LAMPIRAN POIN 1

I. LOGIC DASAR SKEMA DEF PILOT DI PLN P3B SUMATERA

100 ms
3I0> Forward pickup DEF send signal

50 ms

DEF trip ph. A


&
DEF receive signal
Phase DEF trip ph. B
Selection
Voltage Input
DEF trip ph. C
Current Input

Logika dasar skema DEF pilot di P3B Sumatera

II. STANDAR SETTING DAN LOGIC DEF RELE DISTANCE MICOM P443

SETTING DEF MICOM P443 :

GROUP 1 SCHEME LOGIC


AIDED SCHEME 2 34.60
Aid. 2 Selection Programmable 34.61
Aid. 2 Distance Disabled 34.62
Aid. 2 DEF Enabled 34.64
Aid. 2 DEF Dly. 0s 34.65
Aid. 2 DEF Trip 1 and 3 Pole 34.66
Aid. 2 Delta Disabled 34.67
tRev Guard 0s 34.6A
Custom Send Mask* 0001000000 34.78
Custom Time PU 100 ms 34.79
Custom Time DO 0s 34.7A
GROUP1 AIDED DEF
DEF Status Enabled 39.02
DEF Polarizing Zero Sequence 39.03
DEF Chars. Angle -60 deg 39.04
DEF VNpol Set 2.31 V 39.05
DEF FWD Set Sesuai hasil simulasi 39.07

* Custom Send Mask : DEF Forward

Page 1 of 19
PSL LOGIC DEF MICOM P443:

Page 2 of 19
III. STANDAR SETTING DAN LOGIC DEF RELE DISTANCE GE D60

SETTING DEF GE D60 :

PARAMETER NEUTRAL DIR OC1


Function Enabled
Source LINE (SRC 1)
Polarizing Voltage
Polarizing Volt Calculated V0
Op Current Calculated 3I0
POS SEQ Restraint 0.063
Offset 0.00 ohms
Forward ECA 30˚ Lag
Forward Limit Angle 45deg
Forward Pickup 0.010 pu
Reverse Limit Angle 45deg
Reverse Pickup 0.010 pu
Block OFF
Target Self-reset
Events Enabled

NB : setting Current Cut-off level : 0.002 pu (Product SetupDisplay properties)

PARAMETER GROUND IOC1


Function Enabled
Source LINE (SRC 1)
Pickup Sesuai hasil simulasi
Delay 0.10 s
Reset Delay 0.00 s
Block BLK_DEF On (Virtual Output)
Target Self-reset
Events Enabled

Page 3 of 19
FLEXLOGIC DEF GE D60 :

Di-Assign pada Trip


Outputs/Trip Bus
1 phasa

Di-Assign pada
Contact Outputs
DEF Send

Page 4 of 19
IV. STANDAR SETTING DAN LOGIC DEF RELE SIEMENS 7SA522

SETTING DEF SIEMENS 7SA522 :

No. Settings Value


0238A Earth Fault O/C: setting for 1pole AR stages separetely

Setting Group A - Earth Fault Overcurrent-->General


No. Settings Value
3101 Earth Fault overcurrent function ON
3102 Block E/F for Distance protection with every pickup
3174 Block E/F for Distance Protection Pickup in each zone
3104A Stabilisation Slope with Iphase 10%
3105 3I0-Min thershold for Teleprot. Schemes Sesuai hasil simulasi
3170 2nd harmonic ratio for inrush restraint 15%
3171 Max. Current, overriding inrush restraint 10 x In
3172 Instantaneous mode after SwitchOnToFault with pickup and direction
3173 Trip time delay after SOTF 0.00sec

Setting Group A - Earth Fault Overcurrent-->3I0>>>


No. Settings Value
3110 Operating mode Forward
3111 3I0>>> Pickup Sesuai hasil simulasi
3112 T 310>>> Time delay oo sec
3113 Instantaneous trip via Teleprot./BI YES
3114 Instantaneous trip after SwitchOnToFault NO
3115 Inrush Blocking NO
3116 Block 3I0>>> during 1pole dead time YES
3117 Single pole trip with 3I0>>> YES

