Assessing Maximum DG Penetration Levels in A Real Distribution Feeder by Using OpenDSS

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Assessing Maximum DG Penetration levels in a

Real Distribution Feeder by using OpenDSS


Paulo Radatz∗ , Nelson Kagan∗ , Celso Rocha∗ , Jeff Smith† , Roger C. Dugan†
∗ Electric
Energy and Automation Department
Polytechnic School of University of Sao Paulo, Sao Paulo, Brazil
Email: paulo.radatz@usp.br, nelsonk@pea.usp.br, celso.rocha@usp.br
† Electric Power Research Institute, Knoxville, TN 37932 USA

Email: jsmith@epri.com, rdugan@epri.com

Abstract—This paper presents an analysis of the voltage


regulation in a real feeder with Distributed Generation (DG)
for planning purposes. The original feeder has a wind turbine
connected and the study evaluated how the feeder’s voltage is
affected when a new turbine and a PV System are included
in the grid, for different levels of penetration. The distribution
system, the wind turbines and the PV System were modeled
using Open Distribution System Simulator (OpenDSS). Simula- Existing
tion results show that by using the daily simulation mode the Wind System
estimated permissible DG penetration level is higher than the
level evaluated when using the snapshot mode. In addition, if Substation
the volt-var control is considered in the PV System Inverter, the
permissible penetration level is even higher. Added
Index Terms—DER. OpenDSS. Smart Grid. Voltage Level. PV
Added
I. I NTRODUCTION Wind System

Planning and design of electric power systems have been


evolving around the world. On the one hand, there are increas-
ing environmental constraints that make large line construction
projects infeasible and add greater interest in renewable energy Fig. 1. Real Feeder with Distributed Generation
sources. On the other hand, advances in communication sys-
tems enhance the knowledge about the grid state, providing
the traditional ones, requires the use of distribution system
for better observability, with integrated use of its assets.
analysis tools capable to model all such new features.
In distribution systems, this concept can be considered
In this project, EPRI’s Open Distribution System Simulator
in the framework of Smart Grids. Although there is not a
(OpenDSS) was chosen to perform the simulations in order
consensus about its definition, some aspects are common
to analyze the impact of DG penetration in a feeder’s voltage
to many proposed Smart Grid architectures. They include
profile. Specifically, the real feeder already has a wind system
the use of Distributed Generation (DG) based on renewable
and the objective is to include a new wind system and also a
resources, energy storage, automated metering infrastructure
PV system, as shown in Fig. 1, such that the voltage profile
(AMI), automated fault location and automated restoration.
remains within acceptable levels.
Such technologies are supported by a high-speed communica-
tion to metering and control [1]. II. T HE O PEN DSS P ROGRAM
One of the major aspects refers to DG, including not only The OpenDSS is an open source, general-purpose
independent generation but also prosumers. In the past, the frequency-domain simulation engine that has special features
planning of distribution systems were based on keeping accept- for creating models of electric power distribution systems
able conditions during the peak demand. With the penetration and performing many types of analysis related to distribution
of distributed resources, including intermittent sources such planning and power quality. It has the capability of performing
as PV and wind power, the system must be analyzed and sequential-time power flow simulations, the ability to model
designed to dynamic conditions that may occur at any time either n-phase lines of arbitrary configurations and general n-
over the year. phase, m-winding transformers [1].
Besides that, many utility systems are not designed to
incorporate large DG penetration levels. There is an accep- A. PV System Model
tance by the industry that the system’s requirements must be The PV System model in OpenDSS combines a solar
altered. This new reality, with much more complex grids than PV array model with selected characteristics of the inverter

978-1-5090-3792-6/16/$31.00 2016
c IEEE 71
eff.
V1

Inductive Capacitive
100%

% Available vars
P V2 V3
Percent Voltage
Pmpp @ 1 kW/m² .
Temperature I 100%
V4
Base Irradiation 100%
dc .
V
Daily P ac P x eff.
Temperature(t)
Yearly Fig. 3. Volt-Var Curve
Irradiation(t)
Duty
One-Line System - High Side

