8.03 GTP - 11kV Indoor VCB
8.03 GTP - 11kV Indoor VCB
(To be filled up by the Manufacturer in Manufacturer’s Letterhead Pad, otherwise the bid shall be rejected)
Manufacturer's
NESCO's
Sl. No. Description Unit Guaranteed
Requirement
Particulars
1. Manufacturer's Name & Country of origin - To be
mentioned
2. Manufacturer's Model no. - To be
mentioned
3. System nominal voltage kV 11
4. Maximum System Voltage kV 12
5. Rated Frequency Hz 50
6. Rated normal current:
a) Incoming & bus Coupler for Power A 2000
Transformer (20/26.67 MVA)
b) Outgoing Feeder A 630
7. No. of phase nos. 3
8. No. of breaks per phase nos. To be
mentioned
9. Interrupting medium - Vacuum
10.1 Manufacturer's name of Vacuum - ABB/Siemens/
Interrupter GE/Schneider.
10.2 Manufacturer's name and country of To be
origin of Vacuum Interrupter mentioned
11. Manufacturer's model no. of vacuum - To be
interrupter (Model number must be same as mentioned
submitted type test report)
12. Power Frequency withstand voltage kV 28
13. Lightning Impulse withstand voltage on kVp 75
1.2/50 s wave
14. Emergency overload rating of normal at - To be
200C ambient mentioned
15. Duration in any 24 hrs. period - To be
mentioned
16. Busbar Scheme no. Single
17. Number of Busbar nos. 3
18. Temperature Rise of Busbar at rated 0C To be
current mentioned
19. Material of Busbar - Copper
20. Cross-section of Busbar mm2 To be
mentioned
21. Rated normal current of bus bar
20/26.67 MVA A 2500
22. Bus bar insulation material - To be
mentioned
586
590
Manufacturer's
NESCO's
Sl. No. Description Unit Guaranteed
Requirement
Particulars
81.7 Percentage of current setting at which relay % To be
will reset mentioned
81.8 Reset time after removal of 10 time CT rated
current for : To be
a) Phase element (100%) Sec mentioned
b) E/F element (40%) Sec To be
mentioned
81.9 Over & Under voltage Protection Yes
81.10 Frequency Protection Yes
81.11 Three phase Power measurement option Yes
81.12 Trip Relays(Separate trip relay shall be provided )
Manufacturer’s Name and Country To be mentioned
Manufacturer’s Model/type No. To be mentioned
Operating Times <10 ms
Self-reset type for O/C, E/F protection Yes
Design : modular Type To be mentioned
81.13 Trip Circuit Supervision Relay (Separate
relay shall be provided for each trip coil)
Manufacture’s name & country of relay To be
mentioned
Manufacture’s model no. To be
mentioned
82.0 SEPARATE STANDBY EARTH FAULT PROTECTION
82.1 Manufacture's name & country - ABB- (Sweden/
Switzerland/
Finland) /
Siemens-
(Germany)/
Alstom-
(France/UK)/
Schneider-
(France/UK) / SEL
USA.
82.2 Manufacture's model no. - To be
mentioned
82.3 Type of relay - Numerical
programmable
with all
necessary
features
82.4 Range of current setting :
a) Phase element (% of CT rating) % To be
b) Earth fault element (% of CT rating) % mentioned
To be
mentioned
82.5 Range of timing settings at 10 time CT rating Sec To be
mentioned
82.6 Burden of relay at 10 time CT rating VA To be
mentioned
591
Manufacturer's
NESCO's
Sl. No. Description Unit Guaranteed
Requirement
Particulars
82.7 Percentage of current setting at which relay % To be
will reset mentioned
592
82.8 Reset time after removal of 10 time CT
rated current for :
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec To be mentioned
83 Control Switch
Manufacture's Name & Country Shall be mentioned
Manufacture's Model/Type No. Shall be mentioned
Separate TNC/Discrepancy switch and Yes
Local Remote (L/R) selector switch
84 Annunciator
Manufacture's Name & Country Shall be mentioned
Manufacture's Model no. Shall be mentioned
Windows nos. 12
Built in buzzer and buttons for accept, Yes
mute, test, reset, etc.
B 11KV BUS COUPLER CUBICLES
85.0 OVER CURRENT AND EARTH FAULT PROTECTION WITH IDMT & INSTANTANEOUS FEATURES
85.1 Manufacture's name & country of relay - ABB- (Sweden/
Switzerland/
Finland) /Siemens-
(Germany)/
Alstom-
(France/ UK)/
Schneider-
(France/UK) /
SEL, USA
85.2 Manufacture's model no. - To be mentioned
85.3 Type of relay - Numerical
programmable
with all necessary
features
85.3 The Relay shall be IEC 61850 protocol Yes
type.