3I0>>, 3I0>, 3I0 Def.Time agar diblok


No. Settings Value
3120 Operation Mode Inactive
3130 Operation Mode Inactive
3140 Operation Mode Inactive

Setting Group A - Earth Fault Overcurrent-->Direction


No. Settings Value
3160 Polarization with U0+IY (dual polarized)
3162A ALPHA, lower angle for forward direction 338 deg
3163A BETA, upper angle for forward direction 122 deg
3164 Min. zero seq. voltage 3U0 for polarizing 2.3 V
3166 Min. neg. seq. polarizing voltage 3U2 2.3 V
3167 Min. neg. seq. polarizing current 3I2 0.08 A
3168 Compensation angle PHI comp. for Sr 255 deg
3169 Forward direction power threshold 1.5 VA

Page 5 of 19
3186A 3U0 min for forward direction 2.3 V
3187A Reactance X of series capacitor 0.000 ohm

Setting Group A -Teleprotection for Earth fault overcurr.


No. Settings Value
3201 Teleprotection for Earth Fault O/C ON
3202 Line Configuration Two Terminals
3203A Time for send signal prolongation 0.05 sec
3209A Transient Block.: Duration external flt. 0.04 sec
3210A Transient Block.: Blk. T. after ext. flt. 0.05 sec
3212A EF transient block bay DIS YES

CFC LOGIC DEF SIEMENS 7SA522 DAN MASKING I/O:

NB: Timer pickup delay = 100 ms (T1x1ms)


Timer drop off = 0 ms (T2x1ms)

Di Assign pada
Binary Input (BI)
DEF Signal receive

Di Assign pada
Binary Output (BO)
DEF Signal Send

Di Assign pada
Binary Output (BO)
TRIP DEF A/B/C

Page 6 of 19
V. STANDAR SETTING DAN LOGIC DEF RELE MICOM P442

SETTING DEF MICOM P442 :

GROUP 1 AIDED D.E.F


Aided Ch. Status Enable 39.01
Polarisation Zero sequence 39.02
V> Voltage Set 2.300 V 39.03
IN Forward Sesuai hasil simulasi 39.04
Time Delay 100 ms 39.05
Scheme Logic Permissive 39.06
Triping Any phase 39.07
IN Rev Factor 1.000 39.09
Block. Time Add. 0s 39.0A

PSL LOGIC DEF MICOM P442 :

Page 7 of 19
VI. STANDAR SETTING DAN LOGIC DEF RELE ABB REL670

SETTING DEF ABB REL670 :


CVGAPC:1 (Phasa 1 / L1)
CVGAPC:2 (Phasa 2 / L2)
CVGAPC:3 (Phasa 3 / L3)

CVGAPC:1/2/3

Nilai primer CT
phase1/2/3
Nilai primer VT

Sesuai simulasi

Page 8 of 19
Di Assign dari
CONTACT INPUT
DEF CARRIER
RECEIVE Di Assign pada
CONTACT OUTPUT
DEF CARRIER
SENDING

