FD-X Series: IO-Link Instruction Manual

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

758GB 1.

Specifications
FD-XA1
Model
FD-XA5

Clamp-on IO-Link approved standard


Baud rate
v. 1.1
COM2 (38.4 kbps)
Flow Sensor Min. cycle time 3.2 ms

FD-X Series
Process data length 4 Byte

2. Wiring
IO-Link
Instruction Manual Symbol
L+
Color
Brown
Name
20 to 30 VDC
Q2 White Output 2
This instruction manual explains the IO-Link specifications for the clamp-on flow sensor L- Blue 0V
FD-X Series (hereinafter abbreviated as FD-X).
Details about the FD-X functions and how to use the unit can be found in the “FD-X Q1/C Black Output 1*1/ IO-Link
Series Instruction Manual”. A copy of the “FD-X Series Instruction Manual” can be
downloaded off of the KEYENCE website. Alternatively, contact a local KEYENCE *1 Assignment changes according to the settings on the IO-Link master.
representative. When IO-Link is not connected, output 1 is assigned.
The settings file can also be downloaded off of the KEYENCE website.
If it is not possible to gain access to the internet to download the file, contact a local
KEYENCE representative.
KEYENCE Website: www.keyence.com

3. Process data
Process data is a function that communicates specific data in a constant cycle.
The format in which the process data is output, can be selected from the 6 types below.
Refer to "Index 146" in "Device Parameter" on page 4 or "Process Data Output Format" in "5. Settings" on page 6 for information on how to select the format type.
 Process Data Structure: 0=Instantaneous flow rate + Error + Stability level + Alert + Output2 + Output1(Default)
Bit 31 Bit 30 Bit 29 Bit 28 Bit 27 Bit 26 Bit 25 Bit 24 Bit 23 Bit 22 Bit 21 Bit 20 Bit 19 Bit 18 Bit 17 Bit 16
*1, 2
Instantaneous flow rate
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Instantaneous flow rate*1, 2 Error information*3 Stability level*4 Bubble detection*5 Output 2 Output 1

 Process Data Structure: 1=Shot amount + Error + Stability level + Alert + Output2 + Output1
Bit 31 Bit 30 Bit 29 Bit 28 Bit 27 Bit 26 Bit 25 Bit 24 Bit 23 Bit 22 Bit 21 Bit 20 Bit 19 Bit 18 Bit 17 Bit 16
*6
Shot amount
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Shot amount*6 Error information*3 Stability level*4 Bubble detection*5 Output 2 Output 1

 Process Data Structure: 2=Integrated flow value + Error + Stability level + Alert + Output2 + Output1
Bit 31 Bit 30 Bit 29 Bit 28 Bit 27 Bit 26 Bit 25 Bit 24 Bit 23 Bit 22 Bit 21 Bit 20 Bit 19 Bit 18 Bit 17 Bit 16
*7
Integrated flow
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Integrated flow*7 Error information*3 Stability level*4 Bubble detection*5 Output 2 Output 1

 Process Data Structure: 3=Instantaneous flow rate


Bit 31 Bit 30 Bit 29 Bit 28 Bit 27 Bit 26 Bit 25 Bit 24 Bit 23 Bit 22 Bit 21 Bit 20 Bit 19 Bit 18 Bit 17 Bit 16
*1, 8
Instantaneous flow rate
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Instantaneous flow rate*1, 8

 Process Data Structure: 4=Shot amount


Bit 31 Bit 30 Bit 29 Bit 28 Bit 27 Bit 26 Bit 25 Bit 24 Bit 23 Bit 22 Bit 21 Bit 20 Bit 19 Bit 18 Bit 17 Bit 16

Shot amount*9
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
*9
Shot amount

 Process Data Structure: 5=Integrated flow value


Bit 31 Bit 30 Bit 29 Bit 28 Bit 27 Bit 26 Bit 25 Bit 24 Bit 23 Bit 22 Bit 21 Bit 20 Bit 19 Bit 18 Bit 17 Bit 16
*10
Integrated flow
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Integrated flow*10

