TCD
Revision History
Rev. Prepared Checked Approved
Date Revision Contents
No. by by by
Nov. Harold
0 Release YS Kim DH Kim
2007 Lee
Deletion of TCD 57,72,73
Addition of TCD 209
Apr. Harold
1 Change of TCD 240 YS Kim DH Kim
2009 Lee
Application of New PCB – DOC141 &
DHG162, etc
Part TCD
Solon LD Ctrl. No. Solon_LD-TS-03-1
Index
b. Word definition
a) Operation CPU: It designates Main CPU (i186/i960)
b) Speed CPU: It designates INV DSP CPU
c) Error Operation Flag: It decides an elevator operation condition according to this
number that is Control Flag.
Number
Functional Classification Operation condition in case of Trouble
Classification
1 ~ 15 System Error
16 ~ 29 Inverter Interface Error
30 ~ 69 Inverter / Converter Error It is defined by Error Operation Flag of
70 ~ 149 Device Error each TCD
150 ~ 199 Control Error
200 ~ 239 Network Error
240 RUSSIA_OPZX error
Part TCD
Solon LD Ctrl. No. Solon_LD-TS-03-1
Detection
TCD Definition Description Hold Grade
OPER. SPD.
1
2
3
4
Operation CPU S/W WDT trouble
5 ERR_SW_WDT ● R1
occurred
6 ERR_MEM_ALLOC Memory allocation failed ● R1
7 ERR_TASK_CREATE Task making failed ● R1
8 ERR_SEM_CREATE Semaphore making failed ● R1
9 ERR_WDT_CREATE Operation CPU WDT Timer making failed ● R1
10 ERR_INT Non definitional vector Interrupt occurred ● XX
11
12
13
14
15
16 ERR_INV Speed CPU H/W WDT trouble occurred ● R1
17 ERR_INV_RETRY Speed CPU Retry failure ● ● R1
18
19
20
21 ERR_INV_DPRAM Speed CPU DPRAM WRITE trouble ● ● R1
22
23
24
25
26~
29
30 ERR_INV_OC INV over current (H/W detection) ● ● R1
31 ERR_DC_OV DC Link over voltage ● ● R1
32 ERR_INV_U_SHORT INV phase U IGBT trouble ● ● R1
33 ERR_INV_V_SHORT INV phase V IGBT trouble ● ● R1
34 ERR_INV_W_SHORT INV phase W IGBT trouble ● ● R1
35 ERR_INV_TR Regenerative IGBT trouble ● ● R1
36 ERR_INV_H_CT INV Hall CT trouble ● ● R1
ERR_INV_U_STACK_TH
37 INV over heat ● R4
ERMAL
38 ER_Lotor_Lock_ERR LRT operation error ● ● R1
39
40
41 ERR_INV_C_CNTL INV current control trouble ● R1
42
Part TCD
Solon LD Ctrl. No. Solon_LD-TS-03-1
Detection
TCD Definition Description Hold Grade
OPER. SPD.
43
44
45
46
47
48 ERR_INV_DC_LINK_UV DC link under voltage ● R2
49
50
51
ERR_INV_REVERSE_RU
52 INV reverse rotation detection ● R1
N
53 ERR_INV_CHARGE INV charging trouble ● C R1
54 ERR_INV_OVER_LOAD INV over load detection ● R1
55 ERR_INV_LOW_SPEED INV under speed detection ● R2
56 ERR_INV_HIGH_SPEED INV over speed detection ● R3
Brake over current detection (N/A, Si210
57 ER_INV_BRAKE_OC ● R2
only)
Brake malfunction detection (N/A, Si210
58 ER_INV_BRAKE_CNTL ● R2
only)
59 ERR_INV_ANTISTALL INV. No operable for 24 sec. ● R2
60 ERR_INV_SPEC INV Spec Data trouble ● ● R1
61 ERR_INV_SPEC_COM INV Spec write trouble ● R1
62 ERR_INV_V48 INV momentary power failure detection ● R1
63
64
65
66
67
68
69 ERR_V100 Missed phase detection (100V) ● R3
70 ERR_POWER 48V power trouble (missing phase) ● R1
71 ERR_V48 Voltage drop detection (80% below) ● R4
72 ER_C1SW_ON C1SW On error_(N/A for Solon LD) ● ● R1
73 ER_C1SW_OFF C1SW Off error_(N/A for Solon LD) ● ● R1
74 ERR_SPEC_OVER Operation SPEC DATA trouble ● RO
75
76 ERR_EEPROM_WRITE EEPROM Write trouble ● R3
77 ERR_EEPROM_READ EEPROM Read trouble ● ● R1
ERR_EEPROM_FHT_SU EEPROM floor height measuring Table
78 ● R3
M Sum trouble
NVRAM floor height measuring Table
79 ERR_NVRAM_FHT_SUM ● R3
Sum trouble
80
81
82
Part TCD
Solon LD Ctrl. No. Solon_LD-TS-03-1
Detection
TCD Definition Description Hold Grade
OPER. SPD.
83 SafetyChain_Error_detect Safety line fault ● ● R1
84 ERR_R5SC_ON R5SC RELAY ON trouble ● ● R1
85 ERR_R5SC_OFF R5SC RELAY OFF trouble ● R1
86 ERR_C1BR_ON C1BR CTT. ON error ● ● R1
87 ERR_C1BR_OFF C1BR CTT. OFF trouble ● ● R1
88 ERR_C1ST_ON C1ST CTT. ON trouble ● ● R1
89 ERR_C1ST_OFF C1ST CTT. OFF trouble ● ● R1
90 ERR_SUPPRESS_ON SUPPRESS ON trouble ● ● R1
91 ERR_SUPPRESS_OFF SUPPRESS OFF trouble ● ● R1
92 ERR_ENCO R.E disconnected ● ● R1
93 ERR_ENCO_READ R.E pulse counter read trouble ● ● R1
94 ERR_ENCO_COUNTER R.E pulse counter trouble ● ● R1
ERR_MECHANICAL_
95 R5SX OFF trouble (Safety line) ● R1
SAFETY
96 ERR_ABNORMAL_MODE Operation mode input trouble ● R4
97 ERR_CDS, CDS trouble ● R2
98 ERR_LDS LDS trouble ● R2
99 ERR_DUP_IN Dual input signal trouble ● ● R1
100 ERR_SDS1D_ON SD1D ON trouble ● R3
101 ERR_SDS2D_ON SD2D ON trouble ● R3
102
103
104
105
106
107 ERR_SDS1U_ON SD1U ON trouble ● R3
108 ERR_SDS2U_ON SD2U ON trouble ● R3
109
110
111
112
113
114 ERR_POSI(0) PRS (POSI) ON trouble (LDC) ● ● R2
115
116 ERR_LDU PRS (POSI) ON trouble (LDU) ● XX
117 ERR_LDD PRS (POSI) ON trouble (LDD) ● XX
118
119 ERR_SDS SLOW DOWN S/W trouble ● R6
120
121 ● ● R1
122 ER_DES_PARA_ERR DES parameter error ● R1
123 ER_REGE_R_THER Regenerative resister over heat
124
Part TCD
Solon LD Ctrl. No. Solon_LD-TS-03-1
Detection
TCD Definition Description Hold Grade
OPER. SPD.
125 ERR_BRAKE_OFF BRAKE open trouble ● ● R3
126 ERR_MAIN_INV_SPEED Speed different between operation / speed ● ● R3
127 ERR_HALL_TEMP_ERR DES PCB overheat
128
129 ER_MOTOR_THER Motor Thermal ● ● R5
130 ERR_WEIGHT_SENSOR Load detector input trouble ● R3
131 ER_SLACK_ROLL_ERR Slack rope breakdown ● ● R3
132 ERR_OPEN_LOCK Door Open Lock detection ● XX
133 ERR_OPEN_LOCK_3 OPEN_LOCK repeated trouble ● R2
134 ERR_CLOSE_LOCK Door Close Lock detection ● XX
ERR_CLOSE_LOCK_
135 Door Close Lock repeated trouble ● R3
REPEAT
136 ERR_ARD ARD trouble ● ● R1
137
138
139 ERR_NUDGING Nudging trouble ● R7
Discharging voltage of Backup Battery
140 ERR_NVRAM_BATTERY ● XX
under reference
141 ERR_RTC Clock Chip trouble ● XX
142
143
144
145 ERR_INV_DM INV. Door CPU WDT trouble ● R6
ERR_COOLER_FLOAT_S
146 Air-conditioner Float S/W trouble ● XX
W
147 ERR_OBS OBS detection ● ● R1
148
149
150 ERR_SDS1D_OS SD1D Over Speed detection ● R3
151 ERR_SDS2D_OS SD2D Over Speed detection ● R3
152
153
154
155
156
157 ERR_SDS1U_OS SD1U Over Speed detection ● R3
158 ERR_SDS2U_OS SD2U Over Speed detection ● R3
159
160
161
162
163
164 ERR_E_STOP Emergency stop detection ● R3
165
166
Part TCD
Solon LD Ctrl. No. Solon_LD-TS-03-1
Detection
TCD Definition Description Hold Grade
OPER. SPD.
167
ERR_SPEED_DEVIATIO
168 Speed difference (real speed detection) ● ● R3
N
169
170 ERR_DIRECTION Operation direction trouble ● ● R1
Synchronous position trouble when LDC is
171 ERR_DIGI_FLOOR ● R3
activated
172
173
174
175
176
177 ERR_REPEAT Emergency stop occurred frequently ● ● R4
178 ERR_S_DRIVE_REPEAT Safety drive occurred frequently ● ● R5
179
180
181
182 ERR_OVER_DUTY Operation duty trouble ● XX
183
SDS forced deceleration occurred
184 ERR_SDS_FORCE_DEC ● ● R3
frequently
185
186
187
188 ERR_OLS OLS trouble ● R3
189
190 ERR_DECEL_ZONE PRS (POSI) trouble for 2 deceleration ● XX
191 ERR_DOOR_COMMAND Open/Close simultaneous command ● XX
192 ERR_DOOR_POSI Door position trouble ● R6
193 ERR_DOOR_VOLTAGE Door voltage trouble ● R6
ERR_DOOR_MOTOR_TH
194 Door motor over heat ● R6
ERMAL
195 ERR_DOOR_OC Door current trouble ● R6
196 ERR_PHOTO_SHOE Photo-Shoe input error ● XX
197
198
ERR_PCB_PROTECTION
199 PCB protection failed ● XX
_FAIL
200 ERR_CNET_SYNC CNET LON communication trouble ● R4
201
202 ERR_CNET_COM Car communication trouble ● R4
203
204
Part TCD
Solon LD Ctrl. No. Solon_LD-TS-03-1
Detection
TCD Definition Description Hold Grade
OPER. SPD.
205 ER_DES_COMM DES PCB communication. error ● R4
206 ER_REAR_OPB_Comm DCL Board error in REAR OPB R4
207
208
209 R_NPLEX_MASTER_COM N-plex communication error_ ● XX
210
211 ERR_OTHER_MAIN_1 Other elevator trouble ● XX
212
213
214
215
216
217 ERR_HALL_BT_JAM Hall button jam detection ● XX
218
219
220
221
222
223 ERR_1_HALL Hall nod trouble ( More than 1) ● XX
224 ERR_ALL_HALL Hall nod trouble (All) ● XX
225
226
227
228
229
230
231
232
233 ER_ESMI ESMI communication trouble ● XX
234 ER Motor Adj Fail Motor Adjust fail
235 ER_Rope_Brake_Activated Rope Brake error(N/A for MRL)
~
236 ER_TCI_LOCK TOCI LOCK Error ● R4
237 ERR_CRT CRT communication trouble ● XX
238 ER_DES_ERR DES PCB or its Input data Error ● XX
239
240 ERR_RUSSIA_OPZX Landing Door Open (Russia only) ● ● R1
[Meaning] [Condition]
Checks Task errors.