INPUT 1-16 OUTPUT 1


INPUT 17-32 OUTPUT 2

TMAGGIO:1

INPUT 1-16 OUTPUT 1


INPUT 17-32 OUTPUT 2

TMAGGIO:4

Page 9 of 19
INPUT 1-16 OUTPUT 1

FROM ECPSCH:1 INPUT 17-32 OUTPUT 2

TMAGGIO:2

FROM ECPSCH:1

INPUT 1-16 OUTPUT 1


INPUT 17-32 OUTPUT 2

TMAGGIO:5

Page 10 of 19
INPUT 1-16 OUTPUT 1
INPUT 17-32 OUTPUT 2

TSMPPTRC:1

TMAGGIO:1

INPUT 1-16 OUTPUT 1


INPUT 17-32 OUTPUT 2

Di-Assign Pada
BINARY OUTPUT TRIP
L1/L2/L3

TMAGGIO:2

Page 11 of 19
INPUT 1-16 OUTPUT 1
INPUT 17-32 OUTPUT 2

SMPPTRC:2

TMAGGIO:4

INPUT 1-16 OUTPUT 1


INPUT 17-32 OUTPUT 2

Di-Assign Pada
BINARY OUTPUT TRIP
L1/L2/L3

TMAGGIO:5

Page 12 of 19
STANDAR SETTING DAN LOGIC SOTF MiCOM P443
SETTING SOTF MICOM P443:

GROUP1 SCHEME LOGIC


Trip on Reclose 34.80
SOTF Status Enabled ExtPulse 34.81
SOTF Tripping 000011 34.83
TOR Status Enabled 34.84
TOR Tripping 000011 34.85
TOC Reset Delay 10 s 34.86
SOTF Pulse 10 s 34.87
TOC Delay 200 ms 34.88

Note : SOTF Tripping : Zone 1, Zone 2


TOR Tripping : Zone 1, Zone 2

LOGIC PSL SOTF MICOM P443:

Untuk status CB dari PMT menggunakan kontak NO (Normally Open)

Untuk status CB dari PMT menggunakan kontak NC (Normally Close)

Page 13 of 19
Page 14 of 19
STANDARISASI LOGIC DAN SETTING SOTF DISTANCE RELAY
ABB REL670

Logic trip SOTF menggunakan sinyal :

 Sinyal “CB OPEN” pada inputan BC di fungsi logic ZCVPSOF


 Sinyal “ZM01-START” OR “ ZM02-START” pada inputan ZACC di fungsi logic ZCVPSOF

Jika status PMT menggunakan kontak NC (Normally Close) maka sinyal “CB OPEN” merupakan output
gerbang OR dari binary input status CB OPEN R, CB OPEN S, dan CB OPEN T.

Page 15 of 19
Jika status PMT menggunakan kontak NO (NormallyOpen) Sinyal “CB OPEN” diperoleh dari input status CB
CLOSE R, CB CLOSE S, dan CB CLOSE T B yang di INVERT di logic.

Sinyal “ZM01-START” dan “ZM02-START” diperoleh dari output START pada fungsi logic ZMQPDIS dan
ZMQAPDIS.

Page 16 of 19
Setting Group1 SOTF dibuat sebagai berikut:

RATIO PRIMER CT

RATIO PRIMER PT

Page 17 of 19
 KONDISI PMT OPEN

SOTF aktif 1
3
CB OPEN
2

10 s
Z1 START Merah = 1
OR Hitam = 0
Z2 START tSOTF

CB OPEN

Z1/Z2 START

Saat kondisi CB open, kondisi SOTF akan selalu aktif (sinyal 1 selalu bernilai 1). Jika saat kondisi ini rele
merasakan gangguan Z1/Z2 maka perintah SOTF trip akan dikeluarkan. Pada saat pengujian individu rele
agar digunakan CB dummy (status CB close dibuat permanen) atau menonaktifkan sementara fungsi SOTF.

Page 18 of 19
 KONDISI MANUVER PMT CLOSE DIIKUTI GANGGUAN Z1/Z2

SOTF aktif 1
3
CB OPEN
2

10 s
Z1 START
OR
Merah = 1
Z2 START tSOTF
Hitam = 0

CB OPEN

tSOTF
1
Z1/Z2 START

Saat terjadi perubahan status CB dari OPEN ke CLOSE maka sinyal 1 akan diperpanjang selama tSOTF, ini
membuat fungsi SOTF masih aktif selama waktu tSOTF setelah CB close. Jika selama rentang watktu tSOTF
ini rele distance merasakan gangguan Z1/Z2 maka perintah trip SOTF akan dikeluarkan.

Page 19 of 19