARE 6
7 SPARE 1 20 A -- -- 0 VA 0 VA -- -- 20 A 1 SPARE 8
9 SPARE 1 20 A -- -- 0 VA 0 VA -- -- 20 A 1 SPARE 10 TEXAS REGISTERED ENGINEERING
FIRM F-2966
11 SPARE 1 20 A -- -- 0 VA 0 VA -- -- 20 A 1 SPARE 12 777 MAIN ST. STE B-101
13 SPARE 1 20 A -- -- 0 VA 0 VA -- -- 20 A 1 SPARE 14 FORT WORTH, TEXAS 76102
15 SPARE 1 20 A -- -- 0 VA 0 VA -- -- 20 A 1 SPARE 16
17 SPARE 1 20 A -- -- 0 VA 0 VA -- -- 20 A 1 SPARE 18
19 SPARE 1 20 A -- -- 0 VA 0 VA -- -- 20 A 1 SPARE 20
21 SPARE 1 20 A -- -- 0 VA 0 VA -- -- 20 A 1 SPARE 22
23 SPARE 1 20 A -- -- 0 VA 0 VA -- -- 20 A 1 SPARE 24
25 SPARE 1 20 A -- -- 0 VA 0 VA -- -- 20 A 1 SPARE 26
27 SPARE 1 20 A -- -- 0 VA 0 VA -- -- 20 A 1 SPARE 28
29 SPARE 1 20 A -- -- 0 VA 0 VA -- -- 20 A 1 SPARE 30
31 SPACE -- -- -- -- 0 VA 0 VA -- -- -- -- SPACE 32
33 SPACE -- -- -- -- 0 VA 0 VA -- -- -- -- SPACE 34
35 SPACE -- -- -- -- 0 VA 0 VA -- -- -- -- SPACE 36
37 SPACE -- -- -- -- 0 VA 0 VA -- -- -- -- SPACE 38
39 SPACE -- -- -- -- 0 VA 0 VA -- -- -- -- SPACE 40
41 SPACE -- -- -- -- 0 VA 0 VA -- -- -- -- SPACE 42
TOTAL LOAD: 0 VA 0 VA 0 VA
LEGEND:
** 5 mA GROUND FAULT CKT BKR
* 30 mA GROUND FAULT CKT BKR
HP HANDLE PADLOCK CKT BKR
ST SHUNT TRIP CKT BKR
BUILDING J RENOVATIONS
ISSUED: 04-09-2020
PROJECT NO.
4/9/2020 14:42:57
02470420015
SHEET NO:
ELECTRICAL SCHEDULES
JE.6.01
COPYRIGHT c 2020 TEXAS DEPARTMENT OF TRANSPORTATION