Professional Documents
Culture Documents
Cerberuspro Commissioning, Maintenance & Troubleshooting - A6v10210416 (Ip6)
Cerberuspro Commissioning, Maintenance & Troubleshooting - A6v10210416 (Ip6)
Legal notice
Technical specifications and availability subject to change without notice.
Issued by:
Siemens Switzerland Ltd.
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41 724-2424
www.siemens.com/buildingtechnologies
Edition: 2015-12-15
Document ID: A6V10210416_i_en_AU
2 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Table of contents
3 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
9 C- Commissioning networked 'Stations' .................................................40
10 Adding a 'Station' to an existing 'Site'.....................................................41
11 Merging two 'Sites' ..............................................................................42
11.1 Adding 'Site' B to 'Site' A ............................................................................ 43
11.2 Connecting 'Sites' physically to one another............................................... 43
12 Changing and expanding the FDnet/C-NET detector line .........................44
12.1 Extending the detector line to include additional devices ............................ 44
12.1.1 Mount and wire new devices ....................................................... 45
12.1.2 Configure a new device............................................................... 45
12.2 Replacing stationary devices of the same type ........................................... 46
12.3 Permanently removing stationary devices .................................................. 47
12.4 Removing or replacing non-stationary devices ........................................... 48
12.4.1 Base with loop contact ................................................................ 48
12.4.2 Base without loop contact ........................................................... 51
12.4.3 Temporarily removing multiple non-stationary devices................. 53
12.4.4 Permanently removing non-stationary devices ............................ 54
12.5 Replacing 'Manual call point' of the same type ........................................... 55
12.5.1 Switching on the replace mode ................................................... 56
12.5.2 Switching off replace mode ......................................................... 56
12.5.3 Testing 'Manual call point' ........................................................... 56
12.6 Convert two stubs into a loop ..................................................................... 57
12.7 Connecting a sub-stub to a loop................................................................. 57
13 Detailed commissioning steps ..............................................................58
13.1 Preparing 'Station' for commissioning......................................................... 58
13.2 Preparing 'Station' for commissioning –without BDV installation ................. 59
13.3 Auto-configuring 'Station' ........................................................................... 59
13.4 Auto-configuring the detector line............................................................... 60
13.5 Loading automatically created configuration to the PC ............................... 61
13.6 Adapting configuration ............................................................................... 61
13.7 Converting a standalone station to a networked station .............................. 62
13.8 Switch off................................................................................................... 63
13.8.1 Safety during switch-off ............................................................... 63
13.8.2 Switching off the detector line...................................................... 63
13.8.3 Switch off zone ........................................................................... 63
13.9 Switching on .............................................................................................. 64
13.9.1 Switch on detector line ................................................................ 64
13.9.2 Switch on zone ........................................................................... 64
13.10 Restarting the detector line ........................................................................ 64
13.11 Freezing outputs ........................................................................................ 65
13.12 Enabling frozen outputs ............................................................................. 65
13.13 Read in devices on detector line ................................................................ 66
13.14 Detaching the device ................................................................................. 66
13.15 Delete the device on Person Machine Interface ......................................... 67
13.16 Remove the elements ................................................................................ 67
4 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
13.17 Testing detectors .......................................................................................67
13.17.1 Activate the detector ...................................................................68
13.17.2 Testing logged test activations ....................................................68
13.18 Switching on test mode ..............................................................................68
13.19 Switch on normal operation........................................................................69
13.20 Rectify localization errors ...........................................................................70
13.21 Checking 'Site' function ..............................................................................70
13.22 Carrying out final commissioning work .......................................................70
14 Commissioning Ethernet switch (MM) FN2008-A1 .................................. 71
14.1 Install Primary Setup Tool ..........................................................................72
14.2 Assign IP address......................................................................................72
14.3 Configuring FN2008-A1 using Internet browser ..........................................73
15 Commissioning Ethernet switch (modular) FN2012-A1 ............................ 74
15.1 Standalone FN2012-A1 .............................................................................74
15.1.1 Specifying a pre-configured IP address .......................................75
15.2 FN2012-A1 integrated into station ..............................................................76
15.3 FN2012-A1 web interface ..........................................................................77
15.3.1 Commissioning a web interface ...................................................77
15.3.2 Changing the IP address .............................................................78
15.3.3 Configuring the redundancy role..................................................79
15.3.4 Activating/deactivating local ports................................................79
15.3.5 Activating fault monitoring for local ports .....................................80
15.3.6 Activating port mirroring ..............................................................80
15.4 Restarting and resetting the FN2012-A1 ....................................................81
16 Commissioning security module (firewall) FN2009-A1 ............................. 82
16.1 Installing Security Configuration Tool .........................................................83
16.2 Selecting type and entering MAC address..................................................83
16.3 Entering network settings ...........................................................................84
16.4 Creating IP service definitions ....................................................................87
16.5 Creating firewall rules ................................................................................88
17 Commissioning the fire brigade periphery module FCI2001-D1 ................ 90
18 Commissioning of I/O card (remote transmission) FCI2007-A1
and I/O card (horn/monitored) FCI2009-A1 ............................................ 91
19 Commissioning external printer ............................................................ 92
20 Updating the firmware ......................................................................... 95
20.1 Preparation and security ............................................................................95
20.2 Station: Updating the FW of the main CPU and additional CPUs ................96
20.2.1 Standalone station and SAFEDLINK station ................................96
20.2.2 Router station and Ethernet station .............................................97
20.2.3 Updating several 'Stations' simultaneously ..................................98
20.2.4 FW update for main CPU and additional CPUs............................99
20.3 Station: Updating the FW of the additional CPUs only ..............................107
20.3.1 Standalone station and SAFEDLINK station ..............................107
20.3.2 Router station and Ethernet station ...........................................107
20.3.3 FW update for additional CPUs .................................................108
5 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
20.4 Update only the BDV ............................................................................... 109
20.4.1 Standalone station and SAFEDLINK station .............................. 109
20.4.2 Router station and Ethernet station ........................................... 110
20.5 Converting the configuration .................................................................... 110
20.6 Testing the firmware version of the additional CPUs................................. 111
20.7 Creating diagnosis report ......................................................................... 112
20.8 Updating the FW of the peripheral devices ............................................... 112
20.8.1 MCL-USB adapter FDUZ22x..................................................... 113
20.8.2 Floor repeater terminal FT2010 ................................................. 114
20.8.3 Floor repeater display FT2011 .................................................. 116
20.8.4 Mimic display driver FT2001-A1 ................................................ 118
20.8.5 Radio gateway FDCW221 ......................................................... 120
20.8.6 Line tester FDUL221 ................................................................. 121
20.8.7 Line tester with serial interface FDUL221 .................................. 123
20.9 Updating the FW of Ethernet switch (modular) FN2012-A1 ...................... 125
20.9.1 Standalone FN2012-A1............................................................. 125
20.9.2 FN2012-A1 integrated into station ............................................. 127
21 Maintenance..................................................................................... 128
21.1 General ................................................................................................... 128
21.2 Testing .................................................................................................... 128
21.3 Testing and measuring instruments ......................................................... 129
21.4 Preparatory work ..................................................................................... 129
21.5 Test system data ..................................................................................... 130
21.6 Testing the 'Station' ................................................................................. 131
21.7 Check the power supply...........................................................................132
21.8 Testing the printer.................................................................................... 133
21.9 Checking 'Site' function ............................................................................ 133
21.10 Intervals for testing the system function ................................................... 133
21.11 Carrying out final maintenance work ........................................................ 134
22 Repair ............................................................................................. 135
22.1 Disconnect the station from the power supply .......................................... 135
22.2 Spare parts.............................................................................................. 136
22.3 Fault messages on the Person Machine Interface .................................... 137
22.4 Fault indicators on components ............................................................... 138
22.5 Communication problems in networked systems ...................................... 138
22.6 Correcting swapped devices .................................................................... 139
22.7 Correcting an invalid topology .................................................................. 140
22.8 Error message 'Too many devices' .......................................................... 141
22.9 Restart 'Station' ....................................................................................... 141
22.10 Restoring factory setting on the 'Station' .................................................. 142
22.11 Fiber-optic network module FN2006 / FN2007 troubleshooting steps ....... 144
Glossary ................................................................................................... 149
Index ....................................................................................................... 151
6 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
About this document
Applicable documents
1
Scope
The information contained in this document is valid for introduction package IP6.
Target groups
The information in this document is intended for the following target groups:
Document identification
The document ID is structured as follows:
ID code Examples
ID_ModificationIndex_Language_COUNTRY A6V10215123_a_de_DE
-- = multilingual or international A6V10215123_a_en_--
A6V10315123_a_--_--
7 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
About this document
1 Applicable documents
Date format
The date format in the document corresponds to the recommendation of
international standard ISO 8601 (format YYYY-MM-DD).
The 'i' symbol identifies supplementary information and tips for an easier way of
working.
8 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
About this document
Applicable documents
1
9 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
About this document
1 Download center
You will also find information about search variants and links to mobile
applications (apps) for various systems on the home page.
You will find details of further technical terms and abbreviations in the 'Glossary'
chapter.
See also
1 Applicable documents [➙ 9]
10 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
About this document
Revision history
1
The first edition of a language version or a country variant may, for example, be
version 'd' instead of 'a' if the reference document is already this version.
11 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
About this document
1 Revision history
12 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
About this document
Revision history
1
13 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Safety
2 Safety instructions
2 Safety
Battery Heat
Signal word
The signal word classifies the danger as defined in the following table:
NOTICE NOTICE identifies possible damage to property that may result from non-
observance.
14 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Safety
Safety instructions
2
WARNING
Nature and origin of the danger
Consequences if the danger occurs
● Measures / prohibitions for danger avoidance
NOTICE
Nature and origin of the danger
Consequences if the danger occurs
● Measures / prohibitions for danger avoidance
15 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Safety
2 Safety regulations for the method of operation
Electrical installations
WARNING
Electrical voltage
Electric shock
● Work on electrical installations may only be carried out by qualified
electricians or by instructed persons working under the guidance and
supervision of a qualified electrician, in accordance with the electrotechnical
regulations.
● Wherever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
● Lock volt-free areas to prevent them being switched back on again by mistake.
● Label the connection terminals with external external voltage using a
'DANGER External voltage' sign.
● Route mains connections to products separately and fuse them with their own,
clearly marked fuse.
● Fit an easily accessible disconnecting device in accordance with IEC 60950-1
outside the installation.
● Produce earthing as stated in local safety regulations.
CAUTION
Noncompliance with the following safety regulations
Risk of injury to persons and damage to property
● Compliance with the following regulations is required.
16 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Safety
Safety regulations for the method of operation
2
17 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Safety
2 Standards and directives complied with
WARNING
Limited or non-existent fire detection
Personal injury and damage to property in the event of a fire.
● Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
● Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
NOTICE
Incorrect planning and/or configuration
Important standards and specifications are not satisfied.
Fire detection installation is not accepted for commissioning.
Additional expense resulting from necessary new planning and/or configuration.
● Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
● Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
18 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Mounting / Installation
Installing and checking the detector line
3
3 Mounting / Installation
You will find details on the technical term ↑ 'C-NET' in the chapter 'Glossary'.
Most C-NET devices are installed on a base and can be changed with ease.
The bases of non-stationary C-NET devices and stationary C-NET devices must be
installed and uninstalled when the C-NET detector line is switched off and
disconnected from the power supply.
Prerequisites
● The C-NET detector line is not connected to the control panel and is
disconnected from the power supply when the C-NET devices are being
installed, wired and inserted.
● The C-NET detector line is tested with the line tester FDUL221.
● The control panel is commissioned by the commissioning personnel.
Before inserting or connecting an C-NET device, stick the serial number on the
layout plan. The adhesive strip with the serial number can be found on the bottom
of the device.
1. Mount and wire the C-NET devices and stick the serial number for each device
on the layout plan.
2. Install the detector dust caps on the optical point detector if necessary.
3. Install the designation plate if necessary.
19 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Mounting / Installation
3 Mount and install 'Station'
NOTICE
Simultaneous connection of line tester and C-NET detector line to the control
panel
Damage to line tester or control panel
● Do not connect the line tester and the C-NET detector line to the control panel
at the same time.
Acceptance test
ϖ The C-NET detector line is not connected to the control panel.
1. Connect the line tester FDUL221 to the newly installed C-NET detector line.
2. Test the C-NET detector line for short-circuits, open lines and earth faults.
3. Check the number of the devices on the C-NET detector line using the display
on the line tester.
4. Check the branch-off position of the ↑ stubs and the number of devices at the
stubs.
5. Check the type of all C-NET devices.
6. Remedy any errors you notice and carry out the acceptance test again.
You will find information about the line tester in document 008250. See chapter
'Applicable documents'.
20 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Connectivity and communication with 'Station'
Setting Windows firewall
4
See also
1 Applicable documents [➙ 9]
4.1.1 Windows XP
ϖ You have administrator rights on your PC
1. Open the Windows start menu.
2. Select 'Settings' > 'Control panel' > 'Administrative Tools' > 'Services'.
3. Right-click on 'Windows Firewall/Internet Connection Sharing (ICS)' in the new
window.
4. Select 'All Tasks' > 'Exit' in the context menu.
5. Once the work is complete, reactivate the firewall. To do this, proceed as
described above but select 'All Tasks' > 'Start' in the context menu.
NOTICE
Security vulnerability in operating system due to deactivated firewall
Unauthorized access to your PC
● Activate the firewall after the firmware update.
21 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Connectivity and communication with 'Station'
4 Setting Windows firewall
There are different ways of setting up firewall rules in Windows 7/8/10. The
following settings apply for Siemens PCs which use group guidelines controlled
by the domain.
NOTICE
The following settings must be made under Local Security Policy.
● Open Local Security Policy to configure Windows Firewall with Advanced
Security.
22 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Connectivity and communication with 'Station'
Network parameters
4
NOTICE
Security vulnerability in operating system due to open ports
Unauthorized access to your PC
● Deactivate the firewall rule configured above after the firmware update.
23 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Connectivity and communication with 'Station'
4 Connecting the PC to the station
LAN 11
NOTICE
Incorrect disconnection of 'Station'
Establishing a connection to other 'Station' is not possible
● Disconnect the PC from the 'Station' as described in the following instructions.
The connection between the PC and the 'Station' must be disconnected as follows:
1. Select 'Cerberus-Engineering-Tool' > 'Commissioning' in Disconnect.
2. Disconnect the cable connection between PC and 'Station'.
3. Wait ≥2 min. before you establish a connection to another 'Station'.
24 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Connectivity and communication with 'Station'
Loading data to the 'Station'
4
If you use a number of network cards on the PC, observe the information in the
chapter 'IP settings for several network cards' in document A6V10210424. See
chapter 'Applicable documents'.
1 Command is only performed for the 'Station' that is connected to the PC via LAN.
2The configuration of selected 'Stations' or all 'Stations' in the ↑ 'Site' can be
overwritten as an option.
See also
1 Loading configuration from the PC to the station [➙ 27]
1 Initializing 'Station' [➙ 25]
If you use a number of network cards on the PC, observe the information in the
chapter 'IP settings for several network cards' in document A6V10210424. See
chapter 'Applicable documents'.
25 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Connectivity and communication with 'Station'
4 Initializing 'Station'
Initialize 'Station'
NOTICE
Connection module (card cage) FCA2006-A1 defective or installed incorrectly
Control panels identified incorrectly, e.g. FC726 identified as FC724.
● Check that the connection module (card cage) FCA2006-A1 is installed
correctly.
NOTICE
Faulty initialization for networked station
During initialization, the station must not be connected to the network or any other
station.
3. Click on 'Start'.
The 'Set the station to access level 3.2' window opens.
4. Press <MENU> on the 'Station' and enter a valid PIN.
5. Click on 'OK' in the 'Set access level' window.
The 'Station' is initialized.
The 'Station' is restarted.
After a few minutes, the 'Buzzer' sounds twice.
6. Press <Acknowledge> on the ↑ Person Machine Interface to switch off the
'Buzzer'. Do not perform any more actions on the 'Station' until the 'Buzzer' has
sounded for the second time.
See also
1 Loading data to the 'Station' [➙ 25]
26 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Connectivity and communication with 'Station'
Loading configuration from the PC to the station
4
NOTICE
Different network configuration in Cerberus-Engineering-Tool and networked
↑ 'Site'
When the selection displayed for 'Download site' is manually modified, in special
cases1 it may be necessary to reset a 'Station' to the factory setting as well as a
'Initialize station'.
● Do not modify the selection displayed for 'Download site' in normal cases.
● Check the sequence when loading different configuration states in special
cases 1.
● After any change of the network configuration, make sure that all 'Stations' in
the 'Site' for the 'Download site' procedure are selected and can be accessed.
● Temporarily update non-accessible 'Stations' to the latest status of the global
network configuration prior to integration in the network.
If you use a number of network cards on the PC, observe the information in the
chapter 'IP settings for several network cards' in document A6V10210424. See
chapter 'Applicable documents'.
WARNING
Activation of fire or smoke dampers
If fire or smoke dampers are connected to the FS720 via an input/output module,
they may be activated when the station is switched off or when the station or
detector line is restarted.
● If necessary, block the outputs temporarily [➙ 65] before switching off the
station or restarting the station/detector line.
27 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Connectivity and communication with 'Station'
4 Loading configuration from the PC to the station
See also
1 Loading data to the 'Station' [➙ 25]
28 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Connectivity and communication with 'Station'
Loading configuration from the station to the PC
4
You will find information about ↑ BDV names and versions in document
A6V10210424. See chapter 'Applicable documents'.
29 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Connectivity and communication with 'Station'
4 Creating a backup of the 'Site' configuration
Creating a backup
ϖ The ↑ 'Site' is opened in Cerberus-Engineering-Tool.
ϖ The PC is connected to a ↑ 'Station'.
1. Select 'Commissioning' > 'Create backup embedded configuration'.
The 'Create backup embedded configuration' And 'Connect' windows are
opened.
Backup file
● The backup file is saved in the following directory as standard:
C:\ProgramData\Siemens\FX7230\[Softwareversion]\Sites\embeddedBackups
● The backup file has the following name:
<'Site' name>_<backup counter>(_incomplete).fsc
Example: Test_Site_007_incomplete.fsc
– 'Site' name: Name of the 'Site'.
– Backup counter: Three-digit number that is automatically assigned to each
backup.
– 'incomplete': If it was not possible to create a complete backup, 'incomplete'
is added to the file name.
● A maximum of ten 'Site' backup files are saved. If more than ten backup files
are created, the oldest file is automatically overwritten with the new one.
In the pre-settings, you can define that a backup file is created automatically each
time a configuration is loaded from the PC to the ↑ 'Station' using the 'Download
site' command. To do this, select 'Options' > 'Preferences' > 'Commissioning'.
30 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning overview
Commissioning variants
5
5 Commissioning overview
The 'Stations' on the C-WEB, such as control panels FC722/FC724 and fire
terminals FT724, are connected to the power supply and commissioned by the
installation and commissioning personnel.
● Networked 'Stations' must only be commissioned with Cerberus-Engineering-
Tool.
● Standalone control panels can be commissioned with or without Cerberus-
Engineering-Tool.
NOTICE
Impermissible commissioning procedures result in faults during operation.
● Only the procedures described in this document are permitted.
NOTICE
Firmware version of a newly installed fire detection installation not updated
No CPR conformity
● Compare the firmware version of a newly installed fire detection installation
with the firmware version IP6.
● Update the firmware if necessary.
The table below provides an overview of the procedure for commissioning the
'Stations'. The letters A, B1, B2 and C refer to the detailed descriptions in the
following chapters.
31 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning overview
5 Definition of terms
Detailed information about the result of auto-configuration can be found in the 'List
of compatibility'.
↑ Pre-configuration The logical elements incl. customer texts are created in Cerberus-Engineering-
Tool prior to commissioning:
● In the 'Detection' task card up to and including 'Zone' level
● In the 'Control' task card up to and including 'Control' level ('Fire control', 'Evac
control', 'Counter control')
In addition, the logical elements can subsequently be assigned as far as possible
for alarming and control.
↑ Logical channels can be pre-configured. This makes sense if customer texts
are to be configured down to this level.
Read in by line The C-NET detector line can be read in by sending a command via the Person
Machine Interface. During this process, the devices are listed without generating
↑ sections and ↑ zones. I.e., no corresponding logical elements are created in the
↑ 'Detection tree' and ↑ 'Control tree'.
Adaptations The following procedures are examples of adaptations:
● Entering customer text for logical elements
● ↑ Changing detector parameter sets
● ↑ Configuring alarm devices
● Configuring 'Controls'
● Configuring the power supply
32 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning overview
Standard gateway
5
↑ Non-stationary devices Point detectors installed on a base apart from radio detectors.
↑ Stationary devices All devices apart from point detectors, e.g.:
● Manual call point
● Radio detector
● Input/output modules
● Alarm sounder
● ↑ Line separator
● ↑ Radio gateway
● ↑ Floor repeater terminal
● ↑ Floor repeater display
● Mimic display driver
↑ Station Router
IP address: 192.168.200.1 192.168.200.254
Subnet mask: 255.255.255.0 255.255.255.0
Standard gateway: 192.168.200.254
33 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning overview
5 Brief instructions on operating the 'Station'
You will find detailed instructions for operating the 'Stations' in document
A6V10211076. See chapter 'Applicable documents'.
5.5 License
When the data is first loaded from the PC to the ↑ 'Station', the 'Station' receives
the license from Cerberus-Engineering-Tool. Communication between the 'Station'
and Cerberus-Engineering-Tool is then only possible with a valid license.
34 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
A - Commissioning standalone 'Station' without PC
License
6
Prerequisites
● The ↑ detector lines and C-NET devices are installed.
● The acceptance test has been carried out for the detector lines.
