Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

PT/VT Transformer

DATE 31/07/2021 PAGE 1

AMBIENT TEMP. 29,4 °C JOB # RUTIN

SUBSTATION GI BAWEN HUMIDITY 41 % ASSET ID UPT SALATIGA

POSITION BAY UNGARAN 1 TEST STATUS

EQUIPMENT LOCATION CVT PHASA R

MFR DATA ASSET PARAMETERS ASSET RATINGS


MFR PASSONI VILLA CLASS ACCURACY OIL VOL. 126 kg kV
CATALOG/STYLE C2VT 170/5 TYPE Other WEIGHT 440 kg BIL 750 kV
IMPEDANCE %
YEAR 1993 INSULATION TYPE Oil TANK TEMP. 27,5 °C
VA RATING
SERIAL NO. 87932
TEST CONDITIONS PRIMARY SECONDARY
SPECIAL ID TERTIARY
REASON Retest WEATHER

TRANSFORMER OVERALL TESTS

TEST INSULATION TEST TEST CONNECTIONS BUSHING TEST Cap. POWER FACTOR % DIRECT
NO. TESTED MODE kV (pF) IR
ENG GND GAR UST MEAS. 20º C CORR. mA Watts
1 GST-GND H1,H2 X1,Y1 10,00 5.051,76 0,37 0,28 0,755 15,843 0,5740 G

2 GSTg-R H1 X1,Y1 H2 0,755

3 GSTg-R H2 X1,Y1 H1 0,755

4 UST-R H1 X1,Y1 H2 o 0,755

5 UST-R H2 X1,Y1 H1 0,755

6 GST-GND H1,H2 X1,Y1 @2kV 0,755

SUPPLEMENTAL TESTS
TEST INSULATION TEST TEST CONNECTIONS (WINDINGS) TEST Cap. POWER FACTOR % DIRECT
NO. TESTED MODE kV (pF) IR
ENG GND GAR UST MEAS. 20º C CORR. mA Watts
7 UST-R H1,H2 Y1 X1 0,755

8 UST-B H1,H2 X1 Y1 0,755

9 GSTg-R H1 H2,X1,Y1 0,755

10 GSTg-R H2 H1,X1,Y1 0,755


TURNS RATIO TEST

47 kV REF [TTR] CAP (pF) REF [TTR] CAP DF/PF (%)

PHASE NAME
Label Winding Tested H Voltage L Voltage Calc. Ratio kV Cap. (pF) CAP DF/PF (%) Turns Ratio % Error Phase Error (min)
48

MULTIPLE QUICK TESTS

POWER FACTOR % DIRECT


TEST INSULATION TEST TEST Test L(H)
NO TESTED MODE SUPPRESS. kV Freq CAP.(pF) %VDF IR
MEAS. @ 20°C CORR. mA Watts

1 UST-R Freq Variation

COMMENTS: Ratio Core 1 = 6,72 V & Core 2 = 6,72 V


DEFICIENCIES:
PT/VT Transformer

DATE 31/07/2021 PAGE 1

AMBIENT TEMP. 29,1 °C JOB # RUTIN

SUBSTATION GI BAWEN HUMIDITY 41 % ASSET ID UPT SALATIGA

POSITION BAY UNGARAN 1 TEST STATUS

EQUIPMENT LOCATION CVT PHASA S

MFR DATA ASSET PARAMETERS ASSET RATINGS


MFR PASSONI VILLA CLASS ACCURACY OIL VOL. 126 kg kV
CATALOG/STYLE C2VT 170/5 TYPE Other WEIGHT 440 kg BIL 750 kV
IMPEDANCE %
YEAR 1993 INSULATION TYPE Oil TANK TEMP. 27,5 °C
VA RATING
SERIAL NO. 87953
TEST CONDITIONS PRIMARY SECONDARY
SPECIAL ID TERTIARY
REASON Retest WEATHER

TRANSFORMER OVERALL TESTS

TEST INSULATION TEST TEST CONNECTIONS BUSHING TEST Cap. POWER FACTOR % DIRECT
NO. TESTED MODE kV (pF) IR
ENG GND GAR UST MEAS. 20º C CORR. mA Watts
1 GST-GND H1,H2 X1,Y1 10,00 5.038,16 0,35 0,27 0,755 15,821 0,5525 G

