The design of underground water tank is carried out as per IS 3370 part 1 and part 2 code. The design is
by assuming no water table and uncracked design.
b/a 1.73333
Vertical moment
1 x/a -ve moment 6.743 t-m
1/2 x/a +ve moment 1.458 t-m
Horizontal moment
1/2 x/a -ve moment 4.192 t-m
1/2 x/a +ve moment 1.458 t-m
P= 4.500
2.25 1.500
4.5 t/m2
D=(T/2tb)+ (T/2tb)2+(6M/σbt*b)
D=(T/2tb)+ (T/2tb)2+(6M/σbt*b)
Provide D= 50 Cm
d 45 Cm
j 0.8
Ast= (M/σst J d)
Vertical reinf.
Ast 14.41 cm2
Ast 1440.87 mm2
Provide 16mm @100 mm c/c 2010 mm2 Hence Safe
Horizontal Reinf.
D 50 mm
M 6.743 t-m
T 6.525 t-m
e= M/T 1.03345 m
The bottom is considered as resting on ground and hence the water pressure counteracts the upward
soil pressure. The bottom slab is designed as grade slab for Min steel as per IS 3370 assuming depth as
500 mm and reinforcement is provided for D/2 depth as per the surface zone concept of 3370 for
grounded slabs.
DESIGN CHECK OF MINIMUM REINFORCEMENTS FOR UNDERGROUND WATER TANK
As per IS 3370 Min steel required for a cross section is 0.35 %