● The 'Station' is installed, but the batteries are not connected yet.
● The cables for the detector lines and the mains supply have been inserted in
the 'Station', but not connected.
You will find additional information about the individual steps on the specified
pages.
Commissioning
1. If necessary, configure the power supply. Link [➙ 36]
2. Prepare the ↑ 'Station' for commissioning. Link [➙ 58]
3. Perform auto-configuration:
– Auto-configure 'Station'. Link [➙ 59]
OR
– Auto-configure detector lines individually. Link [➙ 60]
4. Adapt the auto-configuration in the ↑ Person Machine Interface, e.g.:
– Changing customer texts. Link [➙ 36]
– Set the ↑ parameter sets of the C-NET devices. Link [➙ 37]
5. Test the function of the ↑ 'Site' and remedy the problems, if any. Link [➙ 70]
6. Perform the completion tasks. Link [➙ 70]
35 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
A - Commissioning standalone 'Station' without PC
6 Configuring the power supply
You will find the pin assignments in document A6V10210368. See chapter
'Applicable documents'.
See also
1 Applicable documents [➙ 9]
36 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
A - Commissioning standalone 'Station' without PC
Setting detector parameter sets
6
37 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
B1 - Commissioning standalone 'Station' with PC, without pre-configuration
7
Prerequisites
● The ↑ detector lines and C-NET devices are installed.
● The acceptance test has been carried out for the detector lines.
● The ↑ 'Station' is installed, but the batteries are not connected yet.
● The cables for the detector lines and the mains supply have been inserted in
the 'Station', but not yet connected.
● Cerberus-Engineering-Tool is installed on the PC.
● The current firmware and ↑ BDV are available on the PC.
You will find additional information about the individual steps on the specified
pages.
Commissioning
1. Prepare the ↑ 'Station' for commissioning. Link [➙ 58]
2. Perform auto-configuration:
– Auto-configure 'Station'. Link [➙ 59]
OR
– Auto-configure detector lines individually. Link [➙ 60]
3. Connect the PC to the 'Station'. Link [➙ 24]
4. Load the automatically created configuration to the PC. Link [➙ 61]
5. Adapt the configuration in Cerberus-Engineering-Tool. Link [➙ 61]
6. Load the configuration from the PC to the 'Station'. Link [➙ 27]
7. Test the function of the ↑ 'Site'. Link [➙ 70]
8. Remedy any errors you notice and load the corrected configuration from the
PC to the 'Station'. Link [➙ 27]
9. Disconnect the PC from the 'Station'. Link [➙ 24]
10. Perform the completion tasks. Link [➙ 70]
38 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
B2 - Commissioning standalone 'Station' with PC, with pre-configuration
8
Prerequisites
● The ↑ detector lines and C-NET devices are installed.
● The acceptance test has been carried out for the detector lines.
● The ↑ 'Station' is installed, but the batteries are not connected yet.
● The cables for the detector lines and the mains supply have been inserted in
the 'Station', but not yet connected.
● Cerberus-Engineering-Tool is installed on the PC.
● The current firmware and ↑ BDV are available on the PC.
You will find additional information about the individual steps on the specified
pages.
Commissioning
1. In Cerberus-Engineering-Tool create a ↑ 'Site' and configure it manually up to
'Zone' level.
2. Prepare the ↑ 'Station' for commissioning – without ↑ BDV installation. Link
[➙ 59]
3. Connect the PC to the 'Station'. Link [➙ 24]
4. Load the configuration from the PC to the 'Station'. Link [➙ 27]
5. Read-in the C-NET devices. Link [➙ 66]
6. Load the configuration from the 'Station' to the PC. Link [➙ 29]
7. Adapt the configuration in Cerberus-Engineering-Tool. Link [➙ 61]
8. Load the configuration from the PC to the 'Station'. Link [➙ 27]
9. Test the function of the 'Site'. Link [➙ 70]
10. Remedy any errors you notice and load the corrected configuration from the
PC to the 'Station'. Link [➙ 27]
11. Disconnect the PC from the 'Station'. Link [➙ 24]
12. Perform the completion tasks. Link [➙ 70]
39 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
C- Commissioning networked 'Stations'
9
Prerequisites
● The ↑ detector lines and C-NET devices are installed.
● The acceptance test has been carried out for the detector lines.
● The ↑ 'Station' is installed, but the batteries are not connected yet.
● The cables for the detector lines and the mains supply have been inserted in
the 'Station', but not yet connected.
● Cerberus-Engineering-Tool is installed on the PC.
● The current firmware and ↑ BDV are available on the PC.
You will find additional information about the individual steps on the specified
pages.
Commissioning
1. Create a ↑ 'Site' and the ↑ 'Stations' in Cerberus-Engineering-Tool and pre-
configure, if required.
2. Prepare each 'Station' individually for commissioning – without ↑ BDV
installation. Link [➙ 59]
3. Connect the PC to each 'Station' individually. Link [➙ 24]
4. Initialize each 'Station' individually. Link [➙ 25]
5. Read-in the C-NET devices for all 'Stations'. Link [➙ 66]
6. Load the configuration from the 'Station' to the PC. Link [➙ 29]
7. Adapt the configuration in Cerberus-Engineering-Tool. Link [➙ 61]
8. Load the configuration from the PC to the 'Station'. Link [➙ 27]
9. Test the function of the 'Site'. Link [➙ 70]
10. Remedy any errors you notice and load the corrected configuration from the
PC to the 'Station'. Link [➙ 27]
11. Disconnect the PC from the 'Station'. Link [➙ 24]
12. Perform the completion tasks. Link [➙ 70]
40 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Adding a 'Station' to an existing 'Site'
10
You will find additional information about the individual steps on the specified
pages.
Commissioning
1. In Cerberus-Engineering-Tool, create the ↑ 'Station' to be integrated and
configure it, if required.
2. Prepare the 'Station' for commissioning - without BDV installation. Link [➙ 59]
3. Connect the PC to the 'Station'. Link [➙ 24]
4. Initialize the 'Station'. Link [➙ 25]
5. Read-in the C-NET devices. Link [➙ 66]
6. Load the configuration from the 'Station' to the PC. Link [➙ 29]
7. Adapt the configuration in Cerberus-Engineering-Tool. Link [➙ 61]
8. Load the configuration from the PC to the 'Station'. Link [➙ 27]
9. Test the function of the ↑ 'Site'. Link [➙ 70]
10. Remedy any errors you notice and load the corrected configuration from the
PC to the 'Station'. Link [➙ 27]
11. Disconnect the PC from the 'Station'. Link [➙ 24]
12. Perform the completion tasks. Link [➙ 70]
41 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Merging two 'Sites'
11 Setting detector parameter sets
NOTICE
Merging standalone 'Stations'
You have to convert standalone 'Stations' to networked ↑ 'Stations' to combine
'Stations' into one ↑ 'Site'. You will find more information in chapter 'Converting a
standalone station to a networked station [➙ 62]'.
Prerequisites
● Both ↑ 'Sites' are part of the same sales channel.
● Both 'Sites' have the same firmware version and ↑ BDV version.
● Both 'Sites' have one network.
● Both 'Sites' combined have at most the allowed number of ↑ 'Stations' for a
'Site'.
● Both 'Sites' combined have at most the allowed number of ↑ SAFEDLINK sub-
nets for a 'Site'.
● Wiring between the two 'Sites' is prepared:
– The 'Ethernet switch (MM) FN2008-A1' is installed in the 'Stations' intended
as ↑ router stations and connected to an optical network (C-WEB/LAN).
– Large SAFEDLINK sub-nets are in the original state and not yet divided.
– Ethernet sub-nets are in the original state.
You will find additional information about the individual steps on the specified
pages.
Commissioning
1. Add ↑ 'Site' B to 'Site' A. Link [➙ 43]
2. Initialize all ↑ 'Stations' that have a new address. Link [➙ 25]
3. Load the configuration of all 'Stations' in 'Site' A from the PC to the 'Station'.
Link [➙ 27]
4. Connect the 'Sites' physically to one another. Link [➙ 43]
5. Load the configuration of the merged 'Site' from the 'Station' to the PC. Link
[➙ 29]
6. Adapt the configuration in Cerberus-Engineering-Tool. Link [➙ 61]
7. Load the configuration from the PC to the 'Station'. Link [➙ 27]
8. Test the function of the 'Site'. Link [➙ 70]
9. Remedy any errors you notice and load the corrected configuration from the
PC to the 'Station'. Link [➙ 27]
42 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Merging two 'Sites'
Adding 'Site' B to 'Site' A
11
See also
1 Applicable documents [➙ 9]
43 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Changing and expanding the FDnet/C-NET detector line
12 Extending the detector line to include additional devices
NOTICE
Incorrect assignment between detector/detector zone and customer text
Inaccurate messages in the event of an alarm
● You must not change the C-NET topology at the same time as adding extra
devices.
● After extending or changing a ↑ 'Site' always run a test to check the
assignment between detector/detector zone and customer text.
You will find additional information about the individual steps on the specified
pages.
44 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Changing and expanding the FDnet/C-NET detector line
Extending the detector line to include additional devices
12
45 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Changing and expanding the FDnet/C-NET detector line
12 Replacing stationary devices of the same type
NOTICE
Incorrect assignment between detector/detector zone and customer text
Inaccurate messages in the event of an alarm
● You must not change the C-NET topology at the same time as adding extra
devices.
● After extending or changing a ↑ 'Site' always run a test to check the
assignment between detector/detector zone and customer text.
You will find additional information about the individual steps on the specified
pages.
See also
1 Applicable documents [➙ 9]
46 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Changing and expanding the FDnet/C-NET detector line
Permanently removing stationary devices
12
You will find additional information about the individual steps on the specified
pages.
You can also delete the physical representation of the C-NET devices individually
via the control panel's ↑ Person Machine Interface. Link [➙ 67]
47 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Changing and expanding the FDnet/C-NET detector line
12 Removing or replacing non-stationary devices
Document the serial number or address and the position in the C-NET for each
device in order to enable the device to be placed in the same position following its
removal.
The work described in this chapter may be performed when the C-NET detector
line is switched on.
See also
1 Restarting the detector line [➙ 64]
48 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Changing and expanding the FDnet/C-NET detector line
Removing or replacing non-stationary devices
12
You will find additional information about the individual steps on the specified
pages.
The work described in this chapter may be performed when the C-NET detector
line is switched on.
49 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Changing and expanding the FDnet/C-NET detector line
12 Removing or replacing non-stationary devices
You will find additional information about the individual steps on the specified
pages.
The work described in this chapter may be performed when the C-NET detector
line is switched on.
50 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Changing and expanding the FDnet/C-NET detector line
Removing or replacing non-stationary devices
12
Mark the allocation of the devices to the respective base to avoid additional work
steps.
You will find additional information about the individual steps on the specified
pages.
See also
1 Correcting swapped devices [➙ 139]
You will find additional information about the individual steps on the specified
pages.
51 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Changing and expanding the FDnet/C-NET detector line
12 Removing or replacing non-stationary devices
You will find additional information about the individual steps on the specified
pages.