*1 If the flow sensor displays something other than a value, one of the following will be output. [Over Current]/[EEPROM Error]: Normal, [Head Error][rEv][----]:0
*2 The range of the instantaneous flow rate (18 bits) is 0 to 250000. The unit is linked to index 233 of the service data.
*3 The error information bits and the error details correspond as shown below.
Bit6: Overcurrent error Bit7: Head error Bit8: EEPROM error Bit9: Reserve
Bit10: Reverse flow error Bit11: Detection impossible error Bit12: Reserve Bit13: Abnormal setting
*4 The stability of the ultrasounic detection is indicated through one of six levels: 0 to 5. (0: Cannot detect, 1 to 4: Low to high stability, 5: Searching for signal)
*5 Regardless of whether bubble detection mode is set, this bit becomes 1 when bubbles are detected.
*6 The range of the shot amount (18 bits) is 0 to 250000. The unit is 0.001 mL for the FD-XS1/XS8 and is 0.001 L for the FD-XS20.
*7 The range of the integrated flow (18 bits) is 0 to 250000. The unit is linked to index 203 of the service data.
*8 The range of the instantaneous flow rate (32 bits) is -999999 to 999999. The unit is linked to index 233 of the service data.
*9 The range of the shot amount (32 bits) is -9999999 to 9999999. The unit is 0.001 mL for the FD-XS1/XS8 and the FD-XS20 [high resolution] and is 0.001 L for the FD-XS20
[standard].
*10 The range of the integrated flow (32 bits) is -999999999 to 999999999. The unit is fixed to the minimum resolution (0.1 mL for the FD-XS1/XS8 and the FD-XS20 [high resolution]
and 0.01 L for the FD-XS20 [standard]).

-1-
4. Service Data
Service data is a function that refreshes information between the IO-Link master and slave only when there is a send request.
Reading/writing of the flow sensor settings and status, and execution of operation commands (tuning, etc.) can be carried out.
 Meaning of each item
Item Value Meaning
Item - Shows the notation in the instruction manual
Record Data structure
Bit (x) Bit No. x in Record
Format String Text string
UInt Unsigned integer
Int Signed integer
R Read possible
R/W Read/write possible
Access
W Write possible
C Operation command
√ Compatible with the data storage function*1
Data storage
- Not compatible with the data storage function
*1 Flow sensor settings are backed up with the IO-Link master. This allows settings to be restored if the flow sensor is replaced.

If parameter writing is executed from IO-Link during initialization, the flow sensor may behave in an unexpected manner. Do not write parameters while
NOTICE
initialization is being executed.

Point When a value that is greater than or equal to the FD-X’s set upper limit is entered, the FD-X operates with the set upper limit.
Also, when a value that is less than or equal to the FD-X’s set lower limit is entered, the FD-X operates with the set lower limit.

4-1 Parameter List


Predefined parameter
Data Default
Index Item Name Format Length Access Range Remark
storage value
12 Device Access Device Access
Record 2 Byte R/W - - - -
(0x0C) Locks Locks

2 Data Storage 0 = Unlock


Data Storage Lock Bit (1) 1 Bit - - 0 -
(0x02) Lock*1 1 = Lock
16
Vendor Name Vendor Name String 64 Byte R - Keyence -
(0x10)
17
Vendor Text Vendor Text String 64 Byte R - www.keyence.com -
(0x11)
18
Product Name Product Name String 64 Byte R - FD-XA1/5 -
(0x12)
19
Product ID Product ID String 64 Byte R - FD-XA1/5 -
(0x13)
20
Product Text Product Text String 64 Byte R - Clamp-on Flow Sensor -
(0x14)
22
Hardware Version Hardware Version String 64 Byte R - - -
(0x16)
23
Firmware Version Firmware Version String 64 Byte R - - -
(0x17)
24 Application Application
String 32 Byte R/W √ *** - -
(0x18) Specific Tag Specific Tag
0xFF91 = Data Storage
Upload Request
0x1800 = Reverse flow -
The fluid flows in the
opposite direction of the
setting
0x1803 = Head error - There is
37 Detailed Device Detailed Device
Record 12 Byte R - 0 a breakage in the sensor Refer to “6. Events”
(0x25) Status Status
cable or the sensorhead is
disconnected.
0x5000 = Device
hardware fault - Device
Exchange
0x7710 = Short circuit -
Check installation
40
Process Data Input Process Data Input UInt 4 Byte R - - - -
(0x28)
*1 Backing up and restoring in the data storage function can be locked.