1. SYS1 LED(green) on DOC-141 lights up or off
(Normal if it flickers)
2. When a Watchdog error occurs
- it is transferred to 74HC4538 chip and recognized by speed
[Explanation]
control section
Tasks are monitored within the software(S/W) regularly. - running control program registers a S/W watchdog error in the
If a task has errors three successive times, S/W Watchdog error occurs. table and reset running control program automatically.
MRL elevator operation control program is composed of 12 tasks. These tasks are
inspected for their any possible errors as shown below.(Initial Error_Counter value
is set to 0(Zero)).
[Countermeasures]
- This error has no relation to the outside connection.
- Check the voltage(5V) on output of SMPS,
If not, replace SMPS.
Task에 error in
Error occurs 발생task? - If the same error continues to happen, replace DOC-141.
Yes
No
Error_Counter를
Increase 1
1 증가시킨다.
Error_Counter
Error_Counter == 3
Yes
시스템에서
Create 사용할
memory pool
메모리for풀(pool)
system생성
Memory
메모리 pool
풀(pool) 생성
실패failed
creating ? ?
No
Yes
Memory
메모리 assigning
풀(pool)에서 for task &
타스크(Task)나
인터럽트 interrupt handlerhandler),
핸들러(Interrupt &
큐(Queue)queue
등에서 in pool.메모리 할당
사용할
No
Memory assigning
메모리 할당 실패 ?
failed ?
프로그램 다음
Perform 단계
Next Yes
stage수행
of P/G
Memory assigning
메모리 할당 Error 발생
error generated?
시스템에서
Create 사용할
memory pool
메모리for풀(pool)
system생성
Task
타스크creating
생성 혹은or
No interrupt
인터럽트 registering
등록 실패 ?
failed?
Yes
프로그램 다음
Perform 단계
next
stage수행
of P/G
Task creating error
타스크 생성 Error 발생
generated
엘리베이터 운전 제어
Initialize elevator 프로그램
operation
시스템
control 초기화
P/G system
Semaphore
Create 생성
semaphore
Semaphore creating
No Semaphore 생성 실패 ?
failed?
Yes
Perform next stage of
프로그램 다음 단계 수행
P/G
Semaphore생성
Semaphore creating
Error
error
Watchdog Timer not only carries out tasks periodically just as several
other tasks do, but also supervises all other tasks. So its period is the
shortest (30m sec) and it has top priority.
Create memory
시스템에서 사용할pool
메모리 풀(pool) 생성
for system
Create
Watchdogwatchdog
Timer 생성
timer
Yes
Watchdog timer
Watchdog Timer
생성 실패
creating ?
failed?
Watchdog
Watchdog timer
Timer 생성 No
creatingError
error발생generated
Assign
메모리 memory타스크(Task)나
풀(pool)에서 for task &
인터럽트interrupt handler
핸들러(Interrupt in
handler)에서
사용할 메모리
memory pool할당
Task
타스크creating
생성 혹은or
No interrupt
인터럽트 등록 실패 ?
registering
Yes
Perform
프로그램 다음next
단계
수행
stage of P/G
Task creating
타스크 생성 Error 발생
error generated
[Reference]
The number of interrupt vector can be checked by ‘A42E’.
(Trace information)
Part ; TCD Code
Solon LD / Trouble Shooting Crtl No.: Solon_LD-TS-03-1
Page: 17/127
○ Operation CPU
TCD 16 Speed CPU H/W WDT trouble occurred Detection Application Si231
○ Speed CPU
[Detection] In case that H/W Watchdog error of DSP maintain over 3 cycle of
detection(Min. 60~ Max. 90ms), detect the trouble and output
the signal of DSP reset.
This trouble can not be detective in case of over 48 volts.
(Voltage drop/ failure)
Part ; TCD Code
Solon LD / Trouble Shooting Crtl No.: Solon_LD-TS-03-1
Page: 18/127
○ Operation CPU
TCD 17 Speed CPU Retry failure Detection Application Si231
○ Speed CPU
[Meaning] DSP H/W Watchdog has been detective and DSP can not be operable [Countermeasures]
even if operation CPU perform retry of DSP more than 4 times.
- Check if the communication connector(64P) between
DOC-141 and DPC-140 is connected well, If connector is
abnormal, replace.
[Explanation] If retry signal of operation CPU keeps up more than 4 times, - Check the voltage(5V) on output of SMPS,
the error is detected and make the elevator being inoperable. If no, replace SMPS.
- Twist the cables of the communication connector(64P)
- Check if ground condition is correct.
- Check if JUMP PIN setting is correct.
- Replace DPC-140.
[Meaning] When communicating DPRAM between operation side & speed side, [Countermeasures]
a error detected if transmitted data is different with feed back data for
- Check if the communication connector(64P) between
4 cycles(120ms) in series.
DOC-141 and DPC-140 is connected well, If connector is
abnormal, replace.
[Explanation] 1. When transmitting data by DPRAM, feed back data - Check the voltage(5V) on output of SMPS,
If no, replace SMPS.
Transmitted data Feed back data - Twist the cables of the communication connector(64P)
- Check if ground condition is correct.
Coil[RS_SUPPRESS_ON]: 0x91C3 Coil[SV_INV_SUPPRESS_FB]: 0x9208 - Replace DOC-141
- Replace DPC-140.
SWD_O[VO_C1ST]: 0x8081 Coil[SV_INV_C1ST_FB]: 0x920A
[Meaning] When current in the electric motor exceeds limit value(If over current [Countermeasures]
occurs,stop switching in order to prevent damages on motor and 1. Check VB connector on DPC-140 PCB.
inverter devices).
2. Verify that HCT cable is properly connected to U and V of HCT.
3. Check a proper connection HCT direction (Normal if HCT ‘arrow’
[Explanation] points downwards).
4. Verify that voltage of HCT connectors are +15V and -15V.
INV U-V-W stack
5. Check J5H jumper on DPC-140 and number of HCT turns, on the
basis of the below table.
HCT
U HCT Position of J5H
V IPM Capacity Motor Name plate
W
+15V TURNS jumper pin
R10 R9 R11 R12
J5H 75A ↓ 4 1-2 4.5~7.5kW
1 2
3 4 R78
100A 4 3-4 9.5~11kW
+5V
150A 4 1-2 13~15kW
R18
10
- 13 OCT
VB - 03
11 + U6HD U4GA
VB - 07
R44 C88
6. Check the earth condition and connection at building
DPC-140 7. Check if ground conditions of building & E&I panel are good.
8. Check followings:
- Resistance R9, 10, 11, 12 and 78 (marked on the left diagram) are properly
To DPC-1XX VB connector
fitted.(R9: 10K, R10: 1.5K, R11: 5K, R12: 12K, R78: 1M)
HCT
HCT 커넥터
- When a short pin is inserted into 3-4 on J5H, the potential of pin 10 on U6H
1 2 3 4 5 6
connector
+15V -15V IAS GND IBS GND is 8.89 ±0.44V.
1 6
HCT 9. Check the R_ENCODER wiring (Refer to TCD 92)
A B
10. Replace HCT & its cable.
HCT
HCT의 ‘arrow’
방향이 should
아래로
11. Replace DPC-140 PCB.
U-phase point 향해야 정상임
downwards
U상 V상
V-phase
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 21/127
○ Operation CPU
TCD 31 DC Link Over voltage Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
When DC link voltage is 770V or more is detected (Stop switching to prevent condenser, IPM
1. Check if the voltage of DC link is 770V±60V.
and IGBT from damages).
2. Check if reference voltage is within 7.9 ±0.5V
Check point (DPP-140,150 : TE40, TE100)
[Diagram]
The gap of regenerative voltage and over voltage must be within
Over voltage
과전압 detection
검출회로 circuit 0.25~0.36V in case of DPP 150 or 140)
3. If item 2, 3 are OK, check the connection between INV STACK
VDC(+)
GW - 03 DPP-150 & DPP-150, replace DPP-150.
15V (GDC) 정상시 LOW(0V)
Normal if Low(0V)
VDC(-)
이상시 HIGH(15V)
Abnormal if High(15V)
4. Check if regenerative IGBT operates normally. (Refer to TCD35:
GP - 09 D23
OV
In case of regenerative IGBT trouble, this error may be occurred.
R101 R36
R31
R102 R37
15V
C10D29 PC7 D30
6. Check if input power of E&I panel is correct.
VG - 13
R103 R38 -9V R47 7. If TCD 31 is detected while the car is not running, check followings:
R30 DPC-140
4
R104 R39
- 2 R21 C5 (INV) - VG connector on DPC-140.
5 VG - 14
+
LED1 R98 C4 IC1 - VA, GA connector on DPP-150.
8. After power off, check regenerative resistors is OK.
-9V
(Before this job, the voltage of DC link is 0V)
[Countermeasures]
[Meaning] Motor capacity 15kW below : In case that U phase of upper or lower 1. In case of DPP-150, check if the condition of GU, GV, GW & GX pin
IGBT in IPM are switching on together or regenerative IGBT in IPM connector are OK, and the connection between IPM and INV. Stack.
is short failure, the trouble occurs. 2. In case of DPP-150, check if the condition of GU, GV, GW & GX pin
connector are OK, and the connection between IPM and INV. Stack.
3. After separating of DPP-150 PCB and IPM, check output of gate
SMPS
(GU-01,02: 15V, GV-01,02: 15V, GW-01,02: 15V, GX-01,02: 15V,
GX-03,02: -9V)
4. Check if the condition of HCT cable and HCT is OK.
5. Check the direction of HCT
[Explanation]
Motor 15kW below: - Normal if HCT ‘arrow’ points to the bottom of CP
S-IPM is used that R IGBT is
mounted at inside. - Check wiring directions and refer to INV. over current.
6. Check for proper connections of the followings:
CONVERTER - VB connector to DPC-140 PCB
DIODE Reactor is applied
S-IPM in case of 15kW
and above
- U-phase HCT signal wire to VB-03
- V-phase HCT signal wire to VB-07.
3Φ 380V
HCT 7. Turn the power ON and check the followings:
U
V - Power condition of DPP-150 PCB
W
IM
- Voltage of GATE terminal
8. If TCD 32 is detected while the car is not running, check followings:
- VG connector on DPC-140.
- GA connector on DPP-150.
9. If the voltage of pin 6 of RA1(coordinates: 8I) on DPC-140 is +15V,
examine the connection between pin 21 on DPC-140 VG connector,
GP - 01
GP - 03
1Φ 110V
GU - 01
GU - 02 and pin 21 on DPP-150 GA connector.
VB - 07
VB - 03
GV - 01
GATE GV - 02
It is normal if they are connected.
GW - 01
SMPS GW - 02 DPP-150 DPC-140
10. Replace DPP-150 PCB.
GX - 01 (GDC) VA VG (INV)
GX - 02
GX - 03 11. Replace DPC-140 PCB.
(In case of IPM 150A ↓, 12. Replace S-IPM
DPP-150 is used.)
In case of S-IPM,
Use GATE SMPS
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 23/127
[Countermeasures]
[Meaning] Motor capacity 15kW below : In case that V phase of upper or lower 1. In case of DPP-150, check if the condition of GU, GV, GW & GX pin
IGBT in IPM are switching on together or regenerative IGBT in IPM connector are OK, and the connection between IPM and INV. Stack.
is short failure, the trouble occurs. 2. In case of DPP-150, check if the condition of GU, GV, GW & GX pin
connector are OK, and the connection between IPM and INV. Stack.
3. After separating of DPP-150 PCB and IPM, check output of gate
SMPS
(GU-01,02: 15V, GV-01,02: 15V, GW-01,02: 15V, GX-01,02: 15V,
GX-03,02: -9V)
[Explanation] 4. Check if the condition of HCT cable and HCT is OK.
5. Check the direction of HCT
Motor 15kW below: - Normal if HCT ‘arrow’ points to the bottom of CP
S-IPM is used that R IGBT is
mounted at inside. - Check wiring directions and refer to INV. over current.
6. Check for proper connections of the followings:
CONVERTER - VB connector to DPC-140 PCB
DIODE Reactor is applied
S-IPM in case of 15kW
and above
- U-phase HCT signal wire to VB-03
- V-phase HCT signal wire to VB-07.
3Φ 380V
HCT 7. Turn the power ON and check the followings:
U
V - Power condition of DPP-150 PCB
W
IM
- Voltage of GATE terminal
8. If TCD 33 is detected while the car is not running, check followings:
- VG connector on DPC-140.
- GA connector on DPP-150.
9. If the voltage of pin 6 of RA1(coordinates: 8I) on DPC-140 is +15V,
examine the connection between pin 21 on DPC-140 VG connector,
GP - 01
GP - 03
1Φ 110V
GU - 01
GU - 02 and pin 21 on DPP-150 GA connector.
VB - 07
VB - 03
GV - 01
GATE GV - 02
It is normal if they are connected.
GW - 01
SMPS GW - 02 DPP-150 DPC-140
10. Replace DPP-150 PCB.
GX - 01 (GDC) VA VG (INV)
GX - 02
GX - 03 11. Replace DPC-140 PCB.
(In case of IPM 150A ↓, 12. Replace IPM
DPP-150 is used.)
In case of S-IPM,
Use GATE SMPS
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 24/127
[Countermeasures]
[Meaning] Motor capacity 15kW below : In case that W phase of upper or lower 1. In case of DPP-150, check if the condition of GU, GV, GW & GX pin
IGBT in IPM are switching on together or regenerative IGBT in IPM connector are OK, and the connection between IPM and INV. Stack.
is short failure, the trouble occurs. 2. In case of DPP-150, check if the condition of GU, GV, GW & GX pin
connector are OK, and the connection between IPM and INV. Stack.
3. After separating of DPP-150 PCB and IPM, check output of gate
SMPS
(GU-01,02: 15V, GV-01,02: 15V, GW-01,02: 15V, GX-01,02: 15V,
GX-03,02: -9V)
[Explanation] 4. Check if the condition of HCT cable and HCT is OK.
5. Check the direction of HCT
Motor 15kW below: - Normal if HCT ‘arrow’ points to the bottom of CP
S-IPM is used that R IGBT is
mounted at inside. - Check wiring directions and refer to INV. over current.
6. Check for proper connections of the followings:
CONVERTER - VB connector to DPC-140 PCB
DIODE Reactor is applied
S-IPM in case of 15kW
and above
- U-phase HCT signal wire to VB-03
- V-phase HCT signal wire to VB-07.
3Φ 380V
HCT 7. Turn the power ON and check the followings:
U
V - Power condition of DPP-150 PCB
W
IM
- Voltage of GATE terminal
8. If TCD 34 is detected while the car is not running, check followings:
- VG connector on DPC-140.
- GA connector on DPP-150.
9. If the voltage of pin 6 of RA1(coordinates: 8I) on DPC-140 is +15V,
examine the connection between pin 21 on DPC-140 VG connector,
GP - 01
GP - 03
1Φ 110V
GU - 01
GU - 02 and pin 21 on DPP-150 GA connector.
VB - 07
VB - 03
GV - 01
GATE GV - 02
It is normal if they are connected.
GW - 01
SMPS GW - 02 DPP-150 DPC-140
10. Replace DPP-150 PCB.
GX - 01 (GDC) VA VG (INV)
GX - 02
GX - 03 11. Replace DPC-140 PCB.
(In case of IPM 150A ↓, 12. Replace IPM
DPP-150 is used.)
In case of S-IPM,
Use GATE SMPS
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 25/127
○ Operation CPU
TCD 35 Regenerative IGBT trouble Detection Application Si231
○ Speed CPU
VB - 07
VB - 03
단상
AC 110V
110V
GATE
DPP-150 VA VG
TRANS DPC-140
(GDC)
GXL - 09 (In case of IPM 100A) (INV)
GXL - 17
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 26/127
○ Operation CPU
TCD 36 Inverter Hall CT trouble Detection Application Si231
○ Speed CPU
[Meaning] When current controlling HCT and VB connector on DPC-140 PCB [Countermeasures]
are not connected.
1. Examine VB connector and cable on DPC-140 PCB
(Connector checking jumper should be connected as in the left diagram)
[Diagram] 2. Examine connector and cable of HCT.
2. If TCD 36 is detected, while the connector is tightly inserted,
replace VB connector cable.
[Meaning] When the thermal switch on radiating plate activates in order to prevent [Countermeasures]
IPM from being damaged by overheating. ( 85 ℃ or more, b contact)
1. Examine the followings:
- GP and GX connectors on DPP-150
[Diagram] - SC, GA connector on DPP-150 and VG connector on DPC-140
- 6,7 of GP connector
INV. STACK
Detect circuit for Overheating - Check for a proper connection between TH Pin 1, Pin 2 on DPP-13X
Normal LOW(0V)
THERMAL GUARD DIODE Abnormal HIGH(15V)
CONV. and terminal ends of thermal guard.
THERMAL1
[Meaning] Stop the lift under unfavorable condition of LRT operation [Countermeasures]
1. TCD will be detected when the motor turning is detected. 4. Check the BS1 and BS2 input line
[Meaning] When a current command, which is over the rated motor [Countermeasures]
current, is detected due to failure in the motor, unstable input power
supply & drop of voltage.
1. Examine the number of turns of HCT
This is detected when the current command value is over 150% of the rated motor current,
while the motor are running at the rated speed, going through starting and acceleration zone.
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 30/127
○ Operation CPU
TCD 48 DC Link Under Voltage Detection Application Si231
○ Speed CPU
GP - 09
VDC(-)
D23
(1: +15V, 2: -9V, 4: GND)
R62
R101 R36
4. If the voltage of pin 3 of RA1(Coordinates 8I) on DPC-140 is +15V,
R63
R102 R37
15V
C13 D36 PC9 D37
then, examine the connection between pin 15 on DPC-140 VG
VG - 15
-9V R49
connector and pin 15 or DPP-150 GA connector.
R103 R38
R35 DPC-140
9 (Normal if they are connected)
R104 R39 + 14 R23 C9 (INV)
8 VG - 16
- 5. This indicates that the voltage has not charged.
LED1 R98 C4 IC1
Check regenerative IGBT ON failure and MAIN IGBT ON failure.
-9V 6. Check the condenser and replace it, if necessary.
7. Replace DPP-150 PCB and DPC-140 PCB.
8. Check RCR resistor and wiring.
9. Check input power.
VDC(+) VDC(-)
PCB
Connector Connector 10. In case that the trouble occurs in the beginning of acceleration,
DPP-150 GP-01 GP-02 check if the door switches is off.
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 31/127
○ Operation CPU
TCD 52 Inverter Reverse Rotation Detection Detection Application Si231
○ Speed CPU
[Meaning] When the actual direction of the motor is opposite to the command. [Countermeasures]
1. Check the connection between the encoder fitted to the motor shaft
and the E&I panel.
[Explanation]
2. Examine that U and V-phase on the STACK pass through those of the
This TCD shall be detected when the actual running direction of the motor is opposite to the HCT in order.
command at a speed of 16 m/min. or more after starting. The detection is carried out at the 3. Check the number of turns of HCT (Refer to the INV over current table)
interval of 10m SEC only on the running of the motor. 4. Check for proper connections of the followings:
- U, V and W-phase INV STACK wires to motor terminals in order
- VG connector on DPC-140 and VA, GA connector on DPP-150
- GU, GV, GW & GX connectors on DPP-150 PCB and IPM
5. Replace DPC-140 PCB
6. Replace DPP-150 PCB
7. Check if the positioning of traction machine is reverse or normal
8. Check if the cable of Rotary Encoder is disconnected (TCD 92)
9. Check the condition of Rotary Encoder wiring
10. Replace HCT.
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 32/127
○ Operation CPU
TCD 53 Inverter Charging Trouble Detection Application Si231
○ Speed CPU
[Meaning] When a failure occurs in the charging circuit which protects the [Countermeasures]
condensers and power devices by damping surge current on a initial
charging of DC link end. 1. Refer to DC LINK under voltage trouble.
2. Check for the connection status of the followings:
[Diagram] - VC connector on DPC-140 and GW and GP connector on DPP-150
C1VD
Option - Wiring of VC connector on DPC-140 PCB (C1VD)
DIODE
RCRR CONVERTER
MCCB
- Wiring of RCRR, RCRS and RCRT resistor
3Φ380V
RCRS
3. Turn the power OFF and check short-circuited DC-link ends.
NOISE (The examination should be carried out after the voltage at DC link has
FILTER RCRT
been completely discharged and LED1 on DPP-150 PCB extinguishes.)
GW - 03
GP - 09
4. Replace DPP-150 PCB
VC - 01
DPC-140 DPP-150
VG VA
VC - 02 (INV) (GDC) 5. Replace DPC-140 PCB
In case C1VD is not applied: DC link voltage will be charged through RCRR, RCRS within 3
seconds after power on, and 8 seconds later, DC link voltage will be inspected whether the
voltage is under 330V or not.
And TCD53 will be appeared even if the voltage is still under 330V after inspecting DC link
voltage 8 seconds later.
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 33/127
○ Operation CPU
TCD 54 Inverter Overload Detection Detection Application Si231
○ Speed CPU
[Meaning] When the current detected on motor exceeds general motor capacity [Countermeasures]
continuously.
1. Check the No. of HCT TURN (Refer to INV over current table)
2. Verify that SPEC such as motor capacity, E&I panel capacity, etc..
[Diagram] are correct.
3. Check VB connector on DPC-140 PCB and HCT connection
4. Verify that there’s no jam in car and CWT rail
2
5. Replace E PROM in DPC-140
DPC-140
6. Replace DPC-140
(INV) 7. Replace HCT
8. Check if the positioning of traction machine is reverse or normal
U - Phase Currency
U상전류
LOW Overload 9. Check if the cable of Rotary Encoder is disconnected
V - Phase Currency A/D - Detected
V상전류 A/D변환 PASS + 과부하 검출
CONVERSION (Refer to TCD 92)
FILTER -
W - Phase Currency
W상전류
150% of Rated
전동기 정격전류
Motor Current
의 150%
This error is detected when the motor’s U, V, and W-phase values that have been radio-
rectified, converted into A/D values, and then gone through LOW PASS FILTER exceed
150% of rated
motor current. Error is detected when the rated value is exceeded for over 1 second.
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 34/127
○ Operation CPU
TCD 55 Inverter Under Speed Detection Detection Application Si231
○ Speed CPU
[Meaning] When actual motor speed does not reach the value commanded. [Countermeasures]
1. Check the connection between E&I panel and the Rotary Encoder
fixed to motor shaft.
2. Verify that U and V-phase on inverter stack side are passing through U
[Explanation] Detection starts 100msec after motor start-up. An error is detected and V-phase of HALL-CT respectively.
when motor speed is detected to be below 4m/min for 100 m/sec while 3. Check the No. of HALL-CT turn (Refer to INV over current table)
speed command value is 6 m/min or more.
4. Check the connection sequence of U, V, and W-phase from inverter
stack to motor terminal.
5. Check the connection between VG connector in DPC-140 PCB and
VA & GA connector of DPP-150.
6. Check the connection between IPM and GU, GV, and GW connector
in DPP-150.
7. Verify that inverter stack IPM(U-phase+, U-phase-, V-phase+, V-
phase-, W-phase+, W-phase-) turn ON and OFF normally and U, V,
and W-phase currents are sine waves with 120 phase difference.
(Verify that U, V, and W-phase currency are sine waves without
deformation by measuring check pin(CHK) 3, 4, and 5 on DPC-140
with scope)
If any error is found, replace the stack.
8. Replace DOC-141 PCB.
9. Replace DPC-140 PCB.
10. Replace DPP-150 PCB.
11. Replace HCT
12. Check if the positioning of traction machine is reverse or normal.
13. Check if the cable of Rotary Encoder is disconnected.
(Refer to TCD 92)
14. Check if the electric power goes to motor terminal.
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 35/127
○ Operation CPU
TCD 56 Inverter Over speed Detection Detection Application Si231
○ Speed CPU
[Meaning] When the actual number of rotations of motor is higher than the normal [Countermeasures]
abnormally.
1. Check the connection between the encoder fitted to the motor shaft
and the E&I panel.
2. Examine that U and V-phase on the STACK pass through those of the
[Explanation]
HCT in order.
This error is detected when the motor’s turn number detected exceeds 16 m/min 3. Check the number of turns of HCT(Refer to the INV over current table).
and, in case of high speed operation, is over 110% of the rated speed. In case of 4. Check for proper connections of the followings:
slow speed, the error is detected when the number is over 120% of the commanded - U, V and W-phase INV STACK wires to motor terminals in order
value for speed.
- VG connector on DPC-140 and VA, GA connector on DPP-150
- GU, GV & GW connectors on DPP-150 PCB and IPM
5. Check the following
- IPM on INV STACK turns ON/OFF normally. (U-phase+, U-phase-,
V-phase+, V-phase-, W-phase+ and W-phase-) and U, V and W-
phase currents are sine waves with 120 degree phase difference.
(When measuring check pin 3, 4 and 5 with a oscilloscope, examine
that U, V and W-phase currents are sine waves without any distortion)
If abnormal, STACK needs replacing.
6. Replace DOC-141 PCB.
7. Replace DPC-140 PCB.
8. Replace DPP-150 PCB.
9. Replace Rotary Encoder and check the line.
10. Replace Hall CT.
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 36/127
○ Operation CPU
TCD 59 ER_INV_ANTI_STALL Detection Application Si231
○ Speed CPU
[Meaning] There is a trouble of Inverter SPEC DATA 3) Check the machine code
• Unable to start
• Alarm LED on DOC-141 lights ON.
• R5SC relay or contactor OFF <Step 2>
Push the STOP switch in E&I panel,
locate J1J jumper to 3-4 and J1G jumper to 1-2 in DPC-140,
and input A52E in DOA-100.
[Countermeasures] When the SUCCESS is displayed following WAIT message
<Step 1> after a while,
Check if the data of Spec address 0100~0110 are correct or not return STOP switch to OFF position,
1) Check the IGBT capacity that is accord to motor capacity
<Step 3>
Motor IGBT Motor IGBT If TCD 60 appears still after the actions taken at step 1, verify
3.7KW 50A 8.1KW 75A that IPM,
motor, speed and TR M/C are fit to the applicable map in the
4.6KW 75A 11KW 100A right. If any errors
6.2KW 75A 7.1KW 75A are found, input a correct data in the corresponding SPEC
address.
6.5KW 75A 12.5KW 150A If SPEC is not corrected, start again after verifying that J1J
jumper to 3-4
2) Check the R.E type
in DPC-140.
Encoder pulse count
72 512 1024 3600 8192
01H 02H 03H 04H 05H
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 38/127
○ Operation CPU
TCD 61 Inverter Spec Write trouble Detection Application Si231
○ Speed CPU
[Meaning] When a momentary power failure is detected in DSP on DPC-140 PCB. [Countermeasures]
[Meaning] When the failure of DC20V or the under voltage of Brake PCB is detected. [Countermeasures]
Coil[SW_SS_ Coil[SW_SS_48V_
20V_DOWN] DOWN_HOLD] v20_err_count >=1
TCD 69
0x923C 0x9240
+1 v20_err_cout
ERD_Inv_Brake_UV
Part: : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 41/127
○ Operation CPU
TCD 70 24V Power Trouble Detection Application Si231
○ Speed CPU
[Meaning] This is the method that detects any possible lost phase of E/L three-phase [Countermeasures]
input power.
1) Check the 24V fuse and LED(1,2) in E&I Panel
2) Check the 24V fuse (FS1,FS2), And replace with new
[Explanation] If IALM(red) LED and P.F(red) LED lights up on DOC-141, one(250V/75A)
operation will be unable.
3) Verify that the voltage between DI-01 pin in DOC-141 PCB
and GND is 24Vdc± 10% .
48Vac_Down_Count >5 TCD 70
4) Check the voltage of DOJ-130 PCB ( PS1&3,3&5) it should be
each 19Vac ± 10%
Left picture below show DC48V at a normal power and the right picture shows wave
form when a phase was lost.
Lost phase detecting circuit in DOC-141 lights ARM LED when it detects a wave
form which falls down 35V or less. If it detects such wave for 300msec, it makes
Error 70.
[ Wave form & voltage on normal ] [ Wave form & voltage on abnormal ]
[Meaning] When input power(3 phases) drops to its 85% or below, [Countermeasures]
the trouble occurs.
1. There is no special countermeasure.
Check the power source from the building.
2. Refer to countermeasures of TCD70.
[Explanation] In case 85% of voltage drop continues for 90 msec, the trouble is
detected.
It is detected by the voltage(DC48V) rectified from AC37V that is
3 phases power for control.
+1 under_85p_count
Part: : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 43/127
○ Operation CPU
TCD 72 ER_C1SW_ON Detection Application Si231
○ Speed CPU
[Meaning] C1SW ON condition lasts for over 540ms after C1SW OFF [Countermeasures]
commanded.
1. Check the C1SW wiring according to drawing.
2. Refer to countermeasures of TCD88.
3. Replace C1SW contactor.
[Explanation]
Coil[SW_SS_48V_
SWD_I[VI_C1SW] SWD_O[VO_C1ST] DOWN_HOLD] Check_out
Coil[SV_INV_
SWD_I[VI_C1SW] SWD_O[VO_C1ST] 0x923D
SW_FAIL]
Coil[SW_SS_
0x8066 0x8081 0x9210 DSP_WD]
Check_out
TMC_Start(C1SW__
ERROR_DETECT_T)
TMC_Check(C1SW_ERROR SWD_I[V1_C1SW]
_DETECT_T,FINISH_STATE) TCD 72
0x802A
Part: : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 44/127
○ Operation CPU
TCD 73 ER_C1SW_OFF Detection Application Si231
○ Speed CPU
[Meaning] C1SW OFF condition lasts for over 540ms after C1SW ON [Countermeasures]
commanded.
1. Check the C1SW wiring according to drawing.
2. Refer to countermeasures of TCD89.
3. Replace C1SW contactor.
[Explanation]
Coil[SW_SS_48V_
SWD_I[VI_C1SW] SWD_O[VO_C1ST] DOWN_HOLD] Check_out
Coil[SV_INV_
SWD_I[VI_C1SW] SWD_O[VO_C1ST] 0x923D
SW_FAIL]
Coil[SW_SS_
0x8066 0x8081 0x9210 DSP_WD]
Check_out
TMC_Start(C1SW__
ERROR_DETECT_T)
TMC_Check(C1SW_ERROR SWD_I[V1_C1SW]
_DETECT_T,FINISH_STATE) TCD 89
0x802A
If data of each BIT is 1, the SPEC DATA of set BIT is the reason of the trouble.
15 14 13 12 11 10 9 8
Service Shelter
- - - - - -
floor plate
7 6 5 4 3 2 1 0
H.CT Rotary
IGBT Motor - Speed TM Gear
TURN Encoder
Part: : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 46/127
○ Operation CPU
TCD 76 EEPROM Write Trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
When different values are found over 100 times while writing data on
EEPROM and reading data from the same address.
1. Verify if SW2 switch in DOC-141 is switched to “WE” side.
2. Verify if EEPROM is properly inserted into DOC-141.
[Explanation] This error means that the SPEC DATA is not written properly due to
3. Check EEPROM.
fault
( 28C64-xxPC: xx should be below 15 )
4. Replace SPEC ROM.
Part: : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 47/127
○ Operation CPU
TCD 77 EEPROM Read Trouble Detection Application Si231
○ Speed CPU
[Meaning] Different data are found over 4 consecutive times while reading data [Countermeasures]
from the same address on EEPROM. 1. Check EEPROM.
( 28C64-xxPC: xx should be below 15)
2. Verify that EEPROM is properly inserted into DOC-141
[Explanation] If there is any different data over 4 times consecutively as same
address data is read. The error is detected BOARD.
3. Replace SPEC ROM.
Part: : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 48/127
○ Operation CPU
TCD 78 Floor Height measuring Table SUM trouble Detection Application Si231
○ Speed CPU
[Symptom]
* How to measure floor height
1. Low speed return operation to the lowest level with buzzer ringing and display 1) Press ‘A12E’ on ANN, and press 3.
ACD = 09.
2) If the floor height is measured successfully, press ‘FFFF’.
2. In case there is no Non-Stop floor, operate the nearest floor.
3. Stop and standby with ACD = 09. 3) If the measuring fails, measure the floor height again.
4) If the measuring fails repeatedly, verify if the total floor number
and the highest floor in EEPROM(28C64) are identical with
those in the field.
Part: : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 49/127
○ Operation CPU
TCD 79 NVRAM Floor Height measuring Table SUM trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
NVRAM floor height table error
If even one of three cases below occurs, this error will occur.
1. When the sum obtained by adding each floor height table value saved in
NVRAM(Backup RAM) and the floor height sum data saved in
RAM(Backup RAM) does not match.
2. When the floor height sum data in NVRAM is 0(Zero).
3. When the floor height of the lowest floor of floor height table in NVRAM is
not the lowest floor height(150000).
[Symptom]
1. Low speed return operation to the lowest level with buzzer ringing and display
ACD = 0B.
[Meaning] In case DOX-100 PCB is not applied to CP, it detects a fault as checking [Countermeasures]
from mechanical switches to pit switch.
1. Verify that DIP SW2 of SPEC2 is off position.
2. Key in A21E on annunciator to check the data of address 8005
(Normal : 01).
[Explanation]
3. Key in A21E on annunciator to check the data of address 82C1
it detects a fault if any mechanical switch on hoistway and safety signal (Normal : 01).
is ‘OFF’ condition. If data is ’00’, check the E stop switch on OPB.
4. Check the voltage at each connector. (Be careful of 110V)
GRS(01~02), LSU(01~02, FLS), LSD(01~02,FLS),
Y1(01,11,12,02), HSAF(04,05,07), GRS(09)
It must be 110Vac ±10%
5. Replace DOC-141 PCB, DCL PCB.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 51/127
○ Operation CPU
TCD 84 R5SY Relay ON trouble Detection Application Si231
○ Speed CPU
[Meaning] R5SY ON condition lasts for over 540ms after R5SC OFF command signal. [Countermeasures]
check_out
TMC_Start(R5SC_
ERROR_DETECT_T)
TMC_Check(R5SC_ERROR_
DETECT_T, FINISH_STATE) SWD_I[VI_R5SC]
TCD 84
0x8001
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 52/127
○ Operation CPU
TCD 85 R5SY Relay off trouble Detection Application Si231
○ Speed CPU
[Meaning] R5SY OFF condition lasts for over 540ms after R5SC ON command signal [Countermeasures]
1. 1. Verify the power supply for DOC-141 PCB.
Di-01 : 24Vdc
Di-11 : 24Vdc
[Explanation] PWR01: 5Vdc
check_out
TMC_Start(R5SC_
ERROR_DETECT_T)
TMC_Check(R5SC_ERROR_
DETECT_T, FINISH_STATE) SWD_I[VI_R5SC]
TCD 85
0x8001
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 53/127
○ Operation CPU
TCD 86 C1BR CTT. on trouble Detection Application Si231
○ Speed CPU
[Meaning] Even after 1200ms away from C1BR off command, C1BR on is [Countermeasures]
maintained.
P24
0x8080 0x9210
1. Check voltage of DI-03 of DOC-141 from above circuit.
0x8029 Coil[SW_SS_DSP_WD]
• When C1BR driving section is ON : DC 24 V
check_out
• When C1BR driving section is OFF : 0 V
TMC_Start(R5SC_
ERROR_DETECT_T) 2. Check the state of input state indicating row(row 3)
TMC_Check(C1BR_ERROR_ column 10 on LCD of DOA-100.
DETECT_T, FINISH_STATE) SWD_I[VI_C1BR]
TCD 86
• When C1BR driving section is ON : 1
0x8029 • When C1BR driving section is OFF : 0
3. Check BS1,BS2 switch by input buffer reading(A21E)
and Voltage measurement
• Even after 540ms away from OFF command of C1BR output, C1BR contact
does not turns OFF, and C1BR contact point input is ON is detected(driving
section ON failure).
• Even with C1BR contact off, C1BR contact point input on is detected, because
of contact point not being off(contact point melted and adhered).
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 54/127
○ Operation CPU
TCD 87 C1BR CTT. OFF trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
Even after 540ms away from C1ST off command, C1ST on is maintained.
P24
• Even after 540ms away from OFF command of C1ST output, C1ST contact
does not become OFF, and C1ST contact point input is ON is detected.
• Even with C1ST contact off, C1ST contact point input on is detected, because
of contact point not being off.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 56/127
○ Operation CPU
TCD 89 C1ST CTT. OFF trouble Detection Application Si231
○ Speed CPU
[Meaning] Even after 540ms away from C1ST on command, C1ST off is maintained. [Countermeasures]
P24
[Meaning] Even after 360ms away from driving OFF command from operation side [Countermeasures]
to speed side,ON feedback is maintained.
1. Check flickering condition of WDT LED(green) of DPC-140.
2. Check connection condition of communication cable(64P)
[Explanation] between operation and speed.
Coil[SV_INV_
Coil[RS_SUPPRESS_ON] RUN_STOP_FB] SWD_I[VI_C1ST] 3. Check flickering condition of SYS2 LED(green) of DOC-141.
0x91C3 0x9207
0x802A
Coil[SV_INV_
Coil[RS_SUPPRESS_ON] RUN_STOP_FB]
0x9207
0x91C3
check_out
TMC_Start(SUPRS_
ON_OFF_DETECT_T)
TMC_Check(SUPRS_ON_OFF_
DETECT_T, FINISH_STATE) Coil[RS_SUPPRESS_ON]
TCD 90
0x91C3
Even suppress OFF command of operation control side is maintained for 360ms,
the suppress command which is a feedback from speed control side does not
become OFF, and maintain continuously ON.
[Symptom]
[Meaning] Even after 360ms away from driving ON command from operation side [Countermeasures]
to speed side,OFF feedback is maintained.
•1. Check flickering condition of WDT LED(green) of DPC-140.
•2. Check connection condition of communication cable(64P)
[Explanation] between operation and speed.
Coil[SV_INV_ • Check flickering condition of SYS2 LED(green) of DOC-141.
Coil[RS_SUPPRESS_ON] RUN_STOP_FB] SWD_I[VI_C1ST]
0x91C3 0x9207
0x48082
Coil[SV_INV_
Coil[RS_SUPPRESS_ON] RUN_STOP_FB]
0x91C3 0x9207
check_out
TMC_Start(SUPRS_
ON_OFF_DETECT_T)
TMC_Check(SUPRS_ON_OFF_
DETECT_T, FINISH_STATE) Coil[RS_SUPPRESS_ON]
TCD 91
0x91C3
[Explanation]
ALM LED (Red color) on DOC-141 is turned on: Operation unable condition
With speed command is more than 1m/min and C1ST & C1BR is on [Countermeasures]
1. In rope compensation operation, if the pulse of R/E doesn’t change for 4.86 seconds,
the trouble occurs.
1. Check the voltage of AD connector on DOC-141 PCB
2. In other operation (not rope compensation), if the pulse of R/E doesn’t change for
1.62 seconds, the trouble occurs.
When E/L stops running
No.1 pin : 15V±5%(R.E)
Coil[RS_RUNNING] SWD_O[VO_C1BR] SWD_I[VI_C1BR] SWD_I[VI_C1ST] No.2 pin : 0V±0.5 (GND)
No.3 pin : 15V±5% or 0V±0.5
0x91C3 0x9207 0x9207 0x48082 No.4 pin : 15V±5% or 0V±0.5
When E/L is running
SWD_O[VO_C1ST] Coil[IS_CMD_V_1] No.1 pin : 15V±5%(R.E)
check_out
No.2 pin : 0V±0.5 (GND)
0x91C3 0x91C3 No.3 pin : 7.5V±5%(Checked by DMM)
check_out enco_diff == 0
No.4 pin : 7.5V±5%(Checked by DMM)
TMC_Start(ENCODER_
DISCON_DETECT_T 2. Replace Rotary Encoder.
TMC_Check(ENCODER_DISCON_ Coil[RS_ROPE_
DETECT_T,FINISH_STATE) COMPEN_REQUEST]
enco_input_er_cnt++
0x8081
TCD 92
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 60/127
○ Operation CPU
TCD 93 R.E pulse counter read trouble Detection Application Si231
○ Speed CPU
[Meaning] The difference is more than 1mm in reading the value of R.E twice. [Symptom]
[Explanation]
In case the difference that is more than 1mm in reading the value of R.E twice, occurs
more than 10 times, TCD is detected.
[Countermeasures]
[Meaning] In case that the case of changed value between R.E counter value read [Countermeasures]
in current cycle and in the previous cycle exceeds 3 times, and
1. Check SPEC data from address 0100H ~ 0112H of control
this exceeded value is continued for 150ms, the trouble is detected.
SPEC.
2. Check if R.E is out of function. (Refer to TCD 92)
[Explanation]
[Meaning] [Countermeasures]
Off detected from hoist way and safety circuit.
1. Verify that DIP SW2 of SPEC2 is ON position.
2. Key in A21E on annunciator to check the data of address 806D
(Normal : 01).
[Explanation]
3. Key in A21E on annunciator to check the data of address 806E
If the mechanical safety signa(99GA, 99BG)l in hoistway is OFF, (Normal : 01).
it detects an error. If data is ’00’, check the E stop switch on OPB.
4. Check the voltage at each connector. (Be careful of 110V)
GRS(01~02), LSU(01~02, FLS), LSD(01~02,FLS),
Y1(01,11,12,02), HSAF(04,05,07), GRS(09)
[Meaning] [Countermeasures]
In case of ERO(E&I Panel) switch signal and ON_CAR TOCI switch
signal having input concurrent time, or no signal of operation being
inputted at the same time. 1. Enter A21E in DOA-100 KEYPAD, and check data of
address 8064,82AD and 82AF for each electric diagram.
[Explanation] 2. Only one from above 3 input ports should be recognized as
“H”.
TMC_Check(POWER_
READY_T,FINISH_STATE) TCD 200 TCD 202
check_out 4. If there are two or more “H”, check the connection and
voltage of each phase.
0x82AE
0x82AD
CND_F_Op[CN_ON_CAR]
0x82AF
CND_F_Op[CN_IN_CAR] CND_F_Op[CN_ON_CAR]
0x82AE 0x82AF
input_err
990 msec
TMC_Start(OP_MODE_
ERROR_DETECT_T)
empty_err
3060 msec
TMC_Start(MODE_INPUT_
ERROR_DETECT_T)
TMC_Check(OP_MODE_ERROR_
DETECT_T, FINISH_STATE) TCD 96
TMC_Check(MODE_INPUT_ERROR_
DETECT_T, FINISH_STATE)
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 64/127
○ Operation CPU
TCD 97 CDS trouble Detection Application Si231
○ Speed CPU
[Meaning] When CDS is inputted after DOLS operation, the trouble is detected. [Countermeasures]
SWD_O
[VO_R2OP] SWD_I[VI_LDS]
check_out
0x8083 0x802C
SWD_I[VI_DOLS] SWD_I[VI_CDS]
0x802D
TMC_Check(R2CD_R2LD_ 0x802B
ERROR_DETECT_T,RUN_STATE)
check_out
990 msec TMC_Start(R2CD_R2LD_
ERROR_DETECT_T)
TMC_Check(R2CD_R2LD_
ERROR_DETECT_T,
FINISH_STATE) Coil[DC_DOLS] SWD_I[VI_CDS] TCD 97
0x90A6 0x802B
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 65/127
○ Operation CPU
TCD 98 LDS trouble Detection Application Si231
○ Speed CPU
[Meaning] When LDS is inputted after DOLS operation, the trouble is detected. [Countermeasures]
SWD_O
[VO_R2OP] SWD_I[VI_LDS]
check_out
0x8083 0x802C
SWD_I[VI_DOLS] SWD_I[VI_CDS]
0x802D
TMC_Check(R2CD_R2LD_ 0x802B
ERROR_DETECT_T,RUN_STATE)
check_out
990 msec TMC_Start(R2CD_R2LD_
ERROR_DETECT_T)
TMC_Check(R2CD_R2LD_
ERROR_DETECT_T,
FINISH_STATE) Coil[DC_DOLS] SWD_I[VI_LDS] TCD 98
0x90A6 0x802C
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 66/127
○ Operation CPU
TCD 99 Dual input signal trouble Detection Application Si231
○ Speed CPU
[Meaning] Different contact states of the same inputs between operation CPU and [Countermeasures]
speed CPU exceeds for 300ms. 1. Check trace data of TCD 99 by means of ‘A42E’ trace mode.
2. The meaning of each bit is as left table, in case that ‘1’ is set
at one of bit, meaning of the bit is the reason of trouble.
[Explanation]
err_count ++
b7 b6 b5 b4 b3 b2 b1 b0
[Meaning] [Countermeasures]
SD1D does not operate from bottom floor.
1. Check the value of address 8023 from MEMORY READ
MODE, when car is at top floor. If it is x00, it is normal. If it is x01,
check voltage of LSD-05, LSD-06 and DI-12. They must have
[Explanation] DC 24V.(DC24V is normal)
if not, check wiring and connection.
It is detected when SD1D input does not enter when car is in bottom floor.
2. Check the value of address 8023 from MEMORY READ
TCD 77 TCD 78 TCD 114 ERD_Digi_Fl_Err MODE when car is in bottom floor. If it is x01, it is normal. If it is
x00, check voltage of LSD-06 and DI-12, and They must have
DC 0V.
