Professional Documents
Culture Documents
Thermal Tuning System For PEFP DTL Resonant Frequency Control
Thermal Tuning System For PEFP DTL Resonant Frequency Control
19521960
Hyeok Jung Kwon, Han Sung Kim and Yong Sub Cho
PEFP, Korea Atomic Energy Research Institute, Deajeon 305-353
1. Design Concept
liquid lines was installed at the downstream of centrifu- system while maintaining the size and the
ow balance
gal pump because the pump NPSH (net positive suction of the water pumping skid [11]. It is comprised of
ow
head) requirements would not be met for the case of high paths that are joined at each node with major compo-
pressure drop in a closed loop and it used only one con- nents of pump, heat exchanger, heater, control valve and
trol valve in each liquid loop. Finally, a PID temperature DTL structures.
controller with nonlinear gain (via gain scheduling) was The results of the network model including pipe siz-
designed using mid-ranging control to avoid saturation ing,
ow rate, velocity and pressure drop are summarized
limits and nonlinear valve characteristics. A fast PID in Table 2. The volume for the selection of the expan-
controller is designed for the hot-side control valve (CV1) sion/reservoir tank means the inner volume of the piping
while the slower controller is designed for the combined leg in each section. From the calculation results for the
dynamics of the cold-side control valve (CV2) and the heater line, the values of velocity and the pressure drop
heat exchanger to elongate the time constant. Figure 3 were rather high and were highly dependent on the pipe
shows a simplied
ow diagram of the water pumping size. Therefore, the heater by-pass valve is always open
skid. more than 50 %. We also calculated the heat load,
ow
rate, design volume of the tank and pressure drop for
DTL21 to DTL107, for the radio frequency quadrupole
2. Numerical Network Model
(RFQ) and medium energy beam transfer (MEBT). The
calculation predicts that dierent types of water pump-
ing skids are needed depending on the
ow rate and the
As shown in Figure 4, a numerical network model has pressure drop requirements.
been used to calculate the pressure drop,
ow rate, ve-
locity and thermal dynamics in the DTL water cooling
-1956- Journal of the Korean Physical Society, Vol. 54, No. 5, May 2009
Table 2. Calculated results of the network modeling for DTL21.
Description Pipe Length Volume Flow Rate Velocity P
Size [m] [m3 ] [m3 /hr] [m/sec] [kg/cm2 ]
1 Pump 65A 54 4.01
2 Pump Discharge 80A 2 0.01 54 2.98 0.20
3 3-Way CV1 80A 54 2.98 0.62
4 By-pass 80A 2 0.01
5 PHE inlet 80A 1 0.005 54 2.98 0.01
6 PHE 65A 54 2.98 0.49
7 PHE Out 80A 1 0.005 54 2.98 0.01
8 Heater 40A 54 11.9 0.45
9 Mixed Out 80A 5 0.026 54 2.98 0.20
10 Skid Out 80A 25 0.129 54 2.98 0.24
11 DTL In 80A 25 0.129 54 2.98 0.24
12 DTL Manifold 80A 8.86 0.046 54 2.98 0.65
13 DTL Out 80A 25 0.129 54 2.98 0.24
14 Skid In 80A 25 0.129 54 2.98 0.24
15 Pump Suction 80A 6 0.031 54 2.98 0.39
16 LCW/Tank line 25A 6
Total 128.86 0.648
The fabricated prototype water pumping skid is shown to remove the dissipated heat. The cold side of the heat
in Figure 5. A horizontal multi-stage water pump, with exchanger is cooled with chilled service water at a
ow
a total
ow rate of 54 m3 /hr and discharge pressure of rate of 13.5 m3 /hr and at 10 C. The valves,
anges and
5 kg/cm2 , was installed to supply the
ow to the DTL other components were installed to match the pressure
structure. The inline electrical heater of the closed-loop drop requirements. The low-conductivity water system
needs to warm up the system in order to achieve an with by-pass of about 1 5 % of the total
ow rate is
initial operating condition downstream of the hot-side composed of 5 m lters, carbon lter, ultraviolet lamp
mixed loop. The expansion tank was lled with N2 gas and 1 m lter. The dimension of the water pumping
to control the pressure in the closed-loop. A counter- skid is about 2.0 2.8 2.0 m3 . The pipe size of the
ow-type compact plate heat exchanger was assembled primary loop and that of the secondary loop are 80 and
Thermal Tuning System for PEFP DTL Resonant Frequency Control { Kyung Ryul Kim et al. -1957-
Fig. 6. DTL water supply temperature behavior during no load performance test.
