Graphic-Display Description and Operation: Short User Manual
Graphic-Display Description and Operation: Short User Manual
Graphic-Display Description and Operation: Short User Manual
PSD02
Graphic-Display
Description and Operation
4BA 452-90040-001
This manual is a supplement to the existing PSD instruction manuals 927-01186-174 & 927-
01185-174.
Subject to change.
All rights reserved, including, but not limited to, translations, reprints, copying or similar..
TOUCH
To parameterize the PSD02 device, you must continue to use the "PSD Control" software.
Technical Data
The menus are navigated via the touch function of the display.
For hat, the screen is divided into 3 parts.
Menu selected
TOUCH on area
1 à „back“
2 à „selection“
3 à „forward“
· If "BACK" / "FORWARD" is pressed, the "Menu Display" will display the next menu.
With a touch on area 2 "SELECTION", the display blanks out and the selected menu will
show up after approx. 10s.
· If no selection is made after 10s, the menu selection changes back to the current menu
display.
· After approx. 60s without any action, the system automatically switches back to "Status
Menu1".
After switching on the device, the start display will be displayed for approx. 40s, after that, it will
automatically switch to "Status menu1".
SN à PSD02-Serialnumber
FW à Firmware Version
An OK / F behind a value, will indicates whether the value is within its limits or not.
The essential measured values and states are displayed in status menu 1 & 2.
In the further course, a reference is made to chapters in the operating instructions "927-01186-
174" for an extended description / explanation of the individual values and results.
Frequency Frequency
U-Control Control voltage
U-Open Trip voltage CLOSE
U-Close Trip voltage OPEN
A-Temp Temperature
Active-MODE MODE-Input
Adap-CTRL Adaptive control
LastSyncOpr No sync. operation
ZeroCrossing No zero crossing on
reference signal OK/F
AUX NOàNormally Closed
NCàNormally Open
CB-INFO Serial number
P-Drive
Oil-pressure
[A, B, C]
P-SF6
SF6-gas pressure
[A, B, C]
These menues show all relevant results of the most recent switching operation of the
evaluation performed by the PSD02.
The values provide clues as to whether the settings regarding the controlled switching are
selected correctly or if corrections are still necessary.
In the further course, a reference is made to chapters in the operating instructions "927-01186-
174" for an extended description / explanation of the individual values and results.
The measured values will changed in real time / after a switching operation has been
performed, in the active menu