Coil[SV_ Coil[SW_SS_48V_ Coil[AC_OP_ Coil[AC_OP_FHM_
FORCE_DECEL] DOWN_HOLD] FHM_MODE] START_MODE] 3. Check if SD1 switches works normally.
0x921D 0x923C 0x9031 0x9032
4. Check assembly condition of SD1D
Coil[SW_GS_
OPEN_ZONE] Coil[AC_OP_MAINT_MODE] SWD_I[VI_LDC]
check_out
0x9256 0x9030 0x8025
Coil[IS_ZERO_V]
0x91F2
FTD_Current_Fl ==
check_out SPD_Floor_Spec.Bottom SWD_I[VI_SD1D]
TCD 100
0x8023
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 68/127
○ Operation CPU
TCD 101 SD2D ON trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
SD2D does not operate from bottom floor.
1. Check the value of address 8024 from MEMORY READ
MODE, when car is at top floor. If it is x00, it is normal. If it is x01,
check voltage of LSD-07, LSD-08 and DI-14. They must have
[Explanation] DC 24V.
DC24V is abnormal, check wiring and connection.
Detected only when the rated speed is 90m/min or more.
Detected when SD2D input does not enter when car is on the bottom floor. 2. Check the value of address 8024 from MEMORY READ
MODE when car is in bottom floor. If it is x00, it is normal. If it is
x01, check voltage of LSD-08 and DI-14, and They must have
TCD 77 ERD_Digi_Fl_Err
DC 0V.
TCD 78 TCD 114
Coil[SW_GS_
OPEN_ZONE] Coil[AC_OP_MAINT_MODE] SWD_I[VI_LDC]
check_out
0x9256 0x9030 0x8025
Coil[IS_ZERO_V]
0x91F2
FTD_Current_Fl ==
check_out SPD_Floor_Spec.Bottom SWD_I[VI_SD2D] TCD 101
SPD_Control_Spec. 0x8024
Contract_Velocity >= 90
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 69/127
○ Operation CPU
TCD 107 SD1U ON trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
SD1U does not operate from bottom floor.
1. Check the value of address 8021 from MEMORY READ MODE,
when car is at bottom floor. If it is x00, it is normal. If it is x01,
check voltage of LSU-05, LSU-06 and DO-10. They must have
[Explanation] DC24V.(DC24V is abnormal) check wiring and connection.
It is detected when SD1U input does not enter when car is in top floor. 2. Check the value of address 8023 from MEMORY READ MODE
when car is in top floor. If it is x01, it is normal. If it is x00, check
voltage of LSU-06 and DI-10, and They must have DC 0V.
TCD 77 TCD 78 TCD 114 ERD_Digi_Fl_Err
Coil[SW_GS_
OPEN_ZONE] Coil[AC_OP_MAINT_MODE] SWD_I[VI_LDC]
check_out
0x9256 0x9030 0x8025
Coil[IS_ZERO_V]
0x91F2
FTD_Current_Fl ==
check_out SPD_Floor_Spec.Top SWD_I[VI_SD1U]
TCD 107
0x8021
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 70/127
○ Operation CPU
TCD 108 SD2U ON trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
SD2U does not operate from bottom floor.
1. Check the value of address 8022 from MEMORY READ MODE,
when car is at bottom floor. If it is x00, it is normal. If it is x01,
check voltage of LSU-07, LSU-08 and DO-13. They must have
[Explanation] DC24V.(DC24V is abnormal) check wiring and connection.
Detected only when the rated speed is 90m/min or more. 2. Check the value of address 8023 from MEMORY READ MODE
Detected when SD2U input does not enter when car is on the top floor. when car is in top floor. If it is x01, it is normal. If it is x00, check
voltage of LSU-08 and DI-13, and They must have DC 0V.
TCD 77 TCD 78 TCD 114 ERD_Digi_Fl_Err 3. Check if SD2U switch works normally.
Coil[SW_GS_
OPEN_ZONE] Coil[AC_OP_MAINT_MODE] SWD_I[VI_LDC]
check_out
0x9256 0x9030 0x8025
Coil[IS_ZERO_V]
0x91F2
FTD_Current_Fl ==
check_out SPD_Floor_Spec.Top SWD_I[VI_SD2U]
TCD 108
SPD_Control_Spec. 0x8022
Contract_Velocity >= 90
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 71/127
○ Operation CPU
TCD 114 PRS ON/OFF trouble (LDC) Detection Application Si231
○ Speed CPU
1. Check at door zone, if the value of 3rd row and 5th column of
DOA-100 is ‘1’.
[Explanation]
Coil[RS_RUNNING] Coil[SW_FS_MAINT] SWD_I[VI_LDC] 2. Check at no door zone, if the value of 3rd row and 5th column
of DOA-100 is ‘0’.
0x91B0 0x929A 0x8025
Coil[SW_GS_LDC]
3. Check the voltage between Y2-03 of MIC plate and MR-04 of
0x9251 DOC-141. (with door zone, 0V is normal and without door zone,
24V is normal)
Coil[SW_GS_OPEN_ZONE] Coil[IS_CUR_V_10]
check_out
0x9256 0x91EB 4. Check if PRS is defective.
check_out 2070 msec
TMC_Start(POSI_
OFF_ERR_T)
TMC_Check(POSI_OFF_
ERR_T,FINISH_STATE)
TCD 114
POSI off error
TMC_Start(POSI_ON_
OFF_DETECT_T)
TMC_Check(POSI_ON_OFF_
DETECT_T,FINISH_STATE) TCD 114
POSI on error
SWD_I[VI_LDC]
old_LDC_state
0x8025
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 72/127
○ Operation CPU
TCD 116 PRS ON/OFF trouble (LDU) Detection Application Si231
○ Speed CPU
[Explanation]
[Countermeasures]
When LDU trouble is detected, rope compensation function would be cut.
1. The trouble will be detected, when SPEC data in address 0016
SPD_Function. TMC_Check(POWER_ Coil{AC_OP_ SPD_I[SP_ is set, even if rope compensation is not applied.
Rope_Compen READY_T,FINISH_STATE) MAINT_MODE] FAC_INSPECT]
[Explanation]
[Countermeasures]
When LDD trouble is detected, rope compensation function would be cut.
1. The trouble will be detected, when SPEC data in address 0016
SPD_Function. TMC_Check(POWER_ Coil{AC_OP_ SPD_I[SP_
Rope_Compen READY_T,FINISH_STATE) MAINT_MODE] FAC_INSPECT]
is set, even if rope compensation is not applied.
ldc_off_event
0x91AF
SWD_I[VI_LDC]
old_ldc
0x8025
Part : TCD Code
Solon LD / Trouble Shooting Ctrl No. : Solon_LD-TS-03-1
Page: 74/127
○ Operation CPU
TCD 119 SLOW DOWN S/W trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
DES Parameter error
1. Check if $018EH(SDI_DIR) data is “0” or “1”.
SWD_DES_ERR_IN&0x01
TCD122
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 76/127
○ Operation CPU
TCD 123 Regenerative Resistor Thermal trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
Regenerative Resistor Thermal error.
1. Check the Regenerative resistor (THB) wiring according to
drawing
2. Check if the FAN works normally.
[Explanation]
3. Check the balancing rate of counter weight.
Coil[SW_GS_POWER_READY] SWD_I[VI_REGEN_R_THERMAL
TCD123
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 77/127
○ Operation CPU
TCD 125 Brake open trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
When speed command is more than 10m/min but real speed is 8m/min
or less, and this continues more than 3 sec. The trouble will be detected.
1. Refer to TCD 86.
2. Check assembly condition of Brake if it works normally.
3. Check the disconnection of Rotary Encoder.
[Explanation]
See TCD 92.
SWD_I[VI_C1BR] Coil[IS_CMD_V_10] Coil[IS_CUR_V_8] Coil[AC_OP_ALP_MODE]
Coil[RS_ROPE_
Coil[RS_DECELERATION] COMPEN_REQUEST]
0x91BE 0x91A8
Coil[RS_ROPE_COMPEN_RUN]
0x91B5 0x92A8
Coil[A_ALP_RUN_PERMIT] Coil[SW_ALP_DIR_DECISION]
check_out
0x9062 0x92BC
check_out
3060 msec TMC_Start(BREAK_
OFF_DETECT_T)
TMC_Check(BREAK_OFF_
DETECT_T,FINISH_STATE)
TCD125
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 78/127
○ Operation CPU
TCD 126 Error_Main_INV_Speed Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
The detected elevator speed by DOC PCB and DPC PCB are differ
from each other over 5m/min while it runs high speed, it detects an error
1. Check the wiring condition from DPC to DOC PCB
[Meaning] [Countermeasures]
Hall temperature detection by DES PCB
1. Check the temperature of DES PCB
Coil[SW_GS_OPEN_ZONE] SWD_DES_ERR_IN&0X04
TCD127
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 80/127
○ Operation CPU
TCD 129 Motor Thermal Error Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
Motor over heat.
1. Check the Regenerative resistor (THB) wiring according to
drawing
[Explanation]
2. Check the balancing rate of counter weight.
Coil[SW_GS_POWER_READY] SWD_MOTOR_THERMAL
TCD129
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 81/127
○ Operation CPU
TCD 130 Load detector input trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
It will be detected in Input trouble of Load detector
Potential meter (PTM)
1. Perform ‘No Load Point Setting’ (A61E) and ‘Full Load Point
Setting’ (A62E).
- ‘No Load Point Setting’ is priority.
[Explanation]
Detected load by load detector exceeds 135% or is under -25%, and either 2. Check if channel value of each PTM shows on 3rd row normally.
condition continues for 2 sec. and more. - Car load mode (A86E)
The exceeded load 110% is considered 110%, and the minus load is considered
0%. 3. SPEC TABLE Load detector setting
$ 0018H : 41 - Potentiometer applied one.
00 - Only weighting device applied.
[Condition]
Car goes to under the unable of high speed operation with door open.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 82/127
○ Operation CPU
TCD 131 Slack Rope trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
It will be detected in Main Rope slack or cut
1. Check the SRS wiring according to drawing
Coil[SW_GS_POWER_READY] SWD_SLACK_ROPE_SW
TCD131
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 83/127
○ Operation CPU
TCD 132 Door open lock detection Detection Application Si231
○ Speed CPU
[Meaning] DOLS signal does not go in within 10 sec. after open command
Door open lock detected
and if this condition repeats 3 times, the trouble will be detected.
[Countermeasures]
1. Check door operating. In case that door can’t operate due to a
[Explanation]
Coil[SW_SS_48V_
foreign substance on sill, remove it.
Coil[RS_
RUNNING] Coil[DC_DOLS] Coil[DC_DCO] DOWN_HOLD] 2. Check if DMC CUT in DOC-141 & apparatus box is placed
on OFF.
0x91B0 0x90A6 0x9082 0x923C 3. Check open command signal.
If data of 2nd row & 13th column of annunciator is ‘1’, open
Coil[A_AUTO_ Coil[SW_GS_ command is energizing.
DOOR_CLOSE] OPEN_ZONE] SWD_O[VO_R2OP] Check if the voltage of DO-07,Y2-09 is 0.7V±0.1V.
check_out
Open_Trouble_Count >= 3
TCD 132
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 84/127
○ Operation CPU
TCD 133 Open_Lock repeated trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
TCD132 occurs 3 times in series
Refer to TCD132.
[Explanation]
If TCD132 occurs, it tries to open door of another floor after moving to another floor.
But if TCD132 occurs 3 times in series, ‘Open Lock repeated trouble’ will
occurs.
