This document provides specifications for two 500 kVAr power factor correction units for Bahrain International Airport. The key details are:
1) The units will correct the power factor from 0.7 inductive to 0.9 capacitive.
2) They will be controlled automatically or manually via an intelligent microprocessor-based controller with Modbus RS485 communication.
3) Protection level will be at least IP 42 and capacitors can be switched in 1-99 seconds.
This document provides specifications for two 500 kVAr power factor correction units for Bahrain International Airport. The key details are:
1) The units will correct the power factor from 0.7 inductive to 0.9 capacitive.
2) They will be controlled automatically or manually via an intelligent microprocessor-based controller with Modbus RS485 communication.
3) Protection level will be at least IP 42 and capacitors can be switched in 1-99 seconds.
This document provides specifications for two 500 kVAr power factor correction units for Bahrain International Airport. The key details are:
1) The units will correct the power factor from 0.7 inductive to 0.9 capacitive.
2) They will be controlled automatically or manually via an intelligent microprocessor-based controller with Modbus RS485 communication.
3) Protection level will be at least IP 42 and capacitors can be switched in 1-99 seconds.
Client Bahrain Airport Company Division Oil, Gas & Petrochemicals-Dubai
Project No. 352911 / DP1115 Document No. 352911/DA3117 Project Title. Fuel Farm Complex and Fuel Hydrant at Bahrain International Airport Page 1 of 1 Rev. 02
1 Equipment tag No. BAC-FD-APFC-01 & 02 71 Manufacturer's country of origin *
2 Description Power Factor correction Unit 72 Make and Model Number * 3 Capacity 500 kVAr each - Note 2 73 Degree of protection * 4 Site Data Refer Datasheet : 352911 / DA0001 74 Paint shade and thickness * 5 Supply Parameter 400Vac 3 ph. 50Hz 75 Method of cooling * SPECIFICATION & GENERAL DATA
6 Supply voltage Variation +/- 6% 76 Maximum heat loss *
7 Frequency variation +/-2% 77 Mounting * 8 System Fault Level 65kA for 1 sec 78 Overall dimensions - length x Depth x Height * mm
VENDOR DATA - PANEL
9 System earthing Solidly earthed 79 Overall weight * kg 10 Space heater voltage / Cable Size 230 Volts, 50Hz, 1ph / 3C X 4mm² 80 weight of largest shipping section * kg 11 Aux power Supply 81 Dimensions of largest shipping section * mm 11a Incomer ACB closing, tripping, protection etc. 110V DC external 82 length x Depth x Height * mm 11b Contactor operation, space heater, lamp etc. 230V AC internal 83 Recommended clearance 12 Location Indoor - Substation building 84 Rear * mm 13 Area Classification/Gas Group Safe Area 85 Front * mm BS 5424, BS 1362, IEC61439, 86 Top * mm 19 Applicable standard IEC61869, IEC60529,IEC 60871, IEC 87 Cable entry * 60831, 88 Noise Level * 20 89 Bus bar dimensions & current rating * 21 90 Bus bar SC capacity and duration * 22 91 Bus Bar Material * 23 Number of capacitor Bank stages 92 Bus Bar size * 24 Type of control Contactor controlled 93 Earth bus bar size & current rating * 25 Control power supply 230V ac internal 94 Earth bus bar Material and location * 95 Intelligent type Microprocessor based 96 Manufacturer's country of origin * 26 APFC Unit controller with communication and 97 Make and Model Number *
VENDOR DATA - CAPACITOR BANK
Display- programmable at site 98 Design / Manufacturing standard * 27 Range of control 0.7 inductive to 0.9 capacitive 99 Overall rated output of capacitor bank * 28 Type of control Automatic and Manual 100 Number of stages * 29 Capacitor switching time adjustable from 1 to 99 sec 101 Rating of each stage * 30 Communication Protocol Modbus - RS485 102 Capacitance value of each capacitor element * 31 Degree of protection IP 42 minimum 103 Inrush current * 32 Type of Construction Compartmentalized 104 Dielectric losses - excluding losses of resistor * 33 Digital power factor meter Required 105 dielectric loss angle * CAPACITOR PANEL