2 GSTg-R H1 X1,Y1 H2 0,755

3 GSTg-R H2 X1,Y1 H1 0,755

4 UST-R H1 X1,Y1 H2 o 0,755

5 UST-R H2 X1,Y1 H1 0,755

6 GST-GND H1,H2 X1,Y1 @2kV 0,755

SUPPLEMENTAL TESTS
TEST INSULATION TEST TEST CONNECTIONS (WINDINGS) TEST Cap. POWER FACTOR % DIRECT
NO. TESTED MODE kV (pF) IR
ENG GND GAR UST MEAS. 20º C CORR. mA Watts
7 UST-R H1,H2 Y1 X1 0,755

8 UST-B H1,H2 X1 Y1 0,755

9 GSTg-R H1 H2,X1,Y1 0,755

10 GSTg-R H2 H1,X1,Y1 0,755


TURNS RATIO TEST

47 kV REF [TTR] CAP (pF) REF [TTR] CAP DF/PF (%)

PHASE NAME
Label Winding Tested H Voltage L Voltage Calc. Ratio kV Cap. (pF) CAP DF/PF (%) Turns Ratio % Error Phase Error (min)
48

MULTIPLE QUICK TESTS

POWER FACTOR % DIRECT


TEST INSULATION TEST TEST Test L(H)
NO TESTED MODE SUPPRESS. kV Freq CAP.(pF) %VDF IR
MEAS. @ 20°C CORR. mA Watts

1 UST-R Freq Variation

COMMENTS: Ratio Core 1 = 6,61 V & Core 2 = 6,61 V


DEFICIENCIES:
PT/VT Transformer

DATE 31/07/2021 PAGE 1

AMBIENT TEMP. 28,8 °C JOB # RUTIN

SUBSTATION GI BAWEN HUMIDITY 41 % ASSET ID UPT SALATIGA

POSITION BAY UNGARAN 1 TEST STATUS

EQUIPMENT LOCATION CVT PHASA T

MFR DATA ASSET PARAMETERS ASSET RATINGS


MFR PASSONI VILLA CLASS ACCURACY OIL VOL. 126 kg kV
CATALOG/STYLE C2VT 170/5 TYPE Other WEIGHT 440 kg BIL 750 kV
IMPEDANCE %
YEAR 1993 INSULATION TYPE Oil TANK TEMP. 27 °C
VA RATING
SERIAL NO. 87960
TEST CONDITIONS PRIMARY SECONDARY
SPECIAL ID TERTIARY
REASON Retest WEATHER

TRANSFORMER OVERALL TESTS

TEST INSULATION TEST TEST CONNECTIONS BUSHING TEST Cap. POWER FACTOR % DIRECT
NO. TESTED MODE kV (pF) IR
ENG GND GAR UST MEAS. 20º C CORR. mA Watts
1 GST-GND H1,H2 X1,Y1 10,00 5.052,27 0,38 0,29 0,770 15,834 0,5881 G

2 GSTg-R H1 X1,Y1 H2 0,770

3 GSTg-R H2 X1,Y1 H1 0,770

4 UST-R H1 X1,Y1 H2 o 0,770

5 UST-R H2 X1,Y1 H1 0,770

6 GST-GND H1,H2 X1,Y1 @2kV 0,770

SUPPLEMENTAL TESTS
TEST INSULATION TEST TEST CONNECTIONS (WINDINGS) TEST Cap. POWER FACTOR % DIRECT
NO. TESTED MODE kV (pF) IR
ENG GND GAR UST MEAS. 20º C CORR. mA Watts
7 UST-R H1,H2 Y1 X1 0,770

8 UST-B H1,H2 X1 Y1 0,770

9 GSTg-R H1 H2,X1,Y1 0,770

10 GSTg-R H2 H1,X1,Y1 0,770


TURNS RATIO TEST

47 kV REF [TTR] CAP (pF) REF [TTR] CAP DF/PF (%)

PHASE NAME
Label Winding Tested H Voltage L Voltage Calc. Ratio kV Cap. (pF) CAP DF/PF (%) Turns Ratio % Error Phase Error (min)
48

MULTIPLE QUICK TESTS

POWER FACTOR % DIRECT


TEST INSULATION TEST TEST Test L(H)
NO TESTED MODE SUPPRESS. kV Freq CAP.(pF) %VDF IR
MEAS. @ 20°C CORR. mA Watts

1 UST-R Freq Variation

COMMENTS: RATIO CORE 1 : 6.60 V, CORE 2 : 6.60 V


DEFICIENCIES: