Download as pdf or txt
Download as pdf or txt
You are on page 1of 361

Doc. No.: C0148.64-2.

41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 1 of 361

ENGINEERING, PROCUREMENT, CONSTRUCTION AND COMMISSIONING


OF KOC MOLTEN SULPHUR HANDLING FACILITIES AT KNPC MAA
REFINERY
CONTRACT CA/CPD/0148

CALCULATION REPORT FOR


NEW SUBSTATION BUILDING

C0148.64-2.41-680-B-E

0 08.Feb.2018 Issued for Construction PKK PKK SUS NK

C 20.Jan.2018 Re-Issued for Approval PKK PKK SUS NK

B 19.Nov.2017 Re-Issued for Approval PKK PKK SUS NK

A 03.Oct.2017 Revalidated & Issued for Approval PKK PKK SUS NK

ORIGINAL/
CHECKED REVIEWED APPROVED
REV. DATE DESCRIPTION REVISED
BY BY BY
BY

ENGINEERING, PROCUREMENT, CONSTRUCTION AND


COMMISSIONING OF KOC MOLTEN SULPHUR
HANDLING FACILITIES AT KNPC MAA REFINERY
CONTRACT CA/CPD/0148
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 2 of 361

SUMMARY OF DOCUMENT REVISIONS


Revision Sheet No Revised Revision Description
All Revalidated & Issued for Approval.
Beam design output pages reduced from 62 to 56 because of dummy
Sheet No. 04 of 275 beam design has been removed in STAAD input accordingly table
contents updated.
Dead load due to 200thk internal wall already considered in design and
Sheet No. 07 of 275
same has been included in load calculation page.
2
Live load on battery room 10kN/m already considered in design and
Sheet No. 07 of 275
same has been included in load calculation page.
Sliding FOS value 1.25 and buoyancy FOS value 1.5 has been
Sheet No. 13 of 275
updated as per design basis.
Sheet No.14 to 17 of 275 Structural framing plan sketches updated as per drawings.

Sheet No. 46 to 48 of 275 Seismic weight has been updated and diagram also got updated as per
STAAD output.

Sheet No. 49 to 50 of 275 Earth pressure calculation updated as per ground water table depth-
2.6m from GL.
Value of Lateral Blast load on roof girder has been changed from
83.7kN/m to 167.4kN/m, because blast lateral load on full wall surface
Sheet No. 51 to 58 of 275
will be applied on the blast side roof beam. Similarly STAAD load
diagram also got updated.
Seismic drift diagram and calculation got updated based on the STAAD
Sheet No. 59 to 60 of 275
output.
Sheet No. 61 to 62 of 275 Beam deflection check got updated based on the STAAD output.
Rev. A 1B3 beam detail removed and this beam no. not applicable for this
Sheet No. 71 of 275
building. Stirrup spacing of Beam 1B3a updated as per STAAD output.
STAAD out put for beam design has been updated based on the
Sheet No. 74 to 130 of 275
STAAD output and there is no change in beam size & reinforcement.
Column No. C1 & C2 updated as per design & drawing. STAAD out put
Sheet No. 131 to 136 of 275 for column design has been updated based on the STAAD output and
there is no change in column size & reinforcement.
STAAD out put for wall design has been updated based on the STAAD
Sheet No. 138 to 144 of 275
output and there is no change in wall size & reinforcement.
Foundation total restoring moment value in both X & Z direction &
Sheet No. 251 to 254 of 275 vertical load updated as per revised foundation overturning moment
calculation table in page no. 270.
Foundation member design related STAAD output values & diagram
Sheet No. 255 to 260 of 275
got updated as per STAAD output.
Foundation top layer reinforcement value and actual moment (Mu)
Sheet No. 263 of 275
updated in table as per design & drawing (i.e. Y16@200 to Y20@200).
Ground water available at the depth of 2.6m from GL hence buoyancy
Sheet No. 264 of 275
calculation performed for the basement portion and found its ok.
Sheet No. 266 to 269 of 275 STAAD input file updated as per final STAAD.
Support reaction and foundation restoring moment calculation updated
Sheet No. 270 to 273 of 275
as per STAAD reaction.
Sheet No. 274 to 275 of 275 Borehole information updated as per geotechnical report.
All Document section re-arranged as per KNPC comments and advice.
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 3 of 361

Sheet No. 5 of 350 Table of contents got updated.


Live load value changed to 20kN/m 2 for first floor level and 5kN/m 2 for
Sheet No. 8 of 350
basement floor level
Sheet No. 12 to 24 of 350 Detailed blast load calculation included in load calculation page.
Sheet No. 26 of 350 Sliding & overturning FOS for blast load case updated as per shell dep.
2
Live load of 20kN/m considered on the entire HVAC floor, the live load
Sheet No. 41 of 350 value will be more than the HVAC machine weight so load due to HVAC
machine shall be removed in document.
Sheet No. 42 to 45 of 350 Dead load - STAAD diagram got updated.
Sheet No. 46 of 350 Live load values got updated as per contract document
Sheet No. 46 to 48 of 350 Live load - STAAD diagram got updated.
Sheet No. 59 to 60 of 350 Seismic load - STAAD diagram got updated.
Lateral blast load applied on roof beam and grade beam as per blast
Sheet No. 63 to 70 of 350
calculation and STAAD blast load diagram got updated.
Sheet No. 71 of 350 Foundation support calculation for STAAD model included.
Rev. B
Sheet No. 72 to 76 of 350 STAAD input section added in section 3.3 and also STAAD input got
updated.
Sheet No. 78 of 350 Slab reinforcement got updated as per design calculation.
Sheet No. 79 to 91 of 350 Slab design revised as per blast load and modified live load.
Sheet No. 92 to 95 of 350 Beam reinforcement got updated as per design calculation.
Sheet No. 96 to 105 of 350 Critical beam deflection and crack width calculation included.
Sheet No. 106 to 162 of 350 STAAD output of beam design got updated.
Sheet No. 164 to 168 of 350 STAAD output of column design got updated.
Sheet No. 169 to 187 of 350 Wall horizontal reinforcement changed to 10 @ 200 c/c
Sheet No. 170 to 187 of 350 Wall displacement and design results updated.
Sheet No. 190 to 243 of 350 Foundation stability check and design got updated.
Member design for blast resistance analysis (dynamic analysis) section
Sheet No. 244 of 350
changed to 5.0.
Sheet No. 348 to 350 of 350 Borehole information got updated as per final Geotechnical report.

Sheet No. 7 of 361 Soil investigation report annexure reference included.

Dead load value break up for switchgear room, HVAC room, air lock
Sheet No. 7 to 8 of 361 & room, fire fighting room & battery room got updated. Relevant changes
Rev. C
Relevant sheets in STAAD input & output and design results of calculation got updated
due to the change in battery room dead load.
Allowable settlement for raft foundation also included in settlement
Sheet No. 26 of 361
section.
Basement level 200thk. base slab BS1 also included in STAAD model
for the raft element design and due to the inclusion of BS1 slab in
General STAAD model the subsequent changes in STAAD input & STAAD
output also got updated. BS1 slab design for STAAD FEM results also
included in foundation design section, refer page nos. 243 to 253.
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 4 of 361

Basement level base slab BS1 also included in STAAD model and for
self weight of 200thk slab automatically generated by STAAD self
Sheet No. 41 of 361 weight commands itself. Slab floor finish load of 0.4kN/m2 applied as
Rev. C pressure load in STAAD & accordingly STAAD diagram got updated.
Total DL applied as floor load in earlier Rev.B STAAD model.
2
Live load of 5.0kN/m for BS1 slab applied as pressure load in STAAD
Sheet No. 46 of 361 & accordingly STAAD diagram got updated. LL applied as floor load in
earlier Rev.B STAAD model.
Calculation of uplift due to ground water pressure for the basement
Sheet No. 61 of 361
level included and same shall be applied in STAAD.
Subgrade modulus for -4m level basement raft modified based on the
Sheet No. 71 of 361
raft type with 50mm settlement.
-4m level Basement portion base slab has been considered as varying
thickness raft foundation (600mm & 200mm) as in line with drawing and
for that raft foundation type the allowable settlement will be considered
as 50mm as per geotechnical report meanwhile the sub grade modulus
Sheet No. 78 of 361 value got changed based on the raft type with 50mm settlement, refer
page no.71. These Changes in plate mat subgrade modulus the design
moment for base slab BS1 got increased and accordingly the slab
reinforcement got increased to Y12@150 c/c bothways and the same
got updated in slab result table.
As per Shell DEP 34.17.10.30 Clause 4.4.2.g, the maximum spacing of
Sheet No. 78 to 86 of 361 roof slab reinforcement shall be limited to 150mm c/c and same shall
be updated in roof slabs RS1 & RS2 design and also in slab table.
Base slab BS1 design for the FEM results from STAAD model newly
Sheet No. 91 of 361 included in the foundation design section page nos. 243 to 253 and
also already available conservative design for BS1 two way slab
retained in page no. 91..
Basement level beam BG1 reinforcement got increased to 4-Y20 for
Sheet No. 92 of 361 the change in design moment in related changes of subgrade modulus
value.
Moment values in beam deflection & crack width calculation got
Sheet No. 96 to 105 of 361
updated.
For equivalent static blast load case the structure Sway check has
Sheet No. 173 of 361
been included.

Sheet No. 169, 175 to 180 of As per Shell DEP 34.17.10.30 Clause 4.4.2.g, the maximum spacing of
wall reinforcement shall be limited to 150mm c/c and same shall be
361
updated in wall W1 design and also in wall result table.
Foundation design calculation got updated due to the changes in plate
design moment and shear stress for the raft subgrade modulus change
and also top layer reinforcement for -4m level raft got increased from
Sheet No. 189 to 253 of 361 Y12@200 to Y12@150 in bothways. BS1 slab design also included in
foundation design section. Foundation result table got updated.
Foundation static check base reaction, overturning and uplift
calculation also got updated due to the changes in support reaction.
Sheet No. 196 of 361 Foundation settlement check has been provided and found its ok.
Sheet No. 361 of 361 SBC report for raft foundation also included in appendix 6.1.
Rev. 0 - As per KNPC approved vide Tr. No. KNPC/GSC-HO/KMS/T-18-1515
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 5 of 361

TABLE OF CONTENTS
1 DESIGN CRITERIA 6

2 STRUCTURAL FRAMING SKETCH 27

3 STAAD MODEL & INPUT 31


3.1 Structural Model for Beam & Node Number 32
3.2 Loading Summary for Stress Analysis 41
3.3 Foundation Support Condition 71
3.4 STAAD Input 72

4 MEMBER DESIGN FOR STATIC ANALYSIS 77


4.1 Design of Slab 78
4.2 Design of Beam & Girder 92
4.3 Design of Column 163
4.4 Design of Wall 169
4.5 Design of Foundation 188

5 MEMBER DESIGN FOR BLAST RESISTANCE ANALYSIS (DYNAMIC ANALYSIS) 254

6 APPENDIX 358
6.1 Geotechnical Investigation Report 358
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 6 of 361

1. DESIGN CRITERIA
1.1 SCOPE
These design criteria contain the general criteria and methods of calculation to be applied
for the design of New Substation for KOC Molten Sulphur Handling Facilities Project At
MAA Refinery

1.2 DESIGN CODE


1) ACI 318-08 : American Concrete Institute
Building Code Requirements for Structural
Concrete and Commentary
2) ASCE 7-10 : American Society of Civil Engineers.
Minimum Design Loads for Buildings and other
Structures.
3) KNPC DEPs
DEP 34.00.01.30: Structural Design and Engineering
DEP 34.11.00.12: Geotechnical and Foundation Engineering - Onshore
DEP 34.17.00.32: Design and Engineering of Buildings
DEP 34.17.10.30: Design of Blast Resistant Onshore Buildings, Control
Rooms and Field Auxiliary Rooms
DEP 34.19.20.31: Reinforced Concrete Structures
4) KNPC Variations to Shell DEPs
5) KNPC Standards

1.3 REFERENCE
1) Geotechnical Investigation Report
2) Foundation Analysis and Design (Joseph. E. Bowels)
3) Principles of Geotechnical Engineering (Braja. M. Das)

1.4 UNIT OF MEASUREMENT


The SI and Metric units shall be used:
Force : kN (kgf)
Length : Meter
Temperature : Degree (Centigrade)

1.5 STRENGTH OF MATERIAL


1) Concrete
(1) Cement Type
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 7 of 361

ASTM C150 (Type-V) or equivalent


(2) Specified Cylinder Compressive Strength at 28 Days
f'c = 35 MPa (350 kgf/cm2 ) for Structural members
f'c = 20 MPa (200 kgf/cm2 ) for Lean Concrete
(3) Unit Weight for Reinforced Concrete
W c = 25 kN/m3 (2.5 t/m3)
(4) Modulus of Elasticity
Ec = 4700*(f c)0.5 for normal weight concrete (in MPa)
(5) Poisson's Ratio
= 0.18
2) Reinforced Bar
Deformed Bar : ASTM A615/A615M(Grade 60) or approved equivalent
(1) Specified Yield Strength
fy = 414 MPa (4,200 kgf/cm2 )
(2) Modulus of Elasticity
Es = 200,000 MPa (2.0x106 kgf/cm2)

1.6 SOIL CONDITION


The following values are assumed.
1) t = 17 kN/m3 (=1.7 tf/m3)
2) sub = 7 kN/m3 (=0.7 tf/m3)
3) Ground Water Level : 2.6m from Ground level
4) Allowable Soil Bearing Capacity (Refer Annexure 6.1)
5)

1.7 DESIGN LOADS


1) Dead Loads
Dead loads are the actual weight of materials forming the structure, foundation, and
all permanently attached appurtenances (e.g. lighting, HVAC, insulation, finishes,
Internal walls).
Concrete Slab Roof
Thk.40 Bed Mortar 0.80 kN /m2
Thk.0.15 P.E Film & Thk.50 Rigid Insulation 0.30 kN /m 2
Thk.4 Bituminous Waterproofing Membrane & Primer 0.20 kN /m2
Thk.25(min.) Leveling Screed for Slope 2.27 kN /m2
Thk.180 Concrete Slab 4.50 kN /m2
Ceiling & Service (HVAC duct + small electrical conduit) 0.45 kN /m2

8.52 kN /m2

Finish Floor on Concrete Slab (Ground Floor) Switch gear room


Electrical cable support + hardener (micron mm thick) 0.40 kN /m2
2
Thk. 180 Concrete 4.50 kN / m
2
4.90 kN /m
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 8 of 361

Finish Floor on Concrete Slab (Ground Floor) HVAC room, fire fighting room & air lock
Hardener Finish (micron mm thick) 0.40 kN /m2 (Conservative)
Thk. 180 Concrete 4.50 kN / m 2

4.90 kN /m2
Finish Floor on Concrete Slab (Ground Floor) Battery room
Thk. 50 Leveling Mortar 1.00 kN / m2
Alkaline Resistant tiles W/Bed Mortar 0.80 kN / m 2
Thk. 180 Concrete 4.50 kN / m 2

6.30 kN / m2
Finish Floor on Concrete Slab (Basement Floor)
Cement Plaster w/ Liquid Waterproofing 0.40 kN / m 2
Thk. 200 Concrete (modeled & self weight assigned in STAAD)
5.00 kN / m2

5.40 kN /m2
Concrete Block Wall (thk.=200)
Thk.200 Concrete Block (Including finishing) 3.80 kN / m2

3.80 kN /m2
Concrete Block Wall (thk.=100)
Thk.100 Concrete Block 1.80 kN / m 2

1.80 kN /m2
Concrete Wall (thk.=250)+Concrete Block (thk.=100)
Concrete Wall (thk.=250) (modeled & self weight assigned in STAAD)
6.25 kN / m2
Thk.50 Insulation 0.20 kN / m 2
Thk.100 Concrete Block 1.80 kN / m 2

8.25 kN /m2
Parapet (thk.=150)
Thk.150 Concrete Wall 3.75 kN / m 2
2

2) Live Loads
Live Loads shall be defined as the weight of all movable loads including personnel,
tools, miscellaneous equipment, movable partitions, parts of dismantled equipment,
panels and stored material.
Live Loads shall be in accordance with DEP 34.00.01.30 as specified below:
Uniform
Category Concentrated Load
Load
2 kN for roof
Roofs accessible for inspection and repair 1 kN/m2
members

For buildings, live loads shall be in accordance with DEP 34.17.00.32 & contract
document:
Category Uniform Load
Switch Room, Air Lock, Battery Room, F/F Room, HVAC 20 kN/m2
Battery Room 20 kN/m2
Cable cellar room 5 kN/m2
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 9 of 361

3) Wind Loads
Wind Loads for Buildings of Any Height
Wind loads shall be calculated based on ASCE 7-10 Section 27.4.1:
F = [q x G x Cp - qi x GCpi] x Af
q : qz for windward walls evaluated at height z above the ground
: qh for leeward walls, side walls, and roofs, evaluated at height h
qi : qh for windward walls, side walls, leeward walls, and roofs of enclosed
buildings and for negative and positive internal pressure evaluation in
partially enclosed buildings
G : Gust effect factor from Section 26.9
(For rigid structures, 0.85 or calculated in accordance with Section 26.9)
Cp : External pressure coefficient from Fig. 27.4-1
GCpi : Internal pressure coefficient from Table 26.11-1
2
Af : Projected area normal to the wind, m
Velocity pressure, qz
qz 0.613K z K zt KdV 2 I ( N / m2 )
Kz = Velocity pressure exposure coefficient (Section 27.3.1)
Kzt = Topographic factor, not less than 1.0 (Section 26.8.2)
= 1.0
Kd = Wind directionality factor (Section 26.6)
I = Importance factor (ASCE 7-05 Table 6-1)
= 1.15 of importance shall be applied for this project in order to consider
Occupancy Category in the resulting load
V = Basic wind speed in m/sec
= 45m/s(from KNPC Standard 40A1) * (1.6)0.5 (to convert to ultimate wind
speed)
= 56.921m/s
(Risk Category : III (Table 1.5-1) , Exposure : C (KNPC Standard 40A1)

ASCE 7-10 Fig. 27.4-1


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 10 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 11 of 361

ASCE 7-10 Table 26.11-

4) Earthquake Load
Earthquake loading shall be considered in accordance to IBC 2009 with the
following parameters (taken from KNPC variations to shell DEP)
Peak Ground Acceleration for MCE SPGA = 0.15g
Short-period Acceleration for MCE SS = 0.32g
One-second Acceleration for MCE S1 = 0.13g
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 12 of 361

n-value for MCE n = 0.45


Site Class = C
Site Coefficient Fa = 1.27 , Fv = 1.67
(SMS = Fa Ss = 0.41g S M1 = Fv S1 = 0.22g)

5) Earth/Water Pressure
Earth and hydrostatic water pressures on retaining walls and underground
structures shall be determined.

6) Blast Load
Blast Load shall be the commonly used criteria as mentioned in the ASCE report
which is defined as:
(1) high pressure short duration triangular shock loading Side-on overpressure of
10 psi (69kPa) with a duration of 20 milliseconds and
(2) low pressure long duration, triangular loading Side-on overpressure of 3 psi
(21kPa) with a duration of 100 milliseconds.

Lateral blast pressure on front wall - Peak Side-on Overpressure & Duration: 69kPa / 20ms

(Reference with ASCE


guidelines)

Reflected over pressure on front wall Pr = 172.8 kpa (69 kpa/20m/s)

Vertical blast pressure on roof slab - Peak Side-on Overpressure & Duration: 69kPa / 20ms

Equivalent peak over pressure on roof slab Pr = 62.91 kpa (69 kpa/20m/s)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 13 of 361

Lateral pressure on front wall - Peak Side-on Overpressure & Duration : 21kPa / 100ms

(Reference with ASCE


guidelines)

Reflected over pressure on front wall Pr = 45.2 kpa (21 kpa/100m/s)

Equivalent peak over pressure on roof slab Pr = 20.44 kpa (21 kpa/100m/s)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 14 of 361

Design data for blast load calculation (as per ASCE guidelines)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 15 of 361

Lateral direction member Resistance/capacity calculation for front wall (Front wall will be
analysed as a oneway beams pinned at both ends) (at grade and roof level)-For all
direction of blast application

(ASCE Table 6.1)

Wall lateral load capacity Ru = 167.4 kN

Resistance calculation of Roof diaphragm for inplane loads (Applied to long side of
building)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 16 of 361

(ASCE Table 6.2)

(ACI318 Section 11.6.4.3)

Roof diaphram lateral load capacity (longer) Ru = 2 x 13928 = 27856 kN


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 17 of 361

Resistance calculation of roof diaphragm fo inplane loads (Applied to short side of


building)

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 18 of 361

(ACI318 Section 11.6.4.3)

Roof diaphram lateral load capacity (shorter) Ru = 2 x 14164 = 28328 kN

Resistance calculation of Shear wall for inplane loads (Applied to long side of building)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 19 of 361

(ACI318 Section 11.6.4.3)

Shear wall lateral load capacity (longer)Ru = 2 x 7131 = 14262 kN

Resistance calculation of Shear wall for inplane loads (Applied to short side of building)

Shear wall lateral load capacity (longer)Ru = 2 x 7252 = 14504 kN


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 20 of 361

Resistance calculation of Roof slab 3m span (Out of plane loads Roof will be
analysed as a one way beam fixed at both ends)

(ASCE Table 6.2)

Roof slab out of plane capacity (longer)Ru = 147.4 kN

Resistance calculation of Roof beam RB1 (Out of plane loads beam fixed at both ends)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 21 of 361

(ASCE Table 6.2)

Roof beam RB1 out of plane


capacity (downward & upward)

Resistance calculation of Roof beam RG2 (Out of plane loads beam fixed at both
ends)

(ASCE Table 6.2)

Roof girder RG2 out of plane


capacity (downward & upward)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 22 of 361

Resistance calculation of Column C1 (Out of plane loads beam fixed at both ends)

Column C1 capacity (downward &


upward)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 23 of 361

Blast Load Applied to Long Side of Building Z direction

Lateral load on front wall


Vertical load on roof (downward)
Vertical load on roof (upward)

Blast Load Applied to Short Side of Building X direction


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 24 of 361

Lateral load on front wall


Vertical load on roof (downward)
Vertical load on roof (upward)

1.8 LOAD COMBINATIONS


1) Ultimate Stress Design (For Concrete Design)
Case Load Combinations
U = 1.4DL
U = 1.2DL + 1.6LL
U = 0.9DL + 1.0WxL
U = 0.9DL + 1.0WzL
U = 0.9DL - 1.0WxL
U = 0.9DL - 1.0WzL
U = 0.9DL + 1.0ExL
U = 0.9DL + 1.0EzL
U = 0.9DL - 1.0ExL
Normal
U = 0.9DL - 1.0EzL
Operation
U = 1.2DL + 1.0LL + 1.0WxL
U = 1.2DL + 1.0LL + 1.0WzL
U = 1.2DL + 1.0LL - 1.0WxL
U = 1.2DL + 1.0LL - 1.0WzL
U = 1.2DL + 1.0LL + 1.0ExL
U = 1.2DL + 1.0LL + 1.0EzL
U = 1.2DL + 1.0LL - 1.0ExL
U = 1.2DL + 1.0LL - 1.0EzL
U = 1.2DL + 1.6LL + 1.6HL
U = DL + BxcL
U = DL + BxtL
U = DL - BxcL
U = DL - BxtL
Blast
U = DL + BzcL
U = DL + BztL
U = DL - BzcL
U = DL - BztL
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 25 of 361

2) Allowable Stress Design (Steel Structure, Soil Pressure)


Soil bearing
Case Load Combinations increase
factor
U = 1.0DL
U = 1.0DL + 1.0LL
U = 1.0DL + 0.6WxL
U = 1.0DL + 0.6WzL
U = 1.0DL - 0.6WxL
U = 1.0DL - 0.6WzL
U = 1.0DL + 0.7ExL
U = 1.0DL + 0.7EzL
U = 1.0DL - 0.7ExL
Normal
U = 1.0DL - 0.7EzL 1.0
Operation
U = 1.0DL + 0.75LL + 0.45WxL
U = 1.0DL + 0.75LL + 0.45WzL
U = 1.0DL + 0.75LL - 0.45WxL
U = 1.0DL + 0.75LL - 0.45WzL
U = 1.0DL + 0.75LL + 0.525ExL
U = 1.0DL + 0.75LL + 0.525EzL
U = 1.0DL + 0.75LL - 0.525ExL
U = 1.0DL + 0.75LL - 0.525EzL
U = 1.0DL + 0.75LL + 1.0HL
U = DL + BxcL
U = DL + BxtL
U = DL - BxcL
U = DL - BxtL
Blast 2.5
U = DL + BzcL
U = DL + BztL
U = DL - BzcL
U = DL - BztL
Where, DL : Dead Load, LL : Live Load, WxL : X-directional Wind Load, WzL : Z-
directional Wind Load, ExL: X-directional Earthquake Load, EzL: Z-directional
Earthquake Load , HL : Earth & Water Pressure, BxcL : X-directional & Downward
Y-directional Blast Load, BxtL : X-directional & Upward Y-directional Blast Load,
BzcL : X-directional & Downward Y-directional Blast Load, BztL : X-directional &
Upward Y-directional Blast Load
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 26 of 361

1.9 BASIC REQUIREMENT


1) Deflection for Concrete Structures
Deflection criteria for concrete members shall satisfy the requirements of ACI 318-
08 Table 9.5(b).
Type of Member Deflection to be considered Deflection
limitation
Flat roofs not supporting or Immediate deflection due to live L / 180
attached to nonstructural load
elements likely to be
damaged by large
deflections
Roof or floor construction That part of the total deflection L / 240
supporting or attached to occurring after attachment of
nonstructural elements not nonstructural elements (sum of
likely to be damaged by the long-term deflection due to
large deflections all sustained loads and the
immediate deflection due to any
additional live load)

1.10 STABILITY
1) Against Overturning
A safety factor would be applied minimum 1.5 for design Normal L/C
A safety factor would be applied minimum 1.2 for design Blast L/C
2) Against Uplift
A safety factor would be applied minimum 1.5 for design
3) Against Sliding
A safety factor would be applied minimum 1.25 for design Normal L/C
A safety factor would be applied minimum 1.00 for design Blast L/C
4) Against Buoyancy
A safety factor of not less than 1.5 shall be provided.

1.11 SETTLEMENT
1) Total Settlement
25 mm for continous strip beam foundation 1.5m level foundation
50 mm for raft foundation 4.0m level basement slab
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 27 of 361

2. STRUCTURAL FRAMING SKETCH


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 28 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 29 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 30 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 31 of 361

3. STAAD MODEL & INPUT

3.1 Structural Model for Beam & Node Number

3.2 Loading Summary for Stress Analysis

3.3 Foundation support condition

3.4 STAAD input


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 32 of 361

3.1 Structural Model for Beam & Node Number


3.1.1 Whole Model
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 33 of 361

3.1.2 Node Number

B.O.F EL+4,500

B.O.F EL+4,500 ~ T.O.C EL+6,900


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 34 of 361

T.O.C EL+6,900

T.O.C EL+6,900 ~ T.O.C EL+8,900


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 35 of 361

T.O.C EL+8,900

T.O.C EL+8,900 ~ T.O.C EL+14,900


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 36 of 361

T.O.C EL+14,900
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 37 of 361

3.1.3 Member Number

B.O.F EL+4,500

B.O.F EL+4,500 ~ T.O.C EL+6,900


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 38 of 361

T.O.C EL+6,900

T.O.C EL+6,900 ~ T.O.C EL+8,900


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 39 of 361

T.O.C EL+8,900

T.O.C EL+8,900 ~ T.O.C EL+14,900


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 40 of 361

T.O.C EL+14,900
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 41 of 361

3.2 Loading Summary for Stress analysis


3.2.1 Dead Load

<Floor Load>
(For Roof Floor) Roof Floor Dead Load : w = 8.52 kN/m2
(For Ground Floor) Ground Floor-Switch gear room, HVAC room, fire fighting room & air lock room
Dead Load : w = 4.90 kN/m2
(For Ground Floor) Ground Floor-Battery room Dead Load : w = 6.30 kN/m2
(Note: Floor loads are automatically distributed to supporting beams by STAAD)

<Beam Load>
(For Roof Floor) Parapet Load : w = 3.75kN/m2*0.3m = 1.125 kN/m
(For Ground Floor) External Wall w/ Concrete Block (thk.=100) : w = 2.00kN/m 2*6.0m = 12.00 kN/m
(For Ground Floor) Internal Wall w/ Concrete Block (thk.=200) : w = 3.80kN/m 2*6.0m = 22.80 kN/m

<Beam Load : HVAC Pad Weight>


CFU-NSS-01 (For Ground Floor)
w = 25kN/m3*0.20m*(0.93m*1.54m/2.00m) = 3.55 kN/m
w = 25kN/m3*0.20m*(0.93m*0.46m/2.00m) = 1.07 kN/m
w = 25kN/m3*0.20m*(0.73m*0.36m/2.00m) = 0.66 kN/m
w = 25kN/m3*0.20m*(0.73m*1.64m/2.00m) = 2.97 kN/m

AHU-101A (For Ground Floor)


w = 25kN/m3*0.20m*(0.65m*3.67m/4.00m) = 2.98 kN/m
w = 25kN/m3*0.20m*(0.65m*0.33m/4.00m) = 0.27 kN/m
w = 25kN/m3*0.20m*(1.40m*0.70m/3.00m) = 1.63 kN/m
w = 25kN/m3*0.20m*(1.40m*2.30m/3.00m) = 5.37 kN/m

AHU-101B (For Ground Floor)


w = 25kN/m3*0.2m*(2.05m*1.13m/3.00m) = 3.84 kN/m
3
w = 25kN/m *0.2m*(2.05m*1.88m/3.00m) = 6.41 kN/m

<Nodal Load : HVAC Pad Weight>


HCP-NSS-01 (For Ground Floor)
3
w = 25kN/m *0.2m*(1.00m*1.00m) = 5.00 kN

<Pressure Load>
2
Basement Floor Finish Dead Load : w = 0.40 kN/m
(For Foundation) Soil Weight (h=1.0m) : w = 17kN/m3*1.0m = 17.00 kN/m2
3 2
(For Foundation) Soil Weight (h=3.4m) : w = 17kN/m *3.4m = 57.80 kN/m
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 42 of 361

(Unit: kN, kN/m, N/mm2)


DEAD LOAD
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 43 of 361

(Unit: kN/m)
DEAD LOAD : ROOF FLOOR : FLOOR LOAD

(Unit: kN/m)
DEAD LOAD : ROOF FLOOR : BEAM LOAD
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 44 of 361

(Unit: kN/m)
DEAD LOAD : GROUND FLOOR : FLOOR LOAD

(Unit: kN/m)
DEAD LOAD : GROUND FLOOR : BEAM LOAD
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 45 of 361

(Unit: N/mm2)
DEAD LOAD : BASEMENT FLOOR : FLOOR PRESSURE

(Unit: N/mm2)
DEAD LOAD : FOUNDATION PRESSURE LOAD
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 46 of 361

3.2.2 Live Load

<Floor Load>
(For Roof Floor) Roof Floor Live Load (Roof) : w = 1.00 kN/m2
(For Ground Floor) Ground Floor Live Load (Battery Room) : w = 20.00 kN/m2
(For Ground Floor) Ground Floor Live Load (Switch Room) : w = 20.00 kN/m2
(For Ground Floor) Ground Floor Live Load (Air Lock) : w = 20.00 kN/m2
(For Ground Floor) Ground Floor Live Load (F/F Room) : w = 20.00 kN/m2
(Note: Floor loads are automatically distributed to supporting beams by STAAD)

<Pressure Load>
(For Basement Floor) Basement Floor Live Load (C/C Room) : w = 5.00 kN/m2

(Unit: kN/m, N/mm2)

LIVE LOAD
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 47 of 361

(Unit: kN/m)
LIVE LOAD : ROOF FLOOR : FLOOR LOAD

(Unit: kN/m)
LIVE LOAD : GROUND FLOOR : FLOOR LOAD
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 48 of 361

(Unit: N/mm2)
LIVE LOAD : BASEMENT FLOOR : FLOOR PRESSURE
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 49 of 361

3.2.3 Wind Load

1. DESIGN DATA 2. DESIGN WIND PRESSURE CACULATION


Basic Wind Speed : 56.9 m/s For Building, enclosed (Buildings of all heights)
Exposure Categories : C #N/A P = qGCp - qh(GCpi) > 770 N/m2
Important Factor, I : 1.15 qz = 0.613*Kd*Kz*Kzt*V^2*I (Unit : N/m2)
Topographic factor : 1
HEIGHT qz V Kz (Kh)
2. BUILDING DATA 0.0 ~ 6.40 1765.51 56.92 0.91
a. HEIGHT (Z) : 6.4
b. WIDTH (B) : 17.7
c. LENGTH (L) : 18.0
d. No of Cal. point (EA) : 1 Mean Height 6.45 1768.11 56.92 0.91

3. DESIGN WIND LOAD CALCULATION 0.6 degree 9000.0


90.0
Cpe

Cpe Cpe

h
WIND A
Z Case I Case II
B Gcpi 0.18 -0.18

PLAN L Cpe ELEVATION Main wind-force resisting systems

WIND B

CASE I ( P ) N/m2 CASE II ( P ) N/m2


ROOF 0 to h >h 0 to h >h h/L qh G Cp
WIND A - CASE -1670.9 -1069.7 -1034.3 -433.2 0.36 1768.11 0.85 -0.90 -0.50
-1670.9 -1069.7 -1034.3 -433.2 0.36 1768.11 0.85 -0.90 -0.50
WIND B - CASE 0 to h >h 0 to h >h h/B qh G Cp
-1670.9 -1069.7 -1034.3 -433.2 0.36 1768.11 0.85 -0.90 -0.50

WINDWARD WALL CASE I ( P ) CASE II ( P ) qz G Cp qh


0.0 ~ 6.4m 882.3 N/m2 1518.8 N/m2 1765.51 0.85 0.80 1768.11

LEEWARD WALL CASE I ( P ) CASE II ( P ) L/B qh G Cp


WIND A - CASE -1064.6 N/m2 -770.0 N/m2 1.02 1768.11 0.85 -0.50
WIND B - CASE -1069.7 N/m2 -770.0 N/m2 0.98 1768.11 0.85 -0.50

SIDE WALL CASE I ( P ) CASE II ( P ) qz G Cp qh


-1370.3 N/m2 -770.0 N/m2 1768.11 0.85 -0.70 1768.11
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 50 of 361

<Wind Load>
Windward Wall : w = 1.766kN/m 2 x 0.85 x 0.8 1.768kN/m 2 x (-0.18) = 1.519 kN/m2
Leeward Wall : w = 1.768kN/m 2 x 0.85 x (-0.50) 1.768kN/m2 x (-0.18)
= -0.428kN/m2 < W(min) = - 0.7700 kN/m 2 W = -0.77 kN/m2
Sidewall : w = 1.768kN/m2 x 0.85 x (-0.70) 1.768kN/m2 x (-0.18)
= -0.6836kN/m2 < W(min) = - 0.7700 kN/m 2 W = -0.77 kN/m 2
Roof Floor : w = 1.768kN/m2 x 0.85 x (-0.9) 1.768kN/m2 x 0.18 = 1.671 kN/m2 (Upward)

(Note: Wind loads (wind pressure) are automatically distributed to supporting beams by STAAD)

(Unit: kN/m)
WIND LOAD (+X DIR.)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 51 of 361

(Unit: kN/m)
WIND LOAD (+X DIR.) : ROOF FLOOR : FLOOR LOAD

(Unit: kN/m)
WIND LOAD (+X DIR.) : WALL : FLOOR LOAD
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 52 of 361

<Wind Load>
Windward Wall : w = 1.766kN/m 2 x 0.85 x 0.8 1.768kN/m2 x (-0.18) = 1.519 kN/m2
Leeward Wall : w = 1.768kN/m 2 x 0.85 x (-0.50) 1.768kN/m2 x (-0.18)
= -0.428kN/m2 < W(min) = - 0.7700 kN/m 2 W = -0.77 kN/m2
Sidewall : w = 1.768kN/m2 x 0.85 x (-0.70) 1.768kN/m2 x (-0.18)
= -0.6836kN/m2 < W(min) = - 0.7700 kN/m 2 W = -0.77 kN/m 2
Roof Floor : w = 1.768kN/m2 x 0.85 x (-0.9) 1.768kN/m 2 x 0.18 = 1.671 kN/m2 (Upward)

(Note: Wind loads (wind pressure) are automatically distributed to supporting beams by STAAD)

(Unit: kN/m)
WIND LOAD (-X DIR.)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 53 of 361

(Unit: kN/m)
WIND LOAD (-X DIR.) : ROOF FLOOR : FLOOR LOAD

(Unit: kN/m)
WIND LOAD (-X DIR.) : WALL : FLOOR LOAD
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 54 of 361

<Wind Load>
Windward Wall : w = 1.766kN/m 2 x 0.85 x 0.8 1.768kN/m2 x (-0.18) = 1.519 kN/m2
Leeward Wall : w = 1.768kN/m 2 x 0.85 x (-0.50) 1.768kN/m2 x (-0.18)
= -0.428kN/m2 < W(min) = - 0.7700 kN/m 2 W = -0.77 kN/m2
Sidewall : w = 1.768kN/m2 x 0.85 x (-0.70) 1.768kN/m2 x (-0.18)
= -0.6836kN/m2 < W(min) = - 0.7700 kN/m 2 W = -0.77 kN/m 2
Roof Floor : w = 1.768kN/m2 x 0.85 x (-0.9) 1.768kN/m 2 x 0.18 = 1.671 kN/m2 (Upward)

(Note: Wind loads (wind pressure) are automatically distributed to supporting beams by STAAD)

(Unit: kN/m)
WIND LOAD (+Z DIR.)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 55 of 361

(Unit: kN/m)
WIND LOAD (+Z DIR.) : ROOF FLOOR : FLOOR LOAD

(Unit: kN/m)
WIND LOAD (+Z DIR.) : WALL : FLOOR LOAD
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 56 of 361

<Wind Load>
Windward Wall : w = 1.766kN/m 2 x 0.85 x 0.8 1.768kN/m2 x (-0.18) = 1.519 kN/m2
Leeward Wall : w = 1.768kN/m 2 x 0.85 x (-0.50) 1.768kN/m2 x (-0.18)
= -0.428kN/m2 < W(min) = - 0.7700 kN/m 2 W = -0.77 kN/m2
Sidewall : w = 1.768kN/m2 x 0.85 x (-0.70) 1.768kN/m2 x (-0.18)
= -0.6836kN/m2 < W(min) = - 0.7700 kN/m 2 W = -0.77 kN/m 2
Roof Floor : w = 1.768kN/m2 x 0.85 x (-0.9) 1.768kN/m 2 x 0.18 = 1.671 kN/m2 (Upward)

(Note: Wind loads (wind pressure) are automatically distributed to supporting beams by STAAD)

(Unit: kN/m)
WIND LOAD (-Z DIR.)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 57 of 361

(Unit: kN/m)
WIND LOAD (-Z DIR.) : ROOF FLOOR : FLOOR LOAD

(Unit: kN/m)
WIND LOAD (-Z DIR.) : WALL : FLOOR LOAD
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 58 of 361

3.2.4 Seismic Load

IBC 2009 Seismic Response Coefficient and Base Shear : New Substation

1. Building Height
hn = 6.4 m

2. Fundamental Period of Structure Ta


X Direction Ct = 0.0488 x= 0.75 (RC Bearing Wall)
Z Direction Ct = 0.0488 x= 0.75 (RC Bearing Wall)
(Values obtained from ASCE 7-10 Table 12.8-1)

X Direction Ta_x = Ct*hn^x = 0.0488*6.4^0.75= 0.1964 sec


Z Direction Ta_z = Ct*hn^x = 0.0488*6.4^0.75= 0.1964 sec

3. Response Modification Factor


X Direction Rx = 4.00 (Ordinary RC Bearing Wall)
Z Direction Rz = 4.00 (Ordinary RC Bearing Wall)

4. Important Factor
I= 1.25

5. Spectral Acceleration
Sds = 2/3*Fa*Ss = 2/3*1.27*0.32 = 0.271
Sd1 = 2/3*Fv*S1 = 2/3*1.67*0.13 = 0.145

6. Seismic Response Coefficient


X Direction Csx = Sds/(Rx/I) = 0.271/(4/1.25) = 0.085
Z Direction Csz = Sds/(Rz/I) = 0.271/(4/1.25) = 0.085

Csx_max = Sd1/(Ta_x*Rx/I) = 0.145/(0.1964*4/1.25) = 0.231


Csz_max = Sd1/(Ta_z*Rx/I) = 0.145/(0.1964*4/1.25) = 0.231
Cs_min = max(0.044*Sds*I , 0.01)= max(0.044(0.271)(1.25) , 0.01) 0.015

X Direction Csx = 0.085


Z Direction Csz = 0.085

7. Design Base Shear


Effective Weight W = 22289.08
21480.01 kN

X Direction Vx = Csx * W = 0.085x22289.08 =


21480.01= 1894.57
1818.64 kN
Z Direction Vz = Csz * W = 21480.01=
0.085x22289.08 = 1894.57
1818.64 kN
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 59 of 361

(Unit: kN)
SEISMIC LOAD (+X DIR.)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 60 of 361

(Unit: kN)
SEISMIC LOAD (+Z DIR.)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 61 of 361

3.2.5 Earth & Water Pressure


Soil & Water Pressure at Wall
Parameters

Description Value Unit Remarks


Angle of Internal Frimction , 27 deg
Taken from Engineering Properties of On-site Soil
Unit Weight of Soil, 17 kN/m3 in "Geotechnical investigation Report for On-shore"
(BH-33)
Effective Unit Weight of Soil, 7 kN/m3

Coefficient of Earth Pressure at rest,


0.55

Depth, H 4 m
Ground Water Level from finished surface -5 m
2.6 m

Surface Load, s 0 kN/m2

Load factor for water pressure 1

0 kPa
Calcuation G.L.
soil

Pressure at Ground Level 3


0.55*17*0 + 0.55*0 = 0 kPa
17kN/m
Pressure at Level of Bottom of Foundation 4m
0.55*17*4 + 0.55*7*0 + 1*1.0*0 + 0.55*0
-1.6m level - 0.55*17*1.6 == 37.13 kPa
14.96 kPa

-4.0m level - 0.55*17*2.6 + 0.55*7*1.4 + 10*1.4 = 43.7 kPa

B.O.F 37.13 kPa


43.7 kPa

Ground water height above raft base = 1.4m

Upward pressure on basement raft due to ground water = 1.4 x 10 = 14 kPa


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 62 of 361

(Unit: N/mm2)
SOIL PRESSURE LOAD

(Unit: N/mm2)
UPLIFT WATER PRESSURE LOAD
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 63 of 361

3.2.6 Blast Load

Blast loads are determined based on the least of the applied load and the capacity of components
directly support by the foundation. (Blast load values refer blast load calculation Page Nos. 23 & 24)

<Floor Load>
Vertical blast load on Roof Floor : w = 8301.6kN / (18.0mx17.7m) = 26.06 kN/m2 (Downward)

<Beam Load>
Lateral blast load on Roof Girder : w = 2963.0kN / (2x17.7m) = 83.7 kN/m

Lateral blast load on Grade Girder : w = 2963.0kN / (2x17.7m) = 83.7 kN/m

(Note: Floor load is automatically distributed to supporting beams by STAAD)

(Unit: kN//m)
BLAST LOAD (+X DIR.) + ROOF(-Y DIR.)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 64 of 361

<Floor Load>
Vertical blast load on Roof Floor : w = 10426.8kN / (18.0mx17.7m) = 32.73 kN/m 2 (Upward)

<Beam Load>
Lateral blast load on Roof Girder : w = 2963.0kN / (2x17.7m) = 83.7 kN/m

Lateral blast load on Grade Girder : w = 2963.0kN / (2x17.7m) = 83.7 kN/m

(Note: Floor load is automatically distributed to supporting beams by STAAD)

(Unit: kN//m)
BLAST LOAD (+X DIR.) + ROOF(+Y DIR.)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 65 of 361

<Floor Load>
Vertical blast load on Roof Floor : w = 8301.6kN / (18.0mx17.7m) = 26.06 kN/m2 (Downward)

<Beam Load>
Lateral blast load on Roof Girder : w = 2963.0kN / (2x17.7m) = 83.7 kN/m

Lateral blast load on Grade Girder : w = 2963.0kN / (2x17.7m) = 83.7 kN/m

(Note: Floor load is automatically distributed to supporting beams by STAAD)

(Unit: kN//m)
BLAST LOAD (-X DIR.) + ROOF(-Y DIR.)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 66 of 361

<Floor Load>
Vertical blast load on Roof Floor : w = 10426.8kN / (18.0mx17.7m) = 32.73 kN/m 2 (Upward)

<Beam Load>
Lateral blast load on Roof Girder : w = 2963.0kN / (2x17.7m) = 83.7 kN/m

Lateral blast load on Grade Girder : w = 2963.0kN / (2x17.7m) = 83.7 kN/m

(Note: Floor load is automatically distributed to supporting beams by STAAD)

(Unit: kN//m)
BLAST LOAD (-X DIR.) + ROOF(+Y DIR.)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 67 of 361

<Floor Load>
Vertical blast load on Roof Floor : w = 8301.6kN / (18.0mx17.7m) = 26.06 kN/m2 (Downward)

<Beam Load>
Lateral blast load on Roof Girder : w = 3013.0kN / (2x18.0m) = 83.7 kN/m

Lateral blast load on Grade Girder : w = 3013.0kN / (2x18.0m) = 83.7 kN/m

(Note: Floor load is automatically distributed to supporting beams by STAAD)

(Unit: kN//m)
BLAST LOAD (+Z DIR.) + ROOF(-Y DIR.)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 68 of 361

<Floor Load>
Vertical blast load on Roof Floor : w = 10426.8kN / (18.0mx17.7m) = 32.73 kN/m 2 (Upward)

<Beam Load>
Lateral blast load on Roof Girder : w = 3013.0kN / (2x18.0m) = 83.7 kN/m

Lateral blast load on Grade Girder : w = 3013.0kN / (2x18.0m) = 83.7 kN/m

(Note: Floor load is automatically distributed to supporting beams by STAAD)

(Unit: kN//m)
BLAST LOAD (+Z DIR.) + ROOF(+Y DIR.)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 69 of 361

<Floor Load>
Vertical blast load on Roof Floor : w = 8301.6kN / (18.0mx17.7m) = 26.06 kN/m2 (Downward)

<Beam Load>
Lateral blast load on Roof Girder : w = 3013.0kN / (2x18.0m) = 83.7 kN/m

Lateral blast load on Grade Girder : w = 3013.0kN / (2x18.0m) = 83.7 kN/m

(Note: Floor load is automatically distributed to supporting beams by STAAD)

(Unit: kN//m)
BLAST LOAD (-Z DIR.) + ROOF(-Y DIR.)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 70 of 361

<Floor Load>
Vertical blast load on Roof Floor : w = 10426.8kN / (18.0mx17.7m) = 32.73 kN/m 2 (Upward)

<Beam Load>
Lateral blast load on Roof Girder : w = 3013.0kN / (2x18.0m) = 83.7 kN/m

Lateral blast load on Grade Girder : w = 3013.0kN / (2x18.0m) = 83.7 kN/m

(Note: Floor load is automatically distributed to supporting beams by STAAD)

(Unit: kN//m)
BLAST LOAD (-Z DIR.) + ROOF(+Y DIR.)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 71 of 361

3.3 Foundation support condition

Foundations modeled as a plate element with plate mat support condition assigned in the STAAD
model.
Borehole considered for foundation design as BH-38, which is governing among the BH-38, 39, 39A
& 40

Vertical spring support constant calculated as below,

WF1A Strip foundation (1.6m founding level)


Net SBC value at 1.6m depth and 2.8m wide strip foundation(WF1A) Qnet-allow = 102.4 kN/m2
(For 25mm settlement and shear criteria FOS = 3) Annexure 6.1
Allowable settlement for strip foundation
Factor of safety against shear failure S.F = 3.0
Subgrade modulus/spring constant for strip foundation(WF1A) Ks =
= 1/0.025 x 3 x 102.4
= 12288 kN/m3

WF1, WF2, F1 & BS1 12m wide raft foundation (4m founding level)
Net SBC value at 4.0m depth and 12m wide raft foundation Qnet-allow = 172.0 kN/m2
(For 50mm settlement and shear criteria FOS = 3) Annexure 6.1
Allowable settlement for raft foundation
Factor of safety against shear failure S.F = 3.0
Subgrade modulus/spring constant for raft foundation Ks = 1/0.05 x 3 x 172.0
= 10320 kN/m3
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 72 of 361

3.4 STAAD input


STAAD SPACE 56 20 63; 57 21 64; 58 22 65; 59 23 66; 60 24 67; 61 29 72; 62 33 76; 63 35 78;
START JOB INFORMATION 64 39 82; 65 43 86; 66 44 112; 67 48 116; 68 50 118; 69 54 122; 70 58 127;
ENGINEER DATE 10-July-17 71 63 134; 72 64 136; 73 65 137; 74 66 257; 75 67 141; 76 72 146; 77 76 272;
END JOB INFORMATION 78 78 268; 79 82 271; 80 86 269; 81 97 174; 82 101 178; 83 103 180; 84 107 184;
INPUT WIDTH 79 85 111 189; 86 112 113; 87 113 114; 88 114 115; 89 115 116; 90 116 117;
UNIT METER KN 91 117 118; 92 118 119; 93 119 120; 94 120 121; 95 121 122; 96 122 123;
JOINT COORDINATES 97 123 124; 98 124 125; 99 125 126; 100 126 127; 101 112 128; 102 127 129;
1 50 -4 0; 2 51.25 -4 0; 3 52.5 -4 0; 4 53.8 -4 0; 5 55 -4 0; 6 56.5 -4 0; 103 125 409; 104 129 133; 106 116 250; 107 118 251; 109 122 252; 110 128 249;
7 58 -4 0; 8 59.2 -4 0; 9 60 -4 0; 10 60.8 -4 0; 11 62 -4 0; 12 63.2 -4 0; 114 132 253; 115 133 141; 116 134 135; 117 135 136; 118 136 137; 119 137 257;
13 65 -4 0; 14 66.75 -4 0; 15 68 -4 0; 16 50 -4 1.25; 17 68 -4 1.25; 123 134 142; 124 141 143; 126 136 262; 127 137 263; 131 142 261; 132 143 266;
18 50 -4 3.15; 19 68 -4 3.15; 20 50 -4 4.35; 21 55 -4 4.35; 22 58 -4 4.35; 133 144 146; 134 145 269; 135 146 147; 136 147 148; 137 148 149; 138 149 272;
23 62 -4 4.35; 24 68 -4 4.35; 25 50 -4 5.55; 26 68 -4 5.55; 27 50 -4 7.25; 139 272 151; 140 151 268; 141 268 153; 142 153 154; 146 157 159; 148 159 160;
28 68 -4 7.25; 29 50 -4 8.7; 30 51.25 -4 8.7; 31 52.5 -4 8.7; 32 53.8 -4 8.7; 149 160 269; 150 146 162; 151 269 163; 152 148 165; 153 272 166; 154 162 164;
33 55 -4 8.7; 34 56.5 -4 8.7; 35 58 -4 8.7; 36 59.2 -4 8.7; 37 60 -4 8.7; 155 163 167; 156 164 165; 157 165 166; 158 164 168; 159 167 169; 160 268 444;
38 60.8 -4 8.7; 39 62 -4 8.7; 40 63.2 -4 8.7; 41 65 -4 8.7; 42 66.75 -4 8.7; 161 154 445; 162 271 184; 163 159 187; 164 168 170; 165 169 171; 166 165 176;
43 68 -4 8.7; 44 50 -1.6 0; 45 51.25 -1.6 0; 46 52.5 -1.6 0; 47 53.8 -1.6 0; 167 166 178; 168 170 172; 169 171 173; 170 172 174; 171 173 189; 172 174 175;
48 55 -1.6 0; 49 56.5 -1.6 0; 50 58 -1.6 0; 51 59.2 -1.6 0; 52 60 -1.6 0; 173 175 176; 174 176 177; 175 177 178; 176 178 179; 177 179 180; 178 180 181;
53 60.8 -1.6 0; 54 62 -1.6 0; 55 63.2 -1.6 0; 56 65 -1.6 0; 57 66.75 -1.6 0; 179 181 182; 180 182 183; 181 183 184; 182 184 185; 183 185 187; 185 187 188;
58 68 -1.6 0; 59 50 -1.6 1.25; 60 68 -1.6 1.25; 61 50 -1.6 3.15; 186 188 189; 187 112 190; 188 116 194; 189 118 196; 190 122 200; 191 127 204;
62 68 -1.6 3.15; 63 50 -1.6 4.35; 64 55 -1.6 4.35; 65 58 -1.6 4.35; 197 174 233; 200 184 243; 201 189 247; 202 190 191; 203 191 192; 204 192 193;
66 62 -1.6 4.35; 67 68 -1.6 4.35; 68 50 -1.6 5.55; 69 68 -1.6 5.55; 205 193 194; 206 194 195; 207 195 196; 208 196 197; 209 197 198; 210 198 199;
70 50 -1.6 7.25; 71 68 -1.6 7.25; 72 50 -1.6 8.7; 73 51.25 -1.6 8.7; 211 199 200; 212 200 201; 213 201 202; 214 202 203; 215 203 2 04; 216 190 205;
74 52.5 -1.6 8.7; 75 53.8 -1.6 8.7; 76 55 -1.6 8.7; 77 56.5 -1.6 8.7; 217 204 206; 218 205 207; 219 206 208; 220 207 209; 221 208 210; 222 192 216;
78 58 -1.6 8.7; 79 59.2 -1.6 8.7; 80 60 -1.6 8.7; 81 60.8 -1.6 8.7; 223 194 412; 224 196 413; 226 200 414; 227 202 221; 228 209 211; 229 210 212;
82 62 -1.6 8.7; 83 63.2 -1.6 8.7; 84 65 -1.6 8.7; 85 66.75 -1.6 8.7; 230 211 213; 231 212 214; 232 213 411; 233 214 415; 234 411 216; 235 216 412;
86 68 -1.6 8.7; 87 50 -1.6 10.2; 88 68 -1.6 10.2; 89 50 -1.6 11.7; 236 412 413; 237 413 414; 239 414 221; 240 221 415; 241 411 223; 242 415 224;
90 68 -1.6 11.7; 91 50 -1.6 13.2; 92 68 -1.6 13.2; 93 50 -1.6 14.7; 243 223 225; 244 224 226; 245 225 227; 246 226 228; 247 216 235; 248 412 416;
94 68 -1.6 14.7; 95 50 -1.6 16.45; 96 68 -1.6 16.45; 97 50 -1.6 17.7; 249 413 417; 251 414 243; 252 221 245; 253 227 229; 254 228 230; 255 229 231;
98 51.25 -1.6 17.7; 99 52.5 -1.6 17.7; 100 53.75 -1.6 17.7; 101 55 -1.6 17.7; 256 230 232; 257 231 233; 258 232 247; 259 233 234; 260 234 235; 261 235 236;
102 56.5 -1.6 17.7; 103 58 -1.6 17.7; 104 59 -1.6 17.7; 105 60 -1.6 17.7; 262 236 416; 263 416 238; 264 238 417; 265 417 240; 266 240 241; 267 241 242;
106 61 -1.6 17.7; 107 62 -1.6 17.7; 108 63.5 -1.6 17.7; 109 65 -1.6 17.7; 268 242 243; 269 243 244; 270 244 245; 271 245 246; 272 246 247; 1830 248 256;
110 66.75 -1.6 17.7; 111 68 -1.6 17.7; 112 50 0 0; 113 51.25 0 0; 114 52.5 0 0; 1832 249 253; 1833 250 254; 1834 249 250; 1835 251 255; 1836 252 248;
115 53.8 0 0; 116 55 0 0; 117 56.5 0 0; 118 58 0 0; 119 59.2 0 0; 120 60 0 0; 1837 250 251; 1838 251 252; 1840 254 136; 1841 255 137; 1842 256 257;
121 60.8 0 0; 122 62 0 0; 123 63.2 0 0; 124 65 0 0; 125 65.9 0 0; 1843 253 254; 1844 254 255; 1845 255 256; 1846 257 406; 1847 271 157;
126 66.75 0 0; 127 68 0 0; 128 50 0 1.25; 129 68 0 1.25; 132 50 0 3.15; 1848 257 267; 1853 262 272; 1854 261 262; 1855 263 268; 1856 262 263;
133 68 0 3.15; 134 50 0 4.35; 135 52.5 0 4.35; 136 55 0 4.35; 137 58 0 4.35; 1857 263 267; 1861 267 271; 1862 267 266; 1873 352 447; 1874 357 24;
141 68 0 4.35; 142 50 0 5.55; 143 68 0 5.55; 144 50 0 7.25; 145 68 0 7.25; 1875 362 420; 1876 364 421; 1877 368 422; 1878 373 33; 1879 375 35;
146 50 0 8.7; 147 51.25 0 8.7; 148 52.5 0 8.7; 149 53.8 0 8.7; 151 56.5 0 8.7; 1880 379 39; 2009 406 141; 2011 252 409; 2012 256 410; 2013 409 410;
153 59.2 0 8.7; 154 60 0 8.7; 155 60.8 0 8.7; 157 63.2 0 8.7; 159 65 0 8.7; 2014 410 406; 2015 154 155; 2016 155 271; 2021 420 21; 2022 421 22;
160 66.75 0 8.7; 162 50 0 10.2; 163 68 0 10.2; 164 50 0 11.7; 165 52.5 0 11.7; 2023 422 23; 2024 429 373; 2025 430 375; 2026 431 379; 2027 438 21;
166 55 0 11.7; 167 68 0 11.7; 168 50 0 13.2; 169 68 0 13.2; 170 50 0 14.7; 2028 439 22; 2029 440 23; 2030 441 439; 2031 442 460; 2032 443 455;
171 68 0 14.7; 172 50 0 16.45; 173 68 0 16.45; 174 50 0 17.7; 175 51.25 0 17.7; 2045 444 180; 2046 445 182; 2047 444 445; 2088 146 411; 2090 272 412;
176 52.5 0 17.7; 177 53.75 0 17.7; 178 55 0 17.7; 179 56.5 0 17.7; 2091 268 413; 2092 271 414; 2093 269 415; 2098 178 416; 2100 180 417;
180 58 0 17.7; 181 59 0 17.7; 182 60 0 17.7; 183 61 0 17.7; 184 62 0 17.7; 2101 447 438; 2130 455 357; 2154 460 440; 2169 261 144; 2171 266 145;
185 63.5 0 17.7; 187 65 0 17.7; 188 66.75 0 17.7; 189 68 0 17.7; 190 50 6.4 0; 2172 132 134;
191 51.25 6.4 0; 192 52.5 6.4 0; 193 53.8 6.4 0; 194 55 6.4 0; 195 56.5 6.4 0; ELEMENT INCIDENCES SHELL
196 58 6.4 0; 197 59.2 6.4 0; 198 60 6.4 0; 199 60.8 6.4 0; 200 62 6.4 0; 1580 116 117 195 194; 1581 117 118 196 195; 1584 178 179 238 416;
201 63.2 6.4 0; 202 65 6.4 0; 203 66.75 6.4 0; 204 68 6.4 0; 205 50 6.4 1.25; 1585 179 180 417 238; 1586 48 49 117 116; 1587 49 50 118 117; 1589 5 6 49 48;
206 68 6.4 1.25; 207 50 6.4 3.15; 208 68 6.4 3.15; 209 50 6.4 4.35; 1590 6 7 50 49; 1592 76 77 151 272; 1593 77 78 268 151; 1595 33 34 77 76;
210 68 6.4 4.35; 211 50 6.4 5.55; 212 68 6.4 5.55; 213 50 6.4 7.25; 1596 34 35 78 77; 1597 101 102 179 178; 1598 102 103 180 179;
214 68 6.4 7.25; 216 52.5 6.4 8.7; 221 65 6.4 8.7; 223 50 6.4 10.2; 1601 112 113 191 190; 1602 113 114 192 191; 1605 114 115 193 192;
224 68 6.4 10.2; 225 50 6.4 11.7; 226 68 6.4 11.7; 227 50 6.4 13.2; 1606 115 116 194 193; 1609 118 119 197 196; 1610 119 120 198 197;
228 68 6.4 13.2; 229 50 6.4 14.7; 230 68 6.4 14.7; 231 50 6.4 16.45; 1613 120 121 199 198; 1614 121 122 200 199; 1617 122 123 201 200;
232 68 6.4 16.45; 233 50 6.4 17.7; 234 51.25 6.4 17.7; 235 52.5 6.4 17.7; 1618 123 124 202 201; 1621 124 126 203 202; 1622 126 127 204 203;
236 53.75 6.4 17.7; 238 56.5 6.4 17.7; 240 59 6.4 17.7; 241 60 6.4 17.7; 1625 174 175 234 233; 1626 175 176 235 234; 1629 176 177 236 235;
242 61 6.4 17.7; 243 62 6.4 17.7; 244 63.5 6.4 17.7; 245 65 6.4 17.7; 1630 177 178 416 236; 1633 180 181 240 417; 1634 181 182 241 240;
246 66.75 6.4 17.7; 247 68 6.4 17.7; 248 62 0 2.5; 249 50 0 2.04; 1637 182 183 242 241; 1638 183 184 243 242; 1641 184 185 244 243;
250 55 0 2.04; 251 58 0 2.04; 252 62 0 2.04; 253 50 0 3.01; 254 55 0 3.01; 1642 185 187 245 244; 1645 187 188 246 245; 1646 188 189 247 246;
255 58 0 3.01; 256 62 0 3.01; 257 62 0 4.35; 261 50 0 5.71; 262 55 0 5.71; 1647 44 45 113 112; 1648 45 46 114 113; 1649 46 47 115 114; 1650 47 48 116 115;
263 58 0 5.71; 266 68 0 5.71; 267 62 0 5.71; 268 58 0 8.7; 269 68 0 8.7; 1652 1 2 45 44; 1653 2 3 46 45; 1655 3 4 47 46; 1656 4 5 48 47;
271 62 0 8.7; 272 55 0 8.7; 273 48.45 -4 0; 274 48.45 -4 1.25; 1657 50 51 119 118; 1658 51 52 120 119; 1659 52 53 121 120; 1660 53 54 122 121;
275 48.45 -4 3.15; 276 48.45 -4 4.35; 277 48.45 -4 5.55; 278 48.45 -4 7.25; 1662 7 8 51 50; 1663 8 9 52 51; 1665 9 10 53 52; 1666 10 11 54 53;
279 48.45 -4 8.7; 280 69.55 -4 0; 281 69.55 -4 1.25; 282 69.55 -4 3.15; 1667 54 55 123 122; 1668 55 56 124 123; 1669 56 57 126 124 ; 1670 57 58 127 126;
283 69.55 -4 4.35; 284 69.55 -4 5.55; 285 69.55 -4 7.25; 286 69.55 -4 8.7; 1672 11 12 55 54; 1673 12 13 56 55; 1675 13 14 57 56; 1676 14 15 58 57;
287 50 -4 -1.55; 288 51.25 -4 -1.55; 289 52.5 -4 -1.55; 290 53.8 -4 -1.55; 1678 72 73 147 146; 1679 73 74 148 147; 1681 74 75 149 148; 1682 75 76 272 149;
291 55 -4 -1.55; 292 56.5 -4 -1.55; 293 58 -4 -1.55; 294 59.2 -4 -1.55; 1684 29 30 73 72; 1685 30 31 74 73; 1687 31 32 75 74; 1688 32 33 76 75;
295 60 -4 -1.55; 296 60.8 -4 -1.55; 297 62 -4 -1.55; 298 63.2 -4 -1.55; 1690 78 79 153 268; 1691 79 80 154 153; 1693 80 81 155 154; 1694 81 82 271 155;
299 65 -4 -1.55; 300 66.75 -4 -1.55; 301 68 -4 -1.55; 302 48.45 -4 -1.55; 1696 35 36 79 78; 1697 36 37 80 79; 1699 37 38 81 80; 1700 38 39 82 81;
303 69.55 -4 -1.55; 304 50 -4 10.45; 305 51.25 -4 10.45; 306 52.5 -4 10.45; 1702 82 83 157 271; 1703 83 84 159 157; 1705 84 85 160 159; 1706 85 86 269 160;
307 53.8 -4 10.45; 308 55 -4 10.45; 309 56.5 -4 10.45; 310 58 -4 10.45; 1708 39 40 83 82; 1709 40 41 84 83 ; 1711 41 42 85 84; 1712 42 43 86 85;
311 59.2 -4 10.45; 312 60 -4 10.45; 313 60.8 -4 10.45; 314 62 -4 10.45; 1713 97 98 175 174; 1714 98 99 176 175; 1715 99 100 177 176;
315 63.2 -4 10.45; 316 65 -4 10.45; 317 66.75 -4 10.45; 318 68 -4 10.45; 1716 100 101 178 177; 1717 103 104 181 180; 1718 104 105 182 181;
319 48.45 -4 10.45; 320 69.55 -4 10.45; 321 48.45 -1.6 10.2; 1719 105 106 183 182; 1720 106 107 184 183; 1721 107 108 185 184;
322 48.45 -1.6 11.7; 323 48.45 -1.6 13.2; 324 48.45 -1.6 14.7; 1722 108 109 187 185; 1723 109 110 188 187; 1724 110 111 189 188;
325 48.45 -1.6 16.45; 326 48.45 -1.6 17.7; 327 69.55 -1.6 10.2; 1727 112 128 205 190; 1730 128 132 207 205; 1732 132 134 209 207;
328 69.55 -1.6 11.7; 329 69.55 -1.6 13.2; 330 69.55 -1.6 14.7; 1735 134 142 211 209; 1738 142 144 213 211; 1739 144 146 411 213;
331 69.55 -1.6 16.45; 332 69.55 -1.6 17.7; 333 50 -1.6 19.25; 1742 146 162 223 411; 1744 162 164 225 223; 1747 164 168 227 225;
334 51.25 -1.6 19.25; 335 52.5 -1.6 19.25; 336 53.75 -1.6 19.25; 1750 168 170 229 227; 1753 170 172 231 229; 1754 172 174 233 231;
337 55 -1.6 19.25; 338 56.5 -1.6 19.25; 339 58 -1.6 19.25; 340 59 -1.6 19.25; 1757 127 129 206 204; 1760 129 133 208 206; 1762 133 141 210 208;
341 60 -1.6 19.25; 342 61 -1.6 19.25; 343 62 -1.6 19.25; 344 63.5 -1.6 19.25; 1765 141 143 212 210; 1768 143 145 214 212; 1769 145 269 415 214;
345 65 -1.6 19.25; 346 66.75 -1.6 19.25; 347 68 -1.6 19.25; 1772 269 163 224 415; 1775 163 167 226 224; 1778 167 169 228 226;
348 48.45 -1.6 19.25; 349 69.55 -1.6 19.25; 350 51.25 -4 1.25; 1781 169 171 230 228; 1784 171 173 232 230; 1785 173 189 247 232;
351 51.25 -4 3.15; 352 51.25 -4 4.35; 353 51.25 -4 5.55; 354 51.25 -4 7.25; 1786 44 59 128 112; 1787 59 61 132 128; 1788 61 63 134 132; 1789 63 68 142 134;
355 66.75 -4 1.25; 356 66.75 -4 3.15; 357 66.75 -4 4.35; 358 66.75 -4 5.55; 1790 68 70 144 142; 1791 70 72 146 144; 1793 1 16 59 44; 1795 16 18 61 59;
359 66.75 -4 7.25; 360 52.5 -4 1.25; 361 53.8 -4 1.25; 362 55 -4 1.25; 1796 18 20 63 61; 1798 20 25 68 63; 1800 25 27 70 68; 1801 27 29 72 70;
363 56.5 -4 1.25; 364 58 -4 1.25; 365 59.2 -4 1.25; 366 60 -4 1.25; 1802 72 87 162 146; 1803 87 89 164 162; 1804 89 91 168 164; 1805 91 93 170 168;
367 60.8 -4 1.25; 368 62 -4 1.25; 369 63.2 -4 1.25; 370 65 -4 1.25; 1806 93 95 172 170; 1807 95 97 174 172; 1808 58 60 129 127; 1809 60 62 133 129;
371 52.5 -4 7.25; 372 53.8 -4 7.25; 373 55 -4 7.25; 374 56.5 -4 7.25; 1810 62 67 141 133; 1811 67 69 143 141; 1812 69 71 145 143; 1813 71 86 269 145;
375 58 -4 7.25; 376 59.2 -4 7.25; 377 60 -4 7.25; 378 60.8 -4 7.25; 1815 15 17 60 58; 1817 17 19 62 60; 1818 19 24 67 62; 1820 24 26 69 67;
379 62 -4 7.25; 380 63.2 -4 7.25; 381 65 -4 7.25; 382 66.75 -1.6 11.7; 1822 26 28 71 69; 1823 28 43 86 71; 1824 86 88 163 269; 1825 88 90 167 163;
383 66.75 -1.6 13.2; 384 66.75 -1.6 14.7; 386 51.25 -1.6 11.7; 1826 90 92 169 167; 1827 92 94 171 169; 1828 94 96 173 171;
387 51.25 -1.6 13.2; 388 51.25 -1.6 14.7; 390 52.5 -1.6 16.45; 1829 96 111 189 173; 1881 302 273 1 287; 1882 287 1 2 288; 1883 288 2 3 289;
391 53.75 -1.6 16.45; 392 55 -1.6 16.45; 393 56.5 -1.6 16.45; 1884 289 3 4 290; 1885 290 4 5 291; 1886 291 5 6 292; 1887 292 6 7 293;
394 58 -1.6 16.45; 395 59 -1.6 16.45; 396 60 -1.6 16.45; 397 61 -1.6 16.45; 1888 293 7 8 294; 1889 294 8 9 295; 1890 295 9 10 296; 1891 296 10 11 297;
398 62 -1.6 16.45; 399 63.5 -1.6 16.45; 400 65 -1.6 16.45; 1892 297 11 12 298; 1893 298 12 13 299; 1894 299 13 14 300; 1895 300 14 15 301;
401 66.75 -1.6 16.45; 402 51.25 -1.6 16.45; 403 51.25 -1.6 10.2; 1896 301 15 280 303; 1897 273 274 16 1; 1898 1 16 350 2; 1899 2 350 360 3;
404 66.75 -1.6 10.2; 406 65.9 0 4.35; 409 65.9 0 2.04; 410 65.9 0 3.01; 1900 3 360 361 4; 1901 4 361 362 5; 1902 5 362 363 6; 1903 6 363 364 7;
411 50 6.4 8.7; 412 55 6.4 8.7; 413 58 6.4 8.7; 414 62 6.4 8.7; 415 68 6.4 8.7; 1904 7 364 365 8; 1905 8 365 366 9; 1906 9 366 367 10; 1907 10 367 368 11;
416 55 6.4 17.7; 417 58 6.4 17.7; 418 48.45 -1.6 8.7; 419 69.55 -1.6 8.7; 1908 11 368 369 12; 1909 12 369 370 13; 1910 13 370 355 14; 1911 14 355 17 15;
420 55 -4 3.15; 421 58 -4 3.15; 422 62 -4 3.15; 423 53.8 -4 3.15; 1912 15 17 281 280; 1913 274 275 18 16; 1914 16 18 351 350; 1915 275 276 20 18;
424 56.8 -4 3.15; 425 60.8 -4 3.15; 426 56.2 -4 3.15; 427 59.2 -4 3.15; 1916 18 20 352 351; 1917 276 277 25 20; 1918 20 25 353 352; 1919 277 278 27 25;
428 63.2 -4 3.15; 429 55 -4 5.55; 430 58 -4 5.55; 431 62 -4 5.55; 1920 25 27 354 353; 1921 278 279 29 27; 1922 27 29 30 354; 1923 355 356 19 17;
432 53.8 -4 5.55; 433 56.8 -4 5.55; 434 60.8 -4 5.55; 435 56.2 -4 5.55; 1924 17 19 282 281; 1925 356 357 24 19; 1926 19 24 283 282; 1927 357 358 26 24;
436 59.2 -4 5.55; 437 63.2 -4 5.55; 438 53.8 -4 4.35; 439 56.8 -4 4.35; 1928 24 26 284 283; 1929 358 359 28 26; 1930 26 28 285 284; 1931 354 30 31 371;
440 60.8 -4 4.35; 441 56.2 -4 4.35; 442 59.2 -4 4.35; 443 63.2 -4 4.35; 1932 371 31 32 372; 1933 372 32 33 373; 1936 375 35 36 376; 1937 376 36 37 377;
444 58 0 17.05; 445 60 0 17.05; 446 52.5 -4 3.15; 447 52.5 -4 4.35; 1938 377 37 38 378; 1939 378 38 39 379; 1940 379 39 40 380; 1941 380 40 41 381;
448 52.5 -4 5.55; 453 65 -4 3.15; 454 65 -4 5.55; 455 65 -4 4.35; 1942 381 41 42 359; 1943 359 42 43 28; 1944 28 43 286 285; 1945 279 319 304 29;
456 56.5 -4 2.3738; 458 60 -4 3.15; 459 60 -4 5.55; 460 60 -4 4.35; 1946 29 304 305 30; 1947 30 305 306 31; 1948 31 306 307 32; 1949 32 307 308 33;
461 56.5 -4 6.11668; 1950 33 308 309 34; 1951 34 309 310 35; 1952 35 310 311 36; 1953 36 311 312 37;
MEMBER INCIDENCES 1954 37 312 313 38; 1955 38 313 314 39; 1956 39 314 315 40; 1957 40 315 316 41;
17 5 362; 18 7 364; 19 11 368; 24 20 352; 25 21 441; 26 22 442; 27 23 443; 1958 41 316 317 42; 1959 42 317 318 43; 1960 43 318 320 286;
30 21 429; 31 22 430; 32 23 431; 51 1 44; 52 5 48; 53 7 50; 54 11 54; 55 15 58; 1961 321 322 89 87; 1962 87 89 386 403; 1963 322 323 91 89; 1964 89 91 387 386;
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 73 of 361
1965 323 324 93 91; 1966 91 93 388 387; 1967 324 325 95 93; 1968 93 95 402 388; 2047 PRIS YD 0.1 ZD 0.1
1969 404 382 90 88; 1970 88 90 328 327; 1971 382 383 92 90; 1972 90 92 329 328; ************************************************************
1973 383 384 94 92; 1974 92 94 330 329; 1975 384 401 96 94; 1976 94 96 331 330; ********************************************************************************
1977 325 326 97 95; 1978 95 97 98 402; 1979 402 98 99 390; 1980 390 99 100 391; *** WIND GENERATION
1981 391 100 101 392; 1982 392 101 102 393; 1983 393 102 103 394; ********************************************************************************
1984 394 103 104 395; 1985 395 104 105 396; 1986 396 105 106 397; SUPPORTS
1987 397 106 107 398; 1988 398 107 108 399; 1989 399 108 109 400; 1881 TO 1933 1936 TO 1960 2033 TO 2044 2102 TO 2109 2115 2118 2119 2124 2127 -
1990 400 109 110 401; 1991 401 110 111 96; 1992 96 111 332 331; 2128 TO 2129 2131 TO 2146 2152 2153 2155 TO 2163 2165 TO 2166 -
1993 326 348 333 97; 1994 97 333 334 98; 1995 98 334 335 99; 2167 PLATE MAT DIRECT Y SUBGRADE 10320 PRINT
1996 99 335 336 100; 1997 100 336 337 101; 1998 101 337 338 102; 1961 TO 2008 2017 TO 2020 PLATE MAT DIRECT Y SUBGRADE 12288 PRINT
1999 102 338 339 103; 2000 103 339 340 104; 2001 104 340 341 105; MEMBER RELEASE
2002 105 341 342 106; 2003 106 342 343 107; 2004 107 343 344 108; 103 156 157 1834 1843 1854 2047 START MY MZ
2005 108 344 345 109; 2006 109 345 346 110; 2007 110 346 347 111; 156 157 1862 2011 2012 2014 2047 END MY MZ
2008 111 347 349 332; 2017 418 321 87 72; 2018 72 87 403 73; DEFINE WIND LOAD
2019 86 88 327 419; 2020 85 404 88 86; 2033 423 438 21 420; TYPE 1
2034 420 21 441 426; 2035 438 432 429 21; 2036 21 429 435 441; INT 0.9181 0 0 0 0 0 0 0 0 0 0 HEIG 4.43 0 0 0 0 0 0 0 0 0 0
2037 424 439 22 421; 2038 439 433 430 22; 2039 421 22 442 427; ********************************************************************************
2040 22 430 436 442; 2041 425 440 23 422; 2042 422 23 443 428; *** LOAD - SEISMIC
2043 440 434 431 23; 2044 23 431 437 443; 2102 350 351 446 360; ********************************************************************************
2103 351 352 447 446; 2104 352 353 448 447; 2105 353 354 371 448; DEFINE IBC 2006
2106 360 446 423 361; 2107 447 448 432 438; 2108 448 371 372 432; SS 0.32 S1 0.13 I 1.25 RX 4 RZ 4 SCLASS 3 CT 0 PX 0.1964 PZ 0.1964 TL 8 FA 1.27 -
2109 432 372 373 429; 2115 429 373 374 435; 2118 364 421 427 365; FV 1.67 K 0
2119 367 425 422 368; 2124 430 375 376 436; 2127 434 378 379 431; SELFWEIGHT 1
2128 368 422 428 369; 2129 431 379 380 437; 2131 369 428 453 370; MEMBER WEIGHT
2132 370 453 356 355; 2133 428 443 455 453; 2134 453 455 357 356; ***PARAPET***
2135 443 437 454 455; 2136 455 454 358 357; 2137 437 380 381 454; 202 TO 221 228 TO 233 241 TO 246 253 TO 272 UNI 1.125
2138 454 381 359 358; 2139 361 423 420 362; 2140 446 447 438 423; ***EXTERNAL***
2141 363 424 421 364; 2142 362 420 426 363; 2143 456 424 363; 2144 456 426 424; 86 TO 102 104 110 114 115 123 124 131 TO 134 150 151 154 155 158 159 164 165 -
2145 456 363 426; 2146 373 33 34 374; 2152 441 435 433 439; 168 TO 183 185 186 1832 2169 2171 2172 UNI 12
2153 426 441 439 424; 2155 365 427 458 366; 2156 427 442 460 458; ***INTERNAL***
2157 442 436 459 460; 2158 436 376 377 459; 2159 366 458 425 367; 103 135 TO 142 146 148 149 153 156 157 1 60 167 1847 2013 2015 2016 -
2160 458 460 440 425; 2161 460 459 434 440; 2162 459 377 378 434; 2045 UNI 22.8
2163 433 374 375 430; 2164 461 433 435; 2165 461 374 433; 2166 461 435 374; **HAVC PAD WEIGHT**
2167 374 34 35 375; 161 UNI 3.55 3.3 7.4
START GROUP DEFINITION 160 UNI 1.07 3.3 7.4
ELEMENT 162 UNI 0.66 3.3 7.4
_BS1 2102 TO 2109 2115 2118 2119 2124 2127 TO 2129 2131 TO 2145 - 161 UNI 2.97 3.3 7.4
2152 2153 2155 TO 2163 2165 2166 162 UNI 2.98 2.75 7.4
_4MRAFT 1881 TO 1933 1936 TO 1960 2033 TO 2044 2102 TO 2109 2115 2118 2119 - 161 UNI 0.27 2.75 7.4
2124 2127 TO 2129 2131 TO 2146 2152 2153 2155 TO 2167 163 UNI 1.63 2.75 7.4
_WF1 1881 TO 1920 1923 TO 1930 162 UNI 5.37 2.75 7.4
_WF2 1921 1922 1931 TO 1933 1936 TO 1960 2146 2167 159 165 UNI 3.84
_F1 2033 TO 2044 163 UNI 6.41 2.75 7.4
_WF1A 1961 TO 2008 2017 TO 2020 2047 CON 5 0.8
FLOOR FLOOR WEIGHT
_ROOF 202 TO 224 226 TO 237 239 TO 249 251 TO 272 _ROOF FLOAD 8.52
_1F 86 TO 104 106 107 109 110 114 TO 119 123 124 126 127 131 TO 142 146 148 - _1F FLOAD 4.9
149 TO 157 159 TO 163 165 167 169 171 176 TO 183 185 186 1830 1832 TO 1838 - _1F(BATTERY) FLOAD 6.3
1840 TO 1848 1853 TO 1857 1861 1862 2009 2011 TO 2016 2045 2046 2169 2171 - ELEMENT WEIGHT
2172 1898 TO 1911 1914 1916 1918 1920 1922 1923 1925 1927 1929 1931 TO 1933 1936 -
_1F(BATTERY) 156 TO 158 164 166 TO 168 170 172 TO 175 1937 TO 1943 2033 TO 2044 2102 TO 2109 2118 2119 2124 2127 TO 2 129 -
_-1F 17 TO 19 24 TO 27 30 TO 32 1873 TO 1880 2021 TO 2032 2101 2130 2154 2131 TO 2140 PRESSURE 0.4
_(-X) 101 110 114 123 131 133 150 154 158 164 168 170 187 197 216 218 220 - ************************************************************
228 230 232 241 243 245 253 255 257 1832 2088 2169 2172 LOAD 8 LOADTYPE Seismic TITLE SEISMIC LOAD(EXL)
_(+X) 102 104 115 124 132 134 151 155 159 165 169 171 191 201 217 219 221 - IBC LOAD X 1
229 231 233 242 244 246 254 256 258 2093 2171 PERFORM ANALYSIS
_(-Z) 86 TO 100 187 TO 191 202 TO 215 CHANGE
_(+Z) 172 TO 183 185 186 197 200 201 259 TO 272 2098 2100 ************************************************************
END GROUP DEFINITION LOAD 9 LOADTYPE Seismic TITLE SEISMIC LOAD(EZL)
ELEMENT PROPERTY IBC LOAD Z 1
1580 1581 1584 TO 1587 1589 1590 1592 1593 1595 TO 1598 1601 1602 1605 1606 - PERFORM ANALYSIS
1609 1610 1613 1614 1617 1618 1621 1622 1625 1626 1629 1630 1633 1634 1637 - CHANGE
1638 1641 1642 1645 TO 1650 1652 1653 1655 TO 1660 1662 1663 1665 TO 1670 - ************************************************************
1672 1673 1675 1676 1678 1679 1681 1682 1684 1685 1687 1688 1690 1691 1693 - LOAD 1 LOADTYPE Dead TITLE DEAD LOAD(DL)
1694 1696 1697 1699 1700 1702 1703 1705 1706 1708 1709 1711 TO 1724 1727 - SELFWEIGHT Y -1
1730 1732 1735 1738 1739 1742 1744 1747 1750 1753 1754 1757 1760 1762 1765 - ONEWAY LOAD
1768 1769 1772 1775 1778 1781 1784 TO 1791 1793 1795 1796 1798 1800 TO 1813 - _ROOF ONE -8.52 GY
1815 1817 1818 1820 1822 TO 1829 THICKNESS 0.3 FLOOR LOAD
1881 TO 1920 1923 TO 1930 THICKNESS 0.6 _1F FLOAD -4.9 GY
1921 1922 1931 TO 1933 1936 TO 1960 2146 2167 THICKNESS 0.6 _1F(BATTERY) FLOAD -6.3 GY
2033 TO 2044 THICKNESS 0.6 ELEMENT LOAD
1961 TO 2008 2017 TO 2020 THICKNESS 0.6 1898 TO 1911 1914 1916 1918 1920 1922 1923 1925 1927 1929 1931 TO 1933 1936 -
2102 TO 2109 2115 2118 2119 2124 2127 TO 2129 2131 TO 2145 2152 2153 2155 - 1937 TO 1943 2033 TO 2044 2102 TO 2109 2115 2118 2119 2124 2127 TO 2129 2131 -
2156 TO 2166 THICKNESS 0.2 2132 TO 2146 2152 2153 2155 TO 2167 PR GY -0.4
DEFINE MATERIAL START MEMBER LOAD
ISOTROPIC STEEL ***PARAPET***
E 2.05e+008 202 TO 221 228 TO 233 241 TO 246 253 TO 272 UNI GY -1.125
POISSON 0.3 ***EXTERNAL***
DENSITY 76.8195 86 TO 102 104 110 114 115 123 124 131 TO 134 150 151 154 155 158 159 164 165 -
ALPHA 1.2e-005 168 TO 183 185 186 1832 2169 2171 2172 UNI GY -12
DAMP 0.03 ***INTERNAL***
ISOTROPIC CONCRETE 103 135 TO 142 146 148 149 153 156 157 160 167 1847 2013 2015 2016 -
E 2.17185e+007 2045 UNI GY -22.8
POISSON 0.17 **HAVC PAD WEIGHT**
DENSITY 25 MEMBER LOAD
ALPHA 1e-005 161 UNI GY -3.55 3.3 7.4
DAMP 0.05 160 UNI GY -1.07 3.3 7.4
ISOTROPIC ALUMINUM 162 UNI GY -0.66 3.3 7.4
E 6.89476e+007 161 UNI GY -2.97 3.3 7.4
POISSON 0.33 162 UNI GY -2.98 2.75 7.4
DENSITY 26.6018 161 UNI GY -0.27 2.75 7.4
ALPHA 2.3e-005 163 UNI GY -1.63 2.75 7.4
DAMP 0.03 162 UNI GY -5.37 2.75 7.4
END DEFINE MATERIAL 159 165 UNI GY -3.84
CONSTANTS 163 UNI GY -6.41 2.75 7.4
MATERIAL CONCRETE ALL 2047 CON GY -5 0.8
MEMBER PROPERTY AMERICAN ELEMENT LOAD
51 TO 55 61 TO 70 76 TO 85 187 TO 191 197 200 201 2088 2090 TO 2093 2098 - 1881 TO 1897 1912 1913 1915 1917 1919 1921 1924 1926 1928 1930 1944 TO 1959 -
2100 PRIS YD 0.6 ZD 0.6 1960 PR GY -57.8
152 153 160 TO 163 166 167 222 TO 224 226 227 234 TO 237 239 240 247 TO 249 - 1961 TO 2008 2017 TO 2020 PR GY -17
251 252 2045 2046 PRIS YD 0.8 ZD 0.4 ************************************************************
1834 1837 1838 1843 TO 1845 1854 1856 1857 1862 2011 2012 PRIS YD 0.6 ZD 0.3 LOAD 2 LOADTYPE Live TITLE LIVE LOAD(LL)
17 TO 19 24 TO 27 30 TO 32 1873 TO 1880 2021 TO 2032 2101 2130 - ONEWAY LOAD
2154 PRIS YD 0.6 ZD 0.4 _ROOF ONE -1 GY
156 157 PRIS YD 0.5 ZD 0.3 FLOOR LOAD
56 TO 60 71 TO 75 PRIS YD 0.5 ZD 0.5 _1F FLOAD -20 GY
202 TO 221 228 TO 233 241 TO 246 253 TO 272 PRIS YD 0.8 ZD 0.45 _1F(BATTERY) FLOAD -20 GY
135 TO 142 146 148 TO 151 154 155 158 159 164 165 168 TO 183 185 186 1847 - ELEMENT LOAD
2015 2016 PRIS YD 0.8 ZD 0.5 1898 TO 1911 1914 1916 1918 1920 1922 1923 1925 1927 1929 1931 TO 19 33 1936 -
106 107 109 119 126 127 1830 1833 1835 1836 1840 TO 1842 1846 1848 1853 1855 - 1937 TO 1943 2033 TO 2044 2102 TO 2109 2115 2118 2119 2124 2127 TO 2129 2131 -
1861 2009 PRIS YD 0.7 ZD 0.4 2132 TO 2146 2152 2153 2155 TO 2167 PR GY -5
86 TO 102 104 110 114 115 123 124 131 TO 134 1832 2169 2171 - *************************************************************
2172 PRIS YD 0.7 ZD 0.45 LOAD 4 LOADTYPE Wind TITLE WIND LOAD(WXL)
103 2013 2014 PRIS YD 0.7 ZD 0.35 FLOOR LOAD
116 TO 118 PRIS YD 0.7 ZD 0.35 _ROOF FLOAD 1.671 GY
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 74 of 361
ONEWAY LOAD LOAD COMB 106 1.0DL-0.6WZL
_(-X) ONE 1.519 GX 1 1.0 7 0.6
_(+X) ONE 0.77 GX LOAD COMB 107 1.0DL+0.7EXL
_(-Z) ONE -0.77 GZ TOWARDS 187 1 1.0 8 0.7
_(+Z) ONE 0.77 GZ TOWARDS 197 LOAD COMB 108 1.0DL+0.7EZL
************************************************************ 1 1.0 9 0.7
LOAD 5 LOADTYPE Wind TITLE WIND LOAD(WZL) LOAD COMB 109 1.0DL-0.7EXL
FLOOR LOAD 1 1.0 8 -0.7
_ROOF FLOAD 1.671 GY LOAD COMB 110 1.0DL-0.7EZL
ONEWAY LOAD 1 1.0 9 -0.7
_(-X) ONE -0.77 GX LOAD COMB 111 DL+0.75LL+0.45WXL
_(+X) ONE 0.77 GX 1 1.0 2 0.75 4 0.45
_(-Z) ONE 1.519 GZ TOWARDS 187 LOAD COMB 112 DL+0.75LL+0.45WZL
_(+Z) ONE 0.77 GZ TOWARDS 197 1 1.0 2 0.75 5 0.45
************************************************************ LOAD COMB 113 DL+0.75LL-0.45WXL
LOAD 6 LOADTYPE Wind TITLE WIND LOAD(-WXL) 1 1.0 2 0.75 6 0.45
FLOOR LOAD LOAD COMB 114 DL+0.75LL-0.45WZL
_ROOF FLOAD 1.671 GY 1 1.0 2 0.75 7 0.45
ONEWAY LOAD LOAD COMB 115 DL+0.75LL+0.525EXL
_(-X) ONE -0.77 GX 1 1.0 2 0.75 8 0.525
_(+X) ONE -1.519 GX LOAD COMB 116 DL+0.75LL-0.525EXL
_(-Z) ONE -0.77 GZ TOWARDS 187 1 1.0 2 0.75 9 0.525
_(+Z) ONE 0.77 GZ TOWARDS 197 LOAD COMB 117 DL+0.75LL+0.525EZL
************************************************************ 1 1.0 2 0.75 8 -0.525
LOAD 7 LOADTYPE Wind TITLE WIND LOAD(-WZL) LOAD COMB 118 DL+0.75LL-0.525EZL
FLOOR LOAD 1 1.0 2 0.75 9 -0.525
_ROOF FLOAD 1.671 GY LOAD COMB 119 DL+0.75LL+1.0HL
ONEWAY LOAD 1 1.0 2 0.75 10 1.0
_(-X) ONE -0.77 GX ******LOAD COMBINATION : STRENGTH DESIGN******
_(+X) ONE 0.77 GX ******OPERATION******
_(-Z) ONE -0.77 GZ TOWARDS 187 LOAD COMB 201 1.4DL
_(+Z) ONE -1.519 GZ TOWARDS 197 1 1.4
************************************************************* LOAD COMB 202 1.2DL+1.6LL
LOAD 10 LOADTYPE None TITLE EARTH PRESSURE LOAD(HL) 1 1.2 2 1.6
ELEMENT LOAD LOAD COMB 203 0.9DL+1.0WXL
1793 1795 1796 1798 1800 1801 TRAP GX Y 43.7 14.96 1 0.9 4 1.0
1815 1817 1818 1820 1822 1823 TRAP GX Y -43.7 -14.96 LOAD COMB 204 0.9DL+1.0WZL
1589 1590 1652 1653 1655 1656 1662 1663 1665 1666 1672 1673 1675 - 1 0.9 5 1.0
1676 TRAP GZ Y 43.7 14.96 LOAD COMB 205 0.9DL-1.0WXL
1595 1596 1684 1685 1687 1688 1696 1697 1699 1700 1708 1709 1711 - 1 0.9 6 1.0
1712 TRAP GZ Y -43.7 -14.96 LOAD COMB 206 0.9DL-1.0WZL
1786 TO 1791 1802 TO 1807 1824 TO 1829 TRAP GX Y 14.96 0 1 0.9 7 1.0
1802 TO 1813 1824 TO 1829 TRAP GX Y -14.96 0 LOAD COMB 207 0.9DL+1.0EXL
1586 1587 1597 1598 1647 TO 1650 1657 TO 1660 1667 TO 1670 1713 TO 1723 - 1 0.9 8 1.0
1724 TRAP GZ Y 14.96 0 LOAD COMB 208 0.9DL+1.0EZL
1592 1593 1597 1598 1678 1679 1681 1682 1690 1691 1693 1694 1702 1703 1705 - 1 0.9 9 1.0
1706 1713 TO 1724 TRAP GZ Y -14.96 0 LOAD COMB 209 0.9DL-1.0EXL
ELEMENT LOAD 1 0.9 8 -1.0
1881 TO 1933 1936 TO 1960 2033 TO 2044 2102 TO 2109 2115 2118 2119 2124 2127 - LOAD COMB 210 0.9DL-1.0EZL
2128 TO 2129 2131 TO 2146 2152 2153 2155 TO 2167 PR GY 14 1 0.9 9 -1.0
************************************************************* LOAD COMB 211 1.2DL+1.0LL+1.0WXL
LOAD 21 LOADTYPE None TITLE BLAST LOAD (BXCL) 1 1.2 2 1.0 4 1.0
ONEWAY LOAD LOAD COMB 212 1.2DL+1.0LL+1.0WZL
_ROOF ONE -26.06 GY 1 1.2 2 1.0 5 1.0
MEMBER LOAD LOAD COMB 213 1.2DL+1.0LL-1.0WXL
101 110 114 123 131 133 150 154 158 164 168 170 216 218 220 228 230 232 241 - 1 1.2 2 1.0 6 1.0
243 245 253 255 257 1832 2169 2172 UNI GX 83.7 LOAD COMB 214 1.2DL+1.0LL-1.0WZL
************************************************************* 1 1.2 2 1.0 7 1.0
LOAD 22 LOADTYPE None TITLE BLAST LOAD (BXTL) LOAD COMB 215 1.2DL+1.0LL+1.0EXL
ONEWAY LOAD 1 1.2 2 1.0 8 1.0
_ROOF ONE 32.73 GY LOAD COMB 216 1.2DL+1.0LL+1.0EZL
MEMBER LOAD 1 1.2 2 1.0 9 1.0
101 110 114 123 131 133 150 154 158 164 168 170 216 218 220 228 230 232 241 - LOAD COMB 217 1.2DL+1.0LL-1.0EXL
243 245 253 255 257 1832 2169 2172 UNI GX 83.7 1 1.2 2 1.0 8 -1.0
************************************************************* LOAD COMB 218 1.2DL+1.0LL-1.0EZL
LOAD 23 LOADTYPE None TITLE BLAST LOAD (-BXCL) 1 1.2 2 1.0 9 -1.0
ONEWAY LOAD LOAD COMB 219 1.2DL+1.6LL+1.6HL
_ROOF ONE -26.06 GY 1 1.2 2 1.6 10 1.6
MEMBER LOAD ******LOAD COMBINATION : BLAST DESIGN******
102 104 115 124 132 134 151 155 159 165 169 171 217 219 221 229 231 233 242 - LOAD COMB 301 DL+BXCL
244 246 254 256 258 2171 UNI GX -83.7 1 1.0 21 1.0
************************************************************* LOAD COMB 302 DL+BXTL
LOAD 24 LOADTYPE None TITLE BLAST LOAD (-BXTL) 1 1.0 22 1.0
ONEWAY LOAD LOAD COMB 303 DL-BXCL
_ROOF ONE 32.73 GY 1 1.0 23 1.0
MEMBER LOAD LOAD COMB 304 DL-BXTL
102 104 115 124 132 134 151 155 159 165 169 171 217 219 221 229 231 233 242 - 1 1.0 24 1.0
244 246 254 256 258 2171 UNI GX -83.7 LOAD COMB 305 DL+BZCL
************************************************************* 1 1.0 25 1.0
LOAD 25 LOADTYPE None TITLE BLAST LOAD (BZCL) LOAD COMB 306 DL+BZTL
ONEWAY LOAD 1 1.0 26 1.0
_ROOF ONE -26.06 GY LOAD COMB 307 DL-BZCL
MEMBER LOAD 1 1.0 27 1.0
86 TO 100 202 TO 215 UNI GZ 83.7 LOAD COMB 308 DL-BZTL
************************************************************* 1 1.0 28 1.0
LOAD 26 LOADTYPE None TITLE BLAST LOAD (BZTL) ***************************
ONEWAY LOAD PERFORM ANALYSIS
_ROOF ONE 32.73 GY DEFINE ENVELOPE
MEMBER LOAD 201 TO 219 ENVELOPE 2 TYPE STRENGTH
86 TO 100 202 TO 215 UNI GZ 83.7 101 TO 119 ENVELOPE 1 TYPE SERVICEABILITY
************************************************************* 301 TO 308 ENVELOPE 3 TYPE SERVICEABILITY
LOAD 27 LOADTYPE None TITLE BLAST LOAD (-BZCL) END DEFINE ENVELOPE
ONEWAY LOAD LOAD LIST 1 2 4 TO 9 21 TO 28
_ROOF ONE -26.06 GY LOAD LIST 101 TO 118
MEMBER LOAD ***********************************************************
172 TO 183 185 186 259 TO 272 UNI GZ -83.7 ***********************************************************
************************************************************* LOAD LIST 201 TO 219
LOAD 28 LOADTYPE None TITLE BLAST LOAD (-BZTL) PARAMETER 1
ONEWAY LOAD CODE AISC
_ROOF ONE 32.73 GY START CONCRETE DESIGN
MEMBER LOAD CODE ACI
172 TO 183 185 186 259 TO 272 UNI GZ -83.7 FC 35000 MEMB 17 TO 19 24 TO 27 30 TO 32 51 TO 104 106 107 109 110 -
************************************************************* 114 TO 119 123 124 126 127 131 TO 142 146 148 TO 183 185 TO 191 197 -
******LOAD COMBINATION : ALLOWABLE STRESS DESIGN****** 200 TO 224 226 TO 237 239 TO 249 251 TO 272 1580 1581 1584 TO 1587 1589 1590 -
******OPERATION****** 1592 1593 1595 TO 1598 1601 1602 1605 1606 1609 1610 1613 1614 1617 1618 -
LOAD COMB 101 1.0DL 1621 1622 1625 1626 1629 1630 1633 1 634 1637 1638 1641 1642 1645 TO 1650 -
1 1.0 1652 1653 1655 TO 1660 1662 1663 1665 TO 1670 1672 1673 1675 1676 1678 1679 -
LOAD COMB 102 1.0DL+1.0LL 1681 1682 1684 1685 1687 1688 1690 1691 1693 1694 1696 1697 1699 1700 1702 -
1 1.0 2 1.0 1703 1705 1706 1708 1709 1711 TO 1724 1727 1730 1732 1735 1738 1739 1742 -
LOAD COMB 103 1.0DL+0.6WXL 1744 1747 1750 1753 1754 1757 1760 1762 1765 1768 1769 1772 1775 1778 1781 -
1 1.0 4 0.6 1784 TO 1791 1793 1795 1796 1798 1800 TO 1813 1815 1817 1818 1820 -
LOAD COMB 104 1.0DL+0.6WZL 1822 TO 1830 1832 TO 1838 1840 TO 1848 1853 TO 1857 1861 1862 1873 TO 1933 -
1 1.0 5 0.6 1936 TO 2009 2011 TO 2044 2088 2090 TO 2093 2098 2100 2101 2130 2154 2169 -
LOAD COMB 105 1.0DL-0.6WXL 2171 2172
1 1.0 6 0.6 FYMAIN 414000 MEMB 17 TO 19 24 TO 27 30 TO 32 51 TO 104 106 107 109 110 114 -
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 75 of 361
115 TO 119 123 124 126 127 131 TO 142 146 148 TO 183 185 TO 191 197 - 2091 TO 2093 2098 2100
200 TO 224 226 TO 237 239 TO 249 251 TO 272 1580 1581 1584 TO 1587 1589 1590 - **C2**
1592 1593 1595 TO 1598 1601 1602 1605 1606 1609 1610 1613 1614 1617 1618 - DESIGN COLUMN 56 TO 60 71 TO 75
1621 1622 1625 1626 1629 1630 1633 1634 1637 1638 1641 1642 1645 TO 1650 - **W1**
1652 1653 1655 TO 1660 1662 1663 1665 TO 1670 1672 1673 1675 1676 1678 1679 - DESIGN ELEMENT 1580 1581 1584 TO 1587 1589 1590 1592 1593 1595 TO 1598 1601 -
1681 1682 1684 1685 1687 1688 1690 1691 1693 1694 1696 1697 1699 1700 1702 - 1602 1605 1606 1609 1610 1613 1614 1617 1618 1621 1622 1625 1626 1629 1630 -
1703 1705 1706 1708 1709 1711 TO 1724 1727 1730 1732 1735 1738 1739 1742 - 1633 1634 1637 1638 1641 1642 1645 TO 1650 1652 1653 1655 TO 1660 1662 1663 -
1744 1747 1750 1753 1754 1757 1760 1762 1765 1768 1769 1772 1775 1778 1781 - 1665 TO 1670 1672 1673 1675 1676 1678 1679 1681 1682 1684 1685 1687 1688 -
1784 TO 1791 1793 1795 1796 1798 1800 TO 1813 1815 1817 1818 1820 - 1690 1691 1693 1694 1696 1697 1699 1700 1702 1703 1705 1706 1708 1709 1711 -
1822 TO 1830 1832 TO 1838 1840 TO 1848 1853 TO 1857 1861 1862 1873 TO 1933 - 1712 TO 1724 1727 1730 1732 1735 1738 1739 1742 1744 1747 1750 1753 1754 1757 -
1936 TO 2009 2011 TO 2044 2088 2090 TO 2093 2098 2100 2101 2130 2154 2169 - 1760 1762 1765 1768 1769 1772 1775 1778 1781 1784 TO 1791 1793 1795 1796 -
2171 2172 1798 1800 TO 1813 1815 1817 1818 1820 1822 TO 1829
FYSEC 414000 ALL END CONCRETE DESIGN
CLT 0.04 MEMB 17 TO 19 24 TO 27 30 TO 32 86 TO 104 106 107 109 110 - ***************
114 TO 119 123 124 126 127 131 TO 142 146 148 TO 183 185 186 202 TO 224 226 - ***************
227 TO 237 239 TO 249 251 TO 272 1830 1832 TO 1838 1840 TO 1848 1853 TO 1857 - *LOAD LIST 301 TO 308
1861 1862 1873 TO 1880 2009 2011 TO 2016 2021 TO 2032 2045 2046 2101 2130 - *PARAMETER 2
2154 2169 2171 2172 *CODE AISC
CLT 0.075 MEMB 51 TO 85 187 TO 191 197 200 201 1580 1581 1584 TO 1587 1589 - *START CONCRETE DESIGN
1590 1592 1593 1595 TO 1598 1601 1602 1605 1606 1609 1610 1613 1614 1617 - *CODE ACI
1618 1621 1622 1625 1626 1629 1630 1633 1634 1637 1638 1641 1642 - *FC 41700 MEMB 17 TO 19 24 TO 27 30 TO 32 51 TO 104 106 107 109 110 -
1645 TO 1650 1652 1653 1655 TO 1660 1662 1663 1665 TO 1670 1672 1673 1675 - *114 TO 119 123 124 126 127 131 TO 142 146 148 TO 183 185 TO 191 197 -
1676 1678 1679 1681 1682 1684 1685 1687 1688 1690 1691 1693 1694 1696 1697 - *200 TO 224 226 TO 237 239 TO 249 251 TO 272 1580 1581 1584 TO 1587 1589 1590 -
1699 1700 1702 1703 1705 1706 1708 1709 1711 TO 1724 1727 1730 1732 1735 - *1592 1593 1595 TO 1598 1601 1602 1605 1606 1609 1610 1613 1614 1617 1618 -
1738 1739 1742 1744 1747 1750 1753 1754 1757 1760 1762 1765 1768 1769 1772 - *1621 1622 1625 1626 1629 1630 1633 1634 1637 1638 1641 1642 1645 TO 1650 -
1775 1778 1781 1784 TO 1791 1793 1795 1796 1798 1800 TO 1813 1815 1817 1818 - *1652 1653 1655 TO 1660 1662 1663 1665 TO 1670 1672 1673 1675 1676 1678 1679 -
1820 1822 TO 1829 2088 2090 TO 2093 2098 2100 *1681 1682 1684 1685 1687 1688 1690 1691 1693 1694 1696 1697 1699 1700 1702 -
CLS 0.04 MEMB 17 TO 19 24 TO 27 30 TO 32 86 TO 104 106 107 109 110 - *1703 1705 1706 1708 1709 1711 TO 1724 1727 1730 1732 1735 1738 1739 174 2 -
114 TO 119 123 124 126 127 131 TO 142 146 148 TO 183 185 186 202 TO 224 226 - *1744 1747 1750 1753 1754 1757 1760 1762 1765 1768 1769 1772 1775 1778 1781 -
227 TO 237 239 TO 249 251 TO 272 1830 1832 TO 1838 1840 TO 1848 1853 TO 1857 - *1784 TO 1791 1793 1795 1796 1798 1800 TO 1813 1815 1817 1818 1820 -
1861 1862 1873 TO 1880 2009 2011 TO 2016 2021 TO 2032 2045 2046 2101 2130 - *1822 TO 1830 1832 TO 1848 1852 TO 1857 1859 1861 1862 1873 TO 2009 -
2154 2169 2171 2172 *2011 TO 2044 2088 2090 TO 2093 2098 2100
CLS 0.075 MEMB 51 TO 85 187 TO 191 197 200 201 2088 2090 TO 2093 2098 2100 *FYMAIN 532800 MEMB 17 TO 19 24 TO 27 30 TO 32 51 TO 104 106 107 109 110 114 -
CLB 0.04 MEMB 17 TO 19 24 TO 27 30 TO 32 86 TO 104 106 107 109 110 - *115 TO 119 123 124 126 127 131 TO 142 146 148 TO 183 185 TO 191 197 -
114 TO 119 123 124 126 127 131 TO 142 146 148 TO 183 185 186 202 TO 224 226 - *200 TO 224 226 TO 237 239 TO 249 251 TO 272 1580 1581 1584 TO 1587 1589 1590 -
227 TO 237 239 TO 249 251 TO 272 1830 1832 TO 1838 1840 TO 1848 1853 TO 1857 - *1592 1593 1595 TO 1598 1601 1602 1605 1606 1609 1610 1613 1614 1617 1618 -
1861 1862 1873 TO 1880 2009 2011 TO 2016 2021 TO 2032 2045 2046 2101 2130 - *1621 1622 1625 1626 1629 1630 1633 1634 1637 1638 1641 1642 1645 TO 1650 -
2154 2169 2171 2172 *1652 1653 1655 TO 1660 1662 1663 1665 TO 1670 1672 1673 1675 1676 1678 1679 -
CLB 0.075 MEMB 51 TO 85 187 TO 191 197 200 201 1580 1581 1584 TO 1587 1589 - *1681 1682 1684 1685 1687 1688 1690 1691 1693 1694 1696 1697 1699 1700 1702 -
1590 1592 1593 1595 TO 1598 1601 1602 1605 1606 1609 1610 1613 1614 1617 - *1703 1705 1706 1708 1709 1711 TO 1724 1727 1730 1732 1735 1738 1739 1742 -
1618 1621 1622 1625 1626 1629 1630 1633 1634 1637 1638 1641 1642 - *1744 1747 1750 1753 1754 1757 1760 1762 1765 1768 1769 1772 1775 1778 1781 -
1645 TO 1650 1652 1653 1655 TO 1660 1662 1663 1665 TO 1670 1672 1673 1675 - *1784 TO 1791 1793 1795 1796 1798 1800 TO 1813 1815 1817 1818 1820 -
1676 1678 1679 1681 1682 1684 1685 1687 1688 1690 1691 1693 1694 1696 1697 - *1822 TO 1830 1832 TO 1848 1852 TO 1857 1859 1861 1862 1873 TO 2009 -
1699 1700 1702 1703 1705 1706 1708 1709 1711 TO 1724 1727 1730 1732 1735 - *2011 TO 2044 2088 2090 TO 2093 2098 2100
1738 1739 1742 1744 1747 1750 1753 1754 1757 1760 1762 1765 1768 1769 1772 - *FYSEC 532800 MEMB 17 TO 19 24 TO 27 30 TO 32 51 TO 104 106 107 109 110 114 -
1775 1778 1781 1784 TO 1791 1793 1795 1796 1798 1800 TO 1813 1815 1817 1818 - *115 TO 119 123 124 126 127 131 TO 142 146 148 TO 183 185 TO 191 197 -
1820 1822 TO 1829 2088 2090 TO 2093 2098 2100 *200 TO 224 226 TO 237 239 TO 249 251 TO 272 1830 1832 TO 1848 1852 TO 1857 -
MAXMAIN 25 MEMB 51 TO 85 152 153 160 TO 163 166 167 187 TO 191 197 200 201 - *1859 1861 1862 1873 TO 1880 2009 2011 TO 2016 2021 TO 2032 2045 TO 2047 2088 -
2045 2046 2088 2090 TO 2093 2098 2100 *2090 TO 2093 2098 2100
MINMAIN 25 MEMB 51 TO 85 152 153 160 TO 163 166 167 187 TO 191 197 200 201 - *CLT 0.05 MEMB 17 TO 19 24 TO 27 30 TO 32 86 TO 104 106 107 109 110 -
2045 2046 2088 2090 TO 2093 2098 2100 *114 TO 119 123 124 126 127 131 TO 142 146 148 TO 183 185 186 202 TO 224 226 -
MINSEC 10 MEMB 17 TO 19 24 TO 27 30 TO 32 51 TO 104 106 107 109 110 - *227 TO 237 239 TO 249 251 TO 272 1580 1581 1584 TO 1587 1589 1590 1592 1593 -
114 TO 119 123 124 126 127 131 TO 142 146 148 TO 183 185 TO 191 197 - *1595 TO 1598 1601 1602 1605 1606 1609 1610 1613 1614 1617 1618 1621 1622 -
200 TO 224 226 TO 237 239 TO 249 251 TO 272 1830 1832 TO 1838 1840 TO 1848 - *1625 1626 1629 1630 1633 1634 1637 1638 1641 1642 1645 TO 1650 1652 1653 -
1853 TO 1857 1861 1862 1873 TO 1880 2009 2011 TO 2016 2021 TO 2032 2045 2046 - *1655 TO 1660 1662 1663 1665 TO 1670 1672 1673 1675 1676 1678 1679 1681 1682 -
2088 2090 TO 2093 2098 2100 2101 2130 2154 2169 2171 2172 *1684 1685 1687 1688 1690 1691 1693 1694 1696 1697 1699 1700 1702 1703 1705 -
MINSEC 10 MEMB 17 TO 19 24 TO 27 30 TO 32 51 TO 104 106 107 109 110 - *1706 1708 1709 1711 TO 1724 1727 1730 1732 1735 1738 1739 1742 1744 1747 -
114 TO 119 123 124 126 127 131 TO 142 146 148 TO 183 185 TO 191 197 - *1750 1753 1754 1757 1760 1762 1765 1768 1769 1772 1775 1778 1781 -
200 TO 224 226 TO 237 239 TO 249 251 TO 272 1830 1832 TO 1838 1840 TO 1848 - *1784 TO 1791 1793 1795 1796 1798 1800 TO 1813 1815 1817 1818 1820 -
1853 TO 1857 1861 1862 1873 TO 1880 2009 2011 TO 2016 2021 TO 2032 2045 2046 - *1822 TO 1830 1832 TO 1848 1852 TO 1857 1859 1861 1862 1873 TO 1880 2009 2011 -
2088 2090 TO 2093 2098 2100 2101 2130 2154 2169 2171 2172 *2012 TO 2016 2021 TO 2032 2045 2046
MINMAIN 20 MEMB 17 TO 19 24 TO 27 30 TO 32 86 TO 104 106 107 109 110 - *CLT 0.075 MEMB 51 TO 85 187 TO 191 197 200 201 2088 2090 TO 2093 2098 2100
114 TO 119 123 124 126 127 131 TO 142 146 148 TO 151 154 TO 159 164 165 168 - *CLS 0.05 MEMB 17 TO 19 24 TO 27 30 TO 32 86 TO 104 106 107 109 110 -
169 TO 183 185 186 202 TO 224 226 TO 237 239 TO 249 251 TO 272 1830 - *114 TO 119 123 124 126 127 131 TO 142 146 148 TO 183 185 186 202 TO 224 226 -
1832 TO 1838 1840 TO 1848 1853 TO 1857 1861 1862 1873 TO 1880 2009 - *227 TO 237 239 TO 249 251 TO 272 1830 1832 TO 1848 1852 TO 1857 1859 1861 -
2011 TO 2016 2021 TO 2032 2101 2130 2154 2169 2171 2172 *1862 1873 TO 1880 2009 2011 TO 2016 2021 TO 2032 2045 2046
MAXMAIN 20 MEMB 17 TO 19 24 TO 27 30 TO 32 86 TO 104 106 107 109 110 - *CLS 0.075 MEMB 51 TO 85 187 TO 191 197 200 201 2088 2090 TO 2093 2098 2100
114 TO 119 123 124 126 127 131 TO 142 146 148 TO 151 154 TO 159 164 165 168 - *CLB 0.05 MEMB 17 TO 19 24 TO 27 30 TO 32 8 6 TO 104 106 107 109 110 -
169 TO 183 185 186 202 TO 224 226 TO 237 239 TO 249 251 TO 272 1830 - *114 TO 119 123 124 126 127 131 TO 142 146 148 TO 183 185 186 202 TO 224 226 -
1832 TO 1838 1840 TO 1848 1853 TO 1857 1861 1862 1873 TO 1880 2009 - *227 TO 237 239 TO 249 251 TO 272 1580 1581 1584 TO 1587 1589 1590 1592 1593 -
2011 TO 2016 2021 TO 2032 2101 2130 2154 2169 2171 2172 *1595 TO 1598 1601 1602 1605 1606 1609 1610 1613 1614 1617 1618 1621 16 22 -
TRACK 0 MEMB 17 TO 19 24 TO 27 30 TO 32 51 TO 104 106 107 109 110 114 TO 119 - *1625 1626 1629 1630 1633 1634 1637 1638 1641 1642 1645 TO 1650 1652 1653 -
123 124 126 127 131 TO 142 146 148 TO 183 185 TO 191 197 200 TO 224 - *1655 TO 1660 1662 1663 1665 TO 1670 1672 1673 1675 1676 1678 1679 1681 1682 -
226 TO 237 239 TO 249 251 TO 272 1830 1832 TO 1838 1840 TO 1848 1853 TO 1857 - *1684 1685 1687 1688 1690 1691 1693 1694 1696 1697 1699 1700 1702 1703 1705 -
1861 1862 1873 TO 1880 2009 2011 TO 2016 2021 TO 2032 2045 2046 2088 2090 - *1706 1708 1709 1711 TO 1724 1727 1730 1732 1735 1738 1739 1742 1744 1747 -
2091 TO 2093 2098 2100 2101 2130 2154 2169 2171 2172 *1750 1753 1754 1757 1760 1762 1765 1768 1769 1772 1775 1778 1781 -
REINF 0 MEMB 51 TO 104 106 107 109 110 114 TO 119 123 124 126 127 131 TO 142 - *1784 TO 1791 1793 1795 1796 1798 1800 TO 1813 1815 1817 1818 1820 -
146 148 TO 183 185 TO 191 197 200 TO 224 226 TO 237 239 TO 249 251 TO 272 - *1822 TO 1830 1832 TO 1848 1852 TO 1857 1859 1861 1862 1873 TO 1880 2009 2011 -
1830 1832 TO 1838 1840 TO 1848 1853 TO 1857 1861 1862 2009 2011 TO 2016 2045 - *2012 TO 2016 2021 TO 2032 2045 2046
2046 2088 2090 TO 2093 2098 2100 2169 2171 2172 *CLB 0.075 MEMB 51 TO 85 187 TO 191 197 200 201 2088 2090 TO 2093 2098 2100
**BG1** *MAXMAIN 25 MEMB 51 TO 85 152 153 160 TO 163 166 167 187 TO 191 197 200 201 -
DESIGN BEAM 17 TO 19 24 TO 27 30 TO 32 1873 TO 1880 2021 TO 2032 2101 2130 2154 *222 TO 224 226 227 234 235 239 240 247 TO 249 251 252 2045 2046 2088 2090 -
**1WG1** *2091 TO 2093 2098 2100
DESIGN BEAM 135 TO 142 146 148 TO 151 154 155 158 159 164 165 168 TO 183 185 - *MINMAIN 25 MEMB 51 TO 85 152 153 160 TO 163 166 167 187 TO 191 197 200 201 -
186 1847 2015 2016 *222 TO 224 226 227 234 235 239 240 247 TO 249 251 252 2045 2046 2088 2090 -
**1WG2** *2091 TO 2093 2098 2100
DESIGN BEAM 86 TO 102 104 110 114 115 123 124 131 TO 134 1832 2169 2171 2172 *MINSEC 10 MEMB 17 TO 19 24 TO 27 30 TO 32 51 TO 104 106 107 109 110 -
**1G1** *114 TO 119 123 124 126 127 131 TO 142 146 148 TO 183 185 TO 191 197 -
DESIGN BEAM 153 160 162 167 2045 *200 TO 224 226 TO 237 239 TO 249 251 TO 272 1830 1832 TO 1848 1852 TO 1857 -
**1G2** *1859 1861 1862 1873 TO 1880 2009 2011 TO 2016 2021 TO 203 2 2045 2046 2088 -
DESIGN BEAM 116 TO 118 *2090 TO 2093 2098 2100
**1G3** *MINSEC 10 MEMB 17 TO 19 24 TO 27 30 TO 32 51 TO 104 106 107 109 110 -
DESIGN BEAM 106 107 109 119 126 127 1830 1833 1835 1836 1840 TO 1842 1846 - *114 TO 119 123 124 126 127 131 TO 142 146 148 TO 183 185 TO 191 197 -
1848 1853 1855 1861 2009 *200 TO 224 226 TO 237 239 TO 249 251 TO 272 1830 1832 TO 1848 1852 TO 1857 -
**1B1** *1859 1861 1862 1873 TO 1880 2009 2011 TO 2016 2021 TO 2032 2045 2046 2088 -
DESIGN BEAM 152 161 163 166 2046 *2090 TO 2093 2098 2100
**1B2** *MINMAIN 20 MEMB 17 TO 19 24 TO 27 30 TO 32 86 TO 104 106 107 109 110 -
DESIGN BEAM 103 2013 2014 *114 TO 119 123 124 126 127 131 TO 142 146 148 TO 151 154 TO 159 164 165 168 -
**1B3** *169 TO 183 185 186 202 TO 221 228 TO 233 236 237 241 TO 246 253 TO 272 1830 -
**1B3a** *1832 TO 1848 1852 TO 1857 1859 1861 1862 1873 TO 1880 2009 2011 TO 2016 2021 -
DESIGN BEAM 156 157 *2022 TO 2032
**1B4** *MAXMAIN 20 MEMB 17 TO 19 24 TO 27 30 TO 32 86 TO 104 106 107 109 110 -
DESIGN BEAM 1834 1837 1838 1843 TO 1845 1854 1856 1857 1862 2011 2012 *114 TO 119 123 124 126 127 131 TO 142 146 148 TO 151 154 TO 159 164 165 168 -
**RWG1** *169 TO 183 185 186 202 TO 221 228 TO 233 236 237 241 TO 246 253 TO 272 1830 -
DESIGN BEAM 202 TO 221 228 TO 233 241 TO 246 253 TO 272 *1832 TO 1848 1852 TO 1857 1859 1861 1862 1873 TO 1880 2009 2011 TO 2016 2021 -
**RG1** *2022 TO 2032
DESIGN BEAM 223 224 226 248 249 251 *TRACK 0 MEMB 17 TO 19 24 TO 27 30 TO 32 51 TO 104 106 107 109 110 114 TO 119 -
**RG2** *123 124 126 127 131 TO 142 146 148 TO 183 185 TO 191 197 200 TO 224 -
DESIGN BEAM 234 235 239 240 *226 TO 237 239 TO 249 251 TO 272 1830 1832 TO 1848 1852 TO 1857 1859 1861 -
**RG3** *1862 1873 TO 1880 2009 2011 TO 2016 202 1 TO 2032 2045 2046 2088 2090 TO 2093 -
DESIGN BEAM 236 237 *2098 2100
**RB1** *REINF 0 MEMB 51 TO 104 106 107 109 110 114 TO 119 123 124 126 127 131 TO 142 -
DESIGN BEAM 222 227 247 252 *146 148 TO 183 185 TO 191 197 200 TO 224 226 TO 237 239 TO 249 251 TO 272 -
**C1** *1830 1832 TO 1848 1852 TO 1857 1859 1861 1862 2 009 2011 TO 2016 2045 2046 -
DESIGN COLUMN 51 TO 55 61 TO 70 76 TO 85 187 TO 191 197 200 201 2088 2090 - *2088 2090 TO 2093 2098 2100
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 76 of 361
***BG1** ***RG1**
*DESIGN BEAM 17 TO 19 24 TO 27 30 TO 32 1873 TO 1880 2021 TO 2032 *DESIGN BEAM 223 224 226 248 249 251
***1WG1** ***RG2**
*DESIGN BEAM 135 TO 142 146 148 TO 151 154 155 158 159 164 165 168 TO 183 185 - *DESIGN BEAM 234 235 239 240
*186 1847 2015 2016 ***RG3**
***1WG2** *DESIGN BEAM 236 237
*DESIGN BEAM 86 TO 102 104 110 114 115 123 124 131 TO 134 1832 1839 1852 1859 ***RB1**
***1G1** *DESIGN BEAM 222 227 247 252
*DESIGN BEAM 153 160 162 167 2045 ***C1**
***1G2** *DESIGN COLUMN 51 TO 55 61 TO 70 76 TO 85 187 TO 191 197 200 201 2088 2090 -
*DESIGN BEAM 116 TO 118 *2091 TO 2093 2098 2100
***1G3** ***C2**
*DESIGN BEAM 106 107 109 119 126 127 1830 1833 1835 1836 1840 TO 1842 1846 - *DESIGN COLUMN 56 TO 60 71 TO 75
*1848 1853 1855 1861 2009 ***W1**
***1B1** *DESIGN ELEMENT 1580 1581 1584 TO 1587 1589 1590 1592 1593 1595 TO 1598 1601 -
*DESIGN BEAM 152 161 163 166 2046 *1602 1605 1606 1609 1610 1613 1614 1617 1618 1621 1622 1625 1626 1629 1630 -
***1B2** *1633 1634 1637 1638 1641 1642 1645 TO 1650 1652 1653 1655 TO 1660 1662 1663 -
*DESIGN BEAM 103 2013 2014 *1665 TO 1670 1672 1673 1675 1676 1678 1679 1681 1682 1684 1685 1687 1688 -
***1B3** *1690 1691 1693 1694 1696 1697 1699 1700 1702 1703 1705 1706 1708 1709 1711 -
***1B3a** *1712 TO 1724 1727 1730 1732 1735 1738 1739 1742 17 44 1747 1750 1753 1754 1757 -
*DESIGN BEAM 156 157 *1760 1762 1765 1768 1769 1772 1775 1778 1781 1784 TO 1791 1793 1795 1796 -
***1B4** *1798 1800 TO 1813 1815 1817 1818 1820 1822 TO 1829
*DESIGN BEAM 1834 1837 1838 1843 TO 1845 1854 1856 1857 1862 2011 2012 *END CONCRETE DESIGN
***RWG1** FINISH
*DESIGN BEAM 202 TO 221 228 TO 233 241 TO 246 253 TO 272
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 77 of 361

4. MEMBER DESIGN FOR STATIC ANALYSIS

4.1 Design of Slab

4.2 Design of Beam & Girder

4.3 Design of Column

4.4 Design of Wall

4.5 Design of foundation


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 78 of 361

4.1 Design of Slab

D12 @ 150 D12 @ 150 D12 @ 150 D12 @ 150

D10 @ 150 D10 @ 150

D10 @ 150 D10 @ 150 D10 @ 150 D10 @ 150

RS2 C 180 D12 @ 150 D10 @ 150 D10 @ 150 D10 @ 150
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 79 of 361

4.1.1 Design of RS2(Roof : Oneway Slab)


ROOF SLAB DESIGN - BLAST LOAD CASE

Design code = ACI 318-08


Material data fc' = 35 Mpa
fy = 414 Mpa
Slab span length L = 4 m (Both end continous)
Slab thickness = 180 mm
Clear cover Cc = 30 mm
Dead load Wd = 8.52 Kpa
Live load Wl = 1 Kpa
Blast load Wb = 26.06 Kpa
Critical load case for member design,
Wu = Wd + Wb = 34.58 Kpa
Bending moment at support Wu x L^2/11 = 50.30 kNm
Bending moment at centre Wu x L^2/16 = 34.58 kNm

Shear force at support Wu x L/2 = 69.16 kN

MEMBER DESIGN CHECK

I) X-Direction / Top

fdc fdy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
41.7 532.8 1.00 1.00 1000 180 30 144.0 50.30 0.00

(1) Flexural Rebar Check

Mu 50.30 x 10 6
Required Rn = = 2
= 2.42565 N/mm²
1.00 x 1,000 x 144

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 2.42565
= 1 - 1 - = 0.00472
533 0.85 x 42

As(req.) =
= 0.00472 x 1000 x 144 = 680 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 180 / 2 = 162 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 144 = 378 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 80 of 361

= 0.25 x x 1000 x 144 / 533 = 436 mm²


4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 680 = 907 mm²
Minimum % of Ast as per shell dep 34.17.10.30 Cl.4.4.2.g = 240/fy in both sides cross section
As(min.3) = 240 / fy x b x h / 2 x 1/100 (Dep 34.17.10.30_Clause 4.4.2 g)
= 240 / 533 x 1000 x 180 / 200 = 405 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 680 mm²
USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 144.0


= 154.89 kN > Vu = 0.00 kN O.K

II) X-Direction / Bottom

fdc fdy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
42 533 1.00 1.00 1000 180 30 145.0 34.58 69.16

(1) Flexural Rebar Check

Mu 34.58 x 10 6
Required Rn = = 2
= 1.64471 N/mm²
1.00 x 1,000 x 145

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 1.64471
= 1 - 1 - = 0.00316
533 0.85 x 42

As(req.) =
= 0.00316 x 1000 x 145 = 459 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 180 / 2 = 162 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 145 = 381 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 145 / 533 = 439 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 459 = 612 mm²
Minimum % of Ast as per shell dep 34.17.10.30 Cl.4.4.2.g = 240/fy in both sides cross section
As(min.3) = 240 / fy x b x h / 2 x 1/100 (Dep 34.17.10.30_Clause 4.4.2 g)
= 240 / 533 x 1000 x 180 / 200 = 405 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 459 mm²
USE : D10 @ 150 ( As = 553 mm² ) O.K !
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 81 of 361

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 145.0


= 155.96 kN > Vu = 69.16 kN O.K

III) Y-Direction / Top

fdc fdy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
42 533 1.00 1.00 1000 180 30 145.0 0.00 0.00

(1) Flexural Rebar Check

Mu 0.00 x 10 6
Required Rn = = 2
= 0.00000 N/mm²
1.00 x 1,000 x 145

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.00
= 1 - 1 - = 0.00
533 0.85 x 42

As(req.) =
= 0.00 x 1000 x 145 = 0 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 180 / 2 = 162 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 145 = 381 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 145 / 533 = 439 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 0 = 0 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 162 mm²
USE : D10 @ 150 ( As = 553 mm² ) O.K !
2 2 2
Ast main, top = 791 mm 20% of Ast main, top = 158 mm < 553 mm
(As per shell dep 34.17.10.30, Cl.4.4.2.g, Provided distribution reinforcement is greater than
the 20% of provided main direction reinforceemnt)

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 145.0


= 155.96 kN > Vu = 0.00 kN O.K
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 82 of 361

IV) Y-Direction / Bottom

fdc fdy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
42 533 1.00 1.00 1000 180 30 145.0 0.00 0.00

(1) Flexural Rebar Check

Mu 0.00 x 10 6
Required Rn = = 2
= 0.00000 N/mm²
1.00 x 1,000 x 145

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.00
= 1 - 1 - = 0.00
533 0.85 x 42

As(req.) =
= 0.00 x 1000 x 145 = 0 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 180 / 2 = 162 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 145 = 381 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 145 / 533 = 439 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 0 = 0 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 162 mm²
USE : D10 @ 150 ( As = 553 mm² ) O.K !
2 2 2
Ast main, bottom = 553 mm 20% of Ast main, bottom = 111 mm < 553 mm
(As per shell dep 34.17.10.30, Cl.4.4.2.g, Provided distribution reinforcement is greater than
the 20% of main direction reinforceemnt)

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 145.0


= 155.96 kN > Vu = 0.00 kN O.K

Check minimum slab thk:

hmin = L/28 = 143 mm

h = hmin x (0.4+fy/700) = 142 mm

Thk provided = 180 mm > 142 mm Hence OK


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 83 of 361

4.1.2 Design of RS1(Roof : Oneway Slab)


ROOF SLAB DESIGN - BLAST LOAD CASE
Design code = ACI 318-08
Material data fc' = 35 Mpa
fy = 414 Mpa
Slab span length L = 3 m (Both end continous)
Slab thickness = 180 mm
Clear cover Cc = 30 mm
Dead load Wd = 8.52 Kpa
Live load Wl = 1 Kpa
Blast load Wb = 26.06 Kpa
Critical load case for member design,
Wu = Wd + Wb = 34.58 Kpa
Bending moment at support Wu x L^2/11 = 28.29 kNm
Bending moment at centre Wu x L^2/16 = 19.45 kNm

Shear force at support Wu x L/2 = 51.87 kN

MEMBER DESIGN CHECK

I) X-Direction / Top

fdc fdy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
41.7 532.8 1.00 1.00 1000 180 30 145.0 28.29 0.00

(1) Flexural Rebar Check

Mu 28.29 x 10 6
Required Rn = = 2
= 1.34567 N/mm²
1.00 x 1,000 x 145

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 1.34567
= 1 - 1 - = 0.00258
533 0.85 x 42

As(req.) =
= 0.00258 x 1000 x 145 = 375 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 180 / 2 = 162 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 145 = 381 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 84 of 361

= 0.25 x x 1000 x 145 / 533 = 439 mm²


4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 375 = 500 mm²
Minimum % of Ast as per shell dep 34.17.10.30 Cl.4.4.2.g = 240/fy in both sides cross section
As(min.3) = 240 / fy x b x h / 2 x 1/100 (Dep 34.17.10.30_Clause 4.4.2 g)
= 240 / 533 x 1000 x 180 / 200 = 405 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 439 mm²

USE : D10 @ 150 ( As = 553 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 145.0


= 155.96 kN > Vu = 0.00 kN O.K

II) X-Direction / Bottom

fdc fdy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
42 533 1.00 1 1000 180 30 145.0 19.45 51.87

(1) Flexural Rebar Check

Mu 19.45 x 10 6
Required Rn = = 2
= 0.92515 N/mm²
1.00 x 1,000 x 145

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.92515
= 1 - 1 - = 0.00176
533 0.85 x 42

As(req.) =
= 0.00176 x 1000 x 145 = 256 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 180 / 2 = 162 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 145 = 381 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 145 / 533 = 439 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 256 = 342 mm²
Minimum % of Ast as per shell dep 34.17.10.30 Cl.4.4.2.g = 240/fy in both sides cross section
As(min.3) = 240 / fy x b x h / 2 x 1/100 (Dep 34.17.10.30_Clause 4.4.2 g)
= 240 / 533 x 1000 x 180 / 200 = 405 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 342 mm²

USE : D10 @ 150 ( As = 553 mm² ) O.K !


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 85 of 361

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 145.0


= 155.96 kN > Vu = 51.87 kN O.K

III) Y-Direction / Top

fdc fdy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
42 533 1.00 1 1000 180 30 145.0 0.00 0.00

(1) Flexural Rebar Check

Mu 0.00 x 10 6
Required Rn = = 2
= 0.00000 N/mm²
1.00 x 1,000 x 145

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.00
= 1 - 1 - = 0.00
533 0.85 x 42

As(req.) =
= 0.00 x 1000 x 145 = 0 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 180 / 2 = 162 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 145 = 381 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 145 / 533 = 439 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 0 = 0 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 162 mm²

USE : D10 @ 150 ( As = 553 mm² ) O.K !


2 2 2
Ast main, top = 553 mm 20% of Ast main, top = 111 mm < 553 mm
(As per shell dep 34.17.10.30, Cl.4.4.2.g, Provided distribution reinforcement is greater than
the 20% of provided main direction reinforceemnt)

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 145.0


= 155.96 kN > Vu = 0.00 kN O.K

IV) Y-Direction / Bottom

fdc fdy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
42 533 1.00 1 1000 180 30 145.0 0.00 0.00
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 86 of 361

(1) Flexural Rebar Check

Mu 0.00 x 10 6
Required Rn = = 2
= 0.00000 N/mm²
1.00 x 1,000 x 145

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.00
= 1 - 1 - = 0.00
533 0.85 x 42

As(req.) =
= 0.00 x 1000 x 145 = 0 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 180 / 2 = 162 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 145 = 381 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 145 / 533 = 439 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 0 = 0 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 162 mm²

USE : D10 @ 150 ( As = 553 mm² ) O.K !


2 2 2
Ast main, top = 553 mm 20% of Ast main, top = 111 mm < 553 mm
(As per shell dep 34.17.10.30, Cl.4.4.2.g, Provided distribution reinforcement is greater than
the 20% of provided main direction reinforceemnt)

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 145.0


= 155.96 kN > Vu = 0.00 kN O.K

Check minimum slab thk

hmin = L/28 = 107 mm

h = hmin x (0.4+fy/700) = 106 mm

Thk provided = 180 mm > 106 mm Hence OK


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 87 of 361

4.1.3 Design of 1S1(Ground Floor : Oneway Slab)


FLOOR SLAB DESIGN - NORMAL LOAD CASE

Design code = ACI 318-08


Material data fc' = 35 Mpa
fy = 414 Mpa
Slab span length L = 3 m (Both end fixed)
Slab thickness = 180 mm
Clear cover Cc = 30 mm
Dead load Wd = 4.90 Kpa
Live load Wl = 20 Kpa
Blast load Wb = 0.00 Kpa
Critical load case for member design,
Wu = 1.2Wd + 1.6Wb = 37.88 Kpa
Bending moment at support Wu x L^2/12 = 28.41 kNm
Bending moment at centre Wu x L^2/16 = 21.31 kNm

Shear force at support Wu x L/2 = 56.82 kN

MEMBER DESIGN CHECK

I) X-Direction / Top

f'c fy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
35 414 0.90 0.75 1000 180 30 145.0 28.41 0.00

(1) Flexural Rebar Check

Mu 28.41 x 10 6
Required Rn = = 2
= 1.50139 N/mm²
0.90 x 1,000 x 145

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 1.50139
= 1 - 1 - = 0.00372
414 0.85 x 35

As(req.) =
= 0.00372 x 1000 x 145 = 540 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 180 / 2 = 162 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 145 = 490 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 145 / 414 = 518 mm²
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 88 of 361

4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)


= 4 / 3 x 540 = 720 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D10 @ 150 ( As = 553 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d 0.90 x 1/6 x


= 0.75 x 1000 x 145.0
= 128.67 kN
107.23 > Vu = 0.00 kN O.K

II) X-Direction / Bottom

f'c fy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
35 414 0.90 0.75 1000 180 30 145.0 21.31 56.82

(1) Flexural Rebar Check

Mu 21.31 x 10 6
Required Rn = = 2
= 1.12604 N/mm²
0.90 x 1,000 x 145

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 1.12604
= 1 - 1 - = 0.00277
414 0.85 x 35

As(req.) =
= 0.00277 x 1000 x 145 = 402 mm²
As(temp.) = 0.0018 xbxh/2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 180 / 2 = 162 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 145 = 490 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 145 / 414 = 518 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 402 = 536 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 518 mm²

USE : D10 @ 150 ( As = 553 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d 0.90 x 1/6 x


= 0.75 x 1000 x 145.0
= 128.67 kN
107.23 > Vu = 56.82 kN O.K
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 89 of 361

III) Y-Direction / Top

f'c fy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
35 414 0.90 0.75 1000 180 30 145.0 0.00 0.00

(1) Flexural Rebar Check

Mu 0.00 x 10 6
Required Rn = = 2
= 0.00000 N/mm²
0.90 x 1,000 x 145

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.00
= 1 - 1 - = 0.00
414 0.85 x 35

As(req.) =
= 0.00 x 1000 x 145 = 0 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 180 / 2 = 162 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 145 = 490 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 145 / 414 = 518 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 0 = 0 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 162 mm²

USE : D10 @ 200 ( As = 395 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d 0.90 x 1/6 x


= 0.75 x 1000 x 145.0
= 128.67 kN
107.23 > Vu = 0.00 kN O.K

IV) Y-Direction / Bottom

f'c fy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
35 414 0.90 0.75 1000 180 30 145.0 0.00 0.00

(1) Flexural Rebar Check

Mu 0.00 x 10 6
Required Rn = = 2
= 0.00000 N/mm²
0.90 x 1,000 x 145
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 90 of 361

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.00
= 1 - 1 - = 0.00
414 0.85 x 35

As(req.) =
= 0.00 x 1000 x 145 = 0 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 180 / 2 = 162 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 145 = 490 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 145 / 414 = 518 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 0 = 0 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 162 mm²

USE : D10 @ 200 ( As = 395 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d 0.90 x 1/6 x


= 0.75 x 1000 x 145.0
= 128.67 kN
107.23 > Vu = 0.00 kN O.K

Check minimum slab thk

hmin = L/28 = 107 mm

h = hmin x (0.4+fy/700) = 106 mm

Thk provided = 180 mm > 106 mm Hence OK


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 91 of 361

4.1.4 Design of -1S1(Basement Floor : Twoway Slab)

ACI 318M-08
W1

W1
Slab edges
Wall -W1 300 thk
Wall -W1 300 thk

5.0
14.48 kpa

18.20 10.10 8.76 4.75


0.35 0.19 0.17 0.09
422 231 200 109
@267 @489
@314

23.73

8.82
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 92 of 361

4.2 Design of Beam & Girder


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 93 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 94 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 95 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 96 of 361

4.2.1 Critical beam deflection check


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 97 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 98 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 99 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 100 of 361

4.2.2 Critical beam crack width check


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 101 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 102 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 103 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 104 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 105 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 106 of 361

4.2.2 STAAD design results of beam Static analysis


(STAAD output results for Normal load cases were attached here and for page limiting purpose STAAD
output results for blast load case not attached, members are design for both normal load case and
blast load case)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 107 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 108 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 109 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 110 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 111 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 112 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 113 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 114 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 115 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 116 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 117 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 118 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 119 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 120 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 121 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 122 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 123 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 124 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 125 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 126 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 127 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 128 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 129 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 130 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 131 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 132 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 133 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 134 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 135 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 136 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 137 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 138 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 139 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 140 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 141 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 142 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 143 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 144 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 145 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 146 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 147 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 148 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 149 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 150 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 151 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 152 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 153 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 154 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 155 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 156 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 157 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 158 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 159 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 160 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 161 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 162 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 163 of 361

4.3 Design of Column

C2 C1
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 164 of 361

STAAD design results of column Static analysis


(STAAD output results for Normal load cases were attached here and for page limiting purpose STAAD
output results for blast load case not attached, members are design for both normal load case and
blast load case)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 165 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 166 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 167 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 168 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 169 of 361

4.4 Design of Wall

150 150 150 150


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 170 of 361

4.4.1 Wall design & displacement check


4.4.1.1 Drift Limits Check for frame
C Row

(Unit: mm)

1) Allowable Seismic Drift Limits Check


EL+14,900 Cdx = 4.00
MEM NO. 195
2093 ; LENGTH L = 6000 mm
JOINT NO. 414
415 ; LOAD CASE 0.7EX X2 = 5.51 mm
3.91
JOINT NO. 258
269 ; LOAD CASE 0.7EX X1 = 0.22 mm
0.19

Cd xe
DRIFT CHECK ; x = 16.9248
11.9 < 0.020 hsx = 120.00
I

Cdx = 4.00
MEM NO. 79&&65
80 64 ; LENGTH L = 4400 mm
JOINT NO. 258
269 ; LOAD CASE 0.7EX X2 = 0.22 mm
0.19
JOINT NO. 39
43 ; LOAD CASE 0.7EX X1 = 0.00 mm

Cd xe
DRIFT CHECK ; x = 0.7136
0.61 < 0.020 hsx = 88.00
I
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 171 of 361

3 Row

(Unit: mm)

1) Allowable Seismic Drift Limits Check


EL+14,900 Cdz = 4.00
MEM NO. 194
189 ; LENGTH L = 6000 mm
JOINT NO. 413
196 ; LOAD CASE 0.7EZ Z2 = 6.72 mm
5.52
JOINT NO. 152
118 ; LOAD CASE 0.7EZ Z1 = 1.31 mm
1.54

Cd xe
DRIFT CHECK ; x = 17.3248
12.74 < 0.020 hsx = 120.00
I

Cdz = 4.00
MEM NO. 8153
68 & ; LENGTH L = 4400 mm
JOINT NO. 152
118 ; LOAD CASE 0.7EZ Z2 = 1.31 mm
1.54
JOINT NO. 35
7 ; LOAD CASE 0.7EZ Z1 = 0.00 mm

Cd xe
DRIFT CHECK ; x = 4.1920
4.93 < 0.020 hsx = 88.00
I
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 172 of 361

4.4.1.2 Displacement summary of wall for blast load in static analysis

L/C - 303 Maximum Displacement due to X-direction load


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 173 of 361

L/C 307 - Maximum Displacement due to Z-direction load

Maximum lateral displacement in X direction (equivalent static blast load) = 13.335 mm (L/C = 303)

Maximum lateral displacement in Z direction (equivalent static blast load) = 13.187 mm (L/C = 307)

Allowable lateral displacement = H/250 = 8000/250 = 32 mm HENCE SAFE IN SWAY STABILITY


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 174 of 361

4.4.1.3 Displacement summary of wall for blast load in dynamic analysis

Support Support Ductility Support


Response
rotation rotation ratio rotation
Bending/l Peak positive Peak negative condition
Case Blast Lateral force response response response response
Wall type oading dispalcement dispalcement (hinge rotation
No. type direction for peak for peak for peak for peak
type (mm) (mm) & ductility ratio)
+ve disp +ve disp +ve disp +ve disp
as per ASCE
(degree) (degree) (degree) (degree)
Building long Out of
Front wall 96.76 0 1.847 0 - - Within limit
side-Z direction plane
Building long Out of
Side wall 21.17 -5.98 0.404 0.114 - - Within limit
side-Z direction plane
Building long Out of
Rear wall 22.78 -4.44 0.435 0.085 - - Within limit
side-Z direction plane
Building short Out of
Front wall 96.76 0 1.847 0 - - Within limit
69 kpa & side-X direction plane
1
20 m/s Building short Out of
Side wall 21.17 -5.98 0.404 0.114 - - Within limit
side-X direction plane
Building short Out of
Rear wall 22.79 -4.44 0.435 0.084 - - Within limit
side-X direction plane
Building long
Side wall In plane 0.33 -0.32 - - 0.56 0.55 Within limit
side-Z direction
Building long
Side wall In plane 0.32 -0.32 - - 0.56 0.57 Within limit
side-X direction

Building long Out of


Front wall 54.78 0 1.046 0 - - Within limit
side-Z direction plane

Building long Out of


Side wall 15.7 -6.43 0.3 0.123 - - Within limit
side-Z direction plane

Building long Out of


Rear wall 17.42 -2.26 0.333 0.043 - - Within limit
side-Z direction plane
2
Building short Out of
Front wall 54.78 0 1.046 0 - - Within limit
side-X direction plane
21 kpa &
100 m/s Building short Out of
Side wall 15.7 -6.43 0.3 0.123 - - Within limit
side-X direction plane

Building short Out of


Rear wall 17.42 -2.27 0.333 0.043 - - Within limit
side-X direction plane

Building long
Side wall In plane 0.16 -0.16 - - 0.28 0.28 Within limit
side-Z direction

Building long
Side wall In plane 0.16 -0.18 - - 0.16 -0.18 Within limit
side-X direction
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 175 of 361

4.4.1.4 Front wall design for blast load static case (Front analysed as one way beam
with pinned ends)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 176 of 361

FRONT WALL DESIGN CHECK - BLAST LOAD CASE

Design code = ACI 318-08


Material data fc' = 35 Mpa
fy = 414 Mpa
Wall span L = 6 m (Both end pinned)
Wall thickness = 300 mm
Clear cover Cc = 40 mm
Blast load Wb = 26.31 Kpa
Critical load case for member design & serviceability check,
Wu = Wb = 26.31 Kpa (Refer load calculation page)
Bending moment at support = 0.00 kNm
Bending moment at centre Wu x L^2/8 = 118.40 kNm

Shear force at support Wu x L/2 = 78.93 kN

MEMBER DESIGN CHECK


I) Vertical Direction / Outside

f'c fy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
42 533 1.00 1.00 1000 300 40 252.0 118.40 78.93

(1) Flexural Rebar Check

Mu 118.40 x 10 6
Required Rn = = 2
= 1.86442 N/mm²
1.00 x 1,000 x 252

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 1.86442
= 1 - 1 - = 0.0036
533 0.85 x 42

As(req.) =
= 0.0036 x 1000 x 252 = 908 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 300 / 2 = 270 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 252 = 662 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 252 / 533 = 763 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 908 = 1211 mm²
Minimum % of Ast as per shell dep 34.17.10.30 Cl.4.4.2.g = 240/fy in both sides cross section
As(min.3) = 240 / fy x b x h / 2 x 1/100 (Dep 34.17.10.30_Clause 4.4.2 g)
= 240 / 533 x 1000 x 300 / 200 = 676 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 908 mm²

USE : D16 @ 150 ( As = 1407 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 252.0


= 271.05 kN > Vu = 78.93 kN O.K
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 177 of 361

II) Vertical Direction / Inside

f'c fy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
42 533 1.00 1 1000 300 40 252.0 0.00 0.00

(1) Flexural Rebar Check

Mu 0.00 x 10 6
Required Rn = = 2
= 0.00000 N/mm²
1.00 x 1,000 x 252

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.00
= 1 - 1 - = 0.00
533 0.85 x 42

As(req.) =
= 0.00 x 1000 x 252 = 0 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 300 / 2 = 270 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 252 = 662 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 252 / 533 = 763 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 0 = 0 mm²
Minimum % of Ast as per shell dep 34.17.10.30 Cl.4.4.2.g = 240/fy in both sides cross section
As(min.3) = 240 / fy x b x h / 2 x 1/100 (Dep 34.17.10.30_Clause 4.4.2 g)
= 240 / 533 x 1000 x 300 / 200 = 676 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 270 mm²

USE : D16 @ 150 ( As = 1407 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 252.0


= 271.05 kN > Vu = 0.00 kN O.K

III) Horizontal Direction / Outside

f'c fy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
42 533 1.00 1 1000 300 40 252.0 0.00 0.00

(1) Flexural Rebar Check

Mu 0.00 x 10 6
Required Rn = = 2
= 0.00000 N/mm²
1.00 x 1,000 x 252

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.00
= 1 - 1 - = 0.00
533 0.85 x 42

As(req.) =
= 0.00 x 1000 x 252 = 0 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 300 / 2 = 270 mm² (One Side)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 178 of 361

As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)


= 1.40 / 533 x 1000 x 252 = 662 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 252 / 533 = 763 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 0 = 0 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 270 mm²

USE : D16 @ 150 ( As = 1407 mm² ) O.K !


2 2 2
Ast main, vertical= 1407 mm 20% of Ast main, vertical = 281 mm < 1407 mm
(As per shell dep 34.17.10.30, Cl.4.4.2.g, Provided distribution reinforcement is greater than
the 20% of provided main direction reinforceemnt)

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 252.0


= 271.05 kN > Vu = 0.00 kN O.K

IV) Horizontal Direction / Inside

f'c fy b h dc d Mu Vu
MPa MPa Tension Shear mm mm mm mm kN.m kN
42 533 1.00 1 1000 300 40 252.0 0.00 0.00

(1) Flexural Rebar Check

Mu 0.00 x 10 6
Required Rn = = 2
= 0.00000 N/mm²
1.00 x 1,000 x 252

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.00
= 1 - 1 - = 0.00
533 0.85 x 42

As(req.) =
= 0.00 x 1000 x 252 = 0 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 300 / 2 = 270 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 252 = 662 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 252 / 533 = 763 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 0 = 0 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 270 mm²

USE : D16 @ 150 ( As = 1407 mm² ) O.K !


2 2 2
Ast main, vertical = 1407 mm 20% of Ast main, vertical = 281 mm < 1407 mm
(As per shell dep 34.17.10.30, Cl.4.4.2.g, Provided distribution reinforcement is greater than
the 20% of provided main direction reinforceemnt)

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 252.0


= 271.05 kN > Vu = 0.00 kN O.K +
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 179 of 361

4.4.1.5 Design check of shear wall for in-plane flexure Blast load on static case
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 180 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 181 of 361

4.4.1.6 STAAD design results of wall Static load cases


(STAAD output results for Normal load cases were attached here and for page limiting purpose STAAD
output results for blast load case not attached, members are design for both normal load case and
blast load case)
1593 TOP : 0.540 0.00 / 201 0.540 0.00 / 210
802. **W1** BOTT: 0.540 9.81 / 218 0.709 53.14 / 219
803. DESIGN ELEMENT 1580 1581 1584 TO 1587 1589 1590 1592 1593 1595 TO 1598 1601 -
804. 1602 1605 1606 1609 1610 1613 1614 1617 1618 1621 1622 1625 1626 1629 1630 - FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
805. 1633 1634 1637 1638 1641 1642 1645 TO 1650 1652 1653 1655 TO 1660 1662 1663 - COVER (BOTTOM): 75.000 MM TH: 300.000 MM
806. 1665 TO 1670 1672 1673 1675 1676 1678 1679 1681 1682 1684 1685 1687 1688 - 1595 TOP : Longitudinal direction - Only minimum steel required.
807. 1690 1691 1693 1694 1696 1697 1699 1700 1702 1703 1705 1706 1708 1709 1711 - 1595 BOTT: Longitudinal direction - Only minimum steel required.
808. 1712 TO 1724 1727 1730 1732 1735 1738 1739 1742 1744 1747 1750 1753 1754 1757 - 1595 TOP : Transverse direction - Only minimum steel required.
809. 1760 1762 1765 1768 1769 1772 1775 1778 1781 1784 TO 1791 1793 1795 1796 - 1595 BOTT: Transverse direction - Only minimum steel required.
810. 1798 1800 TO 1813 1815 1817 1818 1820 1822 TO 1829 1595 TOP : 0.540 5.25 / 201 0.540 34.88 / 218
STAAD SPACE -- PAGE NO. 270 BOTT: 0.540 0.00 / 218 0.540 0.00 / 219

FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM


COVER (BOTTOM): 75.000 MM TH: 300.000 MM
ELEMENT DESIGN SUMMARY 1596 TOP : Longitudinal direction - Only minimum steel required.
---------------------- 1596 BOTT: Longitudinal direction - Only minimum steel required.
1596 TOP : Transverse direction - Only minimum steel required.
ELEMENT LONG. REINF MOM-X /LOAD TRANS. REINF MOM-Y /LOAD 1596 BOTT: Transverse direction - Only minimum steel required.
(SQ.MM/MM) (KN-MM/MM) (SQ.MM/MM) (KN-MM/MM) 1596 TOP : 0.540 6.04 / 201 0.540 37.53 / 218
BOTT: 0.540 0.00 / 218 0.540 0.00 / 219
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
COVER (BOTTOM): 75.000 MM TH: 300.000 MM STAAD SPACE -- PAGE NO. 272
1580 TOP : Longitudinal direction - Only minimum steel required.
1580 BOTT: Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1580 TOP : Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1580 BOTT: Transverse direction - Only minimum steel required. 1597 TOP : Longitudinal direction - Only minimum steel required.
1580 TOP : 0.540 2.62 / 208 0.540 0.00 / 0 1597 BOTT: Longitudinal direction - Only minimum steel required.
BOTT: 0.540 4.46 / 218 0.540 5.56 / 201 1597 TOP : Transverse direction - Only minimum steel required.
1597 BOTT: Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1597 TOP : 0.540 1.90 / 219 0.540 18. 39 / 219
COVER (BOTTOM): 75.000 MM TH: 300.000 MM BOTT: 0.540 0.43 / 201 0.540 4.36 / 208
1581 TOP : Longitudinal direction - Only minimum steel required.
1581 BOTT: Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1581 TOP : Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1581 BOTT: Transverse direction - Only minimum steel required. 1598 TOP : Longitudinal direction - Only minimum steel required.
1581 TOP : 0.540 3.38 / 208 0.540 0.00 / 0 1598 BOTT: Longitudinal direction - Only minimum steel required.
BOTT: 0.540 7.31 / 218 0.540 6.09 / 201 1598 TOP : Transverse direction - Only minimum steel required.
1598 BOTT: Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1598 TOP : 0.540 2.15 / 219 0.540 18.66 / 219
COVER (BOTTOM): 75.000 MM TH: 300.000 MM BOTT: 0.540 0.41 / 208 0.540 4.97 / 208
1584 TOP : Longitudinal direction - Only minimum steel required.
1584 BOTT: Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1584 TOP : Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1584 BOTT: Transverse direction - Only minimum steel required. 1601 TOP : Longitudinal direction - Only minimum steel required.
1584 TOP : 0.540 3.07 / 208 0.540 0.15 / 208 1601 BOTT: Longitudinal direction - Only minimum steel required.
BOTT: 0.540 6.86 / 218 0.540 9.13 / 219 1601 TOP : Transverse direction - Only minimum steel required.
1601 BOTT: Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1601 TOP : 0.540 12.11 / 218 0.540 1.37 / 218
COVER (BOTTOM): 75.000 MM TH: 300.000 MM BOTT: 0.540 5.94 / 208 0.540 2.07 / 208
1585 TOP : Longitudinal direction - Only minimum steel required.
1585 BOTT: Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1585 TOP : Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1585 BOTT: Transverse direction - Only minimum steel required. 1602 TOP : Longitudinal direction - Only minimum steel required.
1585 TOP : 0.540 4.69 / 208 0.540 0.33 / 208 1602 BOTT: Longitudinal direction - Only minimum steel required.
BOTT: 0.540 8.36 / 218 0.540 9.82 / 219 1602 TOP : Transverse direction - Only minimum steel required.
1602 BOTT: Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1602 TOP : 0.540 0.00 / 218 0.540 0.00 / 218
COVER (BOTTOM): 75.000 MM TH: 300.000 MM BOTT: 0.540 3.63 / 215 0.540 3.73 / 201
1586 TOP : Longitudinal direction - Only minimum steel required.
1586 BOTT: Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1586 TOP : Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1586 BOTT: Transverse direction - Only minimum steel required. 1605 TOP : Longitudinal direction - Only minimum steel required.
1586 TOP : 0.540 3.06 / 201 0.540 16.67 / 210 1605 BOTT: Longitudinal direction - Only minimum steel required.
BOTT: 0.540 0.70 / 219 0.540 0.00 / 219 1605 TOP : Transverse direction - Only minimum steel required.
1605 BOTT: Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1605 TOP : 0.540 0.00 / 218 0.540 0.00 / 218
COVER (BOTTOM): 75.000 MM TH: 300.000 MM BOTT: 0.540 6.16 / 218 0.540 5.20 / 201
1587 TOP : Longitudinal direction - Only minimum steel required.
1587 BOTT: Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1587 TOP : Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
STAAD SPACE -- PAGE NO. 271 1606 TOP : Longitudinal direction - Only minimum steel required.
1606 BOTT: Longitudinal direction - Only minimum steel required.
1587 BOTT: Transverse direction - Only minimum steel required. 1606 TOP : Transverse direction - Only minimum steel required.
1587 TOP : 0.540 3.71 / 201 0.540 18.49 / 210 1606 BOTT: Transverse direction - Only minimum steel required.
BOTT: 0.540 0.00 / 219 0.540 0.00 / 219 1606 TOP : 0.540 4.09 / 208 0.540 0.00 / 218
BOTT: 0.540 8.00 / 218 0.540 5.51 / 201
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
COVER (BOTTOM): 75.000 MM TH: 300.000 MM FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1589 TOP : Longitudinal direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1589 BOTT: Longitudinal direction - Only minimum steel required. STAAD SPACE -- PAGE NO. 273
1589 TOP : Transverse direction - Only minimum steel required.
1589 BOTT: Transverse direction - Only minimum steel required. 1609 TOP : Longitudinal direction - Only minimum steel required.
1589 TOP : 0.540 0.00 / 201 0.540 0.00 / 210 1609 BOTT: Longitudinal direction - Only minimum steel required.
BOTT: 0.540 5.21 / 201 0.540 30.98 / 201 1609 TOP : Transverse direction - Only minimum steel required.
1609 BOTT: Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1609 TOP : 0.540 3.03 / 208 0.540 0.00 / 218
COVER (BOTTOM): 75.000 MM TH: 300.000 MM BOTT: 0.540 6.59 / 218 0.540 6.12 / 201
1590 TOP : Longitudinal direction - Only minimum steel required.
1590 BOTT: Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1590 TOP : Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1590 BOTT: Transverse direction - Only minimum steel required. 1610 TOP : Longitudinal direction - Only minimum steel required.
1590 TOP : 0.540 0.00 / 201 0.540 0.00 / 210 1610 BOTT: Longitudinal direction - Only minimum steel required.
BOTT: 0.540 5.23 / 201 0.540 33.07 / 201 1610 TOP : Transverse direction - Only minimum steel required.
1610 BOTT: Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1610 TOP : 0.540 3.11 / 208 0.540 0.00 / 218
COVER (BOTTOM): 75.000 MM TH: 300.000 MM BOTT: 0.540 8.35 / 218 0.540 5.66 / 201
1592 TOP : Longitudinal direction - Only minimum steel required.
1592 BOTT: Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.0 00 MM
1592 TOP : Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1592 TOP : 0.540 0.00 / 201 0.540 0.00 / 210 1613 TOP : Longitudinal direction - Only minimum steel required.
BOTT: 0.540 10.05 / 218 0.698 52.27 / 219 1613 BOTT: Longitudinal direction - Only minimum steel required.
1613 TOP : Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1613 BOTT: Transverse direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1613 TOP : 0.540 3.01 / 208 0.540 0.00 / 218
1593 TOP : Longitudinal direction - Only minimum steel required. BOTT: 0.540 7.86 / 218 0.540 5.61 / 201
1593 BOTT: Longitudinal direction - Only minimum steel required.
1593 TOP : Transverse direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 182 of 361
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1638 TOP : Transverse direction - Only minimum steel required.
1614 TOP : Longitudinal direction - Only minimum steel required. 1638 BOTT: Transverse direction - Only minimum steel required.
1614 BOTT: Longitudinal direction - Only minimum steel required. 1638 TOP : 0.540 3.96 / 208 0.540 0.65 / 209
1614 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 7.41 / 218 0.540 9.69 / 219
1614 BOTT: Transverse direction - Only minimum steel required.
1614 TOP : 0.540 2.70 / 208 0.540 0.00 / 218 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 4.80 / 218 0.540 5.95 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1641 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1641 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1641 TOP : Transverse direction - Only minimum steel required.
1617 TOP : Longitudinal direction - Only minimum steel required. 1641 BOTT: Transverse direction - Only minimum steel required.
1617 BOTT: Longitudinal direction - Only minimum steel required. 1641 TOP : 0.540 5.80 / 208 0.540 1.40 / 201
1617 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 9.73 / 218 0.540 8.51 / 219
1617 BOTT: Transverse direction - Only minimum steel required.
1617 TOP : 0.540 4.88 / 208 0.540 0.00 / 218 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 8.17 / 218 0.540 6.16 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1642 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1642 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1642 TOP : Transverse direction - Only minimum steel required.
1618 TOP : Longitudinal direction - Only minimum steel required. 1642 BOTT: Transverse direction - Only minimum steel required.
1618 BOTT: Longitudinal direction - Only minimum steel required. 1642 TOP : 0.540 3.24 / 208 0.540 2.28 / 201
1618 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 3.45 / 218 0.540 7.59 / 219
1618 BOTT: Transverse direction - Only minimum steel required.
1618 TOP : 0.540 0.81 / 208 0.540 0.00 / 218 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 8.95 / 218 0.540 6.54 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1645 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1645 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1645 TOP : Transverse direction - Only minimum steel required.
1621 TOP : Longitudinal direction - Only minimum steel required. 1645 BOTT: Transverse direction - Only minimum steel required.
1621 BOTT: Longitudinal direction - Only minimum steel required. STAAD SPACE -- PAGE NO. 276
STAAD SPACE -- PAGE NO. 274
1645 TOP : 0.540 1.80 / 208 0.540 1.88 / 201
1621 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 2.04 / 219 0.540 4.81 / 219
1621 BOTT: Transverse direction - Only minimum steel required.
1621 TOP : 0.540 0.03 / 208 0.540 0.00 / 218 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 4.53 / 218 0.540 4.77 / 219 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1646 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1646 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1646 TOP : Transverse direction - Only minimum steel required.
1622 TOP : Longitudinal direction - Only minimum steel required. 1646 BOTT: Transverse direction - Only minimum steel required.
1622 BOTT: Longitudinal direction - Only minimum steel required. 1646 TOP : 0.540 11.55 / 218 0.540 2.08 / 210
1622 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 6.88 / 208 0.540 1.33 / 216
1622 BOTT: Transverse direction - Only minimum steel required.
1622 TOP : 0.540 11.94 / 218 0.540 1.44 / 210 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 6.46 / 208 0.540 2.09 / 216 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1647 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1647 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1647 TOP : Transverse direction - Only minimum steel required.
1625 TOP : Longitudinal direction - Only minimum steel required. 1647 BOTT: Transverse direction - Only minimum steel required.
1625 BOTT: Longitudinal direction - Only minimum steel required. 1647 TOP : 0.540 9.52 / 218 0.540 5.79 / 218
1625 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 0.00 / 208 0.540 0.00 / 216
1625 BOTT: Transverse direction - Only minimum steel required.
1625 TOP : 0.540 11.62 / 218 0.540 1.84 / 210 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 6.18 / 208 0.540 1.69 / 216 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1648 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1648 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1648 TOP : Transverse direction - Only minimum steel required.
1626 TOP : Longitudinal direction - Only minimum steel required. 1648 BOTT: Transverse direction - Only minimum steel required.
1626 BOTT: Longitudinal direction - Only minimum steel required. 1648 TOP : 0.540 5.98 / 219 0.540 10.95 / 219
1626 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 2.62 / 215 0.540 0.00 / 216
1626 BOTT: Transverse direction - Only minimum steel required.
1626 TOP : 0.540 1.37 / 207 0.540 0.80 / 207 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 1.04 / 219 0.540 4.89 / 219 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1649 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1649 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1649 TOP : Transverse direction - Only minimum steel required.
1629 TOP : Longitudinal direction - Only minimum steel required. 1649 BOTT: Transverse direction - Only minimum steel required.
1629 BOTT: Longitudinal direction - Only minimum steel required. 1649 TOP : 0.540 3.61 / 219 0.540 13.58 / 219
1629 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 4.30 / 218 0.540 0.00 / 216
1629 BOTT: Transverse direction - Only minimum steel required.
1629 TOP : 0.540 1.51 / 208 0.540 0.65 / 207 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 2.46 / 219 0.540 7.18 / 219 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1650 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1650 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1650 TOP : Transverse direction - Only minimum steel required.
1630 TOP : Longitudinal direction - Only minimum steel required. 1650 BOTT: Transverse direction - Only minimum steel required.
1630 BOTT: Longitudinal direction - Only minimum steel required. 1650 TOP : 0.540 1.67 / 207 0.540 14.16 / 201
1630 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 2.41 / 219 0.540 0.00 / 216
1630 BOTT: Transverse direction - Only minimum steel required.
1630 TOP : 0.540 4.57 / 208 0.540 0.55 / 208 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 10.25 / 218 0.540 8.67 / 219 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1652 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1652 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1652 TOP : Transverse direction - Only minimum steel required.
1633 TOP : Longitudinal direction - Only minimum steel required. 1652 BOTT: Transverse direction - Only minimum steel required.
1633 BOTT: Longitudinal direction - Only minimum steel required. STAAD SPACE -- PAGE NO. 277
1633 TOP : Transverse direction - Only minimum steel required.
1633 BOTT: Transverse direction - Only minimum steel required. 1652 TOP : 0.540 3.86 / 218 0.540 0.00 / 201
STAAD SPACE -- PAGE NO. 275 BOTT: 0.540 0.77 / 219 0.540 6.93 / 201

1633 TOP : 0.540 3.98 / 208 0.540 0.00 / 208 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 7.93 / 218 0.540 10.73 / 219 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1653 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1653 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1653 TOP : Transverse direction - Only minimum steel required.
1634 TOP : Longitudinal direction - Only minimum steel required. 1653 BOTT: Transverse direction - Only minimum steel required.
1634 BOTT: Longitudinal direction - Only minimum steel required. 1653 TOP : 0.540 0.58 / 219 0.540 0.00 / 201
1634 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 4.65 / 201 0.540 16.90 / 201
1634 BOTT: Transverse direction - Only minimum steel required.
1634 TOP : 0.540 2.73 / 208 0.540 0.00 / 208 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 8.66 / 218 0.540 12.02 / 219 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1655 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1655 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1655 TOP : Transverse direction - Only minimum steel required.
1637 TOP : Longitudinal direction - Only minimum steel required. 1655 BOTT: Transverse direction - Only minimum steel required.
1637 BOTT: Longitudinal direction - Only minimum steel required. 1655 TOP : 0.540 0.00 / 219 0.540 0.00 / 201
1637 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 6.85 / 201 0.540 24.30 / 201
1637 BOTT: Transverse direction - Only minimum steel required.
1637 TOP : 0.540 2.84 / 208 0.540 0.00 / 208 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 8.66 / 218 0.540 11.69 / 219 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1656 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1656 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1656 TOP : Transverse direction - Only minimum steel required.
1638 TOP : Longitudinal direction - Only minimum steel required. 1656 BOTT: Transverse direction - Only minimum steel required.
1638 BOTT: Longitudinal direction - Only minimum steel required. 1656 TOP : 0.540 0.00 / 219 0.540 0.00 / 201
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 183 of 361
BOTT: 0.540 5.99 / 219 0.540 27.53 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1672 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1672 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1672 TOP : Transverse direction - Only minimum steel required.
1657 TOP : Longitudinal direction - Only minimum steel required. 1672 BOTT: Transverse direction - Only minimum steel required.
1657 BOTT: Longitudinal direction - Only minimum steel required. 1672 TOP : 0.540 0.00 / 218 0.540 0.00 / 218
1657 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 6.65 / 219 0.540 31.83 / 201
1657 BOTT: Transverse direction - Only minimum steel required.
1657 TOP : 0.540 4.71 / 201 0.540 19.70 / 210 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 0.00 / 219 0.540 0.00 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1673 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1673 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1673 TOP : Transverse direction - Only minimum steel required.
1658 TOP : Longitudinal direction - Only minimum steel required. 1673 BOTT: Transverse direction - Only minimum steel required.
1658 BOTT: Longitudinal direction - Only minimum steel required. 1673 TOP : 0.540 0.00 / 218 0.540 0.00 / 218
1658 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 7.37 / 201 0.540 28.59 / 201
1658 BOTT: Transverse direction - Only minimum steel required.
1658 TOP : 0.540 3.02 / 219 0.540 23.93 / 218 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 2.01 / 201 0.540 0.00 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1675 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1675 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1675 TOP : Transverse direction - Only minimum steel required.
1659 TOP : Longitudinal direction - Only minimum steel required. 1675 BOTT: Transverse direction - Only minimum steel required.
1659 BOTT: Longitudinal direction - Only minimum steel required. STAAD SPACE -- PAGE NO. 280
1659 TOP : Transverse direction - Only minimum steel required.
1659 BOTT: Transverse direction - Only minimum steel required. 1675 TOP : 0.540 0.00 / 218 0.540 0.00 / 218
STAAD SPACE -- PAGE NO. 278 BOTT: 0.540 4.82 / 201 0.540 18.70 / 201

1659 TOP : 0.540 2.83 / 219 0.540 23.53 / 218 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 1.84 / 214 0.540 0.00 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1676 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1676 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1676 TOP : Transverse direction - Only minimum steel required.
1660 TOP : Longitudinal direction - Only minimum steel required. 1676 BOTT: Transverse direction - Only minimum steel required.
1660 BOTT: Longitudinal direction - Only minimum steel required. 1676 TOP : 0.540 4.21 / 215 0.540 0.00 / 218
1660 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 1.06 / 219 0.540 6.99 / 201
1660 BOTT: Transverse direction - Only minimum steel required.
1660 TOP : 0.540 5.36 / 201 0.540 18.82 / 210 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 1.06 / 219 0.540 0.00 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1678 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1678 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1678 TOP : Transverse direction - Only minimum steel required.
1662 TOP : Longitudinal direction - Only minimum steel required. 1678 BOTT: Transverse direction - Only minimum steel required.
1662 BOTT: Longitudinal direction - Only minimum steel required. 1678 TOP : 0.540 2.27 / 210 0.540 0.00 / 218
1662 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 4.12 / 216 0.540 15.50 / 219
1662 BOTT: Transverse direction - Only minimum steel required.
1662 TOP : 0.540 0.00 / 201 0.540 0.00 / 210 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 4.98 / 219 0.540 34.62 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1679 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1679 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1679 TOP : Transverse direction - Only minimum steel required.
1663 TOP : Longitudinal direction - Only minimum steel required. 1679 TOP : 0.540 3.90 / 218 0.540 0.00 / 218
1663 BOTT: Longitudinal direction - Only minimum steel required. BOTT: 0.540 6.76 / 208 0.748 55.97 / 219
1663 TOP : Transverse direction - Only minimum steel required.
1663 BOTT: Transverse direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1663 TOP : 0.540 0.00 / 201 0.540 0.00 / 210 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
BOTT: 0.540 9.87 / 201 0.540 38.38 / 201 1681 TOP : Longitudinal direction - Only minimum steel required.
1681 BOTT: Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1681 TOP : Transverse direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1681 TOP : 0.540 0.00 / 218 0 .540 0.00 / 218
1665 TOP : Longitudinal direction - Only minimum steel required. BOTT: 0.540 19.84 / 219 1.028 76.11 / 219
1665 BOTT: Longitudinal direction - Only minimum steel required.
1665 TOP : Transverse direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1665 BOTT: Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1665 TOP : 0.540 0.00 / 201 0.540 0.00 / 210 1682 TOP : Longitudinal direction - Only minimum steel required.
BOTT: 0.540 9.71 / 201 0.540 38.25 / 201 1682 BOTT: Longitudinal direction - Only minimum steel required.
1682 TOP : Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1682 TOP : 0.540 0.00 / 218 0.540 0.00 / 218
COVER (BOTTOM): 75.000 MM TH: 300.000 MM BOTT: 0.540 13.93 / 218 0.795 59.36 / 219
1666 TOP : Longitudinal direction - Only minimum steel required.
1666 BOTT: Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1666 TOP : Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1666 BOTT: Transverse direction - Only minimum steel required. 1684 TOP : Longitudinal direction - Only minimum steel required.
1666 TOP : 0.540 0.00 / 201 0.540 0.00 / 210 1684 BOTT: Longitudinal direction - Only minimum steel required.
BOTT: 0.540 6.23 / 219 0.540 34.22 / 201 1684 TOP : Transverse direction - Only minimum steel required.
1684 BOTT: Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1684 TOP : 0.540 1.33 / 201 0.540 7.79 / 201
COVER (BOTTOM): 75.000 MM TH: 300.000 MM BOTT: 0.540 0.00 / 218 0.540 0.00 / 219
1667 TOP : Longitudinal direction - Only minimum steel required.
1667 BOTT: Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1667 TOP : Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1667 BOTT: Transverse direction - Only minimum steel required. STAAD SPACE -- PAGE NO. 281
STAAD SPACE -- PAGE NO. 279
1685 TOP : Longitudinal direction - Only minimum steel required.
1667 TOP : 0.540 4.37 / 201 0.540 16.57 / 201 1685 BOTT: Longitudinal direction - Only minimum steel required.
BOTT: 0.540 2.67 / 219 0.540 0.00 / 201 1685 TOP : Transverse direction - Only minimum steel required.
1685 BOTT: Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1685 TOP : 0.540 10.72 / 219 0.540 20.05 / 218
COVER (BOTTOM): 75.000 MM TH: 300.000 MM BOTT: 0.540 2.24 / 208 0.540 0.00 / 219
1668 TOP : Longitudinal direction - Only minimum steel required.
1668 BOTT: Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1668 TOP : Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1668 BOTT: Transverse direction - Only minimum steel required. 1687 TOP : Longitudinal direction - Only minimum steel required.
1668 TOP : 0.540 2.97 / 219 0.540 15.91 / 219 1687 BOTT: Longitudinal direction - Only minimum steel required.
BOTT: 0.540 4.85 / 218 0.540 0.00 / 201 1687 TOP : Transverse direction - Only minimum steel required.
1687 BOTT: Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1687 TOP : 0.540 5.37 / 201 0.540 28.45 / 218
COVER (BOTTOM): 75.000 MM TH: 300.000 MM BOTT: 0.540 3.09 / 219 0.540 0.00 / 219
1669 TOP : Longitudinal direction - Only minimum steel required.
1669 BOTT: Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1669 TOP : Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1669 BOTT: Transverse direction - Only minimum steel required. 1688 TOP : Longitudinal direction - Only minimum steel required.
1669 TOP : 0.540 4.98 / 219 0.540 11.66 / 219 1688 BOTT: Longitudinal direction - Only minimum steel required.
BOTT: 0.540 1.99 / 217 0.540 0.00 / 201 1688 TOP : Transverse direction - Only minimum steel required.
1688 BOTT: Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1688 TOP : 0.540 4.89 / 201 0.540 31.42 / 218
COVER (BOTTOM): 75.000 MM TH: 300.000 MM BOTT: 0.540 0.00 / 219 0.540 0.00 / 219
1670 TOP : Longitudinal direction - Only minimum steel required.
1670 BOTT: Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1670 TOP : Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1670 BOTT: Transverse direction - Only minimum steel required. 1690 TOP : Longitudinal direction - Only minimum steel required.
1670 TOP : 0.540 10.07 / 218 0.540 5.74 / 218 1690 BOTT: Longitudinal direction - Only minimum steel required.
BOTT: 0.540 0.00 / 217 0.540 0.00 / 201 1690 TOP : Transverse direction - Only minimum steel required.
1690 TOP : 0.540 0.00 / 201 0.540 0.00 / 218
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM BOTT: 0.540 12.06 / 202 0.881 65.57 / 219
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 184 of 361
1711 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1711 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1711 TOP : Transverse direction - Only minimum steel required.
1691 TOP : Longitudinal direction - Only minimum steel required. 1711 BOTT: Transverse direction - Only minimum steel required.
1691 BOTT: Longitudinal direction - Only minimum steel required. 1711 TOP : 0.540 7.37 / 219 0.540 21.28 / 218
1691 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 1.35 / 208 0.540 0.00 / 219
1691 TOP : 0.540 0.55 / 208 0.540 0.00 / 218
BOTT: 0.540 16.95 / 219 1.134 83.67 / 219 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
COVER (BOTTOM): 75.000 MM TH: 300.000 MM
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1712 TOP : Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1712 BOTT: Longitudinal direction - Only minimum steel required.
1693 TOP : Longitudinal direction - Only minimum steel required. 1712 TOP : Transverse direction - Only minimum steel required.
1693 BOTT: Longitudinal direction - Only minimum steel required. 1712 BOTT: Transverse direction - Only minimum steel required.
1693 TOP : Transverse direction - Only minimum steel required. 1712 TOP : 0.540 1.35 / 201 0.540 7.96 / 201
1693 TOP : 0.540 0.65 / 208 0.540 0.00 / 218 BOTT: 0.540 0.00 / 208 0.540 0.00 / 219
BOTT: 0.540 16.65 / 219 1.112 82.14 / 219
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM COVER (BOTTOM): 75.000 MM TH: 300.000 MM
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1713 TOP : Longitudinal direction - Only minimum steel required.
1694 TOP : Longitudinal direction - Only minimum steel required. 1713 BOTT: Longitudinal direction - Only minimum steel required.
1694 BOTT: Longitudinal direction - Only minimum steel required. 1713 TOP : Transverse direction - Only minimum steel required.
1694 TOP : Transverse direction - Only minimum steel required. 1713 BOTT: Transverse direction - Only minimum steel required.
STAAD SPACE -- PAGE NO. 282 STAAD SPACE -- PAGE NO. 284

1694 TOP : 0.540 0.00 / 208 0.540 0.00 / 218 1713 TOP : 0.540 2.40 / 218 0.540 0.00 / 201
BOTT: 0.540 11.96 / 218 0.801 59.83 / 219 BOTT: 0.540 1.12 / 208 0.540 3.76 / 201

FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
COVER (BOTTOM): 75.000 MM TH: 300.000 MM COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1696 TOP : Longitudinal direction - Only minimum steel required. 1714 TOP : Longitudinal direction - Only minimum steel required.
1696 BOTT: Longitudinal direction - Only minimum steel required. 1714 BOTT: Longitudi nal direction - Only minimum steel required.
1696 BOTT: Transverse direction - Only minimum steel required. 1714 TOP : Transverse direction - Only minimum steel required.
1696 TOP : 0.540 5.49 / 218 0.540 40.68 / 218 1714 BOTT: Transverse direction - Only minimum steel required.
BOTT: 0.540 0.00 / 218 0.540 0.00 / 219 1714 TOP : 0.540 4.03 / 202 0.540 15.55 / 202
BOTT: 0.540 0.23 / 208 0.540 1.36 / 208
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
COVER (BOTTOM): 75.000 MM TH: 300.000 MM FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1697 TOP : Longitudinal direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1697 BOTT: Longitudinal direction - Only minimum steel required. 1715 TOP : Longitudinal direction - Only minimum steel required.
1697 BOTT: Transverse direction - Only minimum steel required. 1715 BOTT: Longitudinal direction - Only minimum steel required.
1697 TOP : 0.540 10.60 / 201 0.612 45.96 / 218 1715 TOP : Transverse direction - Only minimum steel required.
BOTT: 0.540 0.00 / 218 0.540 0.00 / 219 1715 BOTT: Transverse direction - Only minimum steel required.
1715 TOP : 0.540 4.36 / 202 0.540 19.75 / 202
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM BOTT: 0.540 0.00 / 208 0.540 2.70 / 208
COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1699 TOP : Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1699 BOTT: Longitudinal direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1699 BOTT: Transverse direction - Only minimum steel required. 1716 TOP : Longitudinal direction - Only minimum steel required.
1699 TOP : 0.540 10.40 / 201 0.608 45.72 / 218 1716 BOTT: Longitudinal direction - Only minimum steel required.
BOTT: 0.540 0.00 / 218 0.540 0.00 / 219 1716 TOP : Transverse direction - Only minimum steel required.
1716 BOTT: Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1716 TOP : 0.540 0.80 / 219 0.540 17.87 / 219
COVER (BOTTOM): 75.000 MM TH: 300.000 MM BOTT: 0.540 0.74 / 201 0.540 3.22 / 208
1700 TOP : Longitudinal direction - Only minimum steel required.
1700 BOTT: Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1700 TOP : Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1700 BOTT: Transverse direction - Only minimum steel required. 1717 TOP : Longitudinal direction - Only minimum steel required.
1700 TOP : 0.540 7.72 / 219 0.540 40.18 / 218 1717 BOTT: Longitudinal direction - Only minimum steel required.
BOTT: 0.540 0.00 / 218 0.540 0.00 / 219 1717 TOP : Transverse direction - Only minimum steel required.
1717 BOTT: Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1717 TOP : 0.540 2.45 / 219 0.540 21.30 / 202
COVER (BOTTOM): 75.000 MM TH: 300.000 MM BOTT: 0.540 0.41 / 208 0.540 4.65 / 208
1702 TOP : Longitudinal direction - Only minimum steel required.
1702 BOTT: Longitudinal direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1702 TOP : Transverse direction - Only minimum steel required. COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1702 TOP : 0.540 0.00 / 219 0.540 0.00 / 218 1718 TOP : Longitudinal direction - Only minimum steel required.
BOTT: 0.540 11.75 / 218 0.698 52.32 / 219 1718 BOTT: Longitudinal direction - Only minimum steel required.
1718 TOP : Transverse direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1718 BOTT: Transverse direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1718 TOP : 0.540 4.00 / 202 0.540 21.68 / 202
1703 TOP : Longitudinal direction - Only minimum steel required. BOTT: 0.540 0.64 / 208 0.540 7.04 / 208
1703 BOTT: Longitudinal direction - Only minimum steel required.
1703 TOP : Transverse direction - Only minimum steel required. FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
1703 TOP : 0.540 0.26 / 208 0.540 0.00 / 218 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
BOTT: 0.540 20.09 / 219 1.023 75.80 / 219 1719 TOP : Longitudinal direction - Only minimum steel required.
1719 BOTT: Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1719 TOP : Transverse direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1719 BOTT: Transverse direction - Only minimum steel required.
1705 TOP : Longitudinal direction - Only minimum steel required. STAAD SPACE -- PAGE NO. 285
1705 BOTT: Longitudinal direction - Only minimum steel required.
STAAD SPACE -- PAGE NO. 283 1719 TOP : 0.540 3.68 / 202 0.540 21.23 / 202
BOTT: 0.540 0.54 / 208 0.540 7.35 / 208
1705 TOP : Transverse direction - Only minimum steel required.
1705 TOP : 0.540 1.25 / 210 0.540 0.00 / 218 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 6.40 / 216 0.752 56.25 / 219 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1720 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1720 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1720 TOP : Transverse direction - Only minimum steel required.
1706 TOP : Longitudinal direction - Only minimum steel required. 1720 BOTT: Transverse direction - Only minimum steel required.
1706 BOTT: Longitudinal direction - Only minimum steel required. 1720 TOP : 0.540 1.87 / 219 0.540 19.39 / 219
1706 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 0.98 / 201 0.540 6.30 / 208
1706 BOTT: Transverse direction - Only minimum steel required.
1706 TOP : 0.540 2.22 / 210 0.540 0.00 / 218 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 3.62 / 216 0.540 11.89 / 219 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1721 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1721 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1721 TOP : Transverse direction - Only minimum steel required.
1708 TOP : Longitudinal direction - Only minimum steel required. 1721 BOTT: Transverse direction - Only minimum steel required.
1708 BOTT: Longitudinal direction - Only minimum steel required. 1721 TOP : 0.540 0.92 / 219 0.540 16.59 / 219
1708 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 1.11 / 201 0.540 6.82 / 208
1708 BOTT: Transverse direction - Only minimum steel required.
1708 TOP : 0.540 8.40 / 219 0.540 36.23 / 218 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 0.00 / 216 0.540 0.00 / 219 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1722 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1722 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1722 TOP : Transverse direction - Only minimum steel required.
1709 TOP : Longitudinal direction - Only minimum steel required. 1722 BOTT: Transverse direction - Only minimum steel required.
1709 BOTT: Longitudinal direction - Only minimum steel required. 1722 TOP : 0.540 4.70 / 202 0.540 23.44 / 202
1709 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 0.05 / 208 0.540 4.89 / 208
1709 BOTT: Transverse direction - Only minimum steel required.
1709 TOP : 0.540 6.84 / 201 0.540 32.88 / 218 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 1.21 / 219 0.540 0.00 / 219 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1723 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1723 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1723 TOP : Transverse direction - Only minimum steel required.
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 185 of 361
1723 BOTT: Transverse direction - Only minimum steel required.
1723 TOP : 0.540 3.62 / 202 0.540 17.86 / 202 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 0.42 / 208 0.540 2.48 / 208 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1754 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1754 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1754 TOP : Transverse direction - Only minimum steel required.
1724 TOP : Longitudinal direction - Only minimum steel required. 1754 BOTT: Transverse direction - Only minimum steel required.
1724 BOTT: Longitudinal direction - Only minimum steel required. 1754 TOP : 0.540 14.02 / 218 0.540 2.67 / 215
1724 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 7.72 / 208 0.540 1.20 / 209
1724 BOTT: Transverse direction - Only minimum steel required.
1724 TOP : 0.540 1.76 / 218 0.540 0.00 / 202 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 1.35 / 208 0.540 4.51 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1757 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1757 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1757 TOP : Transverse direction - Only minimum steel required.
1727 TOP : Longitudinal direction - Only minimum steel required. 1757 BOTT: Transverse direction - Only minimum steel required.
1727 BOTT: Longitudinal direction - Only minimum steel required. STAAD SPACE -- PAGE NO. 288
1727 TOP : Transverse direction - Only minimum steel required.
1727 BOTT: Transverse direction - Only minimum steel required. 1757 TOP : 0.540 15.04 / 218 0.540 2.85 / 218
STAAD SPACE -- PAGE NO. 286 BOTT: 0.540 8.06 / 208 0.540 1.27 / 208

1727 TOP : 0.540 7.19 / 208 0.540 1.19 / 208 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 15.63 / 218 0.540 2.76 / 218 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1760 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1760 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1760 TOP : Transverse direction - Only minimum steel required.
1730 TOP : Longitudinal direction - Only minimum steel required. 1760 BOTT: Transverse direction - Only minimum steel required.
1730 BOTT: Longitudinal direction - Only minimum steel required. 1760 TOP : 0.540 8.50 / 218 0.540 3.82 / 215
1730 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 4.65 / 208 0.540 1.67 / 209
1730 BOTT: Transverse direction - Only minimum steel required.
1730 TOP : 0.540 3.72 / 208 0.540 1.73 / 207 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 7.83 / 218 0.540 2.96 / 217 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1762 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1762 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1762 TOP : Transverse direction - Only minimum steel required.
1732 TOP : Longitudinal direction - Only minimum steel required. 1762 BOTT: Transverse direction - Only minimum steel required.
1732 BOTT: Longitudinal direction - Only minimum steel required. 1762 TOP : 0.540 4.57 / 217 0.540 5.25 / 215
1732 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 1.87 / 207 0.540 2.45 / 209
1732 BOTT: Transverse direction - Only minimum steel required.
1732 TOP : 0.540 2.04 / 209 0.540 2.73 / 207 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 3.24 / 215 0.540 3.54 / 217 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1765 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1765 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1765 TOP : Transverse direction - Only minimum steel required.
1735 TOP : Longitudinal direction - Only minimum steel required. 1765 BOTT: Transverse direction - Only minimum steel required.
1735 BOTT: Longitudinal direction - Only minimum steel required. 1765 TOP : 0.540 7.07 / 217 0.540 5.39 / 215
1735 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 2.60 / 207 0.540 2.85 / 209
1735 BOTT: Transverse direction - Only minimum steel required.
1735 TOP : 0.540 3.51 / 209 0.540 3.20 / 207 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 4.28 / 215 0.540 3.59 / 217 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1768 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1768 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1768 TOP : Transverse direction - Only minimum steel required.
1738 TOP : Longitudinal direction - Only minimum steel required. 1768 BOTT: Transverse direction - Only minimum steel required.
1738 BOTT: Longitudinal direction - Only minimum steel required. 1768 TOP : 0.540 3.95 / 217 0.540 3.64 / 215
1738 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 3.81 / 207 0.540 4.33 / 209
1738 BOTT: Transverse direction - Only minimum steel required.
1738 TOP : 0.540 4.29 / 217 0.540 4.01 / 207 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 3.26 / 207 0.540 2.96 / 217 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1769 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1769 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1769 TOP : Transverse direction - Only minimum steel required.
1739 TOP : Longitudinal direction - Only minimum steel required. 1769 BOTT: Transverse direction - Only minimum steel required.
1739 BOTT: Longitudinal direction - Only minimum steel required. 1769 TOP : 0.540 2.91 / 208 0.540 1.56 / 207
1739 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 6.88 / 218 0.540 6.49 / 217
1739 BOTT: Transverse direction - Only minimum steel required.
1739 TOP : 0.540 6.48 / 218 0.540 5.31 / 215 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 3.36 / 208 0.540 1.93 / 209 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1772 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1772 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1772 TOP : Transverse direction - Only minimum steel required.
1742 TOP : Longitudinal direction - Only minimum steel required. 1772 BOTT: Transverse direction - Only minimum steel required.
1742 BOTT: Longitudinal direction - Only minimum steel required. STAAD SPACE -- PAGE NO. 289
1742 TOP : Transverse direction - Only minimum steel required.
1742 BOTT: Transverse direction - Only minimum steel required. 1772 TOP : 0.540 3.58 / 218 0.540 1.34 / 207
STAAD SPACE -- PAGE NO. 287 BOTT: 0.540 5.47 / 208 0.540 6.60 / 217

1742 TOP : 0.540 5.19 / 208 0.540 5.10 / 215 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 4.43 / 218 0.540 1.85 / 209 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1775 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1775 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1775 TOP : Transverse direction - Only minimum steel required.
1744 TOP : Longitudinal direction - Only minimum steel required. 1775 BOTT: Transverse direction - Only minimum steel required.
1744 BOTT: Longitudinal direction - Only minimum steel required. 1775 TOP : 0.540 3.73 / 217 0.540 1.76 / 207
1744 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 4.07 / 207 0.540 5.08 / 217
1744 BOTT: Transverse direction - Only minimum steel required.
1744 TOP : 0.540 4.05 / 209 0.540 4.01 / 207 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 4.48 / 215 0.540 2.19 / 217 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1778 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1778 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1778 TOP : Transverse direction - Only minimum steel required.
1747 TOP : Longitudinal direction - Only minimum steel required. 1778 BOTT: Transverse direction - Only minimum steel required.
1747 BOTT: Longitudinal direction - Only minimum steel required. 1778 TOP : 0.540 3.62 / 209 0.540 1.73 / 207
1747 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 3.42 / 215 0.540 3.90 / 217
1747 BOTT: Transverse direction - Only minimum steel required.
1747 TOP : 0.540 3.38 / 209 0.540 3.10 / 207 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 4.01 / 215 0.540 2.02 / 217 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1781 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1781 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1781 TOP : Transverse direction - Only minimum steel required.
1750 TOP : Longitudinal direction - Only minimum steel required. 1781 BOTT: Transverse direction - Only minimum steel required.
1750 BOTT: Longitudinal direction - Only minimum steel required. 1781 TOP : 0.540 2.52 / 208 0.540 1.56 / 207
1750 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 2.73 / 218 0.540 3.08 / 217
1750 BOTT: Transverse direction - Only minimum steel required.
1750 TOP : 0.540 2.47 / 218 0.540 2.47 / 215 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 2.36 / 208 0.540 1.67 / 209 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1784 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1784 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1784 TOP : Transverse direction - Only minimum steel required.
1753 TOP : Longitudinal direction - Only minimum steel required. 1784 BOTT: Transverse direction - Only minimum steel required.
1753 BOTT: Longitudinal direction - Only minimum steel required. 1784 TOP : 0.540 5.32 / 208 0.540 1.30 / 207
1753 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 7.11 / 218 0.540 2.57 / 217
1753 BOTT: Transverse direction - Only minimum steel required.
1753 TOP : 0.540 7.08 / 218 0.540 2.30 / 215 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 4.99 / 208 0.540 1.34 / 209 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 186 of 361
1785 TOP : Longitudinal direction - Only minimum steel required. 1801 BOTT: Transverse direction - Only minimum steel required.
1785 BOTT: Longitudinal direction - Only minimum steel required. 1801 TOP : 0.540 0.51 / 219 0.540 7.28 / 201
1785 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 3.50 / 217 0.540 0.00 / 217
1785 BOTT: Transverse direction - Only minimum steel required.
1785 TOP : 0.540 8.34 / 208 0.540 1.23 / 207 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 13.66 / 218 0.540 2.64 / 217 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1802 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1802 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1802 TOP : Transverse direction - Only minimum steel required.
1786 TOP : Longitudinal direction - Only minimum steel required. 1802 BOTT: Transverse direction - Only minimum steel required.
1786 BOTT: Longitudinal direction - Only minimum steel required. STAAD SPACE -- PAGE NO. 292
1786 TOP : Transverse direction - Only minimum steel required.
1786 BOTT: Transverse direction - Only minimum steel required. 1802 TOP : 0.540 2.64 / 207 0.540 5.27 / 207
STAAD SPACE -- PAGE NO. 290 BOTT: 0.540 3.65 / 217 0.540 15.15 / 217

1786 TOP : 0.540 0.00 / 208 0.540 0.00 / 207 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 11.59 / 218 0.540 3.18 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1803 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1803 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1803 TOP : Transverse direction - Only minimum steel required.
1787 TOP : Longitudinal direction - Only minimum steel required. 1803 BOTT: Transverse direction - Only minimum steel required.
1787 BOTT: Longitudinal direction - Only minimum steel required. 1803 TOP : 0.540 0.00 / 207 0.540 4.26 / 207
1787 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 2.26 / 217 0.540 20.72 / 217
1787 BOTT: Transverse direction - Only minimum steel required.
1787 TOP : 0.540 0.84 / 217 0.540 0.00 / 207 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 3.07 / 219 0.540 5.97 / 219 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1804 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1804 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1804 TOP : Transverse direction - Only minimum steel required.
1788 TOP : Longitudinal direction - Only minimum steel required. 1804 BOTT: Transverse direction - Only minimum steel required.
1788 BOTT: Longitudinal direction - Only minimum steel required. 1804 TOP : 0.540 0.00 / 207 0.540 2.29 / 207
1788 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 2.68 / 217 0.540 19.01 / 217
1788 BOTT: Transverse direction - Only minimum steel required.
1788 TOP : 0.540 4.37 / 217 0.540 0.00 / 207 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 0.67 / 207 0.540 7.46 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1805 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1805 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1805 TOP : Transverse direction - Only minimum steel required.
1789 TOP : Longitudinal direction - Only minimum steel required. 1805 BOTT: Transverse direction - Only minimum steel required.
1789 BOTT: Longitudinal direction - Only minimum steel required. 1805 TOP : 0.540 0.00 / 207 0.540 0.11 / 207
1789 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 3.09 / 217 0.540 16.37 / 217
1789 BOTT: Transverse direction - Only minimum steel required.
1789 TOP : 0.540 3.89 / 217 0.540 0.28 / 215 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 1.06 / 207 0.540 9.18 / 209 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1806 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1806 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1806 TOP : Transverse direction - Only minimum steel required.
1790 TOP : Longitudinal direction - Only minimum steel required. 1806 BOTT: Transverse direction - Only minimum steel required.
1790 BOTT: Longitudinal direction - Only minimum steel required. 1806 TOP : 0.540 0.00 / 207 0.540 0.00 / 207
1790 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 2.57 / 217 0.540 12.55 / 217
1790 BOTT: Transverse direction - Only minimum steel required.
1790 TOP : 0.540 0.80 / 207 0.540 3.64 / 207 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 3.78 / 219 0.540 14.32 / 217 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1807 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1807 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1807 TOP : Transverse direction - Only minimum steel required.
1791 TOP : Longitudinal direction - Only minimum steel required. 1807 BOTT: Transverse direction - Only minimum steel required.
1791 BOTT: Longitudinal direction - Only minimum steel required. 1807 TOP : 0.540 1.69 / 218 0.540 0.00 / 207
1791 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 1.41 / 208 0.540 7.54 / 217
1791 BOTT: Transverse direction - Only minimum steel required.
1791 TOP : 0.540 2.13 / 207 0.540 5.82 / 207 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 10.03 / 217 0.540 14.41 / 217 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1808 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1808 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1808 TOP : Transverse direction - Only minimum steel required.
1793 TOP : Longitudinal direction - Only minimum steel required. 1808 BOTT: Transverse direction - Only minimum steel required.
1793 BOTT: Longitudinal direction - Only minimum steel required. STAAD SPACE -- PAGE NO. 293
1793 TOP : Transverse direction - Only minimum steel required.
1793 BOTT: Transverse direction - Only minimum steel required. 1808 TOP : 0.540 12.60 / 218 0.540 2.81 / 201
STAAD SPACE -- PAGE NO. 291 BOTT: 0.540 0.00 / 208 0.540 0.00 / 217

1793 TOP : 0.540 0.00 / 207 0.540 6.43 / 201 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 5.14 / 218 0.540 0.00 / 217 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1809 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1809 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1809 TOP : Transverse direction - Only minimum steel required.
1795 TOP : Longitudinal direction - Only minimum steel required. 1809 BOTT: Transverse direction - Only minimum steel required.
1795 BOTT: Longitudinal direction - Only minimum steel required. 1809 TOP : 0.540 4.44 / 219 0.540 3.72 / 219
1795 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 1.86 / 216 0.540 1.93 / 202
1795 BOTT: Transverse direction - Only minimum steel required.
1795 TOP : 0.540 4.37 / 201 0.540 17.86 / 201 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 0.00 / 218 0.540 0.00 / 217 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1810 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1810 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1810 TOP : Transverse direction - Only minimum steel required.
1796 TOP : Longitudinal direction - Only minimum steel required. 1810 BOTT: Transverse direction - Only minimum steel required.
1796 BOTT: Longitudinal direction - Only minimum steel required. 1810 TOP : 0.540 0.00 / 219 0.540 4.13 / 208
1796 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 7.01 / 215 0.540 7.79 / 202
1796 BOTT: Transverse direction - Only minimum steel required.
1796 TOP : 0.540 6.44 / 217 0.540 23.61 / 201 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 0.00 / 218 0.540 0.00 / 217 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1811 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1811 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1811 TOP : Transverse direction - Only minimum steel required.
1798 TOP : Longitudinal direction - Only minimum steel required. 1811 BOTT: Transverse direction - Only minimum steel required.
1798 BOTT: Longitudinal direction - Only minimum steel required. 1811 TOP : 0.540 1.61 / 209 0.540 7.28 / 207
1798 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 5.16 / 219 0.540 6.56 / 202
1798 BOTT: Transverse direction - Only minimum steel required.
1798 TOP : 0.540 6.66 / 217 0.540 23.34 / 201 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 0.00 / 218 0.540 0.00 / 217 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1812 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1812 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1812 TOP : Transverse direction - Only minimum steel required.
1800 TOP : Longitudinal direction - Only minimum steel required. 1812 BOTT: Transverse direction - Only minimum steel required.
1800 BOTT: Longitudinal direction - Only minimum steel required. 1812 TOP : 0.540 3.19 / 219 0.540 13.44 / 207
1800 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 0.77 / 217 0.540 5.73 / 217
1800 BOTT: Transverse direction - Only minimum steel required.
1800 TOP : 0.540 4.41 / 201 0.540 17.84 / 201 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 0.00 / 218 0.540 0.00 / 217 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1813 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1813 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1813 TOP : Transverse direction - Only minimum steel required.
1801 TOP : Longitudinal direction - Only minimum steel required. 1813 BOTT: Transverse direction - Only minimum steel required.
1801 BOTT: Longitudinal direction - Only minimum steel required. 1813 TOP : 0.540 10.48 / 215 0.540 13.53 / 215
1801 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 2.19 / 209 0.540 5.73 / 209
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 187 of 361
1824 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1824 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1824 TOP : Transverse direction - Only minimum steel required.
1815 TOP : Longitudinal direction - Only minimum steel required. 1824 BOTT: Transverse direction - Only minimum steel required.
1815 BOTT: Longitudinal direction - Only minimum steel required. STAAD SPACE -- PAGE NO. 295
1815 TOP : Transverse direction - Only minimum steel required.
1815 BOTT: Transverse direction - Only minimum steel required. 1824 TOP : 0.540 3.34 / 215 0.540 14.82 / 215
STAAD SPACE -- PAGE NO. 294 BOTT: 0.540 2.63 / 209 0.540 5.12 / 209

1815 TOP : 0.540 6.00 / 218 0.540 0.00 / 215 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 0.00 / 209 0.540 6.63 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1825 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1825 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1825 TOP : Transverse direction - Only minimum steel required.
1817 TOP : Longitudinal direction - Only minimum steel required. 1825 BOTT: Transverse direction - Only minimum steel required.
1817 BOTT: Longitudinal direction - Only minimum steel required. 1825 TOP : 0.540 2.26 / 215 0.540 20.57 / 215
1817 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 0.00 / 209 0.540 4.16 / 209
1817 BOTT: Transverse direction - Only minimum steel required.
1817 TOP : 0.540 0.00 / 218 0.540 0.00 / 215 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 4.75 / 201 0.540 18.83 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1826 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1826 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1826 TOP : Transverse direction - Only minimum steel required.
1818 TOP : Longitudinal direction - Only minimum steel required. 1826 BOTT: Transverse direction - Only minimum steel required.
1818 BOTT: Longitudinal direction - Only minimum steel required. 1826 TOP : 0.540 2.71 / 215 0.540 18.76 / 215
1818 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 0.00 / 209 0.540 2.50 / 209
1818 BOTT: Transverse direction - Only minimum steel required.
1818 TOP : 0.540 0.00 / 218 0.540 0.00 / 215 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 8.19 / 202 0.540 25.37 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1827 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1827 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1827 TOP : Transverse direction - Only minimum steel required.
1820 TOP : Longitudinal direction - Only minimum steel required. 1827 BOTT: Transverse direction - Only minimum steel required.
1820 BOTT: Longitudinal direction - Only minimum steel required. 1827 TOP : 0.540 2.95 / 215 0.540 16.00 / 215
1820 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 0.00 / 209 0.540 0.47 / 209
1820 BOTT: Transverse direction - Only minimum steel required.
1820 TOP : 0.540 0.00 / 218 0.540 0.00 / 215 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 8.05 / 219 0.540 25.30 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1828 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1828 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1828 TOP : Transverse direction - Only minimum steel required.
1822 TOP : Longitudinal direction - Only minimum steel required. 1828 BOTT: Transverse direction - Only minimum steel required.
1822 BOTT: Longitudinal direction - Only minimum steel required. 1828 TOP : 0.540 2.46 / 215 0.540 12.12 / 215
1822 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 0.00 / 209 0.540 0.00 / 209
1822 BOTT: Transverse direction - Only minimum steel required.
1822 TOP : 0.540 0.00 / 218 0.540 0.00 / 215 FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM
BOTT: 0.540 4.51 / 201 0.540 19.38 / 201 COVER (BOTTOM): 75.000 MM TH: 300.000 MM
1829 TOP : Longitudinal direction - Only minimum steel required.
FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM 1829 BOTT: Longitudinal direction - Only minimum steel required.
COVER (BOTTOM): 75.000 MM TH: 300.000 MM 1829 TOP : Transverse direction - Only minimum steel required.
1823 TOP : Longitudinal direction - Only minimum steel required. 1829 BOTT: Transverse direction - Only minimum steel required.
1823 BOTT: Longitudinal direction - Only minimum steel required. 1829 TOP : 0.540 1.52 / 208 0.540 7.20 / 215
1823 TOP : Transverse direction - Only minimum steel required. BOTT: 0.540 1.42 / 218 0.540 0.00 / 209
1823 BOTT: Transverse direction - Only minimum steel required.
1823 TOP : 0.540 4.19 / 215 0.540 0.00 / 215
BOTT: 0.540 0.00 / 201 0.540 8.00 / 201 ***************************END OF ELEMENT DESIGN***************************

FY: 413.997 MPA FC: 35.000 MPA COVER (TOP): 75.000 MM


COVER (BOTTOM): 75.000 MM TH: 300.000 MM
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 188 of 361

4.5 Design of Foundation

4.5.1 Dead Load Support Reaction & Resisting Moment

4.5.2 Overturning & Sliding Check

4.5.3 Basement level foundation buoyancy check

4.5.4 Soil Bearing Capacity Check

4.5.5 Foundation member design


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 189 of 361

4.5 Design of Foundation

150 150

150 150

150 150
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 190 of 361

4.5.1 Dead Load Support Reaction & Resisting Moment


28811.141 279642.87 301829.37
Horizontal Vertical Horizontal Moment distance Moment Mx distance Moment Mz
Node
L/C Fx (kN) Fy (kN) Fz (kN) Mx (kNm) My (kNm) Mz (kNm) ez (m) Fy*ez (kN.m) ex (m) Fy*ex (kN.m)
1 1 DL -71.88 168.724 -92.332 0 -5.335 0 1.55 261.52 1.55 261.52
2 1 DL -17.503 149.292 -26.074 0 -29.225 0 1.55 231.4 2.8 418.02
3 1 DL 3.817 151.529 -22.037 0 -22.39 0 1.55 234.87 4.05 613.69
4 1 DL 25.424 148.311 -38.466 0 -10.457 0 1.55 229.88 5.35 793.46
5 1 DL 16.422 160.265 -69.309 0 -9.215 0 1.55 248.41 6.55 1049.74
6 1 DL 6.149 177.777 -52.002 0 -5.351 0 1.55 275.55 8.05 1431.1
7 1 DL -4.543 160.015 -69.229 0 -12.786 0 1.55 248.02 9.55 1528.14
8 1 DL -17.228 118.296 -41.747 0 -11.298 0 1.55 183.36 10.75 1271.68
9 1 DL 1.104 94.594 -30.088 0 0.488 0 1.55 146.62 11.55 1092.56
10 1 DL 16.754 118.265 -40.036 0 11.963 0 1.55 183.31 12.35 1460.57
11 1 DL -6.924 142.103 -62.647 0 11.203 0 1.55 220.26 13.55 1925.5
12 1 DL -19.236 177.43 -42.992 0 8.044 0 1.55 275.02 14.75 2617.09
13 1 DL -9.499 210.141 -29.011 0 20.908 0 1.55 325.72 16.55 3477.83
14 1 DL 11.531 178.492 -35.94 0 28.535 0 1.55 276.66 18.3 3266.4
15 1 DL 74.101 168.041 -103.042 0 3.751 0 1.55 260.46 19.55 3285.2
16 1 DL -36.476 187.473 -15.24 0 23.084 0 2.8 524.92 1.55 290.58
17 1 DL 37.192 186.234 -29.185 0 -24.814 0 2.8 521.46 19.55 3640.87
18 1 DL -30.324 182.6 -8.993 0 12.751 0 4.7 858.22 1.55 283.03
19 1 DL 29.137 180.703 -27.095 0 -14.057 0 4.7 849.3 19.55 3532.74
20 1 DL -44.349 140.956 -6.625 0 -0.839 0 5.9 831.64 1.55 218.48
21 1 DL -14.13 81.426 6.561 0 -0.231 0 5.9 480.41 6.55 533.34
22 1 DL -6.472 76.896 8.989 0 -0.1 0 5.9 453.69 9.55 734.36
23 1 DL 11.759 75.51 8.915 0 -0.354 0 5.9 445.51 13.55 1023.16
24 1 DL 44.104 139.171 -27.333 0 0.502 0 5.9 821.11 19.55 2720.79
25 1 DL -28.72 169.647 -16.663 0 -12.145 0 7.1 1204.49 1.55 262.95
26 1 DL 29.463 167.09 -49.297 0 12.627 0 7.1 1186.34 19.55 3266.61
27 1 DL -24.652 184.22 -17.366 0 -20.906 0 8.8 1621.14 1.55 285.54
28 1 DL 26.276 180.878 -64.638 0 22.293 0 8.8 1591.73 19.55 3536.16
29 1 DL -49.099 188.459 107.822 0 -0.624 0 10.25 1931.7 1.55 292.11
30 1 DL 106.053 167.638 19.482 0 31.254 0 10.25 1718.29 2.8 469.39
31 1 DL 111.817 171.233 44.38 0 24.308 0 10.25 1755.14 4.05 693.49
32 1 DL 118.187 168.643 56.578 0 5.3 0 10.25 1728.59 5.35 902.24
33 1 DL 81.719 183.061 105.539 0 5.833 0 10.25 1876.38 6.55 1199.05
34 1 DL 16.236 203.494 72.587 0 5.573 0 10.25 2085.81 8.05 1638.13
35 1 DL -30.748 183.142 98.591 0 14.815 0 10.25 1877.21 9.55 1749.01
36 1 DL -46.368 135.119 56.761 0 15.579 0 10.25 1384.97 10.75 1452.53
37 1 DL -25.697 107.844 41.34 0 -0.595 0 10.25 1105.4 11.55 1245.6
38 1 DL -25.398 134.508 50.854 0 -15.938 0 10.25 1378.71 12.35 1661.17
39 1 DL -97.409 160.928 82.284 0 -11.564 0 10.25 1649.51 13.55 2180.57
40 1 DL -147.588 199.7 55.797 0 -6.384 0 10.25 2046.93 14.75 2945.58
41 1 DL -167.759 234.108 48.158 0 -22.118 0 10.25 2399.61 16.55 3874.49
42 1 DL -107.834 197.098 33.826 0 -28.131 0 10.25 2020.25 18.3 3606.89
43 1 DL 69.338 184.8 112.749 0 1.562 0 10.25 1894.2 19.55 3612.84
72 1 DL 0.743 104.786 120.443 0 -11.489 0 10.25 1074.06 1.55 162.42
73 1 DL 57.487 47.033 20.175 0 7.502 0 10.25 482.09 2.8 131.69
85 1 DL 84.085 46.082 -0.361 0 -20.62 0 10.25 472.34 18.3 843.3
86 1 DL 53.01 102.661 244.778 0 9.749 0 10.25 1052.28 19.55 2007.02
87 1 DL 6.02 206.969 -24.986 0 -1.661 0 11.75 2431.89 1.55 320.8
88 1 DL -5.855 202.015 -16.886 0 0.766 0 11.75 2373.68 19.55 3949.39
89 1 DL 2.94 205.261 -7.008 0 0.411 0 13.25 2719.71 1.55 318.15
90 1 DL -3.293 199.551 -1.081 0 -0.976 0 13.25 2644.05 19.55 3901.22
91 1 DL 3.267 203.797 8.741 0 0.736 0 14.75 3006.01 1.55 315.89
92 1 DL -3.267 197.343 11.513 0 -0.879 0 14.75 2910.81 19.55 3858.06
93 1 DL 5.229 219.545 45.121 0 2.739 0 16.25 3567.61 1.55 340.29
94 1 DL -4.039 211.722 39.947 0 -2.542 0 16.25 3440.48 19.55 4139.17
95 1 DL 16.313 201.567 67.178 0 4.486 0 18 3628.21 1.55 312.43
96 1 DL -13.428 193.403 60.611 0 -4.31 0 18 3481.25 19.55 3781.03
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 191 of 361

97 1 DL 152.039 186.903 -87.689 0 1.954 0 19.25 3597.88 1.55 289.7


98 1 DL 26.694 167.379 -38.885 0 6.851 0 19.25 3222.05 2.8 468.66
99 1 DL 49.441 167.388 -24.92 0 -1.451 0 19.25 3222.22 4.05 677.92
100 1 DL 62.793 167.4 -37.824 0 -3.745 0 19.25 3222.45 5.35 895.59
101 1 DL 47.096 184.358 -60.356 0 -6.014 0 19.25 3548.89 6.55 1207.54
102 1 DL 22.73 200.493 -14.277 0 -1.196 0 19.25 3859.49 8.05 1613.97
103 1 DL 1.903 166.82 -48.382 0 -0.234 0 19.25 3211.29 9.55 1593.13
104 1 DL -19.093 132.904 -25.974 0 -1.371 0 19.25 2558.4 10.75 1428.72
105 1 DL -16.748 132.441 1.833 0 -2.093 0 19.25 2549.49 11.55 1529.69
106 1 DL -13.441 132.017 -20.301 0 -4.174 0 19.25 2541.33 12.35 1630.41
107 1 DL -41.578 164.619 -29.831 0 3.589 0 19.25 3168.92 13.55 2230.59
108 1 DL -64.141 195.95 -26.344 0 6.936 0 19.25 3772.04 14.75 2890.26
109 1 DL -49.51 210.825 -34.468 0 4.898 0 19.25 4058.38 16.55 3489.15
110 1 DL -31.221 193.079 -32.444 0 -5.691 0 19.25 3716.77 18.3 3533.35
111 1 DL -132.927 178.664 -82.145 0 -0.956 0 19.25 3439.28 19.55 3492.88
273 1 DL 0 95.825 0 0 0 0 1.55 148.53 0 0
274 1 DL 0 108.997 0 0 0 0 2.8 305.19 0 0
275 1 DL 0 110.319 0 0 0 0 4.7 518.5 0 0
276 1 DL 0 85.649 0 0 0 0 5.9 505.33 0 0
277 1 DL 0 102.34 0 0 0 0 7.1 726.61 0 0
278 1 DL 0 107.34 0 0 0 0 8.8 944.59 0 0
279 1 DL 0 106.519 0 0 0 0 10.25 1091.82 0 0
280 1 DL 0 95.577 0 0 0 0 1.55 148.14 21.1 2016.67
281 1 DL 0 108.66 0 0 0 0 2.8 304.25 21.1 2292.73
282 1 DL 0 110.015 0 0 0 0 4.7 517.07 21.1 2321.32
283 1 DL 0 85.314 0 0 0 0 5.9 503.35 21.1 1800.13
284 1 DL 0 101.671 0 0 0 0 7.1 721.86 21.1 2145.26
285 1 DL 0 106.022 0 0 0 0 8.8 932.99 21.1 2237.06
286 1 DL 0 104.791 0 0 0 0 10.25 1074.11 21.1 2211.09
287 1 DL 0 96.652 0 0 0 0 0 0 1.55 149.81
288 1 DL 0 87.951 0 0 0 0 0 0 2.8 246.26
289 1 DL 0 92.342 0 0 0 0 0 0 4.05 373.99
290 1 DL 0 92.889 0 0 0 0 0 0 5.35 496.96
291 1 DL 0 102.093 0 0 0 0 0 0 6.55 668.71
292 1 DL 0 114.929 0 0 0 0 0 0 8.05 925.18
293 1 DL 0 104.391 0 0 0 0 0 0 9.55 996.93
294 1 DL 0 77.532 0 0 0 0 0 0 10.75 833.47
295 1 DL 0 62.078 0 0 0 0 0 0 11.55 717
296 1 DL 0 77.46 0 0 0 0 0 0 12.35 956.63
297 1 DL 0 92.455 0 0 0 0 0 0 13.55 1252.77
298 1 DL 0 114.209 0 0 0 0 0 0 14.75 1684.58
299 1 DL 0 130.852 0 0 0 0 0 0 16.55 2165.6
300 1 DL 0 105.685 0 0 0 0 0 0 18.3 1934.04
301 1 DL 0 96.645 0 0 0 0 0 0 19.55 1889.41
302 1 DL 0 53.233 0 0 0 0 0 0 0 0
303 1 DL 0 53.198 0 0 0 0 0 0 21.1 1122.48
304 1 DL 0 106.012 0 0 0 0 12 1272.14 1.55 164.32
305 1 DL 0 96.763 0 0 0 0 12 1161.16 2.8 270.94
306 1 DL 0 101.912 0 0 0 0 12 1222.94 4.05 412.74
307 1 DL 0 102.825 0 0 0 0 12 1233.9 5.35 550.11
308 1 DL 0 113.364 0 0 0 0 12 1360.37 6.55 742.53
309 1 DL 0 127.768 0 0 0 0 12 1533.22 8.05 1028.53
310 1 DL 0 116.14 0 0 0 0 12 1393.68 9.55 1109.14
311 1 DL 0 86.115 0 0 0 0 12 1033.38 10.75 925.74
312 1 DL 0 68.863 0 0 0 0 12 826.36 11.55 795.37
313 1 DL 0 85.763 0 0 0 0 12 1029.16 12.35 1059.17
314 1 DL 0 102.039 0 0 0 0 12 1224.47 13.55 1382.63
315 1 DL 0 125.364 0 0 0 0 12 1504.37 14.75 1849.12
316 1 DL 0 142.503 0 0 0 0 12 1710.04 16.55 2358.42
317 1 DL 0 114.337 0 0 0 0 12 1372.04 18.3 2092.37
318 1 DL 0 104.162 0 0 0 0 12 1249.94 19.55 2036.37
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 192 of 361