85.4 Range of current setting :
a) Phase element (% of CT rating) % To be mentioned
b) Earth fault element (% of CT rating) % To be mentioned
85.5 Range of timing settings at 10 time CT Sec To be mentioned
rating
85.6 Burden of relay at 10 time CT rating VA To be mentioned
85.7 Percentage of current setting at which relay % To be mentioned
will reset
85.8 Reset time after removal of 10 time CT rated
current for : Sec To be mentioned
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%)
85.9 Over & Under voltage Protection Yes
85.10 Auxiliary Voltage AC & DC V To be mentioned
86 Trip Relay (Separate trip relay shall be
provided )
Manufacturer’s Name and Country To be mentioned
Manufacturer’s Model/type No. To be mentioned
Operating Times ms <10
Self-reset type for O/C, E/F protection Yes
593
Design : modular Type To be mentioned
87 Trip Circuit Supervision Relay (Separate
relay shall be provided for each trip coil)
Manufacture’s name & country of relay To be mentioned
Manufacture’s model no. To be mentioned
88 Control Switch
Manufacture's Name & Country Shall be mentioned
Manufacture's Model/Type No. Shall be mentioned
Separate TNC/Discrepancy switch and Yes
Local Remote (L/R) selector switch
89 Annunciator
Manufacture's Name & Country Shall be mentioned
Manufacture's Model no. Shall be mentioned
Windows nos. 8
Built in buzzer and buttons for accept, Yes
mute, test, reset, etc.
C 11KV OUTGOING FEEDER CUBICLES
90.0 OVER CURRENT AND EARTH FAULT PROTECTION WITH IDMT & INSTANTANEOUS FEATURES
90.1 Manufacture's name & country of relay - ABB- (Sweden/
Switzerland/
Finland)/
Siemens (Germany)/
Alstom-(France/UK)/
Schneider-
(France/UK)/
SEL, USA
90.2 Manufacture's model no. - To be mentioned
90.3 Type of relay - Numerical
programmable
90.3. The Relay shall be IEC 61850 protocol Yes
type.
90.4 Range of current setting : To be mentioned
a) Phase element (% of CT rating) % To be mentioned
b) Earth fault element (% of CT rating) %
90.5 Range of timing settings at 10 time CT rating Sec To be mentioned
90.6 Burden of relay at 10 time CT rating VA To be mentioned
90.7 Percentage of current setting at which relay % To be mentioned
will reset
90.8 Reset time after removal of 10 time CT rated
current for : To be mentioned
a) Phase element (100%) Sec To be mentioned
b) E/F element (40%) Sec
90.9 Over & Under voltage Protection Yes
90.10 Frequecny Protection Yes
91 Trip relay (Separate relay shall be
provided )
Manufacturer’s Name and Country To be mentioned
Manufacturer’s Model/type No. To be mentioned
Operating Times <10
Self-reset type for O/C, E/F protection Yes
Design : modular Type To be mentioned
92 Trip Circuit Supervision Relay (Separate
relay shall be provided )
594
Manufacture’s name & country of relay To be mentioned
Manufacture’s model no. To be mentioned
93 Control Switch
Manufacture's Name & Country Shall be mentioned
Manufacture's Model/Type No. Shall be mentioned
Separate TNC/Discrepancy switch and Local Yes
Remote (L/R) selector switch
94 Annunciator
Manufacture's Name & Country Shall be mentioned
Manufacture's Model no. Shall be mentioned
Windows nos. 8
Built in buzzer and buttons for accept, mute, Yes
test, reset, etc.
D METERING AND INDICATION FOR TRANSFORMER 11KV INCOMING, 11KV BUS COUPLER AND
11KV OUTGOING FEEDER
95.0 Multi tariff programmable meter
95.1 Manufacture’s Name & Country Siemens (Germany/
Switzerland)/
ABB (Switzerland
/Finland)
AEG (Germany)/
Itron(USA)
/Elster
(USA/Romania)
/Landis+gyr,
(Switzerland/Greece
)
/Toshiba (Japan)/
Honeywell
(USA)/CEWE (UK)
95.2 Manufacture’s Model no. - To be mentioned
95.3 Type of meter - Numerical
Programmable
Multifunction
95.4 Class of accuracy - 0.2
96 Multifunction meter ( KW,KWH, KVARh, Voltage,current, PF)
Manufacturer’s Name and Country - Siemens, ABB, AEG,
Honeywel, CEWE
Manufacture’s Model no. - To be mentioned
Type of meter - Digital
Class of Accuracy - 0.5
Communication Protocol IEC-61850
97.0 INDICATION VOLT METERS & AMMETERS
Manufacturer’s Name and Country - To be mentioned
Manufacture’s Model no. - To be mentioned
Type of meter - Analogue/digital
Class of Accuracy - 1.0
98.0 VOLTMETER WITH SELECTOR SWITCH
595
Manufacturer’s Name and Country To be mentioned
Manufacture’s Model no. To be mentioned
Type of meter Analogue/digital
Class of Accuracy 1.0
99 For Bus Coupler Cubicle two voltmeters Yes
shall be fitted for bus-1 and bus-2
respectively.
100 Bus coupler panel will feed incoming 1 or 2 Yes
PT secondary output voltage to 11 kV
outgoing control Panel for measuring and
protection purpose automatically with
combination of magnetic contact and MCB .
101 11 kV pcm panel of transformer 11 kV Yes
incoming, outgoing feeder PT secondary
voltage supplied to relay must be feed by
MCB for short circuit protection.
102 Capacitive Voltage Divider (CVD) based Yes
Live Line Indicator (LLI) for each panel
103 The PCM Panel Shall be complied all the Yes
technical specification mentioned in
Section-7 and GTP no-8.11 & 8.13.