Fig. 7. Pressure balancing with valve opening through the heat exchanger loop.
50 , being made of the STS 316 pipe, respectively. The to supply cooled water at ambient temperature (about
supporting structures and the electrical wiring have been 15 C) to the heat exchanger and hot-side control valve
constructed considering space allowance, as well as main- was controlled by manual adjustment. In parallel with
tenance and replacement of equipment in the pumping the load performance test, the control valve position de-
skid. pendence of the pressure variations was checked, as indi-
cated in Figure 7. As a result, we estimated that water
temperature was well regulated with the installed water
pumping skid. Especially, the
ows through the heat
IV. PERFORMANCE TEST RESULTS exchanger loop and the by-passing leg increased linearly
with the control valve position in the 20 80 % range.
The prototype water pumping skid has been connected Therefore, the 3-way control valve for the primary loop
to the DTL21 structure. Figure 6 displays temperature was identied as being stable in the designed opening
variation with changing control valve position. The cold- ranges. However, this test cannot identify the charac-
side centrifugal pump with a 1.5-kW power was operated ter of the temperature control due to the absence of the
-1958- Journal of the Korean Physical Society, Vol. 54, No. 5, May 2009
Fig. 11. Dependence of the transient response of frequency shift on the inlet temperature variation.
Furthermore, we assume that the signal sent from GP I 1 mid-ranging control of the cooling water temperatures.
to GP I 2 is the unsaturated signal U1 . Especially, the temperature behaviors of the step-up and
Figures 9 and 10 show the step response features for step-down set points are stabilized with the primary con-
-1960- Journal of the Korean Physical Society, Vol. 54, No. 5, May 2009
trol valve opening position of 50 %. The secondary con- ogy, Republic of Korea.
trol valve opening position was regulated to control the
ow rate. As indicated in Figure 11, the transient re-
sponse of the frequency shift variation was in less than
1 kHz for 20 % to 65 % of the hot side
ow rate in the REFERENCES
heat exchanger loop during a 65 % cold-side
ow rate.
been simulated and tested with 20-MeV DTL systems. [4] H. S. Kim, H. J. Kwon, K. T. Seol and Y. S. Cho, J.
As a result, the hydraulic and the thermal performances
Korean Phys. Soc. , 756 (2008).
52
[5] H. J. Kwon, H. S. Kim, J. H. Jang and Y. S. Cho, J.
have been estimated with the designed values of the tem- Korean Phys. Soc. , 1450 (2007).
perature range of 27 6 C with a precision of less then
50
[6] H. S. Kim, H. J. Kwon, K. T. Seol, Y. G. Song, I. S. Hong
0.1 C. Finally, the temperature control around the and Y. S. Cho, J. Korean Phys. Soc. , 1431 (2007).
50
operating point was achieved with two independent PI [7] K. R. Kim, H. G. Kim, H. S. Kim, S. J. Kwon, J. C.
controllers installed in each loop. A mid-ranging or valve Yoon, W. H. Hwang and J. Park, Proceedings of Particle
position control algorithm was adopted to reject the dis- Accelerator Conference 2007 (Albuquerque, NM, 2007),
turbances quicker and to settle down the set point with p. 2176.
fewer oscillations. The simulation results indicate that [8] H. Y. Kim, H. J. Kwon and Y. S. Cho, Nuclear In-
mid-ranging control largely improves the performance struments and Methods in Physics Research A , 671
569