October 2018
00813-0100-2460, Rev BG
Transfers tank gauging data to Rosemount TankMaster™, Host and DCS systems
Serves up to 64 tanks
Enable other vendor emulation by bringing in data from Enraf®, GPE, Whessoe, L&J, or Varec® gauges
Rosemount 2460 October 2018
Modbus RTU RTU/TCP The system hub also supports connection of other tank gauging
instruments such as TankRadar™ Pro and TankRadar Rex gauges.
Ext. pwr
RS-232
USB
On - TERM - Off
Rx
Tx
Lo - GAIN - Hi
FBM 2180
Contents
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Product certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
2 Emerson.com/Rosemount
October 2018 Rosemount 2460
Rosemount TankRadar
Rosemount TankRadar
Rosemount 2180 Rosemount TankRadar
Rosemount TankRadar
Ext. pwr
RS-232
Ext. pwr
RS-232
USB
On - TERM - Off
Rx
Ext. pwr
Tx
Lo - GAIN - Hi
RS-232
USB
On - TERM - Off
Fieldbus Modems
Rx
Ext. pwr
Tx
Lo - GAIN - Hi
RS-232
USB
On - TERM - Off
Rx
Tx
Lo - GAIN - Hi
USB
On - TERM - Off
Rx
Tx
Lo - GAIN - Hi
FBM 2180
FBM 2180
FBM 2180
FBM 2180
Rosemount
2460
System Hubs
Emerson.com/Rosemount 3
Rosemount 2460 October 2018
Inventory calculation
Real-time inventory calculations include gross and net volumes
Level
as well as mass calculations, according to current API tables (6,
54, 24, 60, A-D) and ASTM D4311.
Tank Capacity Tables (5000 strapping points per tank/table) are
Tank Capacity supported for cylindrical and spherical tanks.
Table
Net Standard Volume can be calculated at a user-specified
reference temperature for specific tables.
Total Observed
Volume
Free
Water
Volume Gross Observed
Volume
Volume Volume
Correction
Factor,
Temperature CTPL (VCF)
T
Reference
Gross Standard
Volume
Sediment &
Water
Net Standard
Volume
4 Emerson.com/Rosemount
October 2018 Rosemount 2460
Ordering information
Table 1. Rosemount 2460 System Hub Ordering Information
Capacity(1)(2)
1 1-16 tanks
4 1-48 tanks
6 1-64 tanks
Firmware
S Standard
R Redundancy(3)
Modbus mapping
S Standard
P GPE (RS485)
4 RS485 Modbus
Emerson.com/Rosemount 5
Rosemount 2460 October 2018
R TRL2 Modbus
P GPE (RS485)
4 RS485 Modbus
R TRL2 Modbus
P GPE (RS485)
4 RS485 Modbus
R TRL2 Modbus
P GPE (RS485)
4 RS485 Modbus
6 Emerson.com/Rosemount
October 2018 Rosemount 2460
Emerson.com/Rosemount 7
Rosemount 2460 October 2018
M1 1 Modbus TCP client. Third party Modbus TCP client (not required for TankMaster).
M5 1-5 Modbus TCP clients. Third party Modbus TCP clients (not required for TankMaster).
Power supply
P 100-250 VAC 50/60 Hz, 24-48 VDC
0 None
Housing
A Aluminum (polyurethane-covered), IP 65
Cable/conduit connections
Includes:
• 2 pcs M25 plugs
G Metal cable glands (M20 x1.5 and M25 x1.5) • 7 pcs M20 plugs
• 2 pcs M25 glands
• 9 pcs M20 glands
Includes:
• 2 pcs M25 plugs
1 NPT adapters (½ -14 NPT and ¾ -14 NPT) • 7 pcs M20 plugs
• 2 pcs ¾-14 NPT adapters
• 9 pcs ½-14 NPT adapters
Includes:
2 Metal plugs (M20 x 1.5 and M25 x1.5) • 2 pcs M25 plugs
• 7 pcs M20 plugs
8 Emerson.com/Rosemount
October 2018 Rosemount 2460
Extra
0 None
Conformance certificate
Q1 Printed copy of certificate of conformance
Extended warranty(10)
WR3 3-year limited warranty
Emerson.com/Rosemount 9
Rosemount 2460 October 2018
Specifications
Communication/configuration specifications
Number of tanks Modem ports can be configured for either field or host
communication according to the model code. For more
Each Rosemount 2460 can be configured for up to 64 tanks. information, see Table 5 on page 12.
The actual number of tanks depends on the electrical interface
and field port configuration. For more information, see Hosts
Table 2.
See Table 3 on page 11 and Table 5 on page 12.
