SYSTEM COMPONENTS 16-13

6.5* Foam Concentrate Pumps. (2) Connections for pump suction, relief, and testing lines
(3) Protected sight gauges or other liquid level devices
6.5.1 Materials. (4) Filling and draining connections
6.5.1.1* The design and materials of construction for foam 6.6.3.5 Tank discharge outlets shall be located to furnish a
concentrate pumps shall be approved for use with the type of positive head on the pump suction.
foam concentrate used in the system.
6.6.4 Pressure-Type Storage Tanks.
6.5.1.2 Special attention shall be paid to the type of seal or
packing used. 6.6.4.1* Pressure-proportioning tanks shall have means for
filling, for gauging the level of foam concentrates, and for
6.5.2 Rated Capacities. drainage, cleaning, and inspection of interior surfaces and of
6.5.2.1 Foam concentrate pumps shall have rated capacities at the concentrate-holding bladder or diaphragm, if provided.
or in excess of the maximum system demand. 6.6.4.2 These tanks shall be stamped to be identified as meet‐
6.5.2.2 To ensure positive injection of foam concentrate, the ing the requirements of ASME Boiler and Pressure Vessel Code,
discharge pressure ratings of pumps at the design discharge Section VIII, Division 1.
capacity shall be in excess of the maximum water pressure avail‐ 6.7 Piping, Valves, Pipe Fittings, and Hangers.
able under any condition at the point of foam concentrate
injection. 6.7.1 Piping, valves, pipe fittings, and hangers, including
corrosion-protection coatings, shall be in accordance with
6.5.3 Overpressurization. NFPA 13.
6.5.3.1* Foam concentrate pumps capable of overpressurizing 6.7.2* Piping, fittings, and valves shall be of a material
the system shall be provided with means of pressure relief from compatible with the foam concentrate, foam solution, or water
the discharge to the supply side of the pump to prevent exces‐ used, as applicable.
sive pressure and temperature.
N 6.7.2.1* Foam concentrate pipe and valves shall be made of
6.5.3.2 Overpressure shall not exceed the working pressure of one of the following materials:
the foam concentrate piping system.
(1) Brass (red or naval)
6.5.4 Flushing. (2) Bronze
6.5.4.1* Foam concentrate pumps shall have means for flush‐ (3) Stainless steel (304 or 316)
ing. (4) Other material, in accordance with the foam concentrate
manufacturer’s certification of compatibility with the
6.5.4.2 Foam concentrate pumps shall be provided with a foam concentrate and as approved by the AHJ
drain cock or valve. [11:4.7.1.1]
6.5.5 Foam concentrate pumps shall be automatic-starting N 6.7.2.2 Carbon steel pipe shall be permitted to be used in
upon system actuation. accordance with the manufacturer’s certification of compatibil‐
ity with the foam concentrate and as approved by the AHJ.
6.5.6 Pumps shall be listed for this service in accordance with
NFPA 20. N 6.7.2.3 Pipe carrying foam concentrate shall not be galvan‐
• ized. [11:4.7.1.3]
6.6 Foam Concentrate Storage Tanks.
N 6.7.2.4 Foam concentrate pipe shall conform to one of the
6.6.1 Storage tanks for foam concentrate shall be constructed following standards:
of materials compatible with the liquid, shall be solidly moun‐
ted, and shall be permanently located. (1) ASTM A312
(2) ASTM B43
6.6.2 The storage temperatures for which foam concentrates (3) ASTM B315
are listed shall be considered the temperature limits for loca‐ (4) Other standards as allowed by 6.7.2.1(4), 6.7.2.2, and
tion of storage tanks. 6.7.2.3
6.6.3 Atmospheric-Type Storage Tanks. [