Professional Documents
Culture Documents
Power Transfer Capability of Long Transmission Lines With Midpoint Sited FACTS and HVDC
Power Transfer Capability of Long Transmission Lines With Midpoint Sited FACTS and HVDC
Authorized licensed use limited to: Velammal Engineering College. Downloaded on July 16,2010 at 05:30:35 UTC from IEEE Xplore. Restrictions apply.
Simplified Model Analysis: As is well known, the power transfer
of a transmission line can be evaluated as:
VS VR
P0 = sin( δ S − δR )
ωlL (1)
Figure 1. Simplified model of the system with FACTS or HVDC
where l and L are the per km series inductance and the length of the line,
(VS , δ S ) and (VR , δR ) are the rms voltages and angles of the sending and
receiving ends of the transmission line. The shunt capacitances are ne-
glected, and the line is assumed to be lossless.
Practically, two transformers should be employed: one at the send-
ing end to boost the generator terminal voltage and the second at the re-
ceiving end to step down the transmission voltage to the load voltage
rating level. Then the leakage reactance of transformer, X T , has to be
taken into consideration. To simplify the analysis, X T is assumed to be
Figure 2. Equivalent- circuit of a long transmission line
identical for these two transformers. Then
VS VR VS
P0 = sin( δ S − δR ) =
ωlL + 2 X T
(2) IS
XT X2
Following the same assumptions, the system with midpoint-sited − sin βL + cosβL j ZC − T sin βL + j 2 X T cosβL
ZC Z C VR
FACTS controllers or HVDC stations can be modeled as in Figure 1,
where the FACTS controllers or HVDC stations are represented as a 1 XT IR
j sin βL − sin βL + cosβL
two-port black box with the terminal voltage V1 and V2 . Z C ZC (6)
Assuming that the FACTS controller or HVDC station to be
lossless, it receives power from the sending end and retransmits the The power transferred through the line is determined by
same power to the receiving end:
P0' = Re( VR I*R )
VS V1 V2VR VS VR
P1 = sin( δ S − δ1 ) = sin( δ2 − δR ). = sin( δ S − δR ).
ωlL / 2 + X T ωlL / 2 + X T ( ZC − X T2 / ZC )sin βL + 2 X T cosβL
(3) (7)
The maximum steady-state stability power is reached at the point when When the line is medium length or shorter,βL is small. One can sim-
the angle difference is 90°. Since the line impedances are halved, the plify (7) the same as (2).
maximum power is doubled when the voltages V1 and V2 are If the FACTS controller or HVDC station is put at the midpoint, the
well-supported. The ratio of these two maximum powers is 2: line is separated as two equal-length stages. Following the same manner,
the FACTS controller or HVDC station can improve power transfer as
P1 , max ωlL + 2 X T
R1 = = = 2. VS V1
P0 , max ωlL / 2 + X T P1' = sin( δ S − δ1 ).
(4) ZC sin(βL / 2 ) + X T cos(βL / 2 ) (8)
Transfer Capability of Long Transmission Line: Distributed pa- Still, the maximum steady-state limits happen when the sine func-
rameters are often used to model a long transmission line [4], e.g., the tion reaches its maximum, 1, for (7) and (8). The ratio of these two lim-
telegraph model. Its π-equivalent circuit can be obtained as shown in its is not always 2, but the following:
Figure 2. The transformers are also modeled by XT at the two ends.
Using the lossless assumption, the π-equivalent parameters are P1', max ( ZC − X T2 / ZC )sin βL + 2 X T cosβL
given by R2 = = .
P0', max ZC sin(βL / 2 ) + X T cos(βL / 2 ) (9)
sin βL tan(βL / 2 )
ZL = jωlL , YL = jωcL . Effect of Converter Transformers: Sometimes the converter
βL βL / 2 transformer has to be employed to reduce the high voltage rating of the
(5)
long transmission line to meet the requirement of the power electronics
where β = ω lc and c is the per km shunt capacitance. equipment. One example is shown in Figure 3 with VSC-HVDC.
Defining ZC = l / c , the voltages and currents of the two ends are As shown in (7), including the converter transformer reactance
determined by the telegraph equation: X T , con , the power equation can be deduced as
Authorized licensed use limited to: Velammal Engineering College. Downloaded on July 16,2010 at 05:30:35 UTC from IEEE Xplore. Restrictions apply.
VS V1 that the improvement in power transmissibility with respect to the
P1' ' = sin( δ S − δ1 ),
( ZC − X T2 / ZC )sin(βL / 2 ) + 2 X T cos(βL / 2 ) (10) steady-state stability limit is by a factor of 2. This improvement comes
from the voltage support capability of the VSC family of FACTS con-
which assumes X T , con = X T for the simplifying reason. At trollers or HVDC stations. This paper shows that the improvement is
δ S − δ1 = 90 °, the ratio is calculated again as only by a factor of 1.59.