See also
1 Applicable documents [➙ 9]
52 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Changing and expanding the FDnet/C-NET detector line
Removing or replacing non-stationary devices
12
Mark the allocation of the devices to the respective base to avoid additional work
steps.
You will find additional information about the individual steps on the specified
pages.
The work described in this chapter may be performed when the C-NET detector
line is switched on.
53 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Changing and expanding the FDnet/C-NET detector line
12 Removing or replacing non-stationary devices
You will find additional information about the individual steps on the specified
pages.
54 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Changing and expanding the FDnet/C-NET detector line
Replacing 'Manual call point' of the same type
12
NOTICE
Incorrect assignment between detector/detector zone and customer text
Inaccurate messages in the event of an alarm
● You must not change the C-NET topology at the same time as adding extra
devices.
● After extending or changing a ↑ 'Site' always run a test to check the
assignment between detector/detector zone and customer text.
You will find additional information about the individual steps on the specified
pages.
55 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Changing and expanding the FDnet/C-NET detector line
12 Replacing 'Manual call point' of the same type
56 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Changing and expanding the FDnet/C-NET detector line
Convert two stubs into a loop
12
You will find additional information about the individual steps on the specified
pages.
ϖ The two ↑ stubs are assigned to the same line pair, e.g., 'Line' 11 and 'Line' 12.
1. Switch both the C-NET detector lines off. Link [➙ 63]
2. Wire both stubs to a ↑ loop. You will find more information about this in
document A6V10210390. See chapter 'Applicable documents'.
3. Read-in the C-NET devices. Link [➙ 66] Start with the first 'Line' (in the
example 'Line' 11).
The second 'Line' is adopted and the loop is formed (in this example,
'Line' 1).
4. Connect the PC to the ↑ 'Station'. Link [➙ 24]
5. Load the configuration from the 'Station' to the PC. Link [➙ 29]
6. Test the function of the ↑ 'Site'. Link [➙ 70]
7. Remedy any errors you notice and load the corrected configuration from the
PC to the 'Station'. Link [➙ 27]
8. Disconnect the PC from the 'Station'. Link [➙ 24]
See also
1 Applicable documents [➙ 9]
You will find additional information about the individual steps on the specified
pages.
See also
1 Applicable documents [➙ 9]
57 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Detailed commissioning steps
13 Preparing 'Station' for commissioning
58 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Detailed commissioning steps
Preparing 'Station' for commissioning –without BDV installation
13
It is not necessary to install the BDV for the further procedure. This saves having
to restart the ↑ 'Station'.
Following preparation, you can for instance perform the following steps, depending
on the selected commissioning variant:
● Initialize the ↑ 'Station'
● Auto-configure the 'Station'
● Load the configuration from the PC to the 'Station'
See also
1 Applicable documents [➙ 9]
59 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Detailed commissioning steps
13 Auto-configuring the detector line
NOTICE
Incorrect order for reading in a ↑ loop, no isolation of second 'Line'
Error when reading in a loop
The C-NET detector lines are detected as ↑ stubs during the first system startup,
e.g., 'Line' 11, 'Line' 12 (2-digit line number), even if they are connected as a loop.
● Before you proceed to reading in the first 'Line', you must isolate the second
'Line'.
● To read in a loop, always select the first 'Line', in this case 'Line' 11. 'Line' 12
is then read in automatically and a loop is displayed with a 1-digit line number,
in this case as 'Line' 1.
● Proceed in the same way from 'Line' 21/22 (loop 2) to 'Line' 41/42 (loop 4).
NOTICE
Overwriting an existing configuration
Parts of an existing customer-specific configuration are lost.
● First save an existing customer-specific configuration.
1. Select 'Main menu' > 'Topology' > 'Hardware tree' > ↑ 'Station' > 'Module' (line
card) > 'Line'.
2. Press the 'MoreOptions' softkey and select 'Execute commands'.
3. Select the 'Auto-configure line' command.
The C-NET detector line is auto-configured.
The following message is shown following successful ↑ auto-configuration:
'Command executed'
See also
1 Applicable documents [➙ 9]
60 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Detailed commissioning steps
Loading automatically created configuration to the PC
13
The description in this chapter only applies if a configuration has not yet been
loaded to the 'Station' and if the ↑ BDV was installed at the 'Station' after the
'Station' was started for the first time.
See also
1 Applicable documents [➙ 9]
61 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Detailed commissioning steps
13 Converting a standalone station to a networked station
NOTICE
Configuring IP addresses manually
Once a standalone 'Station' has been converted to a networked 'Station', you
have to configure the IP address manually.
62 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Detailed commissioning steps
Switch off
13
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
● Deploy staff to monitor the deactivated area.
● You must switch deactivated parts of the 'Site' back on as soon as possible.
63 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Detailed commissioning steps
13 Switching on
13.9 Switching on
WARNING
Activation of fire or smoke dampers
If fire or smoke dampers are connected to the FS720 via an input/output module,
they may be activated when the station is switched off or when the station or
detector line is restarted.
● If necessary, block the outputs temporarily [➙ 65] before switching off the
station or restarting the station/detector line.
1. Select 'Main menu' > 'Topology' > 'Hardware tree' > ↑ 'Station' > 'Module' (line
card) > 'Line'.
2. Press the 'More Options' softkey and select 'Execute commands'.
3. Select the 'Restart line' command.
The ↑ detector line is restarted. The following messages are displayed:
'Line starting up'
'Device config.runs'
64 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Detailed commissioning steps
Freezing outputs
13
Duration of freeze
The output freeze lasts until the next restart or module reset. It is deactivated after
the restart or module reset. See chapter 'Enabling frozen outputs [➙ 65]' for how
to manually deactivate freezing.
65 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Detailed commissioning steps
13 Read in devices on detector line
NOTICE
Incorrect order for reading in a ↑ loop
Error when reading in a loop.
The C-NET detector lines are detected as ↑ stubs during the first system startup,
e.g., 'Line' 11, 'Line' 12 (2-digit line number), even if they are connected as a loop.
● For loop with line separator: Switch the second 'Line' / 'Line' 12 off.
● To read in a loop, always select the first 'Line', in this case 'Line' 11. 'Line' 12
is then read in automatically.
A loop is displayed with a 1-digit line number, in this case as 'Line' 1 once it
has been read in.
● Proceed in the same way from 'Line' 21/22 (loop 2) to 'Line' 41/42 (loop 4).
ϖ For ↑ loop with line separator: The second 'Line' is switched off. Link [➙ 63]
1. In the main menu, select 'Topology' > 'Hardware tree' > ↑ 'Station' > ↑ Line
card > ↑ Detector line.
2. Press the 'More Options' softkey and select 'Execute commands'.
3. Select the 'Read in installed devices' command.
The C-NET devices are read in.
The following message is shown following successful reading in:
'Command executed'
66 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Detailed commissioning steps
Delete the device on Person Machine Interface
13
See also
1 Applicable documents [➙ 9]
You will find additional information about the individual steps on the specified
pages.
67 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Detailed commissioning steps
13 Switching on test mode
See also
1 Applicable documents [➙ 9]
Element Command
Area ● 'Non-MCP zones det.test'
● 'MCP zones det.test'
↑ Section ● 'Non-MCP zones det.test'
● 'MCP zones det.test'
Zone ● 'Detector test'
68 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Detailed commissioning steps
Switch on normal operation
13
Element Command
Area ● 'Non-MCP zones det.test END'
● 'MCP zones det.test END'
↑ Section ● 'Non-MCP zones det.test END'
● 'MCP zones det.test END'
Zone ● 'Detector test END'
You can also switch to ↑ normal operation at superordinate level for the
command in question. Test mode can also be exited in the 'Zone', 'Section' or
'Area', for example.
69 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Detailed commissioning steps
13 Rectify localization errors
If devices are missing or the device types do not correspond to the C-NET
topology, error messages will continue to be displayed.
See also
1 Applicable documents [➙ 9]
70 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning Ethernet switch (MM) FN2008-A1
Carrying out final commissioning work
14
NOTICE
Alternate products for 'Ethernet switch (MM) FN2008-A1'
No compliance with EN 54
● For an EN-54-compliant fire detection installation, you must use the permitted
'Ethernet switch (MM) FN2008-A1'.
The 'Ethernet switch (MM) FN2008-A1' is a class A equipment and may cause
radio interference in residential areas. If interference does occur, observe the
relevant information in document A6V10210390. See chapter 'Applicable
documents'.
Commissioning
1. Install the 'Primary Setup Tool' software. Link [➙ 72]
2. Assign the IP address. Link [➙ 72]
3. Configure the FN2008-A1 using the Internet browser. Link [➙ 73]
4. In Cerberus-Engineering-Tool, create the ↑ links you want e.g., for the
following monitoring functions in a 'Technical zone'.
– Redundant power
– Display error contact
The FN2008-A1 has no IP address in the factory setting. You must manually
assign the IP address.
See also
1 Applicable documents [➙ 9]
71 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning Ethernet switch (MM) FN2008-A1
14 Install Primary Setup Tool
The 'Primary Setup Tool' software is included in the scope of supply for the
FN2008-A1.
72 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning Ethernet switch (MM) FN2008-A1
Configuring FN2008-A1 using Internet browser
14
NOTICE
Incorrect settings of the ports
Malfunction
● The factory setting 'auto-negotiation' for the ports may not be changed.
1. Open the Internet browser and enter the FN2008-A1's IP address in the
address field.
The login window opens.
2. Login:
– User name = 'admin'
– Password = 'admin'
3. Select 'System' > 'Passwords' in the tree view and set a new password for the
following fields:
– 'New User Password'
– 'New Admin Password'
4. Confirm the entered password with 'Confirmation'.
5. Click 'Set Values'.
6. Select 'X204-2' > 'Ring' in the tree view and check the 'Enable ring redundancy'
checkbox.
– Select the 'Automatic Redundancy Detection' redundancy mode.
7. Select 'X204-2' > 'Fault Mask' in the tree view and check the
'Enable Link Down Monitoring' checkbox for each connected port:
– Port 5 and 6 = Ring
– Port 1 = The connected ↑ 'Station'
– Port 2 to 4 only if more stations 'Stations' are connected
FN2008-A1 is configured.
73 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning Ethernet switch (modular) FN2012-A1
15 Standalone FN2012-A1
See also
1 Updating the FW of Ethernet switch (modular) FN2012-A1
[➙ 125]
You will find information on mounting and installing the FN2012-A1 in document
A6V10210390. See chapter 'Applicable documents'.
74 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning Ethernet switch (modular) FN2012-A1
Standalone FN2012-A1
15
If the rotary switch of the FN2012-A1 is in position 'E', the local ports are not
available. You cannot perform a firmware update or call up a web interface for the
FN2012-A1 when the switch is in position 'E'.
An Ethernet switch that is not integrated in a station must be configured via the
rotary switch. If the Ethernet switch is integrated, the rotary switch must be set to
'0'.