-2-
Device Parameter
Index Name Reference item Format Length Access Data storage Default value Range Remark
101 NPN/PNP 0 = NPN
NPN/PNP selection UInt 1 Byte R/W √ 0 -
(0x65) selection 1 = PNP
0 = 50 ms
1 = 100 ms
2 = 500 ms
3 = 1s
102
Response time Response time UInt 1 Byte R/W √ 2 4 = 2.5 s -
(0x66)
5=5s
6 = 10 s
7 = 30 s
8 = 60 s
103 Analog output Analog output 0 = 4 - 20 mA
UInt 1 Byte R/W √ 0 -
(0x67) selection selection 1 = 0 - 20 mA
0 = Full auto calibration : Start
1 = Full auto calibration :
Finish
2 = Multi shot calibration :
Start
3 = Multi shot calibration :
Finish
104 Command 4 = Reset integrated flow
Command request UInt 1 Byte C - 0 -
(0x68) request 5 = Perform conditional
monitoring
6 = Cancel conditional
monitoring
7 = Reset flow hold value
8 = Reset shot hold value
9 = Perform origin adjustment
10 = Reset origin adjustment
105 Analog lower flow Analog output lower Unit: Linked to Index
UInt 4 Byte R/W √ 0 0 to 999999
(0x69) limit limit 233
FD-XS1: 10000
FD-XS8/XS20
106 Analog upper Analog output upper [high resolution]: Unit: Linked to Index
UInt 4 Byte R/W √ 0 to 999999
(0x6A) flow limit limit 80000 233
FD-XS20
[standard]: 20000
110 0 = Normally open
Output 1 logic Ch.1 output logic UInt 1 Byte R/W √ 0 -
(0x6E) 1 = Normally closed
0 = Instantaneous flow rate
mode
111 Output 1 Output 1 detection 1 = Area mode
UInt 1 Byte R/W √ 0
(0x6F) detection mode mode 2 = Pulse output (+) mode
3 = Integrated flow mode
4 = Shot mode
FD-XS1: 1000
FD-XS8/XS20
Output 1 flow set Instantaneous flow
112 [high resolution]: Unit: Linked to Index
value/Lower flow rate threshold (output UInt 4 Byte R/W √ 0 to 999999
(0x70) 8000 233
limit value 1 1 lower limit value)
FD-XS20
[standard]: 2000
FD-XS1: 4000
FD-XS8/XS20
Instantaneous flow
113 Upper flow limit [high resolution]: Unit: Linked to Index
rate threshold (output UInt 4 Byte R/W √ 0 to 999999
(0x71) value 1 32000 233
1 upper limit value)
FD-XS20
[standard]: 8000
FD-XS1: 1000
FD-XS8/XS20
114 Lower shot limit Shot threshold (output [high resolution]:
UInt 4 Byte R/W √ 0 to 9999999 Unit:0.001
(0x72) value 1 1 lower limit value) 3000
FD-XS20
[standard]: 15
FD-XS1: 6000
FD-XS8/XS20
115 Upper shot limit Shot threshold (output [high resolution]:
UInt 4 Byte R/W √ 0 to 9999999 Unit:0.001
(0x73) value 1 1 upper limit value) 18000
FD-XS20
[standard]: 90
118 0 = Normally open
Output 2 logic Output 2 logic UInt 1 Byte R/W √ 0 -
(0x76) 1 = Normally closed
0 = Instantaneous flow rate
mode
1 = Area mode
119 Output 2 Output 2 detection 2 = Pulse output(-) mode
UInt 1 Byte R/W √ 0 -
(0x77) detection mode mode 3 = Shot mode
4 = Error output mode
5 = Bubble alert mode
6 = Error and alert mode
FD-XS1: 2000
FD-XS8/XS20
Output 2 flow set Instantaneous flow
120 [high resolution]: Unit: Linked to Index
value/Lower flow rate threshold (output UInt 4 Byte R/W √ 0 to 999999
(0x78) 16000 233
limit value 2 2 lower limit value)
FD-XS20
[standard]: 4000
FD-XS1: 3000
FD-XS8/XS20
Instantaneous flow
121 Upper flow limit [high resolution]: Unit: Linked to Index
rate threshold (output UInt 4 Byte R/W √ 0 to 999999
(0x79) value 2 24000 233
2 upper limit value)
FD-XS20
[standard]: 6000
FD-XS1: 2000
FD-XS8/XS20
122 Lower shot limit Shot threshold (output [high resolution]:
UInt 4 Byte R/W √ 0 to 9999999 Unit:0.001
(0x7A) value 2 2 lower limit value) 6000
FD-XS20
[standard]: 30
FD-XS1: 4000
FD-XS8/XS20
123 Upper shot limit Shot threshold (output [high resolution]:
UInt 4 Byte R/W √ 0 to 9999999 Unit:0.001
(0x7B) value 2 2 upper limit value) 12000
FD-XS20
[standard]: 60
0 = Off
129 Input 1 function
Input 1 function UInt 1 Byte R/W √ 0 1 = Flow rate zero input -
(0x81) selection
2 = Shot sampling trigger