The elevator keeps hall/car call unable and stops operation.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 85/127
○ Operation CPU
TCD 134 Door close lock detection Detection Application Si231
○ Speed CPU
[Meaning] Door does not close within 10 sec. after close command,
Door close lock detected
the trouble will be detected.
[Countermeasures]
1. Check door operating. In case that door can’t operate due to a
[Explanation]
foreign substance on sill, remove it.
Coil[A_AUTO_ Coil[SW_GS_
DOOR_CLOSE] DOOR_ZONE] Coil[IS_ZERO_V] Coil[DC_DCO] ERD_Door_Err 2. Check if DMC CUT in DOC-141 & apparatus box is placed
on OFF.
0x9050 0x9250 0x91F2 0x9082 3. Check close command signal.
If data of 2nd row & 14th column of annunciator is ‘1’, close
SWD_I[VI_CDS] command is energizing.
SWD_O[VO_R2CL] check_out Check if the volt of CA-02 is 0.7V±0.1V.
0x8684 0x802B 4. If LDS LED isn’t off. Check the volt of AI1-05
Coil[DC_F_CLS] Coil[SW_SV_2ND_FIRE] When door is closed, the volt of AI1-05 & AI1-07 should be
110V.
0x90B5 0x9275 5. When door is closed, check if data of 3rd row & 12th (LDS) &
SWD_I[VI_LDS] 13th (CDS) column of annunciator is ‘1’. ‘1’ is normal.
6. Check if data of 3rd row & 14th column of annunciator is ‘1’.
0x802C
TMC_Check(CLOSE_LOCK_ ‘1’ is normal. (CLS)
DETECT_T,FINISH_STATE) TCD 135 7. If CLS signal is ‘0’
1) Turn off the DMC_CUT2 switch. And close the door fully by
Coil[SW_GS_ manual to check the LED condition of CLS.
Coil[DC_DOLS] OPEN_ZONE]
2) Check the LD5 of DCD-231 PCB
TMC_Check(FORCE_ 0x90A6 0x9256 8. Check if RDZ relay operates normally.
OPEN_T,FINISH_STATE) LED of the relay should be turned on with door zone and off
check_out
With NUGING : 20 sec without door zone.
Without NUGING : 10 sec TMC_Start (CLOSE_
LOCK_DETECT_T)
TMC_Check(CLOSE_LOCK_
DETECT_T,FINISH_STATE) close_lock_count ++
close_lock_count >= 2
TCD 134
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 86/127
○ Operation CPU
TCD 135 Close_Lock repeated trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
TCD134 occurs 12 times (can be changed by SPEC) in series
Refer to TCD134.
[Explanation]
[Meaning] [Countermeasures]
When ALP (ARD) control panel is out of order.
1. Check if the condition of ALP (ARD) is normal by annunciator of
ALP (ARD).
In case of power failure, elevator must go to door zone by the power of ALP
(ARD), but elevator isn’t operable due to abnormal condition.
Abnormal condition
1. Operation unable due to R5SC off.
2. Operation unable due to floor error.
3. Operation unable due to abnormal signal from DSP .
4. In case that the speed exceeds designated speed.(10m/min)
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 88/127
○ Operation CPU
TCD 140 Discharging voltage of Backup Battery under reference Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
NVRAM is abnormal
1. Check if Backup Battery is normal.
This trouble doesn’t hinder elevator operating. It will be returned to normal after
rescue operation to bottom floor.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 89/127
○ Operation CPU
TCD 141 RTC trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
When RTC chip doesn’t operate well, the trouble occurs.
1. Perform ‘RTC set’ by ‘A69E’.
In case that RTC chip is abnormal, the trouble occurs. 3. Replace DOC-141.
This trouble doesn’t hinder elevator operating.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 90/127
○ Operation CPU
TCD 145 ER_INV_Door Trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
When Door CPU Watchdog occurs and RETRY signal repeats
two times, but Door CPU is not returned to normal.
1. Check if the Door power Fuse cut on DOJ PCB.
1) FUSE capacity : 3A
2) Check the isolation between Door power line and Earth.
[Explanation]
2. Check if the DMC_CUT1 switch is OFF position.
In case door watch dog signal is off, The operation part will hold 3. Check the voltage between PJ1 mic jack 8 and 17 on the
door CPU retry signal about 300ms and monitor that Door CPU DCD-23X PCB. (AC93V ~ AC121V : Normal)
shall be return to its normal condition.
4. Replace the DCD-23X PCB : When LD4 (SAFE-OK) LED is
But if the door CPU watch dog signal does not return to normal not flickering.
condition within 5seconds, it outputs a new retry signal. And if it
occurs over 2 times, \it will detects an error. 5. Replace the DCD-23X PCB : When LD6 (WDT) LED is OFF.
Even error is detected, the retry signal is outputted repeatedly. 6. Check the voltage between PJ1-14 and PJ3-1 on the
When the watch dog signal is return to normal condition, the error DCD-23X PCB. (DC24V: Normal)
is cleared by automatically.
7. Check the voltage at DRIN-1 on the
DCL-243 PCB. (DC24V : Normal)
1) In case of not DC24V : Check the DR(IN/OUT) wiring.
2) In case of DC24V : Replace DCL-243 PCB.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 91/127
○ Operation CPU
TCD 146 Air-conditioner Float S/W trouble Detection Application Si231
○ Speed CPU
[Meaning] [Countermeasures]
Float switch is still activated even after drain operation for 1 min.
1. Check the float switch.
[Explanation]
1. This trouble doesn’t hinder elevator operating even if the trouble occurs.
[Meaning] [Condition]
The signal of LDC keep off for 20~45 sec. at on position during high
speed operation. (Detecting time is depend on floor height)
This is hold type, so cut safety line and keep elevator inoperable.
[Explanation]
TMC_Start(OBS_
LDC_ON_DETECT_T)
TMC_Check(OBS_LDC_ON_
DETECT_T,FINISH_STATE)
TCD147
SWD_I[VI_LDC] old_LDC_state
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 93/127
○ Operation CPU
TCD 150 SD1D Over Speed detection Detection Application Si231
○ Speed CPU
[Meaning] Over speed is detected at SD1D zone and emergency stop. [Countermeasures]
1. When SD1D is activated, check the volt of HA-02.
Normal: 24V → 0V.
2. When SD1D is activated, check address 0x8023 by MEMORY
[Explanation] READ MODE (A21E)
1. In case that the condition of forced deceleration is detected. Normal: ‘00’ → ‘01’.
(Coil[SV_FORCE_DECEL] = ON) 3. Check the assembly condition of SD1D.
>> The speed is 15m/min higher than the command at where SD1D is If necessary, adjust it.
activated. And if this condition keeps for 150 msec. and more, the trouble
is detected.
But, if the real speed is less than 30 m/min, No trouble is detected.
2. In case that the condition of forced deceleration is not detected.
Speed 60 m/min 90 m/min 105 m/min
( Coil[SV_FORCE_DECEL] = OFF )
1) 60m/min Distance 1000 mm 1400 mm 1800 mm
>> If the speed is higher than limit speed below according to regular speed at
where SD1D is activated, the trouble will be detected. * Above distance is from ‘0’ level of bottom floor to the center of
switch roller.
2) 90m/min and higher
>> If the speed is higher than limit speed below according to regular speed at
where SD1D is activated and this condition keeps for 150 msec. and more,
the trouble will be detected.
[Meaning] Over speed is detected at SD2D zone and emergency stop. [Countermeasures]
1. When SD2D is activated, check the volt of HA-03.
Normal: 24V → 0V.
2. When SD2D is activated, check address 0x8024 by MEMORY
[Explanation] READ MODE (A21E)
1. In case that the condition of forced deceleration is detected. Normal: ‘00’ → ‘01’.
(Coil[SV_FORCE_DECEL] = ON) 3. Check the assembly condition of SD2D.
>> The speed is 15m/min higher than the command at where SD2D is If necessary, adjust it.
activated. And if this condition keeps for 150 msec. and more, the trouble
is detected.
But, if the speed is less than 30 m/min, No trouble is detected. Speed 90 m/min 105 m/min
2. In case that the condition of forced deceleration is not detected.
( Coil[SV_FORCE_DECEL] = OFF ) Distance 2000 mm 2700 mm
>> If the speed is higher than limit speed below according to regular speed at
where SD2D is activated and this condition keeps for 150 msec. and more, * Above distance is from ‘0’ level of bottom floor to the center of
the trouble will be detected. switch roller.
[Meaning] Over speed is detected at SD1U zone and emergency stop. [Countermeasures]
1. When SD1U is activated, check the volt of HA-06.
Normal: 24V → 0V.
2. When SD1U is activated, check address 0x8021 by MEMORY
[Explanation] READ MODE (A21E)
1. In case that the condition of forced deceleration is detected. Normal: ‘00’ → ‘01’.
(Coil[SV_FORCE_DECEL] = ON) 3. Check the assembly condition of SD1U.
>> The speed is 15m/min higher than the command at where SD1U is If necessary, adjust it.
activated. And if this condition keeps for 150 msec. and more, the trouble
is detected.
But, if the real speed is less than 30 m/min, No trouble is detected.
Speed 60 m/min 90 m/min 105 m/min
2. In case that the condition of forced deceleration is not detected.
( Coil[SV_FORCE_DECEL] = OFF ) Distance 1000 mm 1400 mm 1800 mm
1) 60m/min
>> If the speed is higher than limit speed below according to regular speed at * Above distance is from ‘0’ level of top floor to the center of
where SD1U is activated, the trouble will be detected. switch roller.
2) 90m/min and higher
>> If the speed is higher than limit speed below according to regular speed at
where SD1U is activated and this condition keeps for 150 msec. and more,
the trouble will be detected.
[Meaning] Over speed is detected at SD2U zone and emergency stop. [Countermeasures]
1. When SD2U is activated, check the volt of HA-07.
Normal: 24V → 0V.
2. When SD2U is activated, check address 0x8022 by MEMORY
[Explanation] READ MODE (A21E)
1. In case that the condition of forced deceleration is detected. Normal: ‘00’ → ‘01’.
(Coil[SV_FORCE_DECEL] = ON) 3. Check the assembly condition of SD2U.
>> The speed is 15m/min higher than the command at where SD2U is If necessary, adjust it.
activated. And if this condition keeps for 150 msec. and more, the trouble
is detected.
But, if the real speed is less than 30 m/min, No trouble is detected. Speed 90 m/min 105 m/min
2. In case that the condition of forced deceleration is not detected.
( Coil[SV_FORCE_DECEL] = OFF ) Distance 2000 mm 2700 mm
>> If the speed is higher than limit speed below according to regular speed at
where SD2U is activated and this condition keeps for 150 msec. and more, * Above distance is from ‘0’ level of top floor to the center of
the trouble will be detected. switch roller.
[Meaning] Emergency stop detected, elevator is suddenly stopped during run with [Countermeasures]
more than 10m/min speed by the trouble in relation to R/E.
1. Check whether ERO switch on E&I panel has been operated
during driving.
2. Verify whether switch and connectors in PCB have had
[Explanation] bad contacts.
3. Check if R/E is disconnected.
run_stop Coil[RS_RUNNING] Coil[IS_CUR_V_10] 4. Check if LDS &CDS operate normally.
TCD 164
5. Check the state of R5SC relay.
0x91EE
0x91B0 6. Check the state of ALARM LED.
TCD 92 7. Check the flickering state of SYS1 LED inside DOC-141.
