Professional Documents
Culture Documents
Symmetra PX1 Basic Operation Guide 990-4104
Symmetra PX1 Basic Operation Guide 990-4104
Basic Operation Guide installation and maintenance of the UPS and batteries.
WARNING!
shooting. For advanced operation please refer to the Product Manual CD shipped with the unit,
or to our website www.apc.com.
WARNING!
Only trained persons familiar with the construction and operation of the
equipment, and the electrical and mechanical hazards involved, may install
3 System Components
and remove system components.
Intelligence
CAUTION!
Modules (2)
Read this important information.
Indicates that a switch or current protection
device is in the “ON” position.
Power Battery
Battery Units.
Module Module
• Battery Units do not contain serviceable parts. Do not open.
• Do not dispose Battery Units in a fire for they may explode. Do not mutilate Battery Units Bays
for released electrolyte may be toxic and is harmful to the skin and eyes.
• For configurations including customer-supplied external batteries, refer to manufacturer’s System
battery installation and maintenance instructions. Power
Supply
DC Disconnect Switch Cards
se P uide
e
uid
Card
tatra Tser PX
r X
rt M G
G
k-Se U M
uic m rt a T
U
Q m tatr
Syuickm-Se
Qm
Sy
UPS (empty) Switch Gear
600 lb. (275 kg) Monitor Card
POWER MODULE BATTERY MODULE
60 lb. (26 kg) 4 x 50 lb. (4 x 23 kg) Input / Output Chassis System ID Card
Display / Computer Battery Monitor Card
Interface Card
Documentation Storage Tray
UL
R
XR Comm Card Static Switch Module Figure 5
Figure 3 Figure 4
Figure 2
Basic Operation / Symmetra® PX 10-40 kW, 208 V Basic Operation / Symmetra® PX 10-40 kW, 208 V Basic Operation / Symmetra® PX 10-40 kW, 208 V
990-4104A rev 02 990-4104A rev 02 990-4104A rev 02
4 PowerView Display
Press Up and Down
Capacity: 40.0kVA
Fault Tolerance: n+1
Total UPS Modules: 05
Verify voltage on all phases:
1 Control
Status
Setup
Accessories
Logging
Display
Diags
Help
2 Input: 123.3V 59.9Hz
Output: 0.0V
Runtime: 0hr 0min
Load: A 0%VA
The PowerView is the Symmetra user control interface used to configure the functionality, 16 Batts, 00Bad Bad UPS Modules: 00 Top-Level Menu Status Screen
monitor the system, set alarm thresholds, and to provide audible and visual alarms. Figure 14
Battery Module Status Screen Power Module Status Screen
Low Batt Dur: 2min Low Batt Dur: 10min Set-up Functions
Liquid crystal Shutdwn Dly: 20sec Shutdwn Dly: 20sec Display parameters are set to factory defaults. To change these settings refer to Product Manual
Four LED indicators report display (LCD) Return Dly: 0sec Return Dly: 0sec CD.
the operational status of the Return Bat Cap: 0% Return Bat Cap: 0%
Symmetra. Changing factory default settings:
Five navigation keys are used to Shutdown Menu Shutdown Menu
select and open menu items, to Input Arrow
access information, change system
Figure 10 1 Control
Status
Logging
Display 2 Settings:
Shutdown
Alarms
Bypass
Setup Diags Defaults Copy
parameters, and to launch context- Accessories Help Output Freq Other
sensitive help.
5
Top-Level Menu Settings Menu
Figure 6 Figure 16
Basic Operation
Press ESC ESC until you get to the Top Level Status Screen, which provides you with basic
system status information.
Fuel 10%
Control Functions
Turn load on/off:
1 Turn Load On
Do Self Test
Simulate Power Fail
2 UPS LOAD IS OFF
6 Network Connection /
APC Web Management Card
Load 000% Graceful Reboot
120Vin 000Vout 60Hz Control Menu Load Off Screen
Runtime: 0hr 0m Figure 11
Link-R
X/TX
AP96
06 P
ower
Net
Netw
Press Enter to open the Top-Level Menu screen. This screen is the launching pad to Control Sub-Menu Bypassed Screen Figure 12 serial port ork A
dapt
er
Basic Operation / Symmetra® PX 10-40 kW, 208 V Basic Operation / Symmetra® PX 10-40 kW, 208 V Basic Operation / Symmetra® PX 10-40 kW, 208 V
990-4104A rev 02 990-4104A rev 02 990-4104A rev 02
From the PowerView Display: Threshold Alarm The Redundant Intelli- The main intelligence Replace the intelligence
gence Module is in control module has failed, and the module. Refer to Module
1 Control Logging
2 Web/SNMP Mngmnt Card Display Message Meaning Corrective Action
Status Display
Network Setup
redundant intelligence Replacement Section for
Setup Diags
Accessories Help View Network Setup Redundancy has been lost The Symmetra no longer Option #1: If possible, module is functioning as procedures.
Top-Level Menu Accessories Menu detects redundant power install additional power the primary intelligence
modules. Either power modules. module.