-3-
Index Name Reference item Format Length Access Data storage Default value Range Remark
0 = Off
130 Input 2 function
Input 2 function UInt 1 Byte R/W √ 0 1 = Integrated flow reset input -
(0x82) selection
2 = Zero shift input
FD-XS1: 100
FD-XS8/XS20
131 [high resolution]: Unit: Linked to Index
Hysteresis Hysteresis set value UInt 4 Byte R/W √ 0 to 999999
(0x83) 200 233
FD-XS20
[standard]: 50
0 = 100%
138 Screen
Screen brightness UInt 1 Byte R/W √ 1 1 = 30% -
(0x8A) brightness
2 = Display Off
0 = Unlock
139 1 = Key lock
Key lock Key lock status UInt 1 Byte R/W √ 0 -
(0x8B) 2 = Password lock
3 = Communication lock
0 = Normal (without password)
140
Key lock method Key lock method UInt 1 Byte R/W √ 0 1 = Password-protected key -
(0x8C)
lock
141 Key lock
Key lock password UInt 2 Byte R/W √ 0 0 to 9999 -
(0x8D) password
142 Additional Advanced function 0 = Settings complete
UInt 1 Byte R/W √ 0 -
(0x8E) functions menu settings 1 = Extended functions menu
144
(0x90)
User tag1 User tag1*1 UInt 4 Byte R/W √ 0 0 to 4294967295 -
145
(0x91)
User tag2 User tag2*1 UInt 2 Byte R/W √ 0 0 to 65535 -
0 = Instantaneous flow rate +
Error + Stability level +
Alert + Output2 + Output1
1 = Shot amount + Error +
Stability level + Alert +
146 Process data Process data output Output2 + Output1
UInt 1 Byte R/W √ 0 -
(0x92) structure format 2 = Integrated flow value +
Error + Stability level +
Alert + Output2 + Output1
3 = Instantaneous flow rate
4 = Shot amount
5 = Integrated flow value
148 Instantaneous Instantaneous flow Unit: Linked to Index
Int 4 Byte R - 0 -999999 to 999999
(0x94) flow rate rate 233
149 Integrated flow Unit: Linked to Index
Integrated flow value Int 4 Byte R - 0 -999999999 to 999999999
(0x95) value 203
150
Shot amount Shot amount Int 4 Byte R - 0 -9999999 to 9999999 Unit:0.001
(0x96)
0 = No head
151 1 = FD-XS1
Head Type Head Type UInt 1 Byte R - - -
(0x97) 2 = FD-XS8
3 = FD-XS20
Peak-hold value
160 Peak-hold flow Unit: Linked to Index
(instantaneous flow Int 4 Byte R - 0 -999999 to 999999
(0xA0) value 233
rate)
Bottom-hold value
161 Bottom-hold flow Unit: Linked to Index
(instantaneous flow Int 4 Byte R - 0 -999999 to 999999
(0xA1) value 233
rate)
164 Peak-hold shot Peak-hold value (shot
Int 4 Byte R - 0 -9999999 to 9999999 Unit:0.001
(0xA4) amount amount)
165 Bottom-hold shot Bottom-hold value
Int 4 Byte R - 0 -9999999 to 9999999 Unit:0.001
(0xA5) amount (shot amount)
170 Tuning Calibration target
UInt 1 Byte R/W √ 25 1 to 99 Unit:1 [%]
(0xAA) percentage value
171 Integrated flow rate 0 = Off
Total decrement UInt 1 Byte R/W √ 0 -
(0xAB) subtraction 1 = On
172 0 = Off
Shot decrement Shot rate subtraction UInt 1 Byte R/W √ 0 -
(0xAC) 1 = On
173 0 = Output1
Out1/Out2 Switch Out1/Out2 switch UInt 1 Byte R/W √ 0 -
(0xAD) 1 = Output2
0 = Default
174 Bubble cancel Bubble cancellation
UInt 1 Byte R/W √ 0 1 = Custom -
(0xAE) custom setting
2 = Off
0 = Low
175 Bubble cancel Bubble cancellation
UInt 1 Byte R/W √ 1 1 = Mid -
(0xAF) level sensitivity
2 = High
176
Hold Time Hold Time UInt 1 Byte R/W √ 5 1 to 60 Unit:1 [s]
(0xB0)
177 Bubble alert Bubble detection 0 = Default
UInt 1 Byte R/W √ 0 -
(0xB1) custom setting 1 = Custom
0 = Low
178 Bubble detection
Bubble alert level UInt 1 Byte R/W √ 1 1 = Mid -
(0xB2) sensitivity
2 = High
179 Alert one shot
One-shot output time UInt 1 Byte R/W √ 10 1 to 100 Unit:0.1 [s]
(0xB3) timer
0 = Detection not possible
1 = Low
180 Detection stability 2 = Medium-low
Stability level UInt 1 Byte R - - -
(0xB4) level 3 = Medium-high
4 = High
5 = Searching Signal
Identify if origin
181 0 = Off
Origin adjustment adjustment is currently UInt 1 Byte R - 0 -
(0xB5) 1 = On
being used*2
182 Condition Condition monitoring 0 = Off
UInt 1 Byte R - 0 -
(0xB6) monitoring function 1 = On
188 Simulation shot Simulation shot
UInt 4 Byte R/W - 0 0 to 9999999 Unit:0.001
(0xBC) amount amount
190 Simulation flow Unit: Linked to Index
Simulation flow rate Int 4 Byte R/W - 0 -999999 to 999999
(0xBE) rate 233
191 Reference flow Unit: Linked to Index
Base flow rate UInt 4 Byte R - 0 0 to 999999
(0xBF) rate 233