319 1 DL 0 57.971 0 0 0 0 12 695.65 0 0


320 1 DL 0 56.939 0 0 0 0 12 683.27 21.1 1201.41
321 1 DL 0 110.135 0 0 0 0 11.75 1294.09 0 0
322 1 DL 0 108.505 0 0 0 0 13.25 1437.69 0 0
323 1 DL 0 107.54 0 0 0 0 14.75 1586.22 0 0
324 1 DL 0 116.112 0 0 0 0 16.25 1886.82 0 0
325 1 DL 0 107.249 0 0 0 0 18 1930.48 0 0
326 1 DL 0 98.908 0 0 0 0 19.25 1903.98 0 0
327 1 DL 0 107.289 0 0 0 0 11.75 1260.65 21.1 2263.8
328 1 DL 0 105.213 0 0 0 0 13.25 1394.07 21.1 2219.99
329 1 DL 0 103.783 0 0 0 0 14.75 1530.8 21.1 2189.82
330 1 DL 0 111.492 0 0 0 0 16.25 1811.75 21.1 2352.48
331 1 DL 0 102.356 0 0 0 0 18 1842.41 21.1 2159.71
332 1 DL 0 94.016 0 0 0 0 19.25 1809.81 21.1 1983.74
333 1 DL 0 98.56 0 0 0 0 20.8 2050.05 1.55 152.77
334 1 DL 0 88.739 0 0 0 0 20.8 1845.77 2.8 248.47
335 1 DL 0 88.366 0 0 0 0 20.8 1838.01 4.05 357.88
336 1 DL 0 87.99 0 0 0 0 20.8 1830.19 5.35 470.75
337 1 DL 0 96.339 0 0 0 0 20.8 2003.85 6.55 631.02
338 1 DL 0 104.621 0 0 0 0 20.8 2176.12 8.05 842.2
339 1 DL 0 86.649 0 0 0 0 20.8 1802.3 9.55 827.5
340 1 DL 0 69.087 0 0 0 0 20.8 1437.01 10.75 742.69
341 1 DL 0 68.852 0 0 0 0 20.8 1432.12 11.55 795.24
342 1 DL 0 68.68 0 0 0 0 20.8 1428.54 12.35 848.2
343 1 DL 0 85.643 0 0 0 0 20.8 1781.37 13.55 1160.46
344 1 DL 0 102.449 0 0 0 0 20.8 2130.94 14.75 1511.12
345 1 DL 0 110.664 0 0 0 0 20.8 2301.81 16.55 1831.49
346 1 DL 0 101.966 0 0 0 0 20.8 2120.89 18.3 1865.98
347 1 DL 0 93.818 0 0 0 0 20.8 1951.41 19.55 1834.14
348 1 DL 0 53.066 0 0 0 0 20.8 1103.77 0 0
349 1 DL 0 50.196 0 0 0 0 20.8 1044.08 21.1 1059.14
350 1 DL 0 158.182 0 0 0 0 2.8 442.91 2.8 442.91
351 1 DL 0 144.822 0 0 0 0 4.7 680.66 2.8 405.5
352 1 DL 0 110.234 0 0 0 0 5.9 650.38 2.8 308.66
353 1 DL 0 134.978 0 0 0 0 7.1 958.34 2.8 377.94
354 1 DL 0 155.275 0 0 0 0 8.8 1366.42 2.8 434.77
355 1 DL 0 188.338 0 0 0 0 2.8 527.35 18.3 3446.59
356 1 DL 0 170.22 0 0 0 0 4.7 800.03 18.3 3115.03
357 1 DL 0 128.693 0 0 0 0 5.9 759.29 18.3 2355.08
358 1 DL 0 157.729 0 0 0 0 7.1 1119.88 18.3 2886.44
359 1 DL 0 182.219 0 0 0 0 8.8 1603.53 18.3 3334.61
360 1 DL 0 151.491 0 0 0 0 2.8 424.17 4.05 613.54
361 1 DL 0 143.371 0 0 0 0 2.8 401.44 5.35 767.03
362 1 DL 0 149.867 0 0 0 0 2.8 419.63 6.55 981.63
363 1 DL 0 169.708 0 0 0 0 2.8 475.18 8.05 1366.15
364 1 DL 0 146.257 0 0 0 0 2.8 409.52 9.55 1396.75
365 1 DL 0 109.124 0 0 0 0 2.8 305.55 10.75 1173.08
366 1 DL 0 86.869 0 0 0 0 2.8 243.23 11.55 1003.34
367 1 DL 0 109.134 0 0 0 0 2.8 305.58 12.35 1347.8
368 1 DL 0 131.98 0 0 0 0 2.8 369.54 13.55 1788.33
369 1 DL 0 166.222 0 0 0 0 2.8 465.42 14.75 2451.77
370 1 DL 0 204.143 0 0 0 0 2.8 571.6 16.55 3378.57
371 1 DL 0 149.023 0 0 0 0 8.8 1311.4 4.05 603.54
372 1 DL 0 141.885 0 0 0 0 8.8 1248.59 5.35 759.08
373 1 DL 0 149.182 0 0 0 0 8.8 1312.8 6.55 977.14
374 1 DL 0 169.952 0 0 0 0 8.8 1495.58 8.05 1368.11
375 1 DL 0 145.824 0 0 0 0 8.8 1283.25 9.55 1392.62
376 1 DL 0 108.458 0 0 0 0 8.8 954.43 10.75 1165.92
377 1 DL 0 86.129 0 0 0 0 8.8 757.94 11.55 994.79
378 1 DL 0 107.856 0 0 0 0 8.8 949.13 12.35 1332.02
379 1 DL 0 129.554 0 0 0 0 8.8 1140.08 13.55 1755.46
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 193 of 361

380 1 DL 0 162.174 0 0 0 0 8.8 1427.13 14.75 2392.07


381 1 DL 0 197.345 0 0 0 0 8.8 1736.64 16.55 3266.06
382 1 DL 0 90.382 0 0 0 0 13.25 1197.56 18.3 1653.99
383 1 DL 0 89.559 0 0 0 0 14.75 1321 18.3 1638.93
384 1 DL 0 96.151 0 0 0 0 16.25 1562.45 18.3 1759.56
386 1 DL 0 92.745 0 0 0 0 13.25 1228.87 2.8 259.69
387 1 DL 0 92.217 0 0 0 0 14.75 1360.2 2.8 258.21
388 1 DL 0 99.333 0 0 0 0 16.25 1614.16 2.8 278.13
390 1 DL 0 75.915 0 0 0 0 18 1366.47 4.05 307.46
391 1 DL 0 76.103 0 0 0 0 18 1369.85 5.3 403.35
392 1 DL 0 83.944 0 0 0 0 18 1510.99 6.55 549.83
393 1 DL 0 91.749 0 0 0 0 18 1651.48 8.05 738.58
394 1 DL 0 76.344 0 0 0 0 18 1374.19 9.55 729.09
395 1 DL 0 60.922 0 0 0 0 18 1096.6 10.55 642.73
396 1 DL 0 60.716 0 0 0 0 18 1092.89 11.55 701.27
397 1 DL 0 60.483 0 0 0 0 18 1088.69 12.55 759.06
398 1 DL 0 75.247 0 0 0 0 18 1354.45 13.55 1019.6
399 1 DL 0 89.446 0 0 0 0 18 1610.03 15.05 1346.16
400 1 DL 0 95.968 0 0 0 0 18 1727.42 16.55 1588.27
401 1 DL 0 138.712 0 0 0 0 18 2496.82 18.3 2538.43
402 1 DL 0 128.697 0 0 0 0 18 2316.55 2.8 360.35
403 1 DL 0 93.116 0 0 0 0 11.75 1094.11 2.8 260.72
404 1 DL 0 91.095 0 0 0 0 11.75 1070.37 18.3 1667.04
418 1 DL 0 55.719 0 0 0 0 10.25 571.12 0 0
419 1 DL 0 54.503 0 0 0 0 10.25 558.66 21.1 1150.01
420 1 DL 0 107.806 0 0 0 0 4.7 506.69 6.55 706.13
421 1 DL 0 102.184 0 0 0 0 4.7 480.26 9.55 975.86
422 1 DL 0 98.734 0 0 0 0 4.7 464.05 13.55 1337.85
423 1 DL 0 109.141 0 0 0 0 4.7 512.96 5.35 583.9
424 1 DL 0 69.415 0 0 0 0 4.7 326.25 8.35 579.62
425 1 DL 0 80.506 0 0 0 0 4.7 378.38 12.35 994.25
426 1 DL 0 70.34 0 0 0 0 4.7 330.6 7.75 545.14
427 1 DL 0 79.687 0 0 0 0 4.7 374.53 10.75 856.64
428 1 DL 0 118.384 0 0 0 0 4.7 556.4 14.75 1746.16
429 1 DL 0 102.815 0 0 0 0 7.1 729.99 6.55 673.44
430 1 DL 0 97.859 0 0 0 0 7.1 694.8 9.55 934.55
431 1 DL 0 93.892 0 0 0 0 7.1 666.63 13.55 1272.24
432 1 DL 0 104.109 0 0 0 0 7.1 739.17 5.35 556.98
433 1 DL 0 63.42 0 0 0 0 7.1 450.28 8.35 529.56
434 1 DL 0 76.803 0 0 0 0 7.1 545.3 12.35 948.52
435 1 DL 0 64.063 0 0 0 0 7.1 454.85 7.75 496.49
436 1 DL 0 76.445 0 0 0 0 7.1 542.76 10.75 821.78
437 1 DL 0 112.7 0 0 0 0 7.1 800.17 14.75 1662.33
438 1 DL 0 84.578 0 0 0 0 5.9 499.01 5.35 452.49
439 1 DL 0 58.813 0 0 0 0 5.9 347 8.35 491.09
440 1 DL 0 61.809 0 0 0 0 5.9 364.67 12.35 763.34
441 1 DL 0 59.56 0 0 0 0 5.9 351.4 7.75 461.59
442 1 DL 0 61.489 0 0 0 0 5.9 362.79 10.75 661.01
443 1 DL 0 90.381 0 0 0 0 5.9 533.25 14.75 1333.12
446 1 DL 0 119.615 0 0 0 0 4.7 562.19 4.05 484.44
447 1 DL 0 93.926 0 0 0 0 5.9 554.16 4.05 380.4
448 1 DL 0 113.137 0 0 0 0 7.1 803.27 4.05 458.2
453 1 DL 0 144.996 0 0 0 0 4.7 681.48 16.55 2399.68
454 1 DL 0 137.348 0 0 0 0 7.1 975.17 16.55 2273.11
455 1 DL 0 113.015 0 0 0 0 5.9 666.79 16.55 1870.4
456 1 DL 0 11.086 0 0 0 0 3.92 43.46 8.05 89.24
458 1 DL 0 62.704 0 0 0 0 4.7 294.71 11.55 724.23
459 1 DL 0 60.166 0 0 0 0 7.1 427.18 11.55 694.92
460 1 DL 0 48.658 0 0 0 0 5.9 287.08 11.55 562
461 1 DL 0 6.668 0 0 0 0 7.67 51.14 8.05 53.68
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 194 of 361

4.5.2 Overturning & Sliding Check

1) Blast Load Applied to Long Side of Building


Design Data:
Building Width (B) = 18 m
Building Length (L) = 17.7 m
Foundation Width (BF) = 21.1 m
Heigth of building (H) = 6.4 m
Foundation depth from GL (Hsoil) = 4 m
Soil Density (ys) = 17 kN/m3
Angle of Internal Friction of Soil = 27 degree
Friction Coefficient (Concrete to Soil) = 0.4
Friction Coefficient (Soil to Soil) = 0.51
Overtuning Moment Safety Factor = 1.2
Sliding Safety Factor = 1
Dead Load (STAAD Reaction from table 4.5.1) = 28811.141 kN
Resisting Moment (STAAD Reaction from table 4.5.1) = 279642.87 kN-m
Resisting Moment = £ (Dead Load Reaction x Distance) at each Node
Soil Weight (Foundation Inside, 1.6m deep area) 15.5x6x1.6x17 = 2529.6 kN

Blast laod from blast load calculation,


Lateral blast load = 3013.2 kN
Vertical blast load (compression) = 8301.6 kN
Vertical blast load (tension) = -10426.8 kN

Overturning Moment Check:


Lateral Blast Load, V1 = V / 2 = 1506.6 kN
V2 = V / 2 = 1506.6 kN

Passive Soil Pressure,


Kp = (1+sin27)/(1-sin27) = 2.66
Pp1 = = 361.76 kN/m
Pp2 = = 261.3716 kN/m
Vsoil = (Pp1 x BF) - (Pb2 x (BF-B))
= (361.76X21.1)-(261.3716X(21.1-18))
Vsoil = = 6822.9 kN

Overturning Moment, Mo= V1 x (H + Hsoil) + V2 x (Hsoil) - Vsoil x Hsoil / 3


= 1506.6x(6.4+4)+1506.6x4-6822.9x4/3
= 12597.84 kNm
Resisting Moment, Mr = 279642.87 kNm
Factor of safety against overturning FOSo = 279642.87/12597.84 = 22.2
> 1.2
Satisfy overturning stability

Sliding Check:
Lateral Blast Load, V= = 3013.2 kN
Resisting Force Vr = (0.4x28811.141+0.51x2529.6+6822.9)
= 19637.5 kN
Factor of safety against sliding FOSs = 19637.5/3013.2 = 6.52
> 1
Satisfy sliding stability
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 195 of 361

2) Blast Load Applied to Short Side of Building


Design Data
Building Width (B) = 17.7 m
Building Length (L) = 18 m
Foundation Width (BF) = 20.8 m
Heigth of building (H) = 6.4 m
Foundation depth from GL (Hsoil) = 4 m
Soil Density (ys) = 17 kN/m3
Angle of Internal Friction of Soil = 27 degree
Friction Coefficient (Concrete to Soil) = 0.4
Friction Coefficient (Soil to Soil) = 0.51
Overtuning Moment Safety Factor = 1.2
Sliding Safety Factor = 1
Dead Load (Staad Reaction from table 4.5.1) = 28811.141 kN
Resisting Moment (Staad Reaction from table 4.5.1) = 301829.37 kN-m
Resisting Moment = £ (Dead Load Reaction x Distance) at each Node
Soil Weight (Foundation Inside, 1.6m deep area) 15.5x6x1.6x17 = 2529.6 kN

Blast laod from blast load calculation,


Lateral blast load = 2963 kN
Vertical blast load (compression) = 8301.6 kN
Vertical blast load (tension) = -10426.8 kN

Overturning Moment Check


Lateral Blast Load, V1 = V / 2 = 1506.6 kN
V2 = V / 2 = 1506.6 kN

Passive Soil Pressure,


Kp = (1+sin27)/(1-sin27) = 2.66
Pp1 = = 361.76 kN/m
Pp2 = = 261.3716 kN/m
Vsoil = (Pp1 x BF) - (Pb2 x (BF-B))
= (361.76X20.8)-(261.3716X(20.8-17.7))
Vsoil = = 6714.4 kN

Overturning Moment, Mo= V1 x (H + Hsoil) + V2 x (Hsoil) - Vsoil x Hsoil / 3


= 1506.6x(6.4+4)+1506.6x4-6714.4x4/3
= 12742.51 kNm
Resisting Moment, Mr = 301829.37 kNm
Factor of safety against overturning FOSo = 301829.37/12742.51 = 23.69
> 1.2
Satisfy overturning stability

Sliding Check
Lateral Blast Load, V= = 2963 kN
Resisting Force Vr = (0.4x28811.141+0.51x2529.6+6714.4)
= 19529 kN
Factor of safety against sliding FOSs = 19529/2963 = 6.59
> 1
Satisfy sliding stability
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 196 of 361

4.5.3 Basement level foundation buoyancy check

Width of basement level footing = 12 m

Length of basement level footing = 21.1 m

Height of basement level footing from GL = 4 m

Height of water table from GL = 2.6 m

Ground water depth in basement = 1.4 m

Unit weight of water = 10 kN/m 3

Total uplift forces due to ground water = (12x21.1x1.4x10)

= 3544.8 kN

Total downward weight due to dead load = 28811.14 kN

(From STAAD)

Allowable factor of safety = 1.5

Actual factor of safety against buoyancy = (28811.141/3544.8)

= 8.13 > 1.5

HENCE SAFE

4.5.4 Settlement limit check


1.6m founding level strip foundation - WF1A:

Allowable settlement = 25 mm

Actual settlement below foundation base (Max) = 10.154 mm (STAAD Node. 73, L/C. 102)

< 25 mm Hence OK

4.0m founding level raft foundation - (WF1, WF2 & F1):

Allowable settlement = 50 mm

Actual settlement below foundation base (Max) = 11.488 mm (STAAD Node. 311, L/C. 102)

< 50 mm Hence OK
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 197 of 361

4.5.5 Soil Bearing Capacity Check

Soil bearing pressure check for 4m deep level raft (WF1, WF2, F1 & BS1)
Normal load case governing L/C 102

Gross Allowable Soil Bearing Capacity = Net SBC + Over burden pressure = 172.0 + 17x4.0 = 240.0 kN/m 2
Gross maximum soil baering pressure (Actual) =119.0 kN/m 2, O.K
(Note: Net SBC value 172 kN/m2 taken from Inco borehole report for lower N-value during test time. Soil
improvement will be carried out below the foundation base by means of gravel fill and due to the soil
improvement the N-value will be increase & accordingly SBC value also increase. But in conservative
side we have taken the SBC for lower N-value from inco lab report.)

Blast load case governing L/C 307

Gross Allowable Soil Bearing Capacity = 240.0 x (3.0/1.2) = 600.0 kN/m 2


Gross maximum soil baering pressure (Actual) = 134.0 kN/m 2, O.K
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 198 of 361

Soil bearing pressure check for 1.6m deep strip foundatuion - WF1A

Normal load case governing L/C 102

Gross Allowable Soil Bearing Capacity = Net SBC + Over burden pressure = 102.4 + 17x1.6 = 129.6 kN/m 2
Gross maximum soil baering pressure (Actual) =125.0 kN/m 2, O.K

(Note: Net SBC value 102.4 kN/m2 taken from Inco borehole report for lower N-value during test
time. Soil improvement will be carried out below the foundation base by means of gravel fill and due to
the soil improvement the N-value will be increase & accordingly SBC value also increase. But in
conservative side we have taken the SBC for lower N-value from inco lab report.)

Blast load case governing L/C 305

2
Allowable Soil Bearing Capacity : 129.6x (3.0/1.2) = 324.0 kN/m
Gross maximum soil baering pressure (Actual) =148.0 kN/m 2, O.K
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 199 of 361

4.5.6 Foundation member design

4.5.6.1 Wall strip foundation WF1 design

Normal load case plate member force summary - Ultimate condition

Normal load case plate member force summary - Serviceability condition


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 200 of 361

Blast load case plate member force summary

Plate results from STAAD output


F o o t i n gT h k . L o a d i n g
Re-bar U l t i m a t eS e r v i c e a b i l i t y
Name (m) condition Shear stress
m o m e n tm o m e n t ( M o ) 2
(Su) Nmm
(Mu) kNm kNm
X-direction
t o p b a r D 1 2 @ 1 5 0 96.557 70.281 0.306
(Main)

X-direction
bottom ba Dr2 0 @ 2 0 0 149.011 117.627 0.168
(Main)
Normal
Z-direction
t o p b a r D 1 2 @ 1 5 0 105.02 75.209 0.298
(Dist)

Z-direction
bottom baDr2 0 @ 2 0 0 170.59 131.515 0.319
(Dist)
WF1 0.6
X-direction
t o p b a r D 1 2 @ 1 5 0 51.346 51.346 0.306
(Main)

X-direction
bottom baDr2 0 @ 2 0 0 137.176 137.176 0.129
(Main)
Blast
Z-direction
t o p b a r D 1 2 @ 1 5 0 68.065 68.065 0.26
(Dist)

Z-direction
bottom baDr2 0 @ 2 0 0 163.12 163.12 0.275
(Dist)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 201 of 361

FOOTING DESIGN CHECK - WF1 (NORMAL LOAD CASE)


MEMBER DESIGN CHECK

I) X-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
35 414 0.90 0.75 1000 600 75 519.0 96.56 70.28 0.31

(1) Flexural Rebar Check

Mu 96.56 x 10 6
Required Rn = = 2
= 0.39830 N/mm²
0.90 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.3983
= 1 - 1 - = 0.00097
414 0.85 x 35

As(req.) =
= 0.00097 x 1000 x 519 = 504 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 519 = 1755 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 519 / 414 = 1854 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 504 = 672 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 672 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.90
0.75 x 1/6 x x 1000 x 519.0
= 460.57 kN
383.81 > Vu = 158.81 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 70281000 / { 791 x ( 519.0 - 70/3 ) } = 179.31 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 70 mm
A = 1/2 x b = 500 mm
B = n x As = 5537 mm²
C = -n x As x d = -2873703 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 202 of 361

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= = 249.29 N/mm 2
1.20 x 150 2 + 4 x ( 50 + 12 / 2 ) 2

+ 0
Note, h 400 mm ; = 1.2
= 1.20 [ ]
h < 400 mm ; = 1.35
s = 150 mm
db = D12 mm

fsmax. = 249.29 Mpa > fs = 179.31 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 179.31 - 2.5 x 75.0 = 340 mm

smax2 = 300 mm

Required Min. Space smax = 300 mm > suse = 150 mm O.K

II) X-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm 2
35 414 0.90 0.75 1000 600 75 515.0 149.01 117.63 0.17

(1) Flexural Rebar Check

Mu 149.01 x 10 6
Required Rn = = 2
= 0.62425 N/mm²
0.90 x 1,000 x 515

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.62425
= 1 - 1 - = 0.00152
414 0.85 x 35

As(req.) =
= 0.00152 x 1000 x 515 = 783 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 515 = 1742 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 515 / 414 = 1840 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 783 = 1044 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 1044 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 203 of 361

4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)


= 4 / 3 x 783 = 1044 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 1044 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.90
0.75 x 1/6 x x 1000 x 515.0
= 457.02 kN
380.85 > Vu = 86.52 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 117627000 / { 1570 x ( 515.0 - 96/3 ) } = 155.11 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 96 mm
A = 1/2 x b = 500 mm
B = n x As = 10990 mm²
C = -n x As x d = -5659850 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= = 200.08 N/mm2
1.20 x 200 2 + 4 x ( 50 + 20 / 2 ) 2

+ 0
Note, h 400 mm ; = 1.2
= 1.20 [ ]
h < 400 mm ; = 1.35
s = 200 mm
db = D20 mm

fsmax. = 200.08 Mpa > fs = 155.11 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 155.11 - 2.5 x 75.0 = 422 mm

smax2 = 300 mm

Required Min. Space smax = 300 mm > suse = 200 mm O.K


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 204 of 361

III) Y-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m 2
N/mm
35 414 0.90 0.75 1000 600 75 519.0 105.02 75.21 0.30

(1) Flexural Rebar Check

Mu 105.02 x 10 6
Required Rn = = 2
= 0.43321 N/mm²
0.90 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.43321
= 1 - 1 - = 0.00105
414 0.85 x 35

As(req.) =
= 0.00105 x 1000 x 519 = 545 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 519 = 1755 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 519 / 414 = 1854 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 545 = 727 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 727 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.90
0.75 x 1/6 x x 1000 x 519.0
= 460.57 kN
383.81 > Vu = 154.66 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 75209000 / { 791 x ( 519.0 - 70/3 ) } = 191.89 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 70 mm
A = 1/2 x b = 500 mm
B = n x As = 5537 mm²
C = -n x As x d = -2873703 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 205 of 361

56,000
fsmax. = 2
)
56,000
= = 249.29 N/mm2
1.20 x 150 2 + 4 x ( 50 + 12 / 2 ) 2

+ 0
Note, h 400 mm ; = 1.2
= 1.20 [ ]
h < 400 mm ; = 1.35
s = 150 mm
db = D12 mm

fsmax. = 249.29 Mpa > fs = 191.89 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 191.89 - 2.5 x 75.0 = 306 mm

smax2 = 300 mm

Required Min. Space smax = 300 mm > suse = 150 mm O.K

IV) Y-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
35 414 0.90 0.75 1000 600 75 515.0 170.59 131.52 0.32

(1) Flexural Rebar Check

Mu 170.59 x 10 6
Required Rn = = 2
= 0.71466 N/mm²
0.90 x 1,000 x 515

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.71466
= 1 - 1 - = 0.00175
414 0.85 x 35

As(req.) =
= 0.00175 x 1000 x 515 = 902 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 515 = 1742 mm²
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 206 of 361

As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)


= 0.25 x x 1000 x 515 / 414 = 1840 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 902 = 1203 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 1203 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d 0.90 x 1/6 x


= 0.75 x 1000 x 515.0
457.02 kN
= 380.85 > Vu = 164.29 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 131515000 / { 1570 x ( 515.0 - 96/3 ) } = 173.43 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 96 mm
A = 1/2 x b = 500 mm
B = n x As = 10990 mm²
C = -n x As x d = -5659850 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= = 200.08 N/mm2
1.20 x 200 2 + 4 x ( 50 + 20 / 2 ) 2

+ 0
Note, h 400 mm ; = 1.2
= 1.20 [ ]
h < 400 mm ; = 1.35
s = 200 mm
db = D20 mm

fsmax. = 200.08 Mpa > fs = 173.43 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 173.43 - 2.5 x 75.0 = 358 mm

smax2 = 300 mm

Required Min. Space smax = 300 mm > suse = 200 mm O.K


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 207 of 361

FOOTING DESIGN CHECK - WF1 (BLAST LOAD CASE)


MEMBER DESIGN CHECK

I) X-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 600 75 519.0 51.35 51.35 0.31

(1) Flexural Rebar Check

Mu 51.35 x 10 6
Required Rn = = 2
= 0.19062 N/mm²
1.00 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.19062
= 1 - 1 - = 0.00036
533 0.85 x 42

As(req.) =
= 0.00036 x 1000 x 519 = 187 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 519 = 1364 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 519 / 533 = 1572 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 187 = 250 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 519.0


= 511.74 kN > Vu = 158.81 kN O.K

II) X-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 600 75 515.0 137.18 137.18 0.13

(1) Flexural Rebar Check

Mu 137.18 x 10 6
Required Rn = = 2
= 0.51721 N/mm²
1.00 x 1,000 x 515

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 208 of 361

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.51721
= 1 - 1 - = 0.00098
533 0.85 x 42

As(req.) =
= 0.00098 x 1000 x 515 = 505 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 515 = 1353 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 515 / 533 = 1559 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 505 = 674 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 674 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 515.0


= 507.80 kN > Vu = 66.44 kN O.K

III) Y-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 600 75 519.0 68.07 68.07 0.26

(1) Flexural Rebar Check

Mu 68.07 x 10 6
Required Rn = = 2
= 0.25269 N/mm²
1.00 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.25269
= 1 - 1 - = 0.00048
533 0.85 x 42

As(req.) =
= 0.00048 x 1000 x 519 = 250 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 519 = 1364 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 519 / 533 = 1572 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 209 of 361

= 0.25 x x 1000 x 519 / 533 = 1572 mm²


4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 250 = 334 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 519.0


= 511.74 kN > Vu = 134.94 kN O.K

IV) Y-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 600 75 515.0 163.12 163.12 0.28

(1) Flexural Rebar Check

Mu 163.12 x 10 6
Required Rn = = 2
= 0.61502 N/mm²
1.00 x 1,000 x 515

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.61502
= 1 - 1 - = 0.00116
533 0.85 x 42

As(req.) =
= 0.00116 x 1000 x 515 = 598 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 515 = 1353 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 515 / 533 = 1559 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 598 = 798 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 798 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 515.0


= 507.80 kN > Vu = 141.63 kN O.K
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 210 of 361

4.5.6.2 Wall strip foundation WF2 design

Normal load case plate member force summary - Ultimate condition

Normal load case plate member force summary - Serviceability condition


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 211 of 361

Blast load case plate member force summary

Plate results from STAAD output


F o o t i n gT h k . L o a d i n g
Re-bar U l t i m a t eS e r v i c e a b i l i t y
Name (m) condition Shear stress
m o m e n tm o m e n t ( M o ) 2
(Su) Nmm
(Mu) kNm kNm
X-direction
t o p b a r D 1 2 @ 1 5 0 66.591 48.118 0.159
(Main)

X-direction
bottom ba D r2 0 @ 2 0 0 182.246 132.809 0.373
(Main)
Normal
Z-direction
t o p b a r D 1 2 @ 1 5 0 100.39 74.783 0.151
(Dist)

Z-direction
bottom baD r2 0 @ 2 0 0 57.698 43.988 0.144
(Dist)
WF2 0.6
X-direction
t o p b a r D 1 2 @ 1 5 0 50.278 50.278 0.134
(Main)

X-direction
bottom baD r2 0 @ 2 0 0 173.422 173.422 0.346
(Main)
Blast
Z-direction
t o p b a r D 1 2 @ 1 5 0 92.261 92.261 0.132
(Dist)

Z-direction
bottom baD r2 0 @ 2 0 0 52.48 52.48 0.13
(Dist)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 212 of 361

FOOTING DESIGN CHECK - WF2 (NORMAL LOAD CASE)


MEMBER DESIGN CHECK

I) X-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
35 414 0.90 0.75 1000 600 75 519.0 66.59 48.12 0.16

(1) Flexural Rebar Check

Mu 66.59 x 10 6
Required Rn = = 2
= 0.27469 N/mm²
0.90 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.27469
= 1 - 1 - = 0.00067
414 0.85 x 35

As(req.) =
= 0.00067 x 1000 x 519 = 348 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 519 = 1755 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 519 / 414 = 1854 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 348 = 464 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.90
0.75 x 1/6 x x 1000 x 519.0
= 460.57 kN
383.81 > Vu = 82.52 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 48118000 / { 791 x ( 519.0 - 70/3 ) } = 122.77 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 70 mm
A = 1/2 x b = 500 mm
B = n x As = 5537 mm²
C = -n x As x d = -2873703 mm
n = Es / Ec = 200000 / 4700 f'c = 7
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 213 of 361

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= = 249.29 N/mm2
1.20 x 150 2 + 4 x ( 50 + 12 / 2 ) 2
+ 0
Note, h 400 mm ; = 1.2
= 1.20 [ ]
h < 400 mm ; = 1.35
s = 150 mm
db = D12 mm

fsmax. = 249.29 Mpa > fs = 122.77 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 122.77 - 2.5 x 75.0 = 583 mm

smax2 = 300 mm

Required Min. Space smax = 300 mm > suse = 150 mm O.K

II) X-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm 2
35 414 0.90 0.75 1000 600 75 515.0 182.25 132.81 0.37

(1) Flexural Rebar Check

Mu 182.25 x 10 6
Required Rn = = 2
= 0.76349 N/mm²
0.90 x 1,000 x 515

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.76349
= 1 - 1 - = 0.00187
414 0.85 x 35

As(req.) =
= 0.00187 x 1000 x 515 = 964 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 515 = 1742 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 515 / 414 = 1840 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 964 = 1286 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 1286 mm²
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 214 of 361

Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 1286 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.90
0.75 x 1/6 x x 1000 x 515.0
= 457.02
380.85 kN > Vu = 192.10 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 132809000 / { 1570 x ( 515.0 - 96/3 ) } = 175.13 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 96 mm
A = 1/2 x b = 500 mm
B = n x As = 10990 mm²
C = -n x As x d = -5659850 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= = 200.08 N/mm2
1.20 x 200 2 + 4 x ( 50 + 20 / 2 ) 2

+ 0
Note, h 400 mm ; = 1.2
= 1.20 [ ]
h < 400 mm ; = 1.35
s = 200 mm
db = D20 mm

fsmax. = 200.08 Mpa > fs = 175.13 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 175.13 - 2.5 x 75.0 = 353 mm

smax2 = 300 mm

Required Min. Space smax = 300 mm > suse = 200 mm O.K

III) Y-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
35 414 0.90 0.75 1000 600 75 519.0 100.39 74.78 0.15
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 215 of 361

(1) Flexural Rebar Check

Mu 100.39 x 10 6
Required Rn = = 2
= 0.41411 N/mm²
0.90 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.41411
= 1 - 1 - = 0.00101
414 0.85 x 35

As(req.) =
= 0.00101 x 1000 x 519 = 525 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 519 = 1755 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 519 / 414 = 1854 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 525 = 700 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 700 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.90
0.75 x 1/6 x x 1000 x 519.0
= 460.57 kN
383.81 > Vu = 78.37 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 74783000 / { 791 x ( 519.0 - 70/3 ) } = 190.80 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 70 mm
A = 1/2 x b = 500 mm
B = n x As = 5537 mm²
C = -n x As x d = -2873703 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= 2 2
= 249.29 N/mm2
1.20 x 150 + 4 x ( 50 + 12 / 2 )
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 216 of 361

+ 0
Note, h 400 mm ; = 1.2
= 1.20 [ ]
h< 400 mm ; = 1.35
s = 150 mm
db = D12 mm

fsmax. = 249.29 Mpa > fs = 190.80 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 190.80 - 2.5 x 75.0 = 308 mm

smax2 = 300 mm

Required Min. Space smax = 300 mm > suse = 150 mm O.K

IV) Y-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
35 414 0.90 0.75 1000 600 75 515.0 57.70 43.99 0.14

