Valves Deluge Valve Model h3
Valves Deluge Valve Model h3
TECHNICAL DATA
MODEL H3-Ductile Iron ASTM A
536-77 GRADE 65-45-12
NOMINAL SIZE 200, 150, 100, 80 & 50NB
SERVICE PRESSURE 1.4 to 17.6 kg/sq.cm
(20 to 250 psi)
END CONNECTION Flange X Flange
Groove X Groove
THREADED OPENING BSPT
MOUNTING Vertical or Horizontal
FACTORY 35 kg/sq.cm (500 psi)
HYDROSTATIC
TEST PRESSURE
FLANGE ANSI B 16.5 #150 FF
CONNECTION is standard supply.
(Contact HD Sales for other
options)
WET PILOT As per graph in the
SPRINKLER catalogue
HEIGHT LIMITATION
NET WEIGHT FXF GXG
WITHOUT TRIM 200 NB - 153 kg 143 kg
150 NB - 79 kg 68 kg
100 NB - 50 kg 42 kg DESCRIPTION
80 NB - 35 kg 29 kg Deluge Valve is known as a system control valve in
50 NB - 32 kg 27 kg a deluge system, used for fast application of water
FINISH Red to RAL 3001 in a spray system. Deluge valve protects areas such
as power transformer installation, storage tank,
APPROVAL UL Listed conveyor protection and other industrial application
ORDERING 1. Size of valve etc. With the addition of foaming agent, deluge valve
INFORMATION 2. Flange specification or for can be used to protect aircraft hanger and inflammable
Grooved end specify pipe liquid fire.
outside diameter
3. Valve mounting- Horizontal VALVE OPERATION
or Vertical
HD Deluge Valve is a quick release, hydraulically
4. Trim type
operated diaphragm valve. It has three chambers,
GROOVE PIPE SIZE: isolated from each other by the diaphragm operated
clapper and seat seal. While in SET position, water
NOMINAL SIZE Pipe OD in mm pressure is transmitted through an external bypass
check valve and restriction orifice from the system
2” (50 NB) 60.3 supply side to the top chamber, so that supply
3” (80 NB) 89.0 pressure in the top chamber act across the diaphragm
4” (100 NB) 114.3 operated clapper which holds the seat against the
inlet supply pressure, because of the differential
6” (150 NB) 165.1 pressure design. On detection of fire, the top chamber
6” (150 NB) 168.3 is vented to atmosphere through the outlet port via
opened actuation devices. The top chamber pressure
8” (200 NB) 219.1
cannot be replenished through the restricted inlet
NOTE: FOR 6”(150 NB) STANDARD SUPPLY IS 168.3 mm OD port, and the upward force of the supply pressure
GROOVE PIPE. lifts the clapper allowing the water flow to the system
FOR 165.1mm REQUIREMENT, SPECIFY IN ORDER piping network and alarm devices.
(a) All main valves are open and are sealed with NOTE:
tamper proof seal (1) UL Listing is valid only when Deluge Valve is
(b) Drain valves must be kept closed installed with trim set as per trim drawing.
(c) No leak or drip is detected from the drip valve (2) The trip time of deluge valve on-off device through
detection network, will depend on volume of
(d) All the gauges except the system side water detection network. If the trip time of deluge valve
pressure gauge, should show the required is more, then it can be substantially reduced by
pressure installing check valve in branch of release line in
(e) There should be no leakage in the system the detection network. The check valve flow shall
be towards releasing device.
(iii) NORMAL CONDITION TEST
(3) The pneumatic system must have restricted
(a) The system should be checked for normal orifice at air or gas supply point. The restriction
condition at least once in a week nozzle are supplied with HD dry pilot actuation
trim.
(b) Test the sprinkler alarm bell or electric alarm
by turning the alarm test valve to the test (4) UL Listing is valid only when Listed Solenoid Valve
position. The alarm should sound. This test should provided for electric operation of the deluge valve
be carried out at least once in a week is retained in the trim. If any other solenoid valve
is used, the deluge valve trip time may be quite
(c) Depress the drip valve knob. Significant
high or deluge valve may not trip.
accumulation indicates a possible seat leakage
(5) The Pressure Gauges standard supply is 300 psi
(d) Conduct the water flow test as per the system
for water gauge for system pressure upto 175
testing procedure at least once a month
psi. If system pressure is more than 175 psi,
then order for 600 psi water pressure gauges.
