Cable Test Data Form

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

SECTION 16120

CONDUCTORS AND CABLES

CABLE TEST DATA FORM


Project and Location _______________________________ Project No. ____________________
Circuit Description _________________________________ Date _________________________

DC TEST DATA DC Test Voltage_____________________


Time in Minutes Current ȝ A
Cable Installation New____Used___ Years
After 100% Test
Phase Phase Phase
Voltage is Cable Size_______Length________Meter
A B C
applied
Oper. kV____Grd.______ Ungrd._______
1
2 Rated Cable Voltage_________________
3 Insulation Wall______________________
4
5 (Type & Thickness)
6 Conductor Jacket Wall _______________
7
8 (Type & Thickness)
9 Shield_____________________________
10
11 (Type)
12 Cable Manufacturer __________________
13
14 Temperature_____ Humidity___________
15 Type Terminations___________________
KVDC 1 Min.
Decay Type Splice & Location _______________
Remarks & Fault Location _____________
100 Microamperes (ȝA) = Milliamp
APPLICATION OF TEST VOLTAGE
The initially applied direct-current voltage shall be not greater than 3.0 times the rated
alternating current voltage. The rate of increase from the initially applied voltage to the
specified test voltage shall be approximately uniform and shall be not over 100 percent in 10
seconds nor less than 100 per cent in 60 seconds. The Duration of the direct-current voltage
test shall be 15 minutes for shield cables and 5 minutes for non-shield cables.
TEST CURVE
Notes
Current in Microamperes

1. Plot tests on all


three phases on
this graph.
2. Assign and
indicate values for
each division on
the microampere
scales as required
for the circuit
being tested.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Time in Minutes After 100% Test Voltage is applied

END OF SECTION