8. Check the flickering state of SYS2 LED inside DOC-141.
9. Check if safety switches are activated. (EES, pit, SCS)
TCD 93
* In case of emergency stop with 10m/min speed and more
The reason can be analyzed by ERROR LOG Table (A42E)
TCD 94
- Trace monitor
0x91B0
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 98/127
○ Operation CPU
TCD 168 Speed difference (real speed detection) Detection Application Si231
○ Speed CPU
[Meaning] When the speed difference between command & real is more than In case the speed command value is bigger than feed-backed
30m/min, the trouble is detected. speed and it lasts 540ms, it detects an error.
But the speed command value is smaller than feed-backed
speed and it lasts 2160ms, it detects an error
[Explanation]
[Countermeasures]
0x91EC 0x91E4 0x8080 0x9206
1. Refer to TCD 60 and check if SPEC is correct in accordance
SWD_I[VI_C1ST] SWD_I[VI_R5SC] TCD 164 Coil[SV_INV_SW_FAIL] with the field.
2. Check if brake open & close as its function.
0x802A 0x8001 0x9210 3. Check disconnection of Rotary Encoder (AD Connect).
Coil[RS_FAST_ Refer to TCD 92.
SWD_I[VI_C1BR] SWD_I[VI_LDS] SWD_I[VI_CDS] RUN_COMMAND] check_out 4. Check balancing rate between car & C.WT.
(It must be within 0.45 ~ 0.55)
0x8029 0x802C 0x802B 0x91B1
abs(SVD_Cmd_V - SVD_Cur_V)
check_out >= 30 speed_err_count ++ speed_err_count
SVD_Cmd_V <
speed_err_count > 3
SVD_Cur_V TCD 168
speed_err_count > 12
TCD 168
check_out
=0 speed_err_count
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 99/127
○ Operation CPU
TCD 170 Operation direction trouble Detection Application Si231
○ Speed CPU
[Explanation]
[Countermeasures]
Coil[IS_CUR_V_8] Coil[RS_RUNNING] 1. Check if DIR LED is on.
check_out
2. If DIR LED is on, change the position of DIR jumper in
0x91EA 0x91B0 DOC-141. (Or change spec data ‘00’ in address 0124 to ‘01’)
3. Switch to ERO operation, and perform
UP/DOWN operation for a little while, to check right/reverse
540 msec matter in operating direction.
check_out Coil[RS_UP_RUN] enco_diff < 0 In reverse, change DIR jumper in DOC-141. (Or change spec
TMC_Start(DIR_ data ‘00’ in address 0124 to ‘01’)
0x91AE ERROR_DETECT_T) 4. When rerunning, make sure to reset.
5. Verify if BIT 8 of SPEC1 is OFF.
6. Still no effect, change 2-phases of MOTOR output line.
0x91AF
TMC_Reset(DIR_
ERROR_DETECT_T)
TMC_Check((DIR_ERROR_
SWD_Emergency_Call DETECT_T, FINISH_STATE)
TCD170
ICC_Set_Sys_Output_Port
(RE_DIR_ERROR, ON)
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 100/127
○ Operation CPU
TCD 171[1] Synchronous position trouble Detection
○ Speed CPU
Application Si231
* EF_PF_OVER_V : 0x10
BRD_PF_Control.Dir BRD_PF_Control.Dir
== UP == DN
TCD 171
EF_PF_OVER_V
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 101/127
○ Operation CPU
TCD 171[2] Synchronous position trouble Detection
○ Speed CPU
Application Si231
[Explanation]
3. When the main power turned off , If the direction information is not STOP,
UP or DOWN, it will detect an error
BRD_PF_Control.Dir BRD_PF_Control.Dir BRD_PF_Control.Dir
== UP == DN == STOP
* EF_PF_DIR : 0x20
SWD_I[VI_UL] SWD_I[VI_DL]
TCD 171
EF_PF_DIR
0x8003 0x8004
EF_SDS_OS
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 102/127
○ Operation CPU
TCD 171[3] Synchronous position trouble Detection
○ Speed CPU
Application Si231
[Explanation]
5. If the error of rotary encoder is over than 500mm after leveling, it will be
detected.
Coil[SW_GS_
POWER_READY] SWD_I[VI_LDC] Coil[RS_RUNNING] SWD_I[VI_C1ST]
0x9030
EF_ZONE500
0x9250 0x91E8 0x9190
* EF_PF_DIR : 0x01
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 103/127
○ Operation CPU
TCD 177 Emergency stop occurred frequently Detection Application Si231
○ Speed CPU
[Meaning] It is detected that the failures of high speed running prohibited have [Countermeasures]
occurred 12 times within 10 min
1. Check Error Log Table by A42E, find out the trouble occurred
frequently and perform trouble shooting.
[Explanation]
It is hold type, prohibit operation by R5SC after opening door at door zone
Coil[EM_EO_ Coil[AC_OP_
old_fast_run_cut FAST_RUN_CUT] MAINT_MODE] +1 E_Stop_Count[9]
0x90F4 0x9030
+1 E_Stop_10M_Count
E_Stop_10M_Count >= 12
TCD 177
Coil[EM_EO_FAST_RUN_CUT] old_fast_run_cut
0x90F4
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 104/127
○ Operation CPU
TCD 178 Safety drive occurred frequently Detection Application Si231
○ Speed CPU
[Meaning] Detected that rescue running have occurred more than 6 times [Countermeasures]
within 10 min.
1. Search the reason for stopping out of door zone.
2. If stopping during running, refer to the error log table,
3. When below-stopping or over-stopping during leveling occurs
[Explanation]
verify whether parameter setting for the control of leveling is
It is hold type, prohibit operation by R5SCafter opening door at door zone light. (Pgc_Gain → ADDR:0x0212)
Coil[SW_FS_SAFETY_DRIVE_DETECT] tmp
0x92A8
0x9030
+1 S_Drv_10M_Count
tmp old_safety_drive
Coil[SW_GS_IS_STOP] SWD_I[VI_LDC]
TCD 178
Stop at door zone with door opened for 10 min., and return
normal operation automatically.
[Explanation]
[Condition]
Stand by 10 min. after door open at door zone.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 106/127
○ Operation CPU
TCD 184 SDS forced deceleration occurred frequently Detection Application Si231
○ Speed CPU
Coil[AC_OP_ Coil[SW_SV_
FIREMAN_MODE] 2ND_FIRE]
TMC_Check(OLS_ERROR_
DETECT_T,FINISH_STATE) Coil[SW_GS_DOOR_ZONE]
TCD 188
0x9250
0x802B 0x802D
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 108/127
○ Operation CPU
TCD 191 Duplicated door open/close command (ER_DOOR_COMMAND) Detection
○ Speed CPU
Application Si231
[Meaning] The open&close signals are inputted to DCD PCB at same time [Countermeasures]
If the door is reopened 5 times continuously by photo shoe, it will be display error.
And a case that car door is opened fully as detecting ‘DOLS’ signal but system
detects that car door switch or landing door switch is closed.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 114/127
○ Operation CPU
TCD 199 ER_PCB_Protect_Fail (Korea domestic only) Detection Application Si231
○ Speed CPU
Whenever a DOC PCB or DCL PCB is replaced in Korea, the security system in
CP request serviceman’s ID and approval number. If this requirement is not
satisfied, the PCB protection program will not removed. So, its operation shall be
locked.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 115/127
○ Operation CPU
TCD 200 CNET LON communication trouble Detection Application Si231
○ Speed CPU
[Meaning] DPRAM communication between Main LON and i186 does not operate [Countermeasures]
1. If the trouble doesn’t disappear after system reset on DOC-140,
Check if ROM(OS ROM) of DOC-140 & ROM of main LON are
mounted correctly.
[Explanation]
1.It will detect an error if the 4th bit(DPRAM: 0x10) of input port of i186 2. If the trouble doesn’t disappear after performing 1 item above,
system is ‘HIGH’ condition and a condition that the TOKEN is not passed Replace ROM(OS ROM) of DOC-140 & ROM of main LON.
through LON continuously more than 6 cycle (180msec).
3. Replace DOC-140 even if nothing is improved after performing
2. In case the main LON CPU of DOC-140 PCB is unable to work. item 2 above.
(The 2nd bit(CNET_CPU_ERR:0x04) of input port of i186 system is
‘HIGH’ condition)
0x9300
err_count > 5
TCD 200
[Condition]
LON LED on DOC-140 will light off.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 116/127
○ Operation CPU
TCD 202 Car communication trouble Detection Application Si231
○ Speed CPU
[Condition]
LON LEDs of DOC-140 and DCL-243 are flickering with 1.2 sec. cycle
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 117/127
○ Operation CPU
TCD 205 DES communication trouble Detection Application Si231
○ Speed CPU
[Condition]
LON_OK LED of DES PCB is hold
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 118/127
○ Operation CPU
TCD 206 ER_REAR_OPB_COM Detection Application Si231
○ Speed CPU
[Condition]
LON LEDs of DOC-140 and DCL-243 are flickering with 1.2 sec. cycle
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 119/127
○ Operation CPU
TCD 209 ER_NPLEX_MASTER_COM Detection Application Si231
○ Speed CPU
G_Signal_Wait_Counter == 0
TCD 209
2. Check the N-PLEX communication line. (SH connector)
The communication line should be twisted shield cable.
Group_Fail_Count > 3 3. Check the terminal resistor setting
(HJP-SH jumper must be connected)
[Meaning] Communication error with other car is detected in duplex operation. [Countermeasures]
HJP SH
HJP SH
SH SL SL SH
DHG-162
DHG-162
DHG-162
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 121/127
○ Operation CPU
TCD 217 Hall button jam detection Detection Application Si231
○ Speed CPU
[Meaning] When hall button is being pushed continuously, the trouble is detected. [Countermeasures]
Button_Jam_Detect[0][UP_INDX]
TCD 217
Button_Jam_Detect[0][DN_INDX]
Address Floor
0x9954 1st floor ~ 8th floor UP Button
0x9955 9th floor ~ 16th floor UP Button
0x9956 17th floor ~ 24th floor UP Button
0x9957 25th floor ~ 32nd floor UP Button
0x9958 1st floor ~ 8th floor DOWN Button
0x9959 9th floor ~ 16th floor DOWN Button
0x995A 17th floor ~ 24th floor DOWN Button
0x995B 25th floor ~ 32nd floor DOWN Button
[Meaning] Communication error with all floor in hall line is detected [Countermeasures]
H_Data_Receive_Wait_Counter == 0
[Condition]
When TCD224 occurs, operation mode would be ACD26 and perform backup
operation.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 124/127
○ Operation CPU
TCD 236 TCI LOCK trouble Detection Application Si231
○ Speed CPU
[Meaning] Abnormal E.M switch ON is detected under CAR TOP MAINT operation. [Countermeasures]
When TCD236 occurs, TOCI switch is switched to NORMAL side under Car TOP
Maintenance operation.
Part: TCD Code
Solon LD / Trouble Shooting Ctrl No.: Solon_LD-TS-03-1
Page: 125/127
○ Operation CPU
TCD 237 CRT communication trouble Detection Application Si231
○ Speed CPU
[Explanation]
[Meaning] When elevator stops a floor, a landing door at another floor is [Countermeasures]
opened Then, it detects an error (Russia code area only)
1. Check if the Russia code application
1) In case of Si210, The following 2 options effect on this
error
[Explanation] 2) In case of Si25x and Si23x, Russia code(0042) effects on
this error
The elevator will be stop immediately under normal operation mode, the error is
hold until the main power is turned off. It does not detects this error under <<OPZX error detects Spec>>
inspection mode.
Addr Label Contents
0042 Russia Russia code application, 0x01
Normal Mode VI_OPZX
TCD240 07CA OPZX Landing door detection function
application, 0x01
803C