20
19
18
17
16
15
14
13
12
11
10
6
21
4
3
B
A
A
OUTLET ET-W
OUTLET
**
PS2 **
PS2
PG PG PG PG
**
SV **
SV
OD TO DETECTION LINE OD TO DETECTION LINE
~
~
DV DV
M M
~ ~
OD OD
INLET
INLET
FLANGE X FLANGE GROOVE X GROOVE
SCHEMATIC 1
ET-D
TO DETECTION TO DETECTION
LINE LINE
**
PS1 **
PS1
OUTLET
PG PG
**
PS2 **
PS2
PG PG
PG DPA PG DPA
**
SV
OD
**
SV
OD
OD OD
~
DV DV
M M
~ ~
OD OD
INLET
INLET
SCHEMATIC 2
ETW-T
** **
OUTLET
OUTLET
PS2 PS2
G G
PG PG
NRV PG NRV PG
OD OD
**
SV
**
SV
OD TO DETECTION LINE OD TO DETECTION LINE
~
~
DV DV
M M
~ ~
OD OD
INLET
INLET
FLANGE X FLANGE GROOVE X GROOVE
SCHEMATIC 3
ETD-T
TO DETECTION TO DETECTION
LINE LINE
**
PS1 **
PS1
AIR SUPPLY AIR SUPPLY
NRV RN NRV RN
OUTLET
OUTLET
**
PS2 **
PS2
G PG G PG
PG PG
NRV PG NRV PG
OD DPA OD DPA
**
SV
OD **
SV
OD
OD OD
~
DV DV
M M
~ ~
OD OD
INLET
INLET
SCHEMATIC 4
OUTLET ETW-D
OUTLET
**
PS2
DR.V **
PS2
DR.V
PG PG
~ ~
OD OD
PG PG
**
SV OD **
SV OD
OD OD
~
~
DV OD DV OD
TO DETECTION LINE TO DETECTION LINE
M M
~ ~
OD OD
INLET
INLET
FLANGE X FLANGE GROOVE X GROOVE
SCHEMATIC 5
ETD-D
TO DETECTION TO DETECTION
LINE LINE
**
PS1 **
PS1
AIR SUPPLY AIR SUPPLY
NRV RN NRV RN
OUTLET
OUTLET
PG PG
**
PS2 **
PS2
DR.V DR.V
PG ~
OD PG ~
OD
PG PG
DPA DPA
**
SV OD **
SV OD
OD OD
~
OD OD OD OD
DV DV
M M
~ ~
OD OD
INLET
INLET
SCHEMATIC 6
NT-W
** **
OUTLET
OUTLET
PS2 PS2
G G
PG DR.V PG DR.V
NRV NRV
OD ~ OD ~
OD OD
PG PG
**
SV OD **
SV OD
OD OD
~
~
DV OD DV OD
TO DETECTION LINE TO DETECTION LINE
M M
~ ~
OD OD
INLET
INLET
FLANGE X FLANGE GROOVE X GROOVE
SCHEMATIC 7
NT-D
TO DETECTION TO DETECTION
LINE LINE
PS1 ** PS1 **
AIR SUPPLY AIR SUPPLY
** **
OUTLET
OUTLET
NRV RN PG NRV RN PG
PS2 PS2
G G
PG DR.V PG DR.V
NRV NRV
OD ~ OD ~
OD OD
PG PG
DPA ** DPA
**
SV OD SV OD
OD OD
~
OD OD OD OD
DV DV
M M
~ ~
OD OD
INLET
INLET
SCHEMATIC 8
PS1 LOW AIR ALARM PRESSURE SWITCH DR.V DRIP VALVE --- BY USER
PS2 WATER FLOW PRESSURE ALARM SWITCH NRV NON RETURN VALVE ** OPTIONAL
**
SV **
SV
OD OD
~
M M
~ ~
PG OD PG OD
PS2 ** **
PS2
DV DV
INLET OUTLET INLET OUTLET
PG PG
SCHEMATIC 9
TO DETECTION
LINE
ET-D TO DETECTION
LINE
PG PG
**
PS1 **
PS1