Using the rotary switch for device configuration, the Ethernet switch can be set to
pre-defined network addresses or operation modes.
To apply a new configuration, the setting must be made when the device is de-
energized or by means of a hardware reset.
75 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning Ethernet switch (modular) FN2012-A1
15 FN2012-A1 integrated into station
You will find information on mounting and installing the FN2012-A1 in document
A6V10210390. See chapter 'Applicable documents'.
76 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning Ethernet switch (modular) FN2012-A1
FN2012-A1 web interface
15
WARNING
Changing the initial password
When you first access the web interface, change the initial login password.
If you do not change the initial password, the security of the web interface cannot
be guaranteed. Network settings can be changed as a result of unauthorized
access. Changed network settings can cause the fire detection system to
malfunction.
See also
1 Specifying a pre-configured IP address [➙ 75]
77 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning Ethernet switch (modular) FN2012-A1
15 FN2012-A1 web interface
NOTICE
Setting the rotary switch to the '0' position
The change to the IP address only comes into effect when the rotary switch for
device configuration is set to the '0' position. If the rotary switch is set to a
different position, the standard settings for the corresponding position will be
adopted.
78 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning Ethernet switch (modular) FN2012-A1
FN2012-A1 web interface
15
Resetting the FN2012-A1 to the factory setting automatically activates all local
ports. To reset it to the factory setting, press the RESET button for >5 s but <10 s.
79 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning Ethernet switch (modular) FN2012-A1
15 FN2012-A1 web interface
Deactivated ports are not monitored for faults. Fault monitoring cannot be
configured for deactivated ports.
Do not activate fault monitoring for local ports to which a management station has
been connected. With fault monitoring for local ports to which a management
station has been connected, a fault is displayed every time the management
station is restarted.
Activate fault monitoring only for ports to which FS720 stations have been
connected.
NOTICE
Network settings may be disabled
When port mirroring is activated, this may disable the configured network settings.
Only use port mirroring for troubleshooting purposes for a limited period of time.
The network data traffic of source ports can be mirrored to a monitor port in order
to troubleshoot faults. Appropriate software can be used to record and save the
corresponding data traffic for subsequent fault analysis.
ϖ You have specified a pre-configured IP address for the Ethernet switch
(modular) or configured the IP address manually.
ϖ You have already commissioned the web interface.
1. Open the web interface of the Ethernet switch (modular).
2. Select the 'Configuration' tab.
3. Check the 'Enable port mirroring' checkbox.
4. Select the source ports and the monitor port.
5. Confirm your entries with 'Save changes'.
You have activated port mirroring.
80 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning Ethernet switch (modular) FN2012-A1
Restarting and resetting the FN2012-A1
15
On the device
● Restart device: Press the RESET button.
– The configuration is retained.
● Resetting the device to factory settings: Press the RESET button for >5 s but
<10 s.
Resetting the FN2012-A1 to the factory setting automatically activates all ports.
81 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning security module (firewall) FN2009-A1
16 Restarting and resetting the FN2012-A1
Commissioning
1. Install the 'Security Configuration Tool' software. Link [➙ 83]
2. Select the type and enter the MAC address. Link [➙ 83]
3. Enter the network settings. Link [➙ 84]
– Load configuration.
4. Create IP service definitions. Link [➙ 87]
5. Create firewall rules. Link [➙ 88]
– Load configuration.
The FN2009-A1 has no IP address in the factory setting. You must manually
assign the IP address.
NOTICE
FN2009-A1 is not in factory setting and already has an IP address
It is not possible to upload a new configuration
● Press the Reset button on the live FN2009-A1.
82 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning security module (firewall) FN2009-A1
Installing Security Configuration Tool
16
The 'Security Configuration Tool' software is included in the scope of supply for
the FN2009-A1.
The corresponding MAC address can be found on the front of the FN2009-A1.
The FN2009-A1 is type S612V2.
Preparation
ϖ The PC is connected to FN2009-A1.
ϖ 'Security Configuration Tool' is started.
1. Create a new project using the 'Project' > 'New' menu and enter the
administrative project data, 'User name' and 'Password'.
2. Save the new project.
3. Select 'View' > 'Advanced Mode'.
More entry masks for required settings can be viewed.
83 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning security module (firewall) FN2009-A1
16 Entering network settings
Selecting type
1. Highlight the field below the 'Type' designation.
The button for the dropdown list field is displayed.
2. Select 'S612V2'.
Type is selected.
84 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning security module (firewall) FN2009-A1
Entering network settings
16
The following settings apply for the planned network access to ↑ GAP with
activated DHCP server.
'192.168.201.X' must be changed accordingly for network access to the standby
router or with IP address details.
85 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning security module (firewall) FN2009-A1
16 Entering network settings
The following settings apply for the planned network access to GAP with activated
DHCP server.
86 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning security module (firewall) FN2009-A1
Creating IP service definitions
16
NOTICE
Different ↑ BACnet port settings in FN2009-A1 and Cerberus-Engineering-Tool
No communication possible
● Configure the same BACnet port in FN2009-A1 and Cerberus-Engineering-
Tool.
87 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning security module (firewall) FN2009-A1
16 Creating firewall rules
7. Enter the two optional ICMP services required as shown in the figure below:
– 'Name': ICMP0, 'Type': Echo Request, 'Code': No code
– 'Name': ICMP1, 'Type': Echo Reply, 'Code': No code
Optional IP services are created.
2. Select 'Properties…'.
The 'Module Properties' window for the selected module is displayed.
88 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning security module (firewall) FN2009-A1
Creating firewall rules
16
4. Click on 'Add Rule' for each firewall rule you would like to create.
5. Select the corresponding settings and IP services from the dropdown list fields.
6. Enter the required IP addresses.
7. Confirm input with 'OK'.
The firewall rules are created.
89 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning the fire brigade periphery module FCI2001-D1
17
X4 X5 X6
S101
Procedure
1. Check the connected lines for short-circuit and open line.
2. Connect the lines.
During the commissioning of the control panel, fault messages are
indicated, provided that there are any deviations from the basic settings.
3. Press the push-button S101.
The resistance values are read in.
90 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning of I/O card (remote transmission) FCI2007-A1 and I/O card (horn/monitored) FCI2009-A1
18
S501 S501
FCI2007-A1 FCI2009-A1
S501 Button
Procedure
1. Check the connected lines for short-circuit and open line.
2. Connect the lines.
During the commissioning of the control panel, fault messages are
indicated, provided that there are any deviations from the basic settings.
3. Press the S501 button.
The resistance values are read in.
You can also read in the resistance values via the control panel's ↑ Person
Machine Interface.
91 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning external printer
19
Function Value
MENU 1
EMULATE XL24E
FONT COUR 10
QUALITY LETTER
PITCH 10 CPI
LINE SP 6 LPI
CHAR-W NORMAL
CHAR-H NORMAL
ATTRIB NONE
PAGE LG 12.0 IN
LFT-END 1 COLM
TOP-MRG 1 LINE
LANGUAGE LATIN-9
CHR-SET SET1
AGM OFF
PRF-SKP NO-SKIP
ZEROFNT NO-SLSH
CR-CODE CR ONLY
LF-CODE LF & CR
RGHTEND WRAP
==END==
92 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning external printer
19
Function Value
MENU 2
EMULATE DPL24C+
FONT COUR 10
QUALITY LETTER
PITCH 10 CPI
LINE SP 6 LPI
CHAR-W NORMAL
CHAR-H NORMAL
ATTRIB NONE
PAGE LG 11.0 IN
LFT-END 1 COLM
TOP-MRG 1 LINE
LANGUAGE PAGE437
CHR-SET SET2
PRF-SKP NO-SKIP
ZEROFNT NO-SLSH
DC3-CDE ENABLE
CR-CODE CR ONLY
LF-CODE LF & CR
RGHTEND WRAP
==END==
HARDWRE
PPR-OUT DETECT
PRT-DIR BI-DIR
BUZZER ON
WORD-LG 8 BIT
BUFFER NONE
INTRFCE SERIAL
FORMAT 8NONE 1
BAUD-RT 9600
PROTOCL XON/XOF
DSR IGNORE
DUPLEX FULL
CTS IGNORE
CD IGNORE
==END==
93 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Commissioning external printer
19
Function Value
ADJUST
CNT-ORG 1 /6 IN
CNTFINE 1 /180
CUT-ORG 1 /6 IN
CUTFINE 1 /180
CNT-LFT 0 /90
CUT-LFT 0 /90
CUT-ADJ 0 /360
CNT-ADJ 0 /360
CNTADJL 0 /360
==END==
CONFIG
TEAROFF AUTO
TEARPOS VISIBLE
TEAR-EN 4 SEC
CUTLOAD BUTTON
DECODE DIRECT
AREACNT DISABLE
ON-LOAD ONLINE
LOCK NONE
//S// DISABLE
CONT-PE EDGE
GATHER DISABLE
CUT-CTL SPEED
SKIP-PR ENABLE
STATUS ENABLE
BANDCTL ENABLE
TOF-CTL DRIVER
==END==
Table 3: Settings required
94 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Preparation and security
20
WARNING
Fire detection installation is deactivated during the firmware update
Fire may spread unhindered.
● Supervision by people is required.
● Re-activate the fire detection installation as soon as possible.
NOTICE
Data loss during the firmware update
Configuration data, event memory in the 'Station' and specific system data that is
only available on the 'Station' (e.g., modified customer texts, time stamps of
recent alarms, or persistent commands) are deleted.
● Load the configuration data and event memory to Cerberus-Engineering-Tool
before updating the firmware.
NOTICE
Power failure during the firmware update
Firmware is not updated and 'Station' is not working. The firmware update cannot
be repeated and must be performed by the manufacturer.
● Do not disconnect the Station from the power supply during the firmware
update.
95 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Station: Updating the FW of the main CPU and additional CPUs
● The procedure for updating the firmware depends on the 'Station' configuration.
A 'Station' can be configured as follows:
– ↑ Standalone Station
– ↑ SAFEDLINK Station
– ↑ Router Station, ↑ Ethernet Station
– Modular 'Station' with -↑ CPU card
● Windows firewall setting
– To connect the PC to the 'Station', the Windows firewall settings must be
changed if possible. You will find more information on this in chapter
'Setting Windows firewall [➙ 21]'.
● Communication with ↑ GAP via C-WEB/LAN
– A GAP with DHCP must be configured for a connection with the PC via C-
WEB/LAN. You will find more information in document A6V10210424. See
chapter 'Applicable documents'.
See also
1 Updating several 'Stations' simultaneously [➙ 98]
You will find additional information about the individual steps on the specified
pages.
ϖ You are familiar with the information in chapter 'Preparation and security
[➙ 95]'.
1. Import the new firmware into Cerberus-Engineering-Tool.
– Select 'File' > 'Import new resource package' from the menu and open the
file you want.
2. Load the configuration from the 'Station' or your archive to the PC. Link [➙ 29]
3. NOTICE! Possible data loss. Load the configuration data and event memory to
Cerberus-Engineering-Tool before updating the firmware.