(1) Flexural Rebar Check

Mu 57.70 x 10 6
Required Rn = = 2
= 0.24172 N/mm²
0.90 x 1,000 x 515

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.24172
= 1 - 1 - = 0.00059
414 0.85 x 35

As(req.) =
= 0.00059 x 1000 x 515 = 304 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 515 = 1742 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 515 / 414 = 1840 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 304 = 406 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 217 of 361

USE : D20 @ 200 ( As = 1570 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.90
0.75 x 1/6 x x 1000 x 515.0
= 457.02 kN
380.85 > Vu = 74.16 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 43988000 / { 1570 x ( 515.0 - 96/3 ) } = 58.01 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 96 mm
A = 1/2 x b = 500 mm
B = n x As = 10990 mm²
C = -n x As x d = -5659850 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= = 200.08 N/mm2
1.20 x 200 2 + 4 x ( 50 + 20 / 2 ) 2

+ 0
Note, h 400 mm ; = 1.2
= 1.20 [ ]
h < 400 mm ; = 1.35
s = 200 mm
db = D20 mm

fsmax. = 200.08 Mpa > fs = 58.01 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 58.01 - 2.5 x 75.0 = 1443 mm

smax2 = 300 mm

Required Min. Space smax = 300 mm > suse = 200 mm O.K


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 218 of 361

FOOTING DESIGN CHECK - WF2 (BLAST LOAD CASE)


MEMBER DESIGN CHECK

I) X-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 600 75 519.0 50.28 50.28 0.13

(1) Flexural Rebar Check

Mu 50.28 x 10 6
Required Rn = = 2
= 0.18666 N/mm²
1.00 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.18666
= 1 - 1 - = 0.00035
533 0.85 x 42

As(req.) =
= 0.00035 x 1000 x 519 = 182 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 519 = 1364 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 519 / 533 = 1572 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 182 = 243 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 519.0


= 511.74 kN > Vu = 69.55 kN O.K

II) X-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 600 75 515.0 173.42 173.42 0.35

(1) Flexural Rebar Check

Mu 173.42 x 10 6
Required Rn = = 2
= 0.65387 N/mm²
1.00 x 1,000 x 515
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 219 of 361

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.65387
= 1 - 1 - = 0.00124
533 0.85 x 42

As(req.) =
= 0.00124 x 1000 x 515 = 639 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 515 = 1353 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 515 / 533 = 1559 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 639 = 852 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 852 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 515.0


= 507.80 kN > Vu = 178.19 kN O.K

III) Y-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 600 75 519.0 92.26 92.26 0.13

(1) Flexural Rebar Check

Mu 92.26 x 10 6
Required Rn = = 2
= 0.34252 N/mm²
1.00 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.34252
= 1 - 1 - = 0.00065
533 0.85 x 42

As(req.) =
= 0.00065 x 1000 x 519 = 338 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 519 = 1364 mm²
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 220 of 361

As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)


= 0.25 x x 1000 x 519 / 533 = 1572 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 338 = 451 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 519.0


= 511.74 kN > Vu = 68.51 kN O.K

IV) Y-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 600 75 515.0 52.48 52.48 0.13

(1) Flexural Rebar Check

Mu 52.48 x 10 6
Required Rn = = 2
= 0.19787 N/mm²
1.00 x 1,000 x 515

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.19787
= 1 - 1 - = 0.00037
533 0.85 x 42

As(req.) =
= 0.00037 x 1000 x 515 = 191 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 515 = 1353 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 515 / 533 = 1559 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 191 = 255 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 515.0


= 507.80 kN > Vu = 66.95 kN O.K
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 221 of 361

4.5.6.3 Isolated foundation F1 design

Normal load case plate member force summary - Ultimate condition

Normal load case plate member force summary - Serviceability condition


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 222 of 361

Blast load case plate member force summary

Plate results from STAAD output


Footing Thk. Loading
Re-bar Ultimate Serviceability
Name (m) condition Shear stress
moment moment (Mo) 2
(Su) Nmm
(Mu) kNm kNm
X-direction
top bar D12@150 94.065 77.127 0.17
(Main)

X-direction
bottom bar D20@200 23.606 0 0.207
(Main)
Normal
Z-direction
top bar D12@150 0 0 0.322
(Dist)

Z-direction
bottom bar D20@200 154.343 112.461 0.285
(Dist)
F1 0.6
X-direction
top bar D12@150 126.791 126.791 0.084
(Main)

X-direction
bottom bar D20@200 25.459 25.459 0.081
(Main)
Blast
Z-direction
top bar D12@150 0 0 0.205
(Dist)

Z-direction
bottom bar D20@200 81.092 81.092 0.164
(Dist)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 223 of 361

FOOTING DESIGN CHECK - F1 (NORMAL LOAD CASE)


MEMBER DESIGN CHECK

I) X-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
35 414 0.90 0.75 1000 600 75 519.0 94.07 77.13 0.17

(1) Flexural Rebar Check

Mu 94.07 x 10 6
Required Rn = = 2
= 0.38802 N/mm²
0.90 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.38802
= 1 - 1 - = 0.00094
414 0.85 x 35

As(req.) =
= 0.00094 x 1000 x 519 = 488 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 519 = 1755 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 519 / 414 = 1854 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 488 = 651 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 651 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.90
0.75 x 1/6 x x 1000 x 519.0
= 460.57 kN
383.81 > Vu = 88.23 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 77127000 / { 791 x ( 519.0 - 70/3 ) } = 196.78 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 70 mm
A = 1/2 x b = 500 mm
B = n x As = 5537 mm²
C = -n x As x d = -2873703 mm
n = Es / Ec = 200000 / 4700 f'c = 7
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 224 of 361

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= 2 2
= 249.29 N/mm2
1.20 x 150 + 4 x ( 50 + 12 / 2 )
+ 0
Note, h 400 mm ; = 1.2
= 1.20 [ ]
h < 400 mm ; = 1.35
s = 150 mm
db = D12 mm

fsmax. = 249.29 Mpa > fs = 196.78 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 196.78 - 2.5 x 75.0 = 293 mm

smax2 = 300 mm

Required Min. Space smax = 293 mm > suse = 150 mm O.K

II) X-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
35 414 0.90 0.75 1000 600 75 515.0 23.61 0.00 0.21

(1) Flexural Rebar Check

Mu 23.61 x 10 6
Required Rn = = 2
= 0.09889 N/mm²
0.90 x 1,000 x 515

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.09889
= 1 - 1 - = 0.00024
414 0.85 x 35

As(req.) =
= 0.00024 x 1000 x 515 = 124 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 515 = 1742 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 515 / 414 = 1840 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 124 = 166 mm²
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 225 of 361

Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.90
0.75 x 1/6 x x 1000 x 515.0
= 457.02
380.85 kN > Vu = 106.61 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 0 / { 1570 x ( 515.0 - 96/3 ) } = 0.00 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 96 mm
A = 1/2 x b = 500 mm
B = n x As = 10990 mm²
C = -n x As x d = -5659850 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= = 200.08 N/mm2
1.20 x 200 2 + 4 x ( 50 + 20 / 2 ) 2

+ 0
Note, h 400 mm ; = 1.2
= 1.20 [ ]
h < 400 mm ; = 1.35
s = 200 mm
db = D20 mm

fsmax. = 200.08 Mpa > fs = 0.00 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 0.00 - 2.5 x 75.0 = #DIV/0! mm

smax2 = 300 mm

Required Min. Space smax = #DIV/0! mm ## suse = 200 mm #

III) Y-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
35 414 0.90 0.75 1000 600 75 519.0 0.00 0.00 0.32
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 226 of 361

(1) Flexural Rebar Check

Mu 0.00 x 10 6
Required Rn = = 2
= 0.00000 N/mm²
0.90 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.00
= 1 - 1 - = 0.00
414 0.85 x 35

As(req.) =
= 0.00 x 1000 x 519 = 0 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 519 = 1755 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 519 / 414 = 1854 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 0 = 0 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.90
0.75 x 1/6 x x 1000 x 519.0
= 460.57 kN
383.81 > Vu = 167.12 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 0 / { 791 x ( 519.0 - 70/3 ) } = 0.00 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 70 mm
A = 1/2 x b = 500 mm
B = n x As = 5537 mm²
C = -n x As x d = -2873703 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= 2 2
= 249.29 N/mm2
1.20 x 150 + 4 x ( 50 + 12 / 2 )
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 227 of 361

Note, h 400 mm ; = 1.2


= 1.20 [ ]
h< 400 mm ; = 1.35
s = 150 mm
db = D12 mm

fsmax. = 249.29 Mpa > fs = 0.00 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 0.00 - 2.5 x 75.0 = #DIV/0! mm

smax2 = 300 mm

Required Min. Space smax = #DIV/0! mm ## suse = 150 mm #

IV) Y-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
35 414 0.90 0.75 1000 600 75 515.0 154.34 112.46 0.29

(1) Flexural Rebar Check

Mu 154.34 x 10 6
Required Rn = = 2
= 0.64659 N/mm²
0.90 x 1,000 x 515

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.64659
= 1 - 1 - = 0.00158
414 0.85 x 35

As(req.) =
= 0.00158 x 1000 x 515 = 814 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 515 = 1742 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 515 / 414 = 1840 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 814 = 1086 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 1086 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 228 of 361

(2) One-Way Shear Check

- = f'c x b x d = 0.90
0.75 x 1/6 x x 1000 x 515.0
= 457.02 kN
380.85 > Vu = 146.78 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 112461000 / { 1570 x ( 515.0 - 96/3 ) } = 148.30 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 96 mm
A = 1/2 x b = 500 mm
B = n x As = 10990 mm²
C = -n x As x d = -5659850 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= 2 2
= 200.08 N/mm2
1.20 x 200 + 4 x ( 50 + 20 / 2 )

Note, h 400 mm ; = 1.2


= 1.20 [ ]
h< 400 mm ; = 1.35
s = 200 mm
db = D20 mm

fsmax. = 200.08 Mpa > fs = 148.30 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 148.30 - 2.5 x 75.0 = 450 mm

smax2 = 300 mm

Required Min. Space smax = 300 mm > suse = 200 mm O.K


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 229 of 361

FOOTING DESIGN CHECK - F1 (BLAST LOAD CASE)


MEMBER DESIGN CHECK

I) X-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 600 75 519.0 126.79 126.79 0.08

(1) Flexural Rebar Check

Mu 126.79 x 10 6
Required Rn = = 2
= 0.47071 N/mm²
1.00 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.47071
= 1 - 1 - = 0.00089
533 0.85 x 42

As(req.) =
= 0.00089 x 1000 x 519 = 462 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 519 = 1364 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 519 / 533 = 1572 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 462 = 616 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 616 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 519.0


= 511.74 kN > Vu = 43.60 kN O.K

II) X-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 600 75 515.0 25.46 25.46 0.08

(1) Flexural Rebar Check

Mu 25.46 x 10 6
Required Rn = = 2
= 0.09599 N/mm²
1.00 x 1,000 x 515
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 230 of 361

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.09599
= 1 - 1 - = 0.00018
533 0.85 x 42

As(req.) =
= 0.00018 x 1000 x 515 = 93 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 515 = 1353 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 515 / 533 = 1559 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 93 = 124 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 515.0


= 507.80 kN > Vu = 41.72 kN O.K

III) Y-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 600 75 519.0 0.00 0.00 0.21

(1) Flexural Rebar Check

Mu 0.00 x 10 6
Required Rn = = 2
= 0.00000 N/mm²
1.00 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.00
= 1 - 1 - = 0.00
533 0.85 x 42

As(req.) =
= 0.00 x 1000 x 519 = 0 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 519 = 1364 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 519 / 533 = 1572 mm²
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 231 of 361

As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)


= 0.25 x x 1000 x 519 / 533 = 1572 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 0 = 0 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 519.0


= 511.74 kN > Vu = 106.40 kN O.K

IV) Y-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 600 75 515.0 81.09 81.09 0.16

(1) Flexural Rebar Check

Mu 81.09 x 10 6
Required Rn = = 2
= 0.30575 N/mm²
1.00 x 1,000 x 515

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.30575
= 1 - 1 - = 0.00058
533 0.85 x 42

As(req.) =
= 0.00058 x 1000 x 515 = 299 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 515 = 1353 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 515 / 533 = 1559 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 299 = 399 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 515.0


= 507.80 kN > Vu = 84.46 kN O.K
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 232 of 361

4.5.6.4 Wall strip foundation WF1A design

Normal load case plate member force summary - Ultimate


condition

Normal load case plate member force summary - Serviceability condition


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 233 of 361

Blast load case plate member force summary

Plate results from STAAD output


F o o t i n gT h k . L o a d i n g
Re-bar U l t i m a t eS e r v i c e a b i l i t y
Name (m) condition Shear stress
m o m e n tm o m e n t ( M o ) 2
(Su) Nmm
(Mu) kNm kNm
X-direction
t o p b a r D 1 2 @ 2 0 0 34.926 21.854 0.189
(Main)

X-direction
bottom ba D r2 0 @ 2 0 0 78.538 61.245 0.148
(Main)
Normal
Z-direction
t o p b a r D 1 2 @ 2 0 0 13.295 0 0.192
(Dist)

Z-direction
bottom baD r2 0 @ 2 0 0 86.396 66.633 0.202
(Dist)
WF1A 0.6
X-direction
t o p b a r D 1 2 @ 2 0 0 43.703 43.703 0.212
(Main)

X-direction
bottom baD r2 0 @ 2 0 0 94.661 94.661 0.163
(Main)
Blast
Z-direction
t o p b a r D 1 2 @ 2 0 0 33.636 33.636 0.182
(Dist)

Z-direction
bottom baD r2 0 @ 2 0 0 70.32 70.32 0.184
(Dist)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 234 of 361

FOOTING DESIGN CHECK - WF1A (NORMAL LOAD CASE)


MEMBER DESIGN CHECK

I) X-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm 2
35 414 0.90 0.75 1000 600 75 519.0 34.93 21.85 0.19

(1) Flexural Rebar Check

Mu 34.93 x 10 6
Required Rn = = 2
= 0.14407 N/mm²
0.90 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.14407
= 1 - 1 - = 0.00035
414 0.85 x 35

As(req.) =
= 0.00035 x 1000 x 519 = 182 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 519 = 1755 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 519 / 414 = 1854 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 182 = 243 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D12 @ 200 ( As = 565 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.75 x 1/6 x x 1000 x 519.0


= 383.81 kN > Vu = 98.09 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 21854000 / { 565 x ( 519.0 - 60/3 ) } = 77.53 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 60 mm
A = 1/2 x b = 500 mm
B = n x As = 3955 mm²
C = -n x As x d = -2052645 mm
n = Es / Ec = 200000 / 4700 f'c = 7
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 235 of 361

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= 2 2
= 203.58 N/mm 2
1.20 x 200 + 4 x ( 50 + 12 / 2 )

Note, h 400 mm ; = 1.2


= 1.20 [ ]
h< 400 mm ; = 1.35
s = 200 mm
db = D12 mm

fsmax. = 203.58 Mpa > fs = 77.53 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 77.53 - 2.5 x 75.0 = 1033 mm

smax2 = 300 mm

Required Min. Space smax = 300 mm > suse = 200 mm O.K

II) X-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm 2
35 414 0.90 0.75 1000 600 75 515.0 78.54 61.25 0.15

(1) Flexural Rebar Check

Mu 78.54 x 10 6
Required Rn = = 2
= 0.32902 N/mm²
0.90 x 1,000 x 515

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.32902
= 1 - 1 - = 0.0008
414 0.85 x 35

As(req.) =
= 0.0008 x 1000 x 515 = 412 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 515 = 1742 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 515 / 414 = 1840 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 236 of 361

= 4 / 3 x 412 = 550 mm²


Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 550 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.75 x 1/6 x x 1000 x 515.0


= 380.85 kN > Vu = 76.22 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 61245000 / { 1570 x ( 515.0 - 96/3 ) } = 80.76 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 96 mm
A = 1/2 x b = 500 mm
B = n x As = 10990 mm²
C = -n x As x d = -5659850 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= 2 2
= 200.08 N/mm 2
1.20 x 200 + 4 x ( 50 + 20 / 2 )

Note, h 400 mm ; = 1.2


= 1.20 [ ]
h< 400 mm ; = 1.35
s = 200 mm
db = D20 mm

fsmax. = 200.08 Mpa > fs = 80.76 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 80.76 - 2.5 x 75.0 = 984 mm

smax2 = 300 mm

Required Min. Space smax = 300 mm > suse = 200 mm O.K

III) Y-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm 2
35 414 0.90 0.75 1000 600 75 519.0 13.30 0.00 0.19
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 237 of 361

(1) Flexural Rebar Check

Mu 13.30 x 10 6
Required Rn = = 2
= 0.05484 N/mm²
0.90 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.05484
= 1 - 1 - = 0.00013
414 0.85 x 35

As(req.) =
= 0.00013 x 1000 x 519 = 68 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 519 = 1755 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 519 / 414 = 1854 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 68 = 91 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D12 @ 200 ( As = 565 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.75 x 1/6 x x 1000 x 519.0


= 383.81 kN > Vu = 99.65 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 0 / { 565 x ( 519.0 - 60/3 ) } = 0.00 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 60 mm
A = 1/2 x b = 500 mm
B = n x As = 3955 mm²
C = -n x As x d = -2052645 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= 2 2
= 203.58 N/mm2
1.20 x 200 + 4 x ( 50 + 12 / 2 )
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 238 of 361

Note, h 400 mm ; = 1.2


= 1.20 [ ]
h< 400 mm ; = 1.35
s = 200 mm
db = D12 mm

fsmax. = 203.58 Mpa > fs = 0.00 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 0.00 - 2.5 x 75.0 = #DIV/0! mm

smax2 = 300 mm

Required Min. Space smax = #DIV/0! mm ## suse = 200 mm #

IV) Y-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
35 414 0.90 0.75 1000 600 75 515.0 86.40 66.63 0.20

(1) Flexural Rebar Check

Mu 86.40 x 10 6
Required Rn = = 2
= 0.36194 N/mm²
0.90 x 1,000 x 515

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.36194
= 1 - 1 - = 0.00088
414 0.85 x 35

As(req.) =
= 0.00088 x 1000 x 515 = 454 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 515 = 1742 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 515 / 414 = 1840 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 454 = 606 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 606 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 239 of 361

(2) One-Way Shear Check

- = f'c x b x d = 0.75 x 1/6 x x 1000 x 515.0


= 380.85 kN > Vu = 104.03 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 66633000 / { 1570 x ( 515.0 - 96/3 ) } = 87.87 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 96 mm
A = 1/2 x b = 500 mm
B = n x As = 10990 mm²
C = -n x As x d = -5659850 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= 2 2
= 200.08 N/mm2
1.20 x 200 + 4 x ( 50 + 20 / 2 )

Note, h 400 mm ; = 1.2


= 1.20 [ ]
h< 400 mm ; = 1.35
s = 200 mm
db = D20 mm

fsmax. = 200.08 Mpa > fs = 87.87 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 87.87 - 2.5 x 75.0 = 889 mm

smax2 = 300 mm

Required Min. Space smax = 300 mm > suse = 200 mm O.K


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 240 of 361

FOOTING DESIGN CHECK - WF1A (BLAST LOAD CASE)


MEMBER DESIGN CHECK

I) X-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m 2
N/mm
42 533 1 1 1000 600 75 519.0 43.70 43.70 0.21

(1) Flexural Rebar Check

Mu 43.70 x 10 6
Required Rn = = 2
= 0.16225 N/mm²
1.00 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.16225
= 1 - 1 - = 0.00031
533 0.85 x 42

As(req.) =
= 0.00031 x 1000 x 519 = 161 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 519 = 1364 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 519 / 533 = 1572 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 161 = 215 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D12 @ 200 ( As = 565 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 519.0


= 511.74 kN > Vu = 110.03 kN O.K

II) X-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm 2
42 533 1 1 1000 600 75 515.0 94.66 94.66 0.16

(1) Flexural Rebar Check

Mu 94.66 x 10 6
Required Rn = = 2
= 0.35691 N/mm²
1.00 x 1,000 x 515
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 241 of 361

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.35691
= 1 - 1 - = 0.00067
533 0.85 x 42

As(req.) =
= 0.00067 x 1000 x 515 = 346 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 515 = 1353 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 515 / 533 = 1559 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 346 = 462 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 515.0


= 507.80 kN > Vu = 83.95 kN O.K

III) Y-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 600 75 519.0 33.64 33.64 0.18

(1) Flexural Rebar Check

Mu 33.64 x 10 6
Required Rn = = 2
= 0.12487 N/mm²
1.00 x 1,000 x 519

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.12487
= 1 - 1 - = 0.00023
533 0.85 x 42

As(req.) =
= 0.00023 x 1000 x 519 = 120 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 519 = 1364 mm²
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 242 of 361

As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)


= 0.25 x x 1000 x 519 / 533 = 1572 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 120 = 160 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D12 @ 200 ( As = 565 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 519.0


= 511.74 kN > Vu = 94.46 kN O.K

IV) Y-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 600 75 515.0 70.32 70.32 0.18

(1) Flexural Rebar Check

Mu 70.32 x 10 6
Required Rn = = 2
= 0.26513 N/mm²
1.00 x 1,000 x 515

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.26513
= 1 - 1 - = 0.0005
533 0.85 x 42

As(req.) =
= 0.0005 x 1000 x 515 = 258 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 600 / 2 = 540 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 515 = 1353 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 515 / 533 = 1559 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 258 = 344 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 540 mm²

USE : D20 @ 200 ( As = 1570 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 515.0


= 507.80 kN > Vu = 94.76 kN O.K
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 243 of 361

4.5.6.4 Base slab BS1 design

Normal load case plate member force summary -


Ultimate condition

Normal load case plate member force summary - Serviceability condition


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 244 of 361

Blast load case plate member force summary

Plate results from STAAD output


Footing Thk. Loading
Re-bar Ultimate Serviceability
Name (m) condition Shear stress
moment moment (Mo) 2
(Su) Nmm
(Mu) kNm kNm
X-direction
top bar D12@150 17.491 13.746 0.224
(Main)

X-direction
bottom bar D12@150 0.144 0 0.27
(Main)
Normal
Z-direction
top bar D12@150 15.627 12.757 0.241
(Dist)

Z-direction
bottom bar D12@150 1.651 0.954 0.237
(Dist)
BS1 0.2
X-direction
top bar D12@150 17.465 17.465 0.295
(Main)

X-direction
bottom bar D12@150 0.362 0.362 0.294
(Main)
Blast
Z-direction
top bar D12@150 15.473 15.473 0.243
(Dist)

Z-direction
bottom bar D12@150 4.88 4.88 0.268
(Dist)
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 245 of 361

FOOTING DESIGN CHECK - BS1 (NORMAL LOAD CASE)


MEMBER DESIGN CHECK

I) X-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
35 414 0.90 0.75 1000 200 75 119.0 17.49 13.75 0.22

(1) Flexural Rebar Check

Mu 17.49 x 10 6
Required Rn = = 2
= 1.37239 N/mm²
0.90 x 1,000 x 119

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 1.37239
= 1 - 1 - = 0.0034
414 0.85 x 35

As(req.) =
= 0.0034 x 1000 x 119 = 405 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 200 / 2 = 180 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 119 = 402 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 119 / 414 = 425 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 405 = 540 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 425 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.90
0.75 x 1/6 x x 1000 x 119.0
= 105.60
88 kN > Vu = 26.66 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 13746000 / { 791 x ( 119.0 - 31/3 ) } = 160.01 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 31 mm
A = 1/2 x b = 500 mm
B = n x As = 5537 mm²
C = -n x As x d = -658903 mm
n = Es / Ec = 200000 / 4700 f'c = 7
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 246 of 361

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= 2 2
= 221.59 N/mm2
1.35 x 150 + 4 x ( 50 + 12 / 2 )

Note, h 400 mm ; = 1.2


= 1.35 [ ]
h< 400 mm ; = 1.35
s = 150 mm
db = D12 mm

fsmax. = 221.59 Mpa > fs = 160.01 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 160.01 - 2.5 x 75.0 = 404 mm

smax2 = 300 mm

Required Min. Space smax = 300 mm > suse = 150 mm O.K

II) X-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
35 414 0.90 0.75 1000 200 75 119.0 0.14 0.00 0.27

(1) Flexural Rebar Check

Mu 0.14 x 10 6
Required Rn = = 2
= 0.01130 N/mm²
0.90 x 1,000 x 119

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.0113
= 1 - 1 - = 0.00003
414 0.85 x 35

As(req.) =
= 0.00003 x 1000 x 119 = 4 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 200 / 2 = 180 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 119 = 402 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 119 / 414 = 425 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 4 = 6 mm²
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 247 of 361

= 4 / 3 x 4 = 6 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 180 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.90
0.75 x 1/6 x x 1000 x 119.0
= 105.60
88 kN > Vu = 32.13 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 0 / { 791 x ( 119.0 - 31/3 ) } = 0.00 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 31 mm
A = 1/2 x b = 500 mm
B = n x As = 5537 mm²
C = -n x As x d = -658903 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= 2 2
= 221.59 N/mm 2
1.35 x 150 + 4 x ( 50 + 12 / 2 )

Note, h 400 mm ; = 1.2


= 1.35 [ ]
h< 400 mm ; = 1.35
s = 150 mm
db = D12 mm

fsmax. = 221.59 Mpa > fs = 0.00 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 0.00 - 2.5 x 75.0 = #DIV/0! mm

smax2 = 300 mm

Required Min. Space smax = #DIV/0! mm ## suse = 150 mm #

III) Y-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm 2
35 414 0.90 0.75 1000 200 75 119.0 15.63 12.76 0.24
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 248 of 361

(1) Flexural Rebar Check

Mu 15.63 x 10 6
Required Rn = = 2
= 1.22614 N/mm²
0.90 x 1,000 x 119

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 1.22614
= 1 - 1 - = 0.00303
414 0.85 x 35

As(req.) =
= 0.00303 x 1000 x 119 = 361 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 200 / 2 = 180 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 119 = 402 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 119 / 414 = 425 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 361 = 482 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 425 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 0.90
0.75 x 1/6 x x 1000 x 119.0
= 105.60
88 kN > Vu = 28.68 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 12757000 / { 791 x ( 119.0 - 31/3 ) } = 148.50 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 31 mm
A = 1/2 x b = 500 mm
B = n x As = 5537 mm²
C = -n x As x d = -658903 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= 2 2
= 221.59 N/mm2
1.35 x 150 + 4 x ( 50 + 12 / 2 )
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 249 of 361

Note, h 400 mm ; = 1.2


= 1.35 [ ]
h< 400 mm ; = 1.35
s = 150 mm
db = D12 mm

fsmax. = 221.59 Mpa > fs = 148.50 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 148.50 - 2.5 x 75.0 = 450 mm

smax2 = 300 mm

Required Min. Space smax = 300 mm > suse = 150 mm O.K

IV) Y-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm 2
35 414 0.90 0.75 1000 200 75 119.0 1.65 0.95 0.24

(1) Flexural Rebar Check

Mu 1.65 x 10 6
Required Rn = = 2
= 0.12954 N/mm²
0.90 x 1,000 x 119

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 35 2 x 0.12954
= 1 - 1 - = 0.00031
414 0.85 x 35

As(req.) =
= 0.00031 x 1000 x 119 = 37 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 200 / 2 = 180 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 414 x 1000 x 119 = 402 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 119 / 414 = 425 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 37 = 50 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 180 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 250 of 361

(2) One-Way Shear Check

- = f'c x b x d 0.90 x 1/6 x


= 0.75 x 1000 x 119.0
= 105.60
88 kN > Vu = 28.20 kN O.K

(3) Crack Control

- Bending Stress of Rebar


fs = Mo / {As x (d - x/3)}
= 954000 / { 791 x ( 119.0 - 31/3 ) } = 11.11 Mpa
Note, x = {-B + (B² - 4AC)} / 2A = 31 mm
A = 1/2 x b = 500 mm
B = n x As = 5537 mm²
C = -n x As x d = -658903 mm
n = Es / Ec = 200000 / 4700 f'c = 7

- fs Limit Check (in Normal Environmental Exposure Areas)

56,000
fsmax. = 2
)
56,000
= 2 2
= 221.59 N/mm2
1.35 x 150 + 4 x ( 50 + 12 / 2 )

Note, h 400 mm ; = 1.2


= 1.35 [ ]
h< 400 mm ; = 1.35
s = 150 mm
db = D12 mm

fsmax. = 221.59 Mpa > fs = 11.11 Mpa O.K

- s Limit Check

smax1 = 94600 / fs - 2.5 x Cc


= 94600 / 11.11 - 2.5 x 75.0 = 8331 mm

smax2 = 300 mm

Required Min. Space smax = 300 mm > suse = 150 mm O.K


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 251 of 361

FOOTING DESIGN CHECK - BS1 (BLAST LOAD CASE)


MEMBER DESIGN CHECK

I) X-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 200 75 119.0 17.47 17.47 0.30

(1) Flexural Rebar Check

Mu 17.47 x 10 6
Required Rn = = 2
= 1.23332 N/mm²
1.00 x 1,000 x 119

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 1.23332
= 1 - 1 - = 0.00236
533 0.85 x 42

As(req.) =
= 0.00236 x 1000 x 119 = 281 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 200 / 2 = 180 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 119 = 313 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 119 / 533 = 360 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 281 = 375 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 360 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 119.0


= 117.34 kN > Vu = 35.11 kN O.K

II) X-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 200 75 119.0 0.36 0.36 0.29

(1) Flexural Rebar Check

Mu 0.36 x 10 6
Required Rn = = 2
= 0.02556 N/mm²
1.00 x 1,000 x 119
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 252 of 361

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.02556
= 1 - 1 - = 0.00005
533 0.85 x 42

As(req.) =
= 0.00005 x 1000 x 119 = 6 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 200 / 2 = 180 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 119 = 313 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 119 / 533 = 360 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 6 = 8 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 180 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 119.0


= 117.34 kN > Vu = 34.99 kN O.K

III) Y-Direction / Top

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 200 75 119.0 15.47 15.47 0.24

(1) Flexural Rebar Check

Mu 15.47 x 10 6
Required Rn = = 2
= 1.09265 N/mm²
1.00 x 1,000 x 119

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 1.09265
= 1 - 1 - = 0.00208
533 0.85 x 42

As(req.) =
= 0.00208 x 1000 x 119 = 248 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 200 / 2 = 180 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 119 = 313 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 119 / 533 = 360 mm²
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 253 of 361

As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)


= 0.25 x x 1000 x 119 / 533 = 360 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 248 = 331 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 331 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 119.0


= 117.34 kN > Vu = 28.92 kN O.K

IV) Y-Direction / Bottom

f'c fy b h dc d Mu Mo Su
MPa MPa Tension Shear mm mm mm mm kN.m kN.m N/mm2
42 533 1 1 1000 200 75 119.0 4.88 4.88 0.27

(1) Flexural Rebar Check

Mu 4.88 x 10 6
Required Rn = = 2
= 0.34461 N/mm²
1.00 x 1,000 x 119

0.85 f'c 2 x Rn
= 1- 1-
fy 0.85 f'c

0.85 x 42 2 x 0.34461
= 1 - 1 - = 0.00065
533 0.85 x 42

As(req.) =
= 0.00065 x 1000 x 119 = 78 mm²
As(temp.) = 0.0018 x b x h / 2 (ACI 318M-11_Clause 7.12.2)
= 0.0018 x 1000 x 200 / 2 = 180 mm² (One Side)
As(min.1) = 1.40 / fy x b x d (ACI 318M-11_Clause 10.5.1)
= 1.40 / 533 x 1000 x 119 = 313 mm²
As(min.2) = 0.25 x f'c x b x d / fy (ACI 318M-11_Clause 10.5.1)
= 0.25 x x 1000 x 119 / 533 = 360 mm²
4/3 As(req.) = 4 / 3 x As(req.) (ACI 318M-11_Clause 10.5.3)
= 4 / 3 x 78 = 104 mm²
Selected As = max[ min{max{As(min.1), As(min.2)}, 4/3As(req.)}, As(req.), As(temp.)] = 180 mm²

USE : D12 @ 150 ( As = 791 mm² ) O.K !

(2) One-Way Shear Check

- = f'c x b x d = 1.00 x 1/6 x x 1000 x 119.0


= 117.34 kN > Vu = 31.89 kN O.K
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 254 of 361

5.0 MEMBER DESIGN FOR BLAST RESISTANCE ANALYSIS (DYNAMIC ANALYSIS)

5.1 Peak Side-on Overpressure & Duration : 69kPa / 20ms


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 255 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 256 of 361

17
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 257 of 361

All walls will be analysed as one way beams pinned at the both ends (at the base and the top)

(ASCE Table 6.1)

(From ASCE Table 6.1)

Considered wall weight = thickness x length x width x unit weight = 0.3 x 6 x 1 x 25 = 45 kN


Wall weight / gravity = 45 kN /(9.81*1000) = 0.004592 kN.sec 2/mm
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 258 of 361

(From ASCE Table 6.1)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 259 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 260 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 261 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 262 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 263 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 264 of 361

All walls will be analysed as one way beams pinned at the both ends (at the base and the top)

(ASCE Table 6.1)

(ASCE Table 6.1)

Considered wall weight = thickness x length x width x unit weight = 0.3 x 6 x 1 x 25 = 45 kN


Wall weight / gravity = 45 kN /(9.81*1000) = 0.004592 kN.sec2/mm
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 265 of 361

(ASCE Table 6.1)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 266 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 267 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 268 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 269 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 270 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 271 of 361

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 272 of 361

(ASCE Table 6.2)

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 273 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 274 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 275 of 361

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 276 of 361

(ASCE Table 6.2)

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 277 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 278 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 279 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 280 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 281 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 282 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 283 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 284 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 285 of 361

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 286 of 361

(ASCE Table 6.2)

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 287 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 288 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 289 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 290 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 291 of 361

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 292 of 361

(ASCE Table 6.2)

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 293 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 294 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 295 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 296 of 361

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 297 of 361

(ASCE Table 6.2)

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 298 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 299 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 300 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 301 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 302 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 303 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 304 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 305 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 306 of 361

5.2 Peak Side-on Overpressure & Duration : 21kPa / 100ms


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 307 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 308 of 361

17
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 309 of 361

All walls will be analysed as one way beams pinned at the both ends (at the base and the top)

(ASCE Table 6.1)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 310 of 361

(ASCE Table 6.1)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 311 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 312 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 313 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 314 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 315 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 316 of 361

All walls will be analysed as one way beams pinned at the both ends (at the base and the top)

(ASCE Table 6.1)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 317 of 361

(ASCE Table 6.1)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 318 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 319 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 320 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 321 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 322 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 323 of 361

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 324 of 361

(ASCE Table 6.2)

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 325 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 326 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 327 of 361

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 328 of 361

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 329 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 330 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 331 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 332 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 333 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 334 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 335 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 336 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 337 of 361

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 338 of 361

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 339 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 340 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 341 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 342 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 343 of 361

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 344 of 361

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 345 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 346 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 347 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 348 of 361

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 349 of 361

(ASCE Table 6.2)


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 350 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 351 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 352 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 353 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 354 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 355 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 356 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 357 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 358 of 361

6. APPENDIX

6.1 Geotechnical Investigation Report


Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 359 of 361

Net SBC value table for WF1A wall strip foundation at 1.6m depth
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 360 of 361
Doc. No.: C0148.64-2.41-680-B-E
CALCULATION REPORT FOR
Job No.: 0148
NEW SUBSTATION BUILDING
Rev. 0 Page 361 of 361

Net SBC value table for Raft foundation at 4.0m depth - WF1, WF2, F1 & BS1

You might also like