-4-
Index Name Reference item Format Length Access Data storage Default value Range Remark
FD-XS1: 200
FD-XS8/XS20
192 [high resolution]: Unit: Linked to Index
Zero-cut flow rate Zero-cut flow rate UInt 4 Byte R/W √ 0 to 999999
(0xC0) 400 233
FD-XS20
[standard]: 100
193 Flow rate span Span adjustment
UInt 2 Byte R/W √ 1000 100 to 10000 Unit:0.001
(0xC1) adjustment value
FD-XS1: 200
FD-XS8/XS20
194 Integrated flow Integrated flow [high resolution]: Unit: Linked to Index
UInt 2 Byte R/W √ 0 to 9999
(0xC2) threshold value threshold value 600 203
FD-XS20
[standard]: 300
199 Pipe material 0 = Metal
Pipe material selection UInt 1 Byte R/W √ 0 -
(0xC7) selection 1 = Plastic
0 = No correction
200
Flow rate tuning Flow rate tuning UInt 1 Byte R/W √ 0 1 = Pro settings -
(0xC8)
2 = Span adjustment
0 = [XS1/8/20]4 mm, 6 mm, 10
mm
1 = [XS1/8/20]3/8 inch, 8 mm,
Pipe bore 12 mm
202 Pipe bore diameter
diameter UInt 1 Byte R/W √ 0 2 = [XS1/8/20]3 mm, 1/4 inch, -
(0xCA) selection
selection 3/8 inch
3 = [XS20]1/2 inch
4 = [XS20]6A
5 = [XS20]8A
0 = 0.01
FD-XS1: 2 1 = 0.1
FD-XS8/XS20 2=1
203 Integrated flow
Integrated flow unit UInt 1 Byte R/W √ [high resolution]: 2 3 = 10 -
(0xCB) unit
FD-XS20 4 = 100
[standard]: 0 5 = 1000
6 = 10000
204 Flow direction Flow direction 0 = From Cable to LED
UInt 1 Byte R/W √ 0 -
(0xCC) selection selection 1 = From LED to Cable
205 0 = Liter
Flow unit Flow unit selection UInt 1 Byte R/W √ 0 -
(0xCD) 1 = Gallon
FD-XS1: 400
FD-XS8/XS20
207 Pipe outer Pipe outer diameter [high resolution]:
UInt 2 Byte R/W √ 270 to 1430 Unit:0.01 [mm]
(0xCF) diameter input input 600
FD-XS20
[standard]: 1000
208 Pipe thickness
Pipe thickness input UInt 2 Byte R/W √ 100 10 to 400 Unit:0.01 [mm]
(0xD0) input
210 Liquid type 0 = Water
Liquid type selection UInt 1 Byte R/W √ 0 -
(0xD2) selection 1 = User Input
213 Ultrasonic speed
Ultrasonic speed input UInt 2 Byte R/W √ 1497 300 to 1900 Unit:1 [m/s]
(0xD5) input
214 Kinematic Kinematic viscosity
UInt 4 Byte R/W √ 100 1 to 50000 Unit:0.01 [cSt]
(0xD6) viscosity input input
220 0 = Off
Simulation mode Simulation function UInt 1 Byte R/W - 0 -
(0xDC) 1 = On
221 Flow rate zero 0 = Off
Flow rate zero input UInt 1 Byte R/W - 0 -
(0xDD) input 1 = On
222 Shot sampling 0 = Off
Shot sampling input UInt 1 Byte R/W - 0 -
(0xDE) trigger 1 = On
223 0 = Off
Zero Shift input Zero Shift input UInt 1 Byte R/W - 0 -
(0xDF) 1 = On
229 Connected sensor 0 = Off
Blink head LED UInt 1 Byte R/W - 0 -
(0xE5) head blinking 1 = On
0 = Green light - Light off
1 = Light off - Red light
230 Head indicator Status indicator 2 = Green light - Red light
UInt 1 Byte R/W √ 0 -
(0xE6) illumination mode illumination mode 3 = PMI (predictive
maintenance information)
4 = Off
231 Display
Display averaging UInt 1 Byte R/W √ 10 0 to 100 Unit:0.1 [s]
(0xE7) averaging
FD-XS1: 3 0 = 0.001
Display resolution FD-XS8/XS20 1 = 0.01
232 Flow display
(instantaneous flow UInt 1 Byte R/W √ [high resolution]: 3 2 = 0.1 -
(0xE8) resolution
rate) FD-XS20 3=1
[standard]: 1 4 = 10
FD-XS1: 2
Data unit FD-XS8/XS20 0 = 0.001
233 (instantaneous flow
Flow resolution UInt 1 Byte R - [high resolution]: 2 1 = 0.01 -
(0xE9)
rate)*3 FD-XS20 2 = 0.1
[standard]: 0
234 Data unit (shot
Shot resolution UInt 1 Byte R - 0 0 = 0.001 -
(0xEA) amount)*3
FD-XS1: 1
0 = 0.001
FD-XS8/XS20
235 Shot display Display resolution 1 = 0.01
UInt 1 Byte R/W √ [high resolution]: 1 -
(0xEB) resolution (shot amount) 2 = 0.1
FD-XS20
3=1
[standard]: 0
0 = Idle
253 1 = Exe
Command status Command status UInt 1 Byte R - 0 -
(0xFD) 2 = Success
3 = Failure
*1 Flow sensor specific number can be allocated.
*2 Indicates change in zero position from factory setting.
*3 Indicates the data unit when reading over IO-Link.