– Saving the configuration data also backs up specific system data which is
only available on the 'Station'. This includes modified customer texts, time
stamps of recent alarms, or persistent commands.
4. Convert the configuration if necessary and rectify conversion faults. Link
[➙ 110]
5. Connect the PC to the 'Station'. Link [➙ 24]
6. Update the firmware on the main CPU and the additional CPUs. Link [➙ 99]
7. Initialize the 'Station'. Link [➙ 25]
8. Test the firmware version on the additional CPUs. Link [➙ 111]
– Update the firmware, if required, of the additional CPUs again, if there is a
higher firmware version available. Link [➙ 108]
9. Disconnect the PC from the 'Station'. Link [➙ 24]
96 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Station: Updating the FW of the main CPU and additional CPUs
20
You will find additional information about the individual steps on the specified
pages.
ϖ You are familiar with the information in chapter 'Preparation and security
[➙ 95]'.
ϖ A GAP with DHCP must be configured for the connection with the PC via C-
WEB/LAN.
1. Import the new firmware into Cerberus-Engineering-Tool.
– Select 'File' > 'Import new resource package' from the menu and open the
file you want.
2. Load the configuration from the 'Station' or your archive to the PC. Link [➙ 29]
3. NOTICE! Possible data loss. Load the configuration data and event memory to
Cerberus-Engineering-Tool before updating the firmware.
– Saving the configuration data also backs up specific system data which is
only available on the 'Station'. This includes modified customer texts, time
stamps of recent alarms, or persistent commands.
4. Convert the configuration if necessary and rectify conversion faults. Link
[➙ 110]
5. Via the Ethernet switch (MM) FN2008-A1, connect the PC to the C-WEB/LAN.
6. Update the firmware on the main CPU and the additional CPUs. Link [➙ 99]
7. Initialize the 'Station'. Link [➙ 25]
– Remove the network connection to the 'Station'and connect the PC locally
to the 'Station'. Link [➙ 24]
8. Test the firmware version on the additional CPUs. Link [➙ 111]
– Update the firmware, if required, of the additional CPUs again, if there is a
higher firmware version available. Link [➙ 108]
9. Disconnect the PC from the 'Station'. Link [➙ 24]
10. Restore the network connection.
97 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Station: Updating the FW of the main CPU and additional CPUs
You will find additional information about the individual steps on the specified
pages.
ϖ You are familiar with the information in chapter 'Preparation and security
[➙ 95]'.
ϖ A GAP with DHCP must be configured for the connection with the PC via C-
WEB/LAN.
ϖ The 'Stations' are displayed together.
ϖ You can update not more than eight 'Stations' simultaneously.
1. Import the new firmware into Cerberus-Engineering-Tool.
– Select the 'File' > 'Import new resource package' menu item and open the
file you want.
2. Load the configuration from the 'Station' or your archive to the PC. Link [➙ 29]
3. NOTICE! Data loss. Save the configuration data before updating the firmware.
– Saving the configuration data also backs up specific system data which is
only available on the 'Station'. This includes modified customer texts, time
stamps of recent alarms, or persistent commands.
4. Convert the configuration if necessary and rectify conversion faults. Link
[➙ 110]
5. Connect the PC to the Ethernet switch (MM) FN2008-A1.
6. Update the firmware on the main CPU and the additional CPUs. Link [➙ 99]
– Set each 'Station' individually in update mode. You can set the 'Stations' in
update mode without any waiting time one directly after the other.
– Wait until the update of each 'Station' is completed.
7. Initialize each 'Station' individually. Link [➙ 25] To do so, you must connect the
PC to each 'Station' locally. Link [➙ 24]
8. Test the firmware version on the additional CPUs on each 'Station'. Link
[➙ 111]
– Update the firmware, if required, of the additional CPUs again, if there is a
higher firmware version available. Link [➙ 108]
9. Disconnect the PC from the 'Station'. Link [➙ 24]
10. Restore the network connection, if required.
98 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Station: Updating the FW of the main CPU and additional CPUs
20
Initializing the 'Station' instead of installing the ↑ BDV saves time. During
initialization, the BDV and the configuration data are loaded to the 'Station'.
You will find information on troubleshooting for the firmware update in chapter
'Error during firmware update [➙ 106]'.
99 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Station: Updating the FW of the main CPU and additional CPUs
2. Set the 'S38-2' switch to 'ON' on the rear of the operating unit.
3. Press the 'S32' button for approx. 5 s until the 'Station' restarts.
100 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Station: Updating the FW of the main CPU and additional CPUs
20
101 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Station: Updating the FW of the main CPU and additional CPUs
Initializing the 'Station' instead of installing the ↑ BDV saves time. During
initialization, the BDV and the configuration data are loaded to the 'Station'.
You will find information on troubleshooting for the firmware update in chapter
'Error during firmware update [➙ 106]'.
102 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Station: Updating the FW of the main CPU and additional CPUs
20
2. Keep the 'S32' button on the rear of the operating unit pressed and press
<Acknowledge> on the ↑ Person Machine Interface at the same time for
approx. 5 s until the ↑ 'Station' restarts.
103 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Station: Updating the FW of the main CPU and additional CPUs
104 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Station: Updating the FW of the main CPU and additional CPUs
20
4. Select 'Start'.
The following window is opened:
5. Confirm the firmware update with 'Yes' or reject the firmware update with 'No'.
The following window is opened:
105 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Station: Updating the FW of the main CPU and additional CPUs
6. Click on 'OK'.
The following window is opened:
106 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Station: Updating the FW of the additional CPUs only
20
You will find additional information about the individual steps on the specified
pages.
See also
1 Loading configuration from the station to the PC [➙ 29]
You will find additional information about the individual steps on the specified
pages.
107 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Station: Updating the FW of the additional CPUs only
NOTICE
Updating the firmware of the degraded mode module FN2001
If the firmware of the degraded mode module FN2001 has to be updated, it must
be temporarily connected to the slot for the main module FN2001 (from slot X12
to X13).
108 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Update only the BDV
20
9. Click on 'OK'.
The 'Station' is restarted.
After a few minutes, the 'Buzzer' sounds twice.
10. Press <Acknowledge> on the Person Machine Interface to switch off the
'Buzzer'. Do not perform any more actions on the 'Station' until the 'Buzzer' has
sounded for the second time.
11. Click on 'Close' in the 'FW update additional CPUs' window.
See also
1 Preparation and security [➙ 95]
See also
1 Applicable documents [➙ 9]
You will find additional information about the individual steps on the specified
pages.
109 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Converting the configuration
You will find additional information about the individual steps on the specified
pages.
110 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Testing the firmware version of the additional CPUs
20
111 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Creating diagnosis report
You will find more information about creating reports and the diagnosis report in
document A6V10210424. See chapter 'Applicable documents'.
See also
1 Applicable documents [➙ 9]
If the hardware product version is not compatible with the current firmware, a
corresponding error message is displayed during the update process.
In this instance, the hardware must be replaced in accordance with the
information in the 'Release Notes'.
112 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Updating the FW of the peripheral devices
20
Preparation
ϖ The driver for the MCL-USB adapter is installed on the PC.
1. Select 'File' > 'Import new resource package'.
2. In the selection window open the corresponding file F-FXS2007-XX_x_x_...zip.
3. Connect the MCL-USB adapter to the PC.
The orange LED on the MCL-USB adapter flashes for a short while. When the
device is ready for operation, the green LED lights up.
USB
FDUZ221/FDUZ227
Check the COM port setting under 'Options' > 'Preferences' > 'Periphery update'
before performing the firmware update.
113 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Updating the FW of the peripheral devices
WARNING
Incorrect assignment between detector/detector zone and customer text
Misleading messages in the event of an alarm
● Never change the wiring during the firmware update.
The firmware must be updated individually for each ↑ floor repeater terminal.
Preparation
ϖ The ↑ floor repeater terminal is fed by a 24 V external power supply or by the
C-NET detector line.
ϖ The driver for the MCL-USB adapter FDUZ221 or FDUZ227 is installed on the
PC.
1. Select 'File' > 'Import new resource package'.
2. In the selection window, open an F-FXS7211-XX_x_x_...zip file matching the
↑ 'Site'.
3. Open the device and connect the PC via the MCL-USB adapter to the device.
FT2010
X100
USB
MC-Link
FDUZ221/FDUZ227
24 V
Figure 4: Connect the PC to the floor repeater terminal
114 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Updating the FW of the peripheral devices
20
Check the COM port setting under 'Options' > 'Preferences' > 'Periphery update'
before performing the firmware update.
115 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Updating the FW of the peripheral devices
WARNING
Incorrect assignment between detector/detector zone and customer text
Misleading messages in the event of an alarm
● Never change the wiring during the firmware update.
The firmware must be updated individually for each ↑ floor repeater display.
Preparation
ϖ The ↑ floor repeater display is fed by a 24 V external power supply or by the C-
NET detector line.
ϖ The driver for the MCL-USB adapter FDUZ221 or FDUZ227 is installed on the
PC.
1. Select 'File' > 'Import new resource package'.
2. In the selection window, open an F-FXS7211-XX_x_x...zip file that matches the
↑ 'Site'.
3. Open the device and connect the PC via the MCL-USB adapter to the device.
FT2011
X100
USB
MC-Link
FDUZ221/FDUZ227
24 V
Figure 5: Connect the PC to the floor repeater display
116 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Updating the FW of the peripheral devices
20
Check the COM port setting under 'Options' > 'Preferences' > 'Periphery update'
before performing the firmware update.
117 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Updating the FW of the peripheral devices
WARNING
Incorrect assignment between detector/detector zone and customer text
Misleading messages in the event of an alarm
● Never change the wiring during the firmware update.
The firmware must be updated individually for each mimic display driver.
Preparation
ϖ The mimic display driver is fed by a 24 V external power supply or by the C-
NET detector line.
ϖ The driver for the MCL-USB adapter FDUZ221 or FDUZ227 is installed on the
PC.
1. Select 'File' > 'Import new resource package'.
2. In the selection window, open an F-FXS7211-XX_x_x_...zip file matching the
↑ 'Site'.
3. Connect the PC to the device via the MCL-USB adapter.
FT2001-A1
X2
USB
MC-Link
FDUZ221/FDUZ227
118 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Updating the FW of the peripheral devices
20
Check the COM port setting under 'Options' > 'Preferences' > 'Periphery update'
before performing the firmware update.
119 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Updating the FW of the peripheral devices
21
S200 ON
1 1
1
1 1
See also
1 Applicable documents [➙ 9]
120 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Updating the FW of the peripheral devices
20
Preparation
1. Save the latest firmware file on your PC.
2. Select 'File' > 'Import new resource package' in the Engineering Tool.
3. In the selection window, open the firmware file with the corresponding
language F-FXS2007-XX_x_x_...zip.
DC USB
FDUL221 FDUZ221/FDUZ227
MC-Link
B
Figure 7: Connect the PC to the line tester
121 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Updating the FW of the peripheral devices
Check the COM port setting under 'Options' > 'Preferences' > 'Periphery update'
before performing the firmware update.
