Short user manual

PSD02

Graphic-Display
Description and Operation
4BA 452-90040-001

Works with firmware v2.1.0.n or higher

EM TP SW AIS OPS B MF-ES IE TE 4BA 452-90040-001


Walter/Groth 11.2018/rev28
Status and measurement display for PSD02 version 072,

from firmware version v2.1.0.n or higher.


Operating instructions for the graphic touch display on the PSD02.

This manual is a supplement to the existing PSD instruction manuals 927-01186-174 & 927-
01185-174.

Part number of the operating instruction: 4BA 452-90040-001

Created by: Siemens AG


Energy Management Division
EM TP SW AIS OPS B MF-ES IE TE
13629 Berlin, Germany

Subject to change.

All rights reserved, including, but not limited to, translations, reprints, copying or similar..

TOUCH

G The display is equipped with a touch function.

Operation with a ballpoint pen or other pointed object will


damage the touch surface and destroy the operating
module.

EM TP SW AIS OPS B MF-ES IE TE 4BA 452-90040-001


Walter/Groth 11.2018/rev28
General

The display is used exclusively to display status and measured values.

No parameterization can be made via the touch function of the display.

To parameterize the PSD02 device, you must continue to use the "PSD Control" software.

Technical Data

· GRAPHICS DISPLAY 160x104, 78x61mm


· TECHNOLOGY: FSTN POS. TRANSFLECTIVE, BLACK ON WHITE
· HIGH-CONTRAST LCD SUPERTWIST DISPLAY
· BACKLIGHT: WHITE, LED
· 60x104 PIXELS (13 LINES à 26 CHARACTERS OR 6x20 LARGE CHAR.)
· OPERATING TEMPERATURE RANGE -20°C TO +70°C (STORAGE -30°C TO +80°C)
· TOUCH-PANEL: RESITIVE, LIFE TIME 100000CYCLES

Menu and display selection

4 different menus can be displayed.

- Status Menu 1 Current status / measured values


- Status Menu 2 Current pressure values, - if pressure sensors are used
- Last Close Result values of the last "Close - operation"
- Last Open Result values of the last "Open - operation"

EM TP SW AIS OPS B MF-ES IE TE 4BA 452-90040-001


Walter/Groth 11.2018/rev28
Navigation

The menus are navigated via the touch function of the display.
For hat, the screen is divided into 3 parts.

Menu selected

TOUCH on area

1 à „back“
2 à „selection“
3 à „forward“

· If "BACK" / "FORWARD" is pressed, the "Menu Display" will display the next menu.
With a touch on area 2 "SELECTION", the display blanks out and the selected menu will
show up after approx. 10s.
· If no selection is made after 10s, the menu selection changes back to the current menu
display.
· After approx. 60s without any action, the system automatically switches back to "Status
Menu1".

EM TP SW AIS OPS B MF-ES IE TE 4BA 452-90040-001


Walter/Groth 11.2018/rev28
Start Menu

After switching on the device, the start display will be displayed for approx. 40s, after that, it will
automatically switch to "Status menu1".

Through a TOUCH on the display, is changed immediately.

SN à PSD02-Serialnumber
FW à Firmware Version

EM TP SW AIS OPS B MF-ES IE TE 4BA 452-90040-001


Walter/Groth 11.2018/rev28
Status menus

An OK / F behind a value, will indicates whether the value is within its limits or not.

OK: value within the limits

F: value out of limits

STATUS MENU1 & 2

The essential measured values and states are displayed in status menu 1 & 2.

In the further course, a reference is made to chapters in the operating instructions "927-01186-
174" for an extended description / explanation of the individual values and results.

Breaker condition: „Software- & Application Manual“ chapter 6.5.1.1.3


Staus signals: „Software- & Application Manual“ chapter 6.5.1.1.2
Errors: „Software- & Application Manual“ chapter 6.5.1.1.4
Operationg Mode: „Software- & Application Manual“ chapter 6.8.4.3.1

Frequency Frequency
U-Control Control voltage
U-Open Trip voltage CLOSE
U-Close Trip voltage OPEN
A-Temp Temperature
Active-MODE MODE-Input
Adap-CTRL Adaptive control
LastSyncOpr No sync. operation
ZeroCrossing No zero crossing on
reference signal OK/F
AUX NOàNormally Closed
NCàNormally Open
CB-INFO Serial number

P-Drive
Oil-pressure
[A, B, C]
P-SF6
SF6-gas pressure
[A, B, C]

EM TP SW AIS OPS B MF-ES IE TE 4BA 452-90040-001


Walter/Groth 11.2018/rev28
Result Menus

LAST CLOSE / OPEN:

These menues show all relevant results of the most recent switching operation of the
evaluation performed by the PSD02.

The values provide clues as to whether the settings regarding the controlled switching are
selected correctly or if corrections are still necessary.

In the further course, a reference is made to chapters in the operating instructions "927-01186-
174" for an extended description / explanation of the individual values and results.

„Software- & Application Manual“ chapter 6.8.5.6

DATE DD.MM.YYYY HH:MM:SS


tdCMD Command delay
tOPR Closing time
tMAKE Make time
tdOPR Closing time difference
tdMake Make time difference
Imax Max. current
Usmax Max. voltage Us
Upmax Max. voltage Up

DATE DD.MM.YYYY HH:MM:SS


tdCMD Command delay
tOPR Opening time
tBRK Break time
tdOPR Opening time difference
tdBRK Break time difference
Imax Max. current
Usmax max. voltage Us
Upmax max. voltage Up

The measured values will changed in real time / after a switching operation has been
performed, in the active menu

On an inactivity of 60s will automatically switch to "Status Menu 1".

EM TP SW AIS OPS B MF-ES IE TE 4BA 452-90040-001


Walter/Groth 11.2018/rev28