Standard Command
Data
Index Name Reference item Format Length Access Value Range Remark
storage
System Command Initialization UInt 1 Byte W ー 130 Initialization -
2 With the FD-XS20 connected,
(0x02) Initialization (FD-XS20
System Command UInt 1 Byte W ー 161 initializes the sensor in high- -
high resolution)
resolution mode

-5-
5. Settings
During IO-Link communication, the process data output format can be selected from the
following screen on the sensor itself.
For details on other settings, refer to the FD-X Series Instruction Manual.

Initial Settings
When IO-Link is connected, set ch.1 to OUT.

Normal
screen
Press and hold
MODE

Basic
Settings

Process
data output
format selection

A Advanced Flow Resolution Password Lock IO Data Format


Settings 1 Off Format Type 0

Setting range:
・Format Type 0 = Instantaneous flow rate + Error + Stability level + Alert + Output2 + Output1(Default)
・Format Type 1 = Shot amount + Error + Stability level + Alert + Output2 + Output1
・Format Type 2 = Integrated flow value + Error + Stability level + Alert + Output2 + Output1
・Format Type 3 = Instantaneous flow rate
・Format Type 4 = Shot amount
・Format Type 5 = Integrated flow value

MODE
Press and hold
to complete the settings.

-6-
6. Events WARRANTIES AND DISCLAIMERS
When an event occurs, the flow sensor turns ON the event flag in the process data (1) KEYENCE warrants the Products to be free of defects in materials and
telegram. workmanship for a period of one (1) year from the date of shipment. If any
The master detects the event flag and reads the value that corresponds to the event that models or samples were shown to Buyer, such models or samples were used
has occurred. merely to illustrate the general type and quality of the Products and not to
This allows the status of the flow sensor to be forwarded to the PLC or monitor through represent that the Products would necessarily conform to said models or
the IO-Link master.
samples. Any Products found to be defective must be shipped to KEYENCE with
Service data exchange is not carried out while an event is being read.
all shipping costs paid by Buyer or offered to KEYENCE for inspection and
Value Name Meaning examination. Upon examination by KEYENCE, KEYENCE, at its sole option, will
Data Storage Upload refund the purchase price of, or repair or replace at no charge any Products
0xFF91 Settings were changed on the flow sensor.
Request found to be defective. This warranty does not apply to any defects resulting from
Reverse flow - The fluid any action of Buyer, including but not limited to improper installation, improper
The fluid flows in the opposite direction of the interfacing, improper repair, unauthorized modification, misapplication and
0x1800 flows in the opposite