Pmpp (T)

kV kvar PF Connection
T
Substation Transformer
Fig. 2. PV System Model LTC

typically needed for the assessment of distribution system A B C


impacts [2], such as efficiency curve, maximum power point
tracking (MPPT), cut-in/cut-out as function of dc voltage and
reactive power control. The latter can be set through the
InvControl element. The PV System and InvControl element Fig. 4. Substation Diagram
are described as follows:
1) PV System Element: The model basically injects an characteristic is symmetric, except for the fact that the reactive
active power, Pout , into the grid connection node. It is a power appears inductive. That is, the inverter starts to absorb
function of irradiation, temperature, inverter efficiency and reactive power.
the rated power at the maximum power point, Pmpp , which
is defined for a selected temperature, usually 25 ◦ C and an B. Wind System Model
irradiation of 1 kW/m2 . Fig. 2 shows its block diagram and Reference [4] presents the OpenDSS models for the four
Equation 1 provides Pout (t). main wind generator technologies. In this project, Double Fed
Induction Generator (DFIG) technology was utilized. DFIG
Pout (t) = P (t) × ef f (P (t)) (1) consists of a Wounded Rotor Induction Generator (WRIG)
and a back-to-back converter. The stator winding of a WRIG
Where
is directly connected to the grid, while the rotor winding is
2
P (t) = Pmpp (1kW/m )×irrad(t)×irradBase×Pmpp (T (t)) connected through a converter. The main advantage of this
technology is that real and reactive power can be decoupled,
And differently from the usual technologies, in which the machine
• P (t): Output power of the PV array at a specific time, t. absorbs reactive power to have its iron core magnetized.
2
• Pmpp (1kW/m ): Rated power at the maximum power Another important factor in this technology is that only a
point and a selected temperature. small portion of the power is delivered to the grid through the
• irrad(t): Per unit irradiation value at t. converter, usually around 30% of the total power delivered,
• irradBase: Base irradiation value for shape multipliers. which reduces the cost of the turbine.
• Pmpp (T (t)): Pmpp correction factor as function of the Finally, the back-to-back converter can be used to control
temperature at t. reactive power injected into the grid.
• ef f (P (t)): Inverter efficiency for a given P (t).
III. T HE R EAL S YSTEM
2) InvControl element’s VoltVar Function: The PVSystem
element can be controlled through the InvControl element. The real distribution system consists of a substation with
This element can set several inverter operation modes [3]. In three feeders. Fig. 4 illustrates the substation diagram where
this project, the volt-var mode was used in order to regulate feeder A, Fig. 1, is the object of study.
the feeder’s voltage. This mode follows the curve in Fig. 3. This section describes the distribution system modeling that
Below the voltage V1 , the inverter provides 100% of its uses data provided by a US utility, which were:
available reactive power. Between V1 and V2 , it provides • Feeder data in CYME format (host utility planning tool)
reactive power according to a decreasing ramp. A dead band • Transmission equivalent impedance on high-side of sub-
is defined between V2 and V3 . For voltages beyond V3 , the station transformer

72
TABLE I TABLE III
F EEDER ’ S DATA T RANSFORMER ANDLTC E QUIVALENT DATA

Parameter Quantity/Value Transformer Parameter Value


Lines 1187 Primary Voltage 138 kV
Fuse 105 Secondary Voltage 12.47 kV
Recloser 6 Rated Power 24 MVA
Switch 23 Primary Tap 131.1 kV
Non-controlled Capacitor Bank 1 Z 8.17 %
Controlled Capacitor Bank 2 X/R 15.86
Load 407 LTC Parameter Value
Total Load Rated Power 8435 kW
Rated Voltage 120.0 V
Transformers 3
Set Point 124.5 V
Wind Generator 1
Band 3V
Bus 1422
Delay 60 s
Section 1441

TABLE II feeder A were neglected and the active power for its consumers
T RANSMISSION E QUIVALENT DATA
were considered according to the Equation 2 and reactive
power of each customer is related to its own power factor,
Parameter Value
Positive Sequence Resistance 0.40 Ω
obtained from the feeder data in CYME. This equation is
Positive Sequence Reactance 3.79 Ω reasonable, once that the consumers of each feeder have the
Zero Sequence Resistance 1.45 Ω same nature.
Zero Sequence Reactance 6.21 Ω
PB (t) + PC (t)
PAN ew (t) = M aximum
(2)
PB + PCM aximum
• Substation transformer including its Load Tap Changer Where
(LTC) • PA
N ew
(t): Defined active power for loads in Feeder A, in
• Three capacitor banks pu, at a specific time, t.
• Technical information on the existing wind turbine • PB (t): Actual active power measured at the feeder’s B
• Active and reactive power measurements on each feeder head, at a specific time, t.
during one year • PC (t): Actual active power measured at the feeder’s C