AIR SUPPLY AIR SUPPLY
RN NRV RN NRV
DPA DPA
OD **
SV OD **
SV
OD OD
~
M M
~ ~
PG OD PG OD
**
PS2 **
PS2
DV DV
INLET OUTLET INLET OUTLET
PG PG
SCHEMATIC 10
TO DETECTION
LINE ETW-T TO DETECTION
LINE
**
SV **
SV
OD OD
~
M M
** **
~ ~
PG PS2 OD PG PS2 OD
G G
NRV NRV
~ ~
OD OD
DV DV
INLET OUTLET INLET OUTLET
PG PG
SCHEMATIC 11
TO DETECTION
LINE
ETD-T TO DETECTION
LINE
PG
PG
**
PS1 **
PS1
AIR SUPPLY AIR SUPPLY
RN NRV RN NRV
DPA DPA
OD **
SV OD **
SV
OD OD
~
~
M M
~ ~
OD OD
PG
**
PS2
PG
**
PS2
G G
NRV NRV
~ ~
OD OD
DV DV
INLET OUTLET INLET OUTLET
PG PG
SCHEMATIC 12
**
SV **
SV
OD OD
~
M M
~ ~
PG OD PG OD
**
PS2 **
PS2
DV DV
INLET OUTLET INLET OUTLET
PG PG
DR.V DR.V
~ ~
OD OD
~ ~
OD OD
OD OD
PG
**
PS1
PG
**
PS1
AIR SUPPLY AIR SUPPLY
RN NRV RN NRV
DPA DPA
OD **
SV OD **
SV
OD OD
~
~
M M
~ ~
PG OD OD
PG
**
PS2 **
PS2
DV DV
INLET OUTLET OUTLET
INLET
PG PG
DR.V ~ DR.V
OD ~
OD
~ ~
OD OD
OD OD
SCHEMATIC 14
PS1 LOW AIR ALARM PRESSURE SWITCH DR.V DRIP VALVE --- BY USER
PS2 WATER FLOW PRESSURE ALARM SWITCH NRV NON RETURN VALVE ** OPTIONAL
TO DETECTION
LINE NT-W TO DETECTION
LINE
**
SV **
SV
OD OD
~
M M
** **
~ ~
PS2 OD PS2 OD
PG PG
G G
NRV NRV
~ ~
OD OD
DV DV
INLET OUTLET INLET OUTLET
PG PG
DR.V DR.V
~ ~
OD OD
~ ~
OD OD
OD OD
SCHEMATIC 15
PG
**
PS1
PG
**
PS1
AIR SUPPLY AIR SUPPLY
RN NRV RN NRV
DPA DPA
OD **
SV OD **
SV
OD OD
~
~
M M
~ ~
OD
PG **
PS2
OD
PG **
PS2
G G
NRV NRV
~ ~
OD OD
DV DV
OUTLET INLET OUTLET
INLET
PG PG
DR.V DR.V ~
~
OD OD
~ ~
OD OD
OD OD
DV 200NB DV 150NB
KG/SQ.CM KG/SQ.CM
2 4 6 8 10 12 14 16 18
2 4 6 8 10 12 14 16 18 240
220. 70
ET
65
220. FE
200 60 25
65
E T 200 ET 60
180 FE 55 FE
MAXIMUM PILOT LINE HEIGHT - FT. ------
METERS
METERS
120 40
35
120
35
100 30
100 30
80 25
80 25
20
60 20
60
15
15
40
10 40
10
20 5 20 5
0 0
20 50 100 150 200 250 20 50 100 150 200 250
SYSTEM SUPPLY PRESSURE - PSI ------ SYSTEM SUPPLY PRESSURE - PSI ------
EQUIVALENT LENGTH BASED ON 1/2” SCHEDULE 40 PIPE WITH C=120 EQUIVALENT LENGTH BASED ON 1/2” SCHEDULE 40 PIPE WITH C=120
DV 100NB DV 80NB
KG/SQ.CM KG/SQ.CM
2 4 6 8 10 12 14 16 18
240 2 4 6 8 10 12 14 16 18
70
220.
65
220.