The decrement is accounted for by better modeling: telegraph equa-
P1',' max ( ZC − X T2 / ZC )sin βL + 2 X T cosβL tion to represent transmission (18%), leakage impedances of converter
R3 = '
= . transformers accounted for (12%), and line resistances.
P 0 , max ( ZC − X T2 / ZC )sin(βL / 2 ) + 2 X T cos(βL / 2 ) (11) References:
[1] E.W. Kimbark, “How to improve system stability without risk-
Digital Simulation Test: The digital simulation test is conducted ing subsynchronous resonance,” IEEE Trans. Power App. Syst., vol.
by a real-time simulator, HYPERSIM [5], which gives detailed models PAS-96, no. 5, pp. 1608-1619, Sep./Oct. 1977.
of turbine generator, speed governor, exciter, transmission line, trans- [2] B.T. Ooi, M. Kazerani, Z. Wolanski, F.D. Galiana, D. McGillis,
former, etc. and G. Joos, “Midpoint siting of FACTS devices in transmission lines,”
The test system is shown in Figure 3, where a VSC-HVDC, which IEEE Trans. Power Delivery, vol. 12, no. 4, pp. 1717-1722, Oct. 1997.
consists of two voltage source converters serving as power dispatcher [3] Z. Huang, B.T. Ooi, L.-A. Dessaint, and F.D. Galiana, “Ex-
(PD) and dc voltage regulator (VR), respectively [3], is sited at the mid- ploiting voltage support of voltage source HVDC,” in Proc. 2002 IEEE
point of a long transmission line. The line parameters are r = 0.0147 PES Winter Meeting, New York, NY, 2002.
Ω/km, l = 0.0009 H/km, and c = 1.308 ×10 −8 F/km. The leakage [4] J. Machowski, J.W. Bialek, and J.R. Bumby, Power System Dy-
reactance is X T = 7.93Ω for all the transformers. namics and Stability. New York: Wiley, 1997.
Figure 4 and Table 1 give the results of theoretical calculation and [5] Power System Simulator - HYPERSIM: User’s Manual,
digital simulation. P0, test and P1, test are obtained by the numerical fitting DMNU-5700-1.3A, TEQSIM International Inc., Jun. 1999.
of the simulation results. Copyright Statement: ISSN 0282-1724/02/$17.00 2002 IEEE.
From Figure 4 and Table 1, it is shown that the simplified model is Manuscript received 1 September 2001, revised 15 November 2001.
not accurate enough to evaluate the transfer capability of a long trans- This paper is published herein in its entirety.
mission line, thus the telegraph model should be used so as not to
over-estimate the contribution of FACTS controllers or HVDC stations.
Because the line shunt capacitances generate considerable reactive
power to support voltage, the telegraph model gives more power than
that analyzed by the simplified model, whereas the ratio of 2 is reduced Cigré 2002 General Session
by 18%. The longer the line, the more reduction will be expected,
shown by (9).
25-30 August 2002, Paris, France
The converter transformers, when applicable, will reduce the bene- The Cigré 2002 General Session will be held 25-30
fit from the FACTS controllers or HVDC stations, by 12% in this case. August 2002 in Paris, France. For more information,
The discrepancy between the theoretical calculation and the digital refer to the Cigré Web site, http://www.cigre.org.
simulation can be attributed to the line resistance, which was included
The preferential subjects proposed by study com-
in the digital simulation model but not in the analysis.
Conclusion: This paper re-evaluated the benefit of FACTS control- mittees and selected by the technical committee for
lers and HVDC stations that are sited at the midpoint of long transmis- the session reflect the dual objective of Cigré: to capi-
sion lines. Previously, using the simplified model, it has been claimed talize on technical knowledge thus making it available
to the largest number, and to meet the expectations of
members facing a constantly changing world in the
areas of technology, environment, finance, and the
opening of markets. Preferential subjects may be
found on the Web, http://www.cigre.org/GB/
2002/fs2002session.htm.
As technical knowledge can no longer progress in-
dependently of knowledge in other areas, in most of
Figure 3. AC system with midpoint sited VSC-HVDC the preferential subjects proposed all or several areas
of knowledge are associated. Also, a growing number
of topics reflect concerns common to several techni-
cal areas which in the present organization of Cigré
are handled separately. Joint sessions, workshops
and panels increase in number at every Session, and
are a way to meet the need to share knowledge and
experience beyond the borders existing at present be-
tween the various technical fields.
In this light, the Administrative Council of Cigré has
asked the technical committee recently to propose
evolutions in the organization of the technical activi-
ties and in the format of the Paris Sessions. The 2002
session will be a turning point as it will be the last to
be based on the present organization yet at the same
time introducing in form and content the future orga-
nization.
Authorized licensed use limited to: Velammal Engineering College. Downloaded on July 16,2010 at 05:30:35 UTC from IEEE Xplore. Restrictions apply.