A. Feeder modeling head, at a specific time, t.


M aximum
• PB : Maximum active power measured at the
The feeder data was converted from CYME format using a feeder’s B head.
converter written in the Python language. It includes all the • PC
M aximum
: Maximum active power measured at the
passive components in the system, such as lines, transformers, feeder’s C head.
capacitors and loads, as shown in Table I.
E. Wind System Modeling
B. Transmission Equivalent Model
For both existing and new wind systems, the technology
The transmission equivalent model was defined in OpenDSS DFIG was used. The wind turbine control method utilized was
directly from the data provided, as shown in Table II. the active power factor control, in which the power factor of
the wind system was regulated to be constant and equal to
C. Substation Transformer and its LTC
one. The study was performed defining three distinct values
The substation was modeled using a 138/12.47 kV trans- for their rated power.
former with its primary tap being fixed at the value of 0.95
pu and its secondary equipped with a LTC, as described in F. PV System Modeling
Table III. The PV system was also modeled with three distinct values
of rated power being defined on two control modes, one with
D. Load Modeling for Feeder A,B, and C
a unit power factor and the other with the volt-var inverter
Feeder loads were modeled as constant power loads. For the function.
feeders B and C, the load shape used were taken straight from
the data provided. However, for the consumers of feeder A, the IV. A PPROACH OF THE A NALYSIS
data provided was not the actual consumed active and reactive In order to perform the analysis there was a tradeoff
power, because of the existing wind turbine. In other words, between results accuracy and both simulation time and model
the data given for this feeder represents the difference between complexity. On one hand the power flow could be solved as
the consumed power and the generated power by the wind a time-series which provides more accurate results, but takes
turbine. Then, the active and reactive power measurements in a longer simulation time and also requires more information

73
Fig. 5. Load shape for the Loads in Feeder A Fig. 6. Load shape for Feeder A customers, Feeder B, and Feeder C in the
Selected Days

about the system such as load shapes, generation curves and


control functions. On the other hand, the power flow could be
solved as a snapshot which takes a shorter simulation time,
requires less information about the system, but it is likely to
give less accurate results than the times-series. In this sense,
the approach chosen was to compare the results for both of
such approaches by using the corresponding simulation mode
according to some criteria.

A. Load Shapes
As the goal was to evaluate voltage issues in feeder A, the
criteria was applied in the load shape defined by Equation 2,
shown in Fig. 5 for the whole year. To simplify the analysis,
only the load shape for two days were chosen according to
the criteria of maximum and minimum demand, which are Fig. 7. Irradiation and Output Power Curves for the Wind Systems
expected to be related to undervoltage and overvoltage issues,
respectively. The maximum demand criteria was basically
V. S IMULATIONS AND R ESULTS
to pick the day in which the highest absolute demand was
verified. The selected day was 08/26/2014, in which there A. Snapshot Simulation
was a demand of 1 pu at 4:15pm. This day was named as In the snapshot mode the power flow is calculated for a
workday. The minimum criteria was to select the day in which specific condition in time. For the simulations three variables
the lowest absolute demand was verified between 10am and were defined:
2pm. This interval was assumed, because it is likely that the • Feeder loading value, 2 options: workday (1 pu) or
peak PV system’s generation happens during this window and weekend (0.39 pu)
it is known that under these circumstances, the overvoltage • Wind System Power, 4 options: 0 , 0.9 MVA, 1.5 MVA,
problem is amplified. The selected day was 04/19/2015 in 2.25 MVA
which there was a demand of 0.39 pu at 10:30am. This day • PV System Power, 4 options: 0 , 1 MVA, 2 MVA, 3 MVA
was named as weekend. The load shape for the selected days Hence, two groups of 16 connections each were defined.
are shown in Fig. 6. The first group of connections corresponds to a heavy load
(workday) and the second group corresponds to a light load
B. Irradiation Curve and Output Power Curve of the Wind
(weekend). Besides that, a base case was defined considering
System
no extra DG connection. To analyze the influence of a high
Two typical irradiation curves and output power curve of DG penetration in the feeder, the simulations were performed
the wind system with a 1-s step size were defined. As for the fixing the capacitor banks control and the LTC control accord-
irradiation, one curve represents a sunny day and the other one ing to its state obtained from the base case, as shown in Table
a cloudy day. As for the wind system, one curve represents a IV. The idea was to evaluate the worst case, in which there is
day with high-speed winds and the other one a day with low a transition between a state with no prior DG connection to a
speed winds. The total four curves are shown in Fig. 7. state where the system has a maximum per unit DG penetration

