T-930 Ethernet Analog Input and Output Module

Technical Data

IMPORTANT

Please carefully read this manual before work on PLC.

Shut off the power before installation and wiring.

Check your wiring before power on .

The PLC must not be used in inflammable and explosive environment.

The power must be applied within the specified voltage.

NOTICE

1. The manual is subject to change without prior notice.

2. Do not hesitate to contact us if you discover any mistakes in this

manual or if having question.


T-930 以太网模拟量输入输出模块使用说明

1. Technical data of T-930

T-930 Programmable Controller is a product of TengCon Company’s T-900


series PLC ,It combines an ARM industrial CPU with a maximum frequency of
72MHz.an extended 32M SDRAM and a 4M FLASH, an embedded operating
system.a 2M user program memory and a 2M user data memory.Programming the
T-930 on KW Multiprog programming system and communicate via a Ethernet cable
make user’s programming very easy.Furthermore. T-930 also provide 2 RS232/485
interface.It provide the following input and output :16 analog inputs, 8 analog output,
24V DC input ,because of its flexibility ,T-930 can be applied in many small industrial
automation control applications .

1.1. T-930 Physical Feature

Dimension 169 x 134 x 63mm (W x H x D)


Weight 0.5Kg
Mount Standard rail or bolts
Working temperature From -40ºC to 85 ºC

北京腾控科技 http://www.tengcon.com 第 2 页
T-930 以太网模拟量输入输出模块使用说明

1.1. Power supply

Power Rated voltage 220V AC or 24VDC


supply Range From 90VAC to 250VAC or 24VDC
Rated current 40mA/220VAC(AO,24VOUT full load)
14mA/220VAC(AO,24VOUT full load)

Terminals POWER(L N )
Isolated Rated voltage 24VDC
power Rated current 0.2A
output Output resistance About 20 ohm
Terminals VOUT(24V+、24V-)

1.1. Communication

Ethernet 1 port RJ45, 10M/100M adaptive, MODBUS /TCP


protocol
At first start up,Set DIP ON with force the IP address
to the default 192.168.1.99,otherwise the configured
IP address is used.

RS232 1 port COM0:for internal test


RS232/4 2 port COM2/DB9 (2TXD、3RXD、5GND)232 direct
85 connect
COM1/DB9 RS485(pin 2 is B、pin 3 is A);default:
MODBUS RTU Slave baud rate :19200,1,8,E,address
is 1

DIP 8 bits Set DIP ON will force the IP address to the default
192.168.1.99

北京腾控科技 http://www.tengcon.com 第 3 页
T-930 以太网模拟量输入输出模块使用说明

Run/Stop 2 switches Run/Stop(in stop mode,only PLC program stopped)


switch
Commun 6 pcs indicator(flashing)、COM1 COM2 serial port
ication communication indicator(flashing when
indicator communicating)、LINK Ethernet linking indicator、
DATA Ethernet communicating indicator

1.1. Memory

User program memory size 2M Byte


User data memory 2M Byte
Back-up battery data 1K Byte
memory
Data back-up time 1Year

1.1. CPU Feature

CPU frequency 48MHz 72MHz for minimum


Minimum instruction processing time 4ms
INT and bit operation From1 to 4us
Floating-point algorithm About 40us
1ms timer quantity Unlimited
Clock Internal clock Back-up battery

1.2. I/O feature

Type Quantity Description


Built-in analog inputs 16 0-20mA of 0-5V
Built-in analog outputs 8 0-20mA or 0-10V
I/O state indicators 44 pcs Partly not in use

2. I/O Specifications

2.1. Analog input

The 16 analog inputs,each can configured to current input or voltage input via

北京腾控科技 http://www.tengcon.com 第 4 页
T-930 以太网模拟量输入输出模块使用说明

software configuration.An additional 16-bit ADC is used,CPU will pool the data
every 10ms .
Input signal 0-20mA in current 0-5V in voltage input
input
Input configuration Software configuration
Inputs 16
Terminals AI(AI01~AI08,3M;AI11~AI18,4M)
Input resistance About 250Ω About 200KΩ
Indicators The LED indicator light if the corresponding input
greater than low limit
No input:current input ,light on ;Voltage input,light
off.
Resolution 16-bit
Digital scope 0-20000
Conversion cycle 10ms

2.2. Analog output

The 8 analog outputs each can be configured to current 0-20mA or 0-10v


voltage output via software programming ,an additional 12-bit DAC chip is
used .In current output mode,the channel worked as a current source with
25KΩinternal resistance,in voltage output mode,as a voltage source with
180Ωinternal resistance.
Output signal 0-20mA in current output 0-10V in voltage output
Output configuration Voltage and current output single
Outputs 8
Terminals AO1(VO1、IO1,VO2、IO2,VO3、IO3,VO4、
IO4; M1)
AO2(VO5、IO5,VO6、IO6,VO7、IO7,VO8、