Note that each Rosemount 5900S Radar Level Gauge with 2-in-1
functionality corresponds to two tanks. Enraf emulation
Number of devices per field port Support for data polling of Enraf field devices.
Protocol:
Table 2 lists the maximum number of devices that can be
connected to each Rosemount 2460 field port. GPU
Examples of devices are Rosemount 2410, Rosemount
Electrical interface:
TankRadar Pro, and legacy devices, such as Rosemount
TankRadar Rex and Rosemount TankRadar TRL2. Enraf Bi-phase Mark
Table 2. Number of Devices Support for emulation of Enraf CIU 858 for connection to
existing host system or service/configuration tool.
Maximum number of devices
Interface
connected to each field port Protocol:
GPU
RS485 16
Electrical interface:
TRL2(1) 8
RS485
Enraf BPM 10
RS232
GPE 20 mA/RS485 10(2)
GPE emulation
Whessoe 20 mA/RS485 10(2)
Support for data polling of GPE field devices.
L&J 10(2)
Protocol:
Varec 10(2)
GPE
E+H NRF590 Tank Side
16(3) Electrical interface:
Monitor (TSM)
20 mA Digital Current Loop
1. Devices such as Rosemount 2410 Tank Hub, Rosemount TankRadar Rex,
Rosemount TankRadar Pro, TRL2 gauges, and DAU are supported. RS485
2. In certain situations, more than 10 devices may work. Contact Emerson™
Automation Solutions/Tank Gauging Service Department for advice. Whessoe emulation
3. Other devices using the Tank Side Monitor Modbus mapping are also
supported. Support for data polling of Whessoe field devices.
1. For more information, see Table 3 on page 11 and Table 4 on page 12.
2. For more information, see Table 6 on page 12.
10 Emerson.com/Rosemount
October 2018 Rosemount 2460
RS232 7-8
RS232 7
RS232 7
Emerson.com/Rosemount 11
Rosemount 2460 October 2018
L&J 1500 XL, MCG 2000 L&J Tankway L&J Tankway 300-4800
Ports 1 2 3 4 5 6 7 8
Alternative 6+2 (standard) Field Field Field Field Field Field Host Host
Port Port Port Port Port Port Port Port
Alternative 5+3 Field Field Field Field Field Host Host Host
Port Port Port Port Port Port Port Port
Alternative 4+4 Field Field Field Field Host Host Host Host
Port Port Port Port Port Port Port Port
USB 2.0(3) USB memory stick for logging diagnostic data (service purposes only)
1. When connecting the system hub to the local LAN network, make sure the connection is secure to prevent unauthorized access.
2. CAT 5 or 6 cable is recommended.
3. FAT32 file system.
12 Emerson.com/Rosemount
October 2018 Rosemount 2460
USB
RS232
Modem Modbus
DCS/Other hosts RTU/TCP
(TRL2, RS485, RS232)
Rosemount
2410 Tank Hub
TRL2,
Primary bus: RS485,
Field devices other vendors Field devices
Tankbus TRL2, RS485
TankMaster
Rosemount
2410 Tank Hub
Field devices
Tankbus
Emerson.com/Rosemount 13
Rosemount 2460 October 2018
Cable size
Additional specifications
Power: 0.75 to 2.1 mm² (18-14 AWG)
Bus: 0.5 to 2.5 mm² (20-14 AWG) depending on communication Metrology sealing possibility
interface
Yes
Built-in mains fuses
Write protection
T1.6 A
Yes, via software configuration and/or hardware switch.
Backup battery
3V CR 1632 lithium
Mechanical specifications
Housing material
Polyurethane-covered die-cast aluminum
Installation
Wall mounted by four screws. For more information, see
“Dimensional drawings” on page 16.
Weight
7 kg (15 lbs)
14 Emerson.com/Rosemount
October 2018 Rosemount 2460
Product certifications
Rev 3.1
Electromagnetic compatibility
compliance
FCC
This device complies with Part 15 of the FCC Rules.
Standards: FCC 47 CFR Part 15B,
15.107 Conducted emission class A,
15.109 Radiated Emission class A
Emerson.com/Rosemount 15
Rosemount 2460 October 2018
Dimensional drawings
Figure 3. Rosemount 2460 System Hub
158
(6.2)
246
265
(9.7)
(10.4)
348 (13.7)
16 Emerson.com/Rosemount
October 2018 Rosemount 2460
6.5 (0.3) x4
36
(1.4)
186 87
(7.3) (3.4)
12.5 (4.9) x4
465
(18.3)
374 (14.7)
Emerson.com/Rosemount 17
Rosemount 2460 Product Data Sheet
00813-0100-2460, Rev BG October 2018