65 200 60
200
ET 60
180 E ET 55
FE 5F
MAXIMUM PILOT LINE HEIGHT - FT. ------
180 25 55 2
T 50
EE 160 ET
160 0 F 50
0 FE 45
25 25
45 140
140 E T 40
FE ET
METERS
0 40
FE
METERS
50 120 0 35
120 50
35
100 30
100 30
80 25
80 25
20
20 60
60
15
15
40
40 10
10
20 20 5
5
0 0
20 50 100 150 200 250 20 50 100 150 200 250
SYSTEM SUPPLY PRESSURE - PSI ------ SYSTEM SUPPLY PRESSURE - PSI ------
EQUIVALENT LENGTH BASED ON 1/2” SCHEDULE 40 PIPE WITH C=120 EQUIVALENT LENGTH BASED ON 1/2” SCHEDULE 40 PIPE WITH C=120
DV - 50NB
KG/SQ.CM
2 4 6 8 10 12 14 16 18
220.
65
200 60
T
EE
180 55
F
MAXIMUM PILOT LINE HEIGHT - FT. ------
25 50
160 T
EE
0F 45
140 25
40
ET
120 FE
METERS
0 35
50
100 30
80 25
20
60
15
40
10
20 5
0
20 50 100 150 200 250
40
30
20
Nominal Pressure Loss in Pounds per Square Inch (psi)
10
8
6 * *
* *
5
4
)
CH
3
IN
*
(8
CH
)
B
2
CH
IN
N
0
IN
(6
20
)
CH
(4
B
N
IN
B
)
0
N
CH
(3
1.0
15
0
10
B
IN
0.8
N
(2
80
0.6
B
N
0.5
50
0.4
0.3
0.2
0.1
100 200 300 400 600 800 1000 2000 3000 5000 7000 10000 20000
* 2.3 psi Pressure loss @ 15 feet per second (4.57 m/s) velocity having flow of 594 lpm through 50NB DV
* 4.7 psi Pressure loss @ 15 feet per second (4.57 m/s) velocity having flow of 1308 lpm through 80NB DV
* 4.7 psi Pressure loss @ 15 feet per second (4.57 m/s) velocity having flow of 2255 lpm through 100NB DV
* 7.5 psi Pressure loss @ 15 feet per second (4.57 m/s) velocity having flow of 5117 lpm through 150NB DV
* 8.4 psi Pressure loss @ 15 feet per second (4.57 m/s) velocity having flow of 8854 lpm through 200NB DV
LIMITED WARRANTY
HD FIRE PROTECT PVT. LTD. hereby referred to as HD FIRE warrants to the original purchaser of the fire protection products manufactured by HD FIRE and to any other person
to whom such equipment is transferred, that such products will be free from defect in material and workmanship under normal use and care, for two (2) years from the date of
shipment by HD FIRE. Products or Components supplied or used by HD FIRE, but manufactured by others, are warranted only to the extent of the manufacturer’s warranty.
No warranty is given for product or components which have been subject to misuse, improper installation, corrosion, unauthorized repair, alteration or un-maintained.
HD FIRE shall not be responsible for system design errors or improper installation or inaccurate or incomplete information supplied by buyer or buyer’s representatives.
HD FIRE will repair or replace defective material free of charge, which is returned to our factory, transportation charge prepaid, provided after our inspection the material is
found to have been defective at the time of initial shipment from our works. HD FIRE shall not be liable for any incidental or consequential loss, damage or expense arising directly
or indirectly from the use of the product including damages for injury to person, damages to property and penalties resulting from any products and components manufactured
by HD FIRE. HD FIRE shall not be liable for any damages or labour charges or expense in making repair or adjustment to the product. HD FIRE shall not be liable for any
damages or charges sustained in the adaptation or use of its engineering data & services. In no event shall HD Fire’s product liability exceed an amount equal to the sale price.
The foregoing warranty is exclusive and in lieu of all other warranties and representation whether expressed, implied, oral or written, including but not limited
to, any implied warranties or merchantability or fitness for a particular purpose. All such other warranties and representations are hereby cancelled.
NOTICE :
The equipment presented in this bulletin is to be installed in accordance with the latest publication standards of NFPA or other similar organisations and also with the
provision of government codes or ordinances wherever applicable.
The information provided by us is to the best of our knowledge and belief, and consist of general guidelines only. Site handling and installation control is not in our scope.
Hence we give no guarantee for result and take no liability for damages, loss or penalties whatsoever, resulting from our suggestion, information, recommendation or
damages due to our product.
Product development is a continuous programme of HD FIRE PROTECT PVT. LTD. and hence the right to modify any specification without prior notice is reserved with
the company.
D-6/2, ROAD NO. 34, WAGLE INDUSTRIAL ESTATE, THANE 400 604, INDIA.