3 IP>>159.215.086.082
Mask>>255.255.255.000 4 IP>>159.215.086
Mask>>255.255.255.000 module(s) have failed, or Option #2: Decrease the
Gway>>159.215.086.001 Gway>>159.215.086.001
Accept changes Accept changes the load has increased. load
Network Set-up Screen Network Set-up Screen Figure 19 Option #3: Disable the If the problem persists, note UPS model #, serial #, and date purchased before
redundancy alarm by calling Tech Support at: 1 (800) 800 4272.
Note: If a Default Gateway is unavailable, use the IP address of a computer located on the setting redundancy to zero.
same subnet as the Management Card that is usually running. The Management Card uses the (Path: Startup-Setup- For advanced configuration, refer to
Default Gateway to test the network when traffic is very light. See “Watchdog Features” in Alarms-Redundancy-select Product Manual CD (shipped with unit) and/or our website @ www.apc.com.
the “Introduction” of the Network Management Card User’s Guide CD (.\doc\usrguide.pdf) zero)
for more information about the watchdog role of the Default Gateway. The Management
Card User’s Guide CD is located in the documentation tray. Runtime is below alarm
threshold
The predicted runtime is
lower than the user-speci-
fied minimum runtime
Option #1: Allow the
battery modules to
recharge.
8 Modular Component Replacement
7 Basic Troubleshooting
alarm threshold. Either the
battery capacity has
decreased, or the load has
increased.
Option #2: If possible,
increase the number of
battery modules.
Option #3: Decrease the
WARNING!
Only trained persons familiar with the construction and operation of the equipment,
and the electrical and mechanical hazards involved, may install and remove system
This Basic Troubleshooting section will allow you to solve most load. components.
problems using the PowerView display. Option #4: Use the display
to decrease the minimum
If a problem is reported, ensure that the system component in question is runtime alarm threshold Replacing Intelligence Modules
correctly installed (refer to Module Replacement, Section 8). (Path: Startup-Setup-
Alarms-Runtime-select). Loosen the 2 Phillips screws at both sides of the
module (top of module). Push down the small tab
General Status
on the left side of the module to de-activate the
Bypass module. Using the handle, carefully pull out the
Display Message Meaning Corrective Action
module. Reverse procedures for installation. Dis-
Display Message Meaning Corrective Action play shows message saying it has registered the
Input Freq outside config- The input frequency to the Option #1: Improve the
ured range Symmetra is outside the frequency of the incoming Bypass is not in range The frequency and/or Option #1: Decrease the new module.
configured range. The out- voltage. (either freq or voltage) voltage is out of acceptable sensitivity to input
put frequency will not Option #2: Widen range of range for bypass. This frequency. (Path: Startup-
synchronize with the input acceptable incoming One intelligence module can be replaced
message occurs when the Setup-OutputFreq-select).
frequency. Normal bypass frequency with the Power- without interrupting power to the connected
Symmetra is online, and Option #2: Correct input
equipment provided another functioning
is not available. View. (Path: Startup-Setup- indicates that the bypass voltage to provide
intelligence module is installed.
Output Freq Select. mode may not be available acceptable voltage and/or Figure 20
Option #3: Proceed with if required. frequency.
startup. Normal bypass is
not available. General Fault
AC adequate for UPS but The Symmetra will func- Option #1: Improve the
Display Message Meaning Corrective Action
not for bypass tion online with the input incoming voltage.
voltage, but in the event Option #2: Proceed with Need Bat Replacement One or more battery Refer to Module Replace-
that bypass is required, the startup. Normal bypass is modules are in need of ment Section for
input voltage is not not available. replacement procedures.
adequate to power the load
equipment.
Basic Operation / Symmetra® PX 10-40 kW, 208 V Basic Operation / Symmetra® PX 10-40 kW, 208 V Basic Operation / Symmetra® PX 10-40 kW, 208 V
990-4104A rev 02 990-4104A rev 02 990-4104A rev 02
Replacing Power Modules Replacing Cards Appendix A: Total Power OFF Procedure
Loosen the 2 Phillips screws at both sides of the
card. Carefully pull out the card. Reverse
procedures for installation. Display shows
message saying it has registered the new card.
1 To de-activate the module, turn Locking Set System Enable Switch
Latch (with arrow pointing towards the 1
module) counter-clockwise until it points
2 5th
Figure 23
to the STAND-BY Position
4th
downwards. 3rd
2nd
2 Unscrew spring-activated knobs on both 1st
id e
e
PXXu id
lock mechanism prevents the module from Set DC Disconnect to
rPGGu
2
raaUTTs M
seeMr
ettarrrtt U
being pulled clear of the UPS). With the mod- the OFF Position
m--SSetta
mickm
k
SSQQyyuumic
ule still resting in the UPS, release the lock by Part No Part No
pushing the black plastic tab on either side of 40kW Enclosure Only SYCF40KF Display and Computer SYCDCI
Figure 21
the module. Interface Card
3 Pull out the module. Reverse procedures 1 10kW Power Module SYPM10KF Battery Monitoring Card SYCBTMON
for installation. Display shows message saying 3 Figure 26
Battery Module SYBT4 Switch Gear Monitoring SYCSGMON
it has registered the new module.
Card
Basic Operation / Symmetra® PX 10-40 kW, 208 V Basic Operation / Symmetra® PX 10-40 kW, 208 V Basic Operation / Symmetra® PX 10-40 kW, 208 V
990-4104A rev 02 990-4104A rev 02 990-4104A rev 02