74
TABLE IV TABLE VI
BASE C ASE E QUIPMENT S TATES S CENARIOS

Equipment State Options


Scenario
LTC 1 pu PV Wind Feeder Loading
Capacitor Bank 1 Off 1 Cloudy Low Workday
Capacitor Bank 2 Off 2 Cloudy Low Weekend
3 Cloudy High Workday
4 Cloudy High Weekend
TABLE V 5 Sunny Low Workday
S NAPSHOT S IMULATION R ESULTS FOR THE G ROUP WITH L IGHT L OAD 6 Sunny Low Weekend
7 Sunny High Workday
8 Sunny High Weekend
Options - Added MVA Voltage Violation with
Connection
Wind System PV System Fixed Controls
Base 0.0 0.0 -
2 0.9 0.0 No TABLE VII
3 0.0 1.0 No DAILY S IMULATION R ESULTS
4 0.9 1.0 Yes
5 1.5 0.0 Yes
6 1.5 1.0 Yes Scenario
7 0.0 2.0 Yes Connection Voltage Violation
1 2 3 4 5 6 7 8
8 0.9 2.0 Yes Base 3 3 3 3 - - - - No
9 1.5 2.0 Yes 2 3 3 3 3 - - - - No
10 2.25 0.0 Yes 3 3 3 3 3 3 3 3 3 No
11 2.25 1.0 Yes 4 3 3 3 3 3 3 3 3 No
12 2.25 2.0 Yes 5 3 3 3 3 - - - - No
13 0.0 3.0 Yes 6 3 3 3 3 3 3 3 : No
14 0.9 3.0 Yes 7 3 3 3 3 3 3 3 3 No
15 1.5 3.0 Yes 8 3 3 3 : 3 : 3 : No
16 2.25 3.0 Yes 9 3 : : : 3 : : : No
10 7 7 7 7 - - - - Yes
11 7 7 7 7 7 7 7 7 Yes
12 7 7 7 7 7 7 7 7 Yes
and the control elements such as LTC and capacitors bank 13 3 : 3 : 3 : 3 : No
cannot operate due to its inherent delay. In summary, this 14 3 : 3 : 3 : : : No
approach identifies the worst-case voltage response that could 15 7 7 7 7 7 7 7 7 Yes
16 7 7 7 7 7 7 7 7 Yes
occur prior to voltage regulation response mechanisms.
For the heavy load group, there was no violation in the
voltage levels. Then, for this simulation mode, only the results
of the light load group are presented, as shown in Table system, as shown in Table VI. The results for this simulation
V, where the last column shows whether there was voltage mode are shown in Table VII, where symbols stand for as
violation or not. follows:
• -: Scenario does not exist, because there is no PV system
B. Daily Simulation
installed
In the daily mode, the power flow is calculated for a 24 • 3: Scenario has been simulated and there is no voltage
hour period. In this case, a 1-s step size was considered. Then violation
for each simulation, a total number of 86,400 power flows • :: Scenario has been simulated and there is voltage
were performed. If voltage violations were detected, the volt- violation, but the voltage violation is solved when the
var inverter function was triggered to analyze improvements in volt-var function of the PV system’s inverter is used
the voltage levels. For the daily simulation case, five variables • 7: There is voltage violation even when the volt-var
were defined: function is used
• Feeder loading curves, 2 options: workday or weekend
• Wind System Power, 4 options: 0 , 0.9 MVA, 1.5 MVA, C. Results Analysis
2.25 MVA According to Table VII, one can notice that among the
• PV System Power, 4 options: 0 , 1 MVA, 2 MVA, 3 MVA connections that can be implemented without any voltage
• Output power curve of the wind system, 2 options: high violation, some of them do not require the volt-var inverter
speed or low speed winds function. Tables VIII and IX present the three highest penetra-
• Irradiation curve, 2 options: sunny or cloudy day tion levels without and with the volt-var function, respectively.
There are still 16 possible connections according to the It can be seen that the penetration level can be significantly
rated power of the wind system and the PV System. However, increased when this function is utilized. Moreover, one can
each of them has 8 scenarios according to the feeder loading, notice that the traditional undervoltage issue, which is likely
the irradiation curve, and the output power curve of the wind to happen during heavy loads can become an overvoltage issue,

75
TABLE VIII
M AXIMUM P ENETRATION L EVELS IN DAILY S IMULATION M ODE
WITHOUT VOLT-VAR

Connection Power MVA DERs


4 1.9 Both
5 1.5 Wind
7 2.0 Solar

TABLE IX
M AXIMUM P ENETRATION L EVELS IN DAILY S IMULATION M ODE WITH
VOLT-VAR

Connection Power MVA DERs


9 3.5 Both
13 3.0 Solar
14 3.9 Both

Fig. 8. Maximum ∆V
TABLE X
M AXIMUM P ENETRATION IN S NAPSHOT S IMULATION M ODE

Connection Power MVA DERs


In this study, the software OpenDSS was utilized to analyze
2 0.9 Wind the impact of a high DG penetration level in a real feeder. In
3 1.0 Solar the first moment, the snapshot simulation mode was utilized
which needs few variables to represent the system. In a second
moment, the daily simulation mode was utilized. In this mode,
as it can be seen in the daily mode results for the scenarios several variables are needed to model the system and the
1, 3, 5, and 7, in Table VII. analysis gets more complex.
However, it was seen that the results obtained through the
D. Two methods comparison daily mode are more reasonable than the obtained through
In order to compare the two simulation modes, a common the snapshot mode, allowing a higher DG penetration level
scenario is needed. That being said, the results for the snapshot in the grid. Moreover, when the volt-var inverter function is
mode is compared with the results of the daily mode in which considered, an even higher penetration level can be achieved.
the volt-var function was not considered. In Table VIII, it can Finally, one should notice that DG changes the traditional
be seen that utilizing the daily simulation mode, 2 MVA are undervoltage issues in the feeder to overvoltage issues. There-
allowed to be connected. However, with the static snapshot fore, planning studies should be altered accordingly. In other
simulation, only 1 MVA can be connected, as shown in Table words, the traditional practice of considering only the peak
X. This fact is reasonable, because the minimum demand and demand is not suitable to systems with high DG penetration
the maximum penetration levels are not necessarily coincident levels.
as assumed in the snapshot simulation mode. Furthermore, the
ACKNOWLEDGMENT
LTC control and the capacitors control were allowed to operate
in the daily simulation mode, differently from than snapshot The authors would like to thank First Energy Corp., Akron,
simulation, as explained in Section V-A. This fact is exposed Ohio USA, for providing the system’s model and data.
in Fig. 8, in which the maximum voltage difference in pu R EFERENCES
between each simulation and the base case is shown for each
[1] R. C. Dugan and T. E. McDermott, “An open source platform for
connection. For the daily mode, the worst case for overvoltage collaborating on smart grid research,” in 2011 IEEE Power and Energy
was considered, which is scenario 8. Society General Meeting, July 2011, pp. 1–7.
[2] EPRI, “Common functions for smart inverters, version 3,” EPRI, Palo
VI. C ONCLUSION Alto, CA, Tech. Rep. 3002002233, February 2014.
[3] W. Sunderman, R. C. Dugan, and J. Smith, “Open source modeling of
The Smart Grid concept aims to ensure a reliable supply advanced inverter functions for solar photovoltaic installations,” in 2014
of electricity in the future, the increase in DG penetration IEEE PES T D Conference and Exposition, April 2014, pp. 1–5.
levels and use of new equipment to support AMI and high- [4] P. Chirapongsananurak, S. Santoso, R. C. Dugan, and J. Smith, “Voltage
regulation in distribution circuits with wind power,” in 2012 IEEE Power
speed communication to metering and control, establishing, by and Energy Society General Meeting, July 2012, pp. 1–8.
consequence, a new scenario for electric distribution systems.
In this scenario, it is essential to utilize software tools
capable of modeling unbalanced networks and distributed gen-
eration and, furthermore, to perform the power flow calculation
in a period of analysis, e.g., one day.

76

You might also like