北京腾控科技 http://www.tengcon.com 第 5 页
T-930 以太网模拟量输入输出模块使用说明

IO8; M2)
Load Load R≤500Ω,Output Load R≥10kΩ,Output
resistance is about resistance is about 40Ω
25KΩ, Load voltage=output *R/
Load current=Output (R+45)
*25K /(R+25K)
Indicators The LED indicator light if the corresponding output
greater than low limit
Resolution 16-bit
Digital scope 0-20000
Conversion cycle 10ms
3. Register configuration and images
3.1. Input register definition
Function code: 04,totally 65535
Modbus PLC address Quantity Remark
address
30001-16 %IW64-66-- Built-in 16 analog inputs Full scale 20000
-94
300017-64 %IW96-98-- reserved
-190
3.2. Holding register definition
Function Code: 03/06,Totally 65535
Modbus PLC address Description Remark
address
40001-2 Not in use Default 0x55aa Must not be
changed !
40003 Not in use Version Code
40004-10 Not in use Real Clock Year-Month-Day-Hour
-Minute-Second-Week

北京腾控科技 http://www.tengcon.com 第 6 页
T-930 以太网模拟量输入输出模块使用说明

40011-42 totally 32 16-bit data,occupy 64 Byte and image to


%IB192~%IB255
40011-12 %ID192 Reserved
40013-14 %ID196 Reserved
40015-16 %ID200 Reserved
40017 %IW204 Reserved

40018 %IW206 Reserved


40019-20 %ID208 Reserved
40021-22 %ID212 Reserved
40023-24 %ID216 Reserved
40025 %IW220 DIP input value =DIP code
40026 %IW222 Run/Stop state =1 Run/=2 Stop
40027 %IW224 Serial port 1 , MODBUS Default 1
slave address
40028 %IW226 Serial port 2, MODBUS Default 1
slave address
40029 %IW228 Reserved
40030-42 %IW230-254 Reserved (13 pcs)
40043-74 totally 32 16-bit data,occupy 64 Byte and image to
%QB64~%QB127
40043 %QW64 Reserved
40044 %QW66 Reserved
40045 %QW68 Reserved
40046 %QW70 Reserved
40047 %QW72 Reserved
40048 %QW74 Reserved
40049 %QW76 Reserved
40050-52 %QW78-80-82 44 I/O state indicators =1 light on
40053 %QW84 Analog input low value 100
light on

北京腾控科技 http://www.tengcon.com 第 7 页
T-930 以太网模拟量输入输出模块使用说明

40054 %QW86 Analog input high value 20000


light flash
4055 %QW88 Analog output low value 100
light on
4056 %QW90 Analog output high value 20000
light flash
40057-64 %QW92-94--106 The 1st to 8th analog Analog output :
output value setting 0--20000
40065-74 %QW108-110--1 Reserved
26
40075-80 Not in use Reserved(6 pcs)
40081~84 Not in use IP address(4 pcs) Default
192.168.1.99
40085~88 Not in use Subnet mask (4 pcs) Default
255.255.255.0
40089~92 Not in use Broadcast address ( 4 Default
pcs) 192.168.1.255
40093~96 Not in use Gateway address (4 pcs) Default
192.168.1.254
40097~99 Not in use Reserved
40100 Not in use Serial port RS485 R/T Default =8
delay correct value
40101 Not in use Reserved
40102-103 Not in use Serial port 1 ,2 baud rate Set baud rate
set setting table
default 0xD007
40104 Not in use Reserved
40105 Not in use Analog input mode 1 : Voltage input
choice: (Default)
A bit corresponding to a 0:Current input

北京腾控科技 http://www.tengcon.com 第 8 页
T-930 以太网模拟量输入输出模块使用说明

channel
40106~121 Not in use The 1st to 16th analog input Corrected to
coefficient 20000
40122~137 Not in use The 1st to 8th analog output Zero offset :
coefficient About 0
proportionality
coefficient:about
20000
40129-999 Not in use Reserved
9
410001- %MW3.0- Intermediate variable 65535 Bytes
442768 %MW3.65534 image

460001- %MW3.100000- Intermediate variable 1948 bytes


460975 %MW3.101947 image
Save power-off

3.3. 波特率设置表:
Set point value
Baud
Odd Even Non
rate
HEX DEC HEX DEC HEX DEC
300 9001 36865 D001 53249 1001 4097
600 9002 36866 D002 53250 1002 4098
1200 9003 36867 D003 53251 1003 4099
2400 9004 36868 D004 53252 1004 4100
4800 9005 36869 D005 53253 1005 4101
9600 9006 36870 D006 53254 1006 4102
19200 9007 36871 D007 53255 1007 4103
38400 9008 36872 D008 53256 1008 4104
57600 9009 36873 D009 53257 1009 4105
115200 900A 36874 D00A 53258 100A 4106

北京腾控科技 http://www.tengcon.com 第 9 页
T-930 以太网模拟量输入输出模块使用说明

4. Dimension and electric wiring

4.1. Dimension

北京腾控科技 http://www.tengcon.com 第 10 页
T-930 以太网模拟量输入输出模块使用说明

4.2. Analog input wiring


(1)Two wire connection :

4.3. Voltage output wiring

北京腾控科技 http://www.tengcon.com 第 11 页
T-930 以太网模拟量输入输出模块使用说明

4.4. Current output wiring

5.Contact Us
Address:Room 312,Guangyuan Building ,Guangyuanzha No.5,Zuzhuyuan
Road,Haidian District,Beijing,P.R.C.
Telephone:008610-56790086
Fax:008610-6870-3551
Web:http://www.tengcon.com
Support:supprt@ tengcon.com
Sales: sales@ tengcon.com