setting. mishandling, such as exposure to excessive current, heat, coldness, moisture,
direction of the setting
Head error - There is a vibration or outdoors air. Components which wear are not warranted.
breakage in the sensor (2) KEYENCE is pleased to offer suggestions on the use of its various Products.
0x1803 cable or the An error has occurred on the head. They are only suggestions, and it is Buyer's responsibility to ascertain the fitness
sensorhead is of the Products for Buyer’s intended use. KEYENCE will not be responsible for
disconnected. any damages that may result from the use of the Products.
Device hardware fault - (3) The Products and any samples (“Products/Samples”) supplied to Buyer are not
0x5000 An error has occurred in the EEPROM. to be used internally in humans, for human transportation, as safety devices or
Device Exchange
fail-safe systems, unless their written specifications state otherwise. Should any
Short circuit - Check
0x7710 An overcurrent error has occurred. Products/Samples be used in such a manner or misused in any way, KEYENCE
installation
assumes no responsibility, and additionally Buyer will indemnify KEYENCE and
hold KEYENCE harmless from any liability or damage whatsoever arising out of
any misuse of the Products/Samples.
(4) OTHER THAN AS STATED HEREIN, THE PRODUCTS/SAMPLES ARE
PROVIDED WITH NO OTHER WARRANTIES WHATSOEVER. ALL EXPRESS,
IMPLIED, AND STATUTORY WARRANTIES, INCLUDING, WITHOUT
LIMITATION, THE WARRANTIES OF MERCHANTABILITY, FITNESS FOR A
PARTICULAR PURPOSE, AND NON-INFRINGEMENT OF PROPRIETARY
RIGHTS, ARE EXPRESSLY DISCLAIMED.
IN NO EVENT SHALL KEYENCE AND ITS AFFILIATED ENTITIES BE LIABLE
TO ANY PERSON OR ENTITY FOR ANY DIRECT, INDIRECT, INCIDENTAL,
PUNITIVE, SPECIAL OR CONSEQUENTIAL DAMAGES (INCLUDING,
WITHOUT LIMITATION, ANY DAMAGES RESULTING FROM LOSS OF USE,
BUSINESS INTERRUPTION, LOSS OF INFORMATION, LOSS OR
INACCURACY OF DATA, LOSS OF PROFITS, LOSS OF SAVINGS, THE
COST OF PROCUREMENT OF SUBSTITUTED GOODS, SERVICES OR
TECHNOLOGIES, OR FOR ANY MATTER ARISING OUT OF OR IN
CONNECTION WITH THE USE OR INABILITY TO USE THE PRODUCTS,
EVEN IF KEYENCE OR ONE OF ITS AFFILIATED ENTITIES WAS ADVISED
OF A POSSIBLE THIRD PARTY’S CLAIM FOR DAMAGES OR ANY OTHER
CLAIM AGAINST BUYER. In some jurisdictions, some of the foregoing warranty
disclaimers or damage limitations may not apply.

BUYER'S TRANSFER OBLIGATIONS:


If the Products/Samples purchased by Buyer are to be resold or delivered to a
third party, Buyer must provide such third party with a copy of this document, all
specifications, manuals, catalogs, leaflets and written information provided to
Buyer pertaining to the Products/Samples.
E 1101-3

-7-
Copyright (c) 2020 KEYENCE CORPORATION. All rights reserved.