122 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Updating the FW of the peripheral devices
20
Preparation
ϖ The line tester is supplied via a mains adapter.
ϖ An RS232 port is available on the PC.
1. Select 'File' > 'Import new resource package'.
2. In the selection window, open the most recent file with the corresponding
language F-FXS2007-XX_x_x_...zip.
3. Connect the device to the PC via the RS232 interface in the battery
compartment.
DC
FDUL221
RS 232
B S
123 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Updating the FW of the peripheral devices
Check the COM port setting under 'Options' > 'Preferences' > 'Periphery update'
before performing the firmware update.
124 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Updating the FW of Ethernet switch (modular) FN2012-A1
20
125 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
20 Updating the FW of Ethernet switch (modular) FN2012-A1
0 125 250 375 500 625 750 875 1000 1125 1250 1375 1500 1625 1750 1875 [ms]
0 125 250 375 500 625 750 875 1000 1125 1250 1375 1500 1625 1750 1875 [ms]
126 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Updating the firmware
Updating the FW of Ethernet switch (modular) FN2012-A1
20
127 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Maintenance
21 General
21 Maintenance
21.1 General
General rule
It is assumed that the ↑ 'Site' was commissioned in accordance with the existing
directives, i.e., all functions have been tested and the 'Site' data has been saved
and archived.
Protocol
● Measurement values must be recorded according to specifications.
● Recorded measurement values must be stored in the site file.
NOTICE
Non-observance of rules during maintenance work
Insufficient maintenance and damage to the ↑ 'Site' or parts thereof
● Always de-energize the ↑ 'Station' first before connecting, fitting, or removing
components.
● Prevent electrostatic discharge.
● If undertaking work on components, you must use an EMC mat.
● Do not touch the modules unnecessarily with your bare hands.
● Do not unnecessarily switch off the 'Site' or parts thereof for long periods of
time.
21.2 Testing
FS720 offers various test functions for efficient testing of devices and logical
functions. Some test methods can be combined, others have to be carried out
individually.
The fire detection installation is in 'Test' operation mode if one of the following test
modes is activated:
● 'Detector test'
● 'Walk test'
● 'Control test'
● 'Installation test'
● Test variants
You will find more information on testing the system in document A6V10211076.
See chapter 'Applicable documents'.
128 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Maintenance
Testing and measuring instruments
21
129 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Maintenance
21 Test system data
Remote transmission
Check that the phone numbers and the names of the remote transmission
receivers are up to date.
Firmware
1. Read out the current firmware version from the ↑ 'Station': To do this, select
'Topology' > 'Hardware tree' > 'Station' > 'MoreOptions' > 'Show details' in the
main menu.
2. Do not replace the current firmware version with the latest version unless this is
necessary to correct faults or add functions.
'Event memory'
Check the content of the 'Event memory' and take the necessary measures, e.g.,
switch on elements that have been switched off temporarily.
Change in use
Verify whether a change of use or changes to the building have an effect on the
configuration and perform the necessary corrections.
130 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Maintenance
Testing the 'Station'
21
Check labeling
Check that the inscription strips are correct and still easily legible.
131 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Maintenance
21 Check the power supply
132 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Maintenance
Testing the printer
21
See also
1 Applicable documents [➙ 9]
See also
1 Applicable documents [➙ 9]
Detector inspection
● Annual visual check of all 'Detectors'.
● Replace 'Detectors' that are badly soiled or mechanically damaged.
Function test
The following table shows the intervals recommended for the function check.
National specifications always take priority.
133 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Maintenance
21 Carrying out final maintenance work
134 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Repair
Disconnect the station from the power supply
22
22 Repair
WARNING
Activation of fire or smoke dampers
If fire or smoke dampers are connected to the FS720 via an input/output module,
they may be activated when the station is switched off or when the station or
detector line is restarted.
● If necessary, block the outputs temporarily [➙ 65] before switching off the
station or restarting the station/detector line.
NOTICE
Connecting or removing components during operation
Damage to components
● Do not connect or remove components during operation.
You will find information about installing and uninstalling the components in
document A6V10210390. See chapter 'Applicable documents'.
Date and time are not saved in the ↑ 'Station'. The date and time must be reset to
restart the 'Station'.
135 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Repair
22 Spare parts
136 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Repair
Fault messages on the Person Machine Interface
22
1
8
10
5 12
137 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Repair
22 Fault indicators on components
See also
1 Applicable documents [➙ 9]
138 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Repair
Correcting swapped devices
22
Troubleshooting
'Faults' of C-NET devices of the same type that have been swapped over can
then be rectified using the ↑ Person Machine Interface without having to find the
original base.
139 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Repair
22 Correcting an invalid topology
Invalid topologies
Stub on ↑ stub or ↑ loop interrupted
Loop on loop
Troubleshooting
1. Check the detector line with the line tester FDUL221. You will find more
information about this in document 008250. See chapter 'Applicable
documents'.
2. Create a valid topology:
– Rectify the fault by changing over the wiring or plan the detector line again.
– If there are several stub outputs between two C-NET devices, change over
the wiring or add a ↑ line separator FDCL221 between each stub.
3. Read in the C-NET detector line again.
See also
1 Read in devices on detector line [➙ 66]
140 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Repair
Error message 'Too many devices'
22
WARNING
Activation of fire or smoke dampers
If fire or smoke dampers are connected to the FS720 via an input/output module,
they may be activated when the station is switched off or when the station or
detector line is restarted.
● If necessary, block the outputs temporarily [➙ 65] before switching off the
station or restarting the station/detector line.
141 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Repair
22 Restoring factory setting on the 'Station'
ϖ Switches S38-1 and S38-2 are set to the 'OFF' position on the PMI &
mainboard FCM2004.
κ On the PCB of the operating unit, press and hold down the 'S32' button for
<2 s.
The 'Station' shuts down.
The 'Station' is switched off for several seconds.
The 'Station' restarts.
142 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Repair
Restoring factory setting on the 'Station'
22
143 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Repair
22 Fiber-optic network module FN2006 / FN2007 troubleshooting steps
Number Pwr x RX1 Fail1 EF1 LNK1 Possible cause LNK2 EF2 Fail2 RX2 Pwr x
Node 1 / line 1 Node 2 / line 2
1 ON ON OFF OFF FLSHG Normal operation FLSHG OFF OFF ON ON
2 ON OFF ON OFF OFF Optical fibers wrong FLSHG OFF ON OFF ON
way round
3a ON OFF ON OFF OFF Break in optical fiber OFF OFF OFF ON ON
RX1
3b ON ON OFF OFF OFF Break in optical fiber OFF OFF ON OFF ON
RX2
4 OFF OFF OFF OFF OFF Energy supply FLSHG OFF ON 1 OFF 1 ON
interrupted
5 ON ON OFF ON 2 FLSHG Ground fault at A1/B1 FLSHG OFF OFF ON ON
6 ON ON OFF OFF OFF A1/B1 wrong way FLSHG OFF OFF ON ON
round
7 ON ON OFF OFF OFF Break in A1 or B1 FLSHG OFF OFF ON ON
Table 8: Searching for faults on fiber-optic cable converter based on LED status
1 Depending on which module with a fully intact supply is connected, RX1 / RX2 is
OFF, and Fail1 or Fail2 is ON.
2 In the event of a ground fault, LED EF1 lights up and LED EF2 flashes (to
144 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Repair
Fiber-optic network module FN2006 / FN2007 troubleshooting steps
22
1 Normal condition
Node 1 FN2006/FN2007 FN2006/FN2007 Node 2
A1 B1 A2 B2 A Power B B Power A B1 A1 B2 A2
VsysA VsysA
H3 H2 H3 H2
H1 H1
FN2001 FN2001
Figure 10: Normal condition
A1 B1 A2 B2 A Power B B Power A B1 A1 B2 A2
VsysA VsysA
H3 H2 H3 H2
H1 H1
FN2001 FN2001
Figure 11: Optical fibers wrong way round
In addition, the following light up on the affected lines: fault indicators H2 / H3 on
the FN2001 network modules.
145 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Repair
22 Fiber-optic network module FN2006 / FN2007 troubleshooting steps
A1 B1 A2 B2 A Power B B Power A B1 A1 B2 A2
VsysA VsysA
H3 H2 H3 H2
H1 H1
FN2001 FN2001
Figure 12: Break in optical fiber RX1
A1 B1 A2 B2 A Power B B Power A B1 A1 B2 A2
VsysA VsysA
H3 H2 H3 H2
H1 H1
FN2001 FN2001
Figure 13: Break in optical fiber RX2
146 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Repair
Fiber-optic network module FN2006 / FN2007 troubleshooting steps
22
A1 B1 A2 B2 A Power B B Power A B1 A1 B2 A2
VsysA VsysA
H3 H2 H3 H2
H1 H1
FN2001 FN2001
Figure 14: Energy supply interrupted
In addition, the following light up on the affected FN2001 network modules: fault
indicators H2 and H3. The fault relay on the affected module responds.
A1 B1 A2 B2 A Power B B Power A B1 A1 B2 A2
VsysA VsysA
H3 H2 H3 H2
H1 H1
FN2001 FN2001
Figure 15: FN2006 / FN2007 Fault scenario 5, Ground fault B1 VP
The ground fault on line 1 (A1/B1) is mirrored on line 2 (A2/B2); in addition, EF2
flashes. The fault relay on the affected module responds.
147 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Repair
22 Fiber-optic network module FN2006 / FN2007 troubleshooting steps
A1 B1 A2 B2 A Power B B Power A B1 A1 B2 A2
VsysA VsysA
H3 H2 H3 H2
H1 H1
FN2001 FN2001
Figure 16: A1 and B1 have been connected the wrong way round on line 1
In addition, the following light up on the affected FN2001 network modules: fault
indicators H3 (line 1) and H2 (line 2).
A1 B1 A2 B2 A Power B B Power A B1 A1 B2 A2
VsysA VsysA
H3 H2 H3 H2
H1 H1
FN2001 FN2001
Figure 17: Break in A1 on line 1
In addition, the following light up on the affected FN2001 network modules: fault
indicators H3 (line 1) and H2 (line 2).
148 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Glossary
Glossary
Alarm device CPU
Element in the fire detection system for acoustic Abbreviation for 'Central Processing Unit'. The
and/or visual alarming, e.g. alarm sounder, computing unit of the fire control panel.
beacon.
Detection tree
Alarm indicator Diagram of the geographical and organizational
Visual display to signal an alarm or pre-alarm. arrangements of sensors in a building. This is a
hierarchical structure comprising the area,
section, and zone.
Alarm organization
Covers all measures which are used for Detector line
alarming, rescue, preventing a fire from
spreading, fire fighting, and orientation in the Electrical connection between the detectors and
event of a fire. Alarm organization may differ the fire control panel. There are collective
depending on the 'Manned' or 'Unmanned' detector lines and addressed detector lines.
operation mode.
