PX033DA-1 + 1 x HCR43

Unit inlet air temperature 22.5 °C Sea level 0 m


Unit inlet air relative humidity 45.0 % Refrigerant R410A
Unit airflow 6857 m³/h Unit power supply 400 V/3 ph/50 Hz
ESP 50 Pa Compressor type scroll
Air flow configuration Downflow Up Expansion valve TXV

Unit performances
Unit PX033DA-1 + 1 x HCR43 Unit power input 10.73 kW
Net total cooling capacity 27.0 kW Unit Net Sens EER 2.43
Net sensible cooling capacity 26.1 kW Unit Net Total EER 2.52
nSHR 0.97 System power input 11.83 kW
Gross total cooling capacity 28.9 kW Internal filter class (EN16890 std) ePM10 50%
Gross sensible cooling capacity 28.0 kW Internal filter air pressure drop 127 Pa
Room SPL (@ 2m, f.f) 62.4 dB(A) Coil air pressure drop 104 Pa
Supply air temperature 11.0 °C Unit air pressure drop 496 Pa
Supply air relative humidity 91.5 % Width 844 mm
Depth 890 mm
Height 1970 mm
Condensing temperature 52.5 °C Weight 340 kg
Fans
Quantity 1 n° Operating Ampere 1 x 2.99 A
Fan modules Basic Full load Ampere 1 x 3.1 A
Power supply 400 V/3 ph/50 Hz Locked rotor Amp. 1 x 0.1 A
Power input 1 x 1.90 kW Room fan modulation (%) 100 %

Compressors
Type scroll Compressors COP 3.33
Power supply 400 V/3 ph/50 Hz Operating Ampere 1 x 16.41 A
Power input 1 x 8.80 kW Full load Ampere 1 x 21.6 A
Locked rotor Amp. 1 x 139.0 A
Relevant data for each condenser
Condenser model HCR43 Max outdoor SPL (@ 5m,f.f.) 53.0 dB(A)
Version Standard Actual outdoor SPL (@ 5m,f.f.) 53.0 dB(A)
Air discharge Vertical Power input 1.10 kW
Power supply 230 V/1 ph/50 Hz Full load Ampere 5.00 A
Variex Yes Locked rotor Amp. 9.60 A
Heat load 37.7 kW Width 2340 mm
Outdoor air temperature 40.0 °C Depth 1112 mm
Condenser airflow (@ max speed) 17000 m³/h Height 910 mm
Condenser actual airflow 17000 m³/h Weight 92 kg

Declared performances just for cooling units according to EN 14511. Products in accordance with the following
Directives:
2006/42/EC; 2014/30/EU;2014/35/EC; 2014/68/EU;
Cooling capacities are gross. To obtain the net cooling capacities the fan heat load must be subtracted

Issued by : EGPSAL023 Date : 5/9/2021 Page 1 of 1