34 Fault Indicator Required 106 Temperature rise *
No of step switched ON ; capacitive / 107 Minimum time between disconnection and reclosure * 35 LED indications inductive load; over temperature alarm 108 Insulation level ( peak/ RMS) * & trip etc. 109 Allowable overload * 36 Lamp test push button Required 110 111 Manufacturer's country of origin * incoming power ON, Abnormal power Make and Model Number 37 Potential free contacts for 112 * factor, over temp, over voltage 113 Control type and method * 38 Method of cooling Natural / Forced Air 114 Provision of Auto / Manual selection * 39 Access to Panel Front with no rear access 115 Manual On/Off provision for each bank * 40 Panel mounting Floor mounted 116 Target power factor setting (0.8 lag to unity) * 41 Floor fixing Integral base frame 117 First In - First Out facility * 42 Cable Entry Bottom 118 First In - last Out facility * 43 Paint shade RAL 7035 119 Display accuracy * 44 Bus Bar Material Electrolytic copper, PVC heat shrunk 120 Power factor Indication * 45 Gland Plate Removable type, 3 mm thick 121 No volt relay to trip all capacitor in event of power * 46 Power cable Type / Size Please refer cable schedule 122 failure 47 123 Protection functions * 48 124 Remote fault alarm * VENDOR DATA APFC UNIT
49 125 Communication protocol *
50 Type of Capacitor Dry self healing type 126 On/ Off indication for each bank * 51 Enclosure Galvanized steel 127 VA Burden CT/PT * 52 Capacitor bank connection Delta 128 Controller switching time * 53 Overall rating of capacitor Bank 500kVAr 129 Number of stages * CAPACITOR BANK
54 No & rating of each capacitor bank stage 8 / 12
55 Allowable tolerance on kVAr rating of capacitors As per IEC 60831 56 Discharge Resistor Required 57 Allowable residual voltage 50V 58 Time limit for arriving at residual voltage 10min (max) 59 Capacitor element protection internal fuse 60 series reactor Required - vendor to evaluate rating 61 62 63 Rating plate Required 64 Earthing bus bar & bosses Required DEVICES & ACC
65 Lifting lugs Required
66 Anti-condensation heater with thermostat Required 67 1-phase, 230V socket outlet Required 68 Panel illumination lamp Required 69 70 NOTES: 1. This data sheet should be used in conjunction with Engineering specifications of APFC unit ,LV Switchgears and Single Line diagram as applicable. 2. Equipment rating is indicative only, contractor to verify the same based on actual electrical load details and vendor data . 3. All components shall be as per approved vendor list of the project 4. * details shall be furnished by vendor 5. Type test certificates shall be provided for review and approval. 6. The cable size shall be as per approved cable schedule based on actual equipment rating and installation. 7. Factory and site acceptance test shall be ensured by contractor, In addition to third party inspection during FAT shall be arranged as minimum. 8. One year operating & commissioning spares shall be supplied. REV DATE DESCRIPTION ORIGNR CHKD APPD. 00 14/03/2016 Preliminary SW VT ADS 01 15/06/2016 For Approval SW VT ADS 02 02/08/2016 Issued for Tender SW VT ADS PLEASE NOTE: THIS DATASHEET SHOULD NOT BE USED FOR CONSTRUCTION OR FOR ORDERING MATERIALS UNTIL IT IS APPROVED.
P:\Dubai\ONG\DUO Sub Div\ProjDocs\2015\DP1115- BAC-Fuel Farm-BIA\ENGG\03_Electrical\Documents\Fuel Depot\Datasheets\02.08.2016\352911_DA3117-APFC Unit (01)