Effect
Assignment An impact caused by a control, e.g., activation of
Creating a reference between two elements, a hardware output or a command.
e.g., logical channel and physical channel.
Ethernet station
Auto-configuration Participants in the Ethernet sub-net without local
A zone is created for each sensor channel connection for the PC.
(automatic detector and manual call point). A
control is created for each alarm sounder. IO- External alarm indicator
modules, FT2010, FT2011, and external alarm Optical element for displaying the fire location,
indicators are not auto-configured. which is at some distance from the detector. It is
normally mounted in the room at the point where
Automatic fire detector the corresponding detector is accessible.
Device which measures a physical parameter
(e.g. warmth) in order to detect a fire. Floor repeater display
A display device without operating elements.
BACnet
Abbreviation for 'Building Automation and Floor repeater terminal
Control Networks'. It is a network protocol for A display device with operating elements for
building automation, such as for communication acknowledging and resetting alarms and faults.
between a management station (MMS) and a fire
detection installation. GAP
Abbreviation for 'Global Access Point'.
BDV Participant in the Ethernet sub-net for the
Abbreviation for 'Base Data Variant'. connection between the Ethernet sub-net and a
Configuration files for the embedded software. A management station (BACnet client) and / or for
BDV contains country-specific templates, all remote access with the PC. If there is a
texts, specifications for message layout, menu secondary GAP, the GAP becomes the main
definitions, specifications for activating the LEDs GAP. Can be operated as a DHCP server in the
on the PMI, detector parameter set settings, Ethernet sub-net.
definitions for system-specific parts of the tool
interface, etc. Line card
Card for connecting peripheral devices. The card
C-NET can be a plug-in card or it can be integrated into
Addressed detector line for C-NET devices. the periphery board.
Control tree
Structure tree with control group and control.
149 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Glossary
Router station
Participant in the SAFEDLINK sub-net for the
connection between the SAFEDLINK sub-net
and the Ethernet sub-net (FCnet/C-WEB/LAN)
via the Ethernet switch (modular) FN2012-A1.
150 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Index
Index
A D
Acceptance test............................................... 20 Date / time .................................................... 138
Alarm counter ................................................. 95 Deleting
Auto-configuration ........................................... 35 Device ............................................................ 67
Definition of terms ........................................... 32 Detector
Detector line ................................................... 60 Test mode ...................................................... 68
Station ............................................................ 59 Testing ........................................................... 67
Detector inspection ........................................ 133
B Detector line
Backup ........................................................... 29 Auto-configuration........................................... 60
Install .............................................................. 19
C
Commissioning ............................................... 31 Restart............................................................ 64
According to wiring sequence.......................... 19 Switch off ........................................................ 63
Auto-configuration ........................................... 35 Switching on ................................................... 64
Networked station ........................................... 40 Testing ........................................................... 19
Overview ........................................................ 31 Detector self-test ........................................... 133
Standalone station with PC, Device
with pre-configuration ..................................... 39 Remove .......................................................... 48
Standalone station with PC, Remove (base without loop contact) ............... 51
without pre-configuration ................................ 38 Replace (base without loop contact)................ 51
Standalone station without PC ........................ 35 Replacing (different types) .............................. 52
With serial number .......................................... 19 Replacing (stationary) ..................................... 46
Without PC ..................................................... 35 Swapped ...................................................... 139
Communication problems ............................... 138 Temporarily remove ........................................ 53
Component Disconnect power
Indication of faults ......................................... 138 Station .......................................................... 135
Configuration Download .................................................. 25, 27
Conversion ................................................... 110 Download center
Load to station .......................................... 25, 27 URL ................................................................ 10
Loading to PC ................................................. 29
Connecting a sub-stub to a loop E
FDnet/C-NET detector line .............................. 57 Error message
Connection to the station .................................. 21 'Topology is invalid' ....................................... 140
Connectivity .................................................... 21 Ethernet switch
Conversion ................................................... 110 IP address ................................................ 75, 78
Configuration ................................................ 110 Web interface ................................................. 77
Convert stubs into loops Ethernet switch (MM) ....................................... 71
FDnet/C-NET detector line .............................. 57 Event memory................................................. 95
CPU Expand
Updating the firmware ..................................... 99 FDnet/C-NET detector line .............................. 44
CPU (other) Site ................................................................. 41
Updating the firmware ................................... 108 External printer................................................ 92
Customer text ................................................. 36
151 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Index
F I
Factory setting ............................................... 142 I/O card (horn/monitored) FCI2009-A1................ 91
Fault indicators .............................................. 137 I/O card (remote transmission) FCI2007-A1 ........ 91
FCI2007-A1 I/O card (remote transmission) ........ 91 Indication of faults
FCI2009-A1 I/O card (horn / monitored) .............. 91 Component ................................................... 138
FDnet/C-NET detector line Initialize
Connecting a sub-stub to a loop ...................... 57 Station ............................................................ 25
Convert stubs into loops.................................. 57 Install
Expand ........................................................... 44 Detector line ................................................... 19
Removing a device (non-stationary) ................ 54 IP address
Removing a device (stationary) ....................... 47 Ethernet switch ......................................... 75, 78
Replacing a device with one of
a different type (non-stationary)....................... 50 L
Replacing a device with one of License ........................................................... 34
the same type (non-stationary) ........................ 49 Line
Replacing manual call points........................... 55 Auto-configuration........................................... 60
FDUL221 line tester Restart............................................................ 64
Updating the firmware ................................... 121 Line tester
FDUL221 serial line tester Updating the firmware ................................... 121
Updating the firmware ................................... 123 Load
FDUZ221 MCL-USB adapter From PC to station .................................... 25, 27
Updating the firmware ................................... 113 From station to PC .......................................... 29
Fire brigade periphery module FCI2001-D1 ......... 90 Load data to PC
Firewall Site ................................................................. 29
Safety module................................................. 82 Load data to the station
Windows 7 ...................................................... 22 Site ................................................................. 27
Windows firewall ....................................... 21, 96 Localization error ............................................. 70
Windows XP ................................................... 21
Floor repeater display M
Main CPU
Updating the firmware ................................... 116
Updating the firmware ..................................... 99
Floor repeater terminal
Maintenance ................................................. 128
Updating the firmware ................................... 114
MCL-USB adapter
FN2008 A1 ...................................................... 71
Updating the firmware ................................... 113
FN2009-A1...................................................... 82
Measuring instrument ..................................... 129
FN2012-A1
Merge
Integrated into station ..................................... 76
Sites ............................................................... 42
Standalone ..................................................... 74
Mimic display driver
FT2001-A1 mimic display driver
Updating the firmware ................................... 118
Updating the firmware ................................... 118
FT2010 floor repeater terminal N
Updating the firmware ................................... 114 Network cable
FT2011 floor repeater display Moving.......................................................... 138
Updating the firmware ................................... 116 Networked station ............................................ 40
FUJITSU DL3750+ ........................................... 92 Normal operation ............................................. 69
Function test..................................... 70, 133, 133
Fuse ............................................................... 29 O
Original language .............................................. 7
H
Hardware reset
Station .......................................................... 141
152 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Index
P Resetting
Password .................................. 99, 102, 108, 111 FN2012-A1 ..................................................... 81
PC Restart
Connect to station ........................................... 24 Detector line ................................................... 64
Disconnecting from station .............................. 24 FN2012-A1 ..................................................... 81
PMI Station .......................................................... 141
Fault indicators ............................................. 137
Power supply S
Safety module (firewall) .................................... 82
Configuring ..................................................... 36
Scalance X204 2 ............................................. 71
Testing ......................................................... 132
Serial line tester
Pre-configuration
Updating the firmware ................................... 123
Definition of terms ........................................... 32
Series number ................................................ 19
Preparation
Set parameter set
Station ............................................................ 58
Use Person Machine Interface ........................ 37
Preparation without BDV
Site
Station ............................................................ 59
Expand ........................................................... 41
Primary Setup Tool .......................................... 72
Load data to PC.............................................. 29
Printer
Load data to the station................................... 27
Testing ......................................................... 133
Merge ............................................................. 42
R Test intervals ................................................ 133
Radio gateway FDCW221 .............................. 120 Source language ............................................... 7
Updating the firmware ................................... 120 Spare parts ................................................... 136
Radio gateway FDCW241 .............................. 120 Standalone station ................................ 35, 38, 39
Updating the firmware ................................... 120 Start
Read in Detector line ................................................... 64
Definition of terms ........................................... 32 Station
Device ............................................................ 66 Auto-configure ................................................ 59
Remove Disconnect power ......................................... 135
Device ............................................................ 48 Factory setting .............................................. 142
Device (base without loop contact) .................. 51 Hardware reset ............................................. 141
Device (temporary) ......................................... 53 Initialize .......................................................... 25
Removing a device (non-stationary) Load data ....................................................... 25
FDnet/C-NET detector line .............................. 54 Mount and install............................................. 20
Removing a device (stationary) Preparation ..................................................... 58
FDnet/C-NET detector line .............................. 47 Preparation without BDV ................................. 59
Replace Resetting ...................................................... 142
Device (base without loop contact) .................. 51 Restart.......................................................... 141
Device (different types) ................................... 52 Switching off ................................................. 135
Device (stationary) .......................................... 46 Swapped
Replacing a device with one of Device .......................................................... 139
a different type (non-stationary) Switch off
FDnet/C-NET detector line .............................. 50 Detector line ................................................... 63
Replacing a device with one of Switching off
the same type (non-stationary)
Station .......................................................... 135
FDnet/C-NET detector line .............................. 49
Switching on
Replacing manual call points
Detector line ................................................... 64
FDnet/C-NET detector line .............................. 55
System data ................................................. 130
153 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Index
T
Test ........................................................ 70, 133
Test intervals .......................................... 133, 133
Test mode ....................................................... 68
Detector.......................................................... 68
Exit ................................................................. 69
Test unit........................................................ 129
Testing
Detector.................................................... 67, 67
Detector line ................................................... 19
Function ....................................................... 133
Power supply ................................................ 132
Printer........................................................... 133
System data ................................................. 130
Time / date .................................................... 138
Topology is invalid.......................................... 140
U
Uninstalling
Device ............................................................ 66
Update BDV .................................................. 109
Updating the firmware
Additional CPUs............................................ 108
Main CPU and additional CPUs ...................... 99
Peripheral devices ........................................ 112
Station ............................................................ 95
Upload ............................................................ 29
W
Web interface
Ethernet switch ............................................... 77
Windows 7
Firewall ........................................................... 22
Windows firewall ........................................ 21, 96
Windows XP
Firewall ........................................................... 21
Z
Zone
Switch off ........................................................ 63
Switching on ................................................... 64
154 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Index
155 | 156
Building Technologies A6V10210416_i_en_AU
Fire Safety 2015-12-15
Issued by © Siemens Switzerland Ltd, 2008
Siemens Switzerland Ltd
Building Technologies Division Technical specifications and availability subject to change without notice.
International Headquarters
Gubelstrasse 22
CH-6301 Zug
+41 41-724 24 24
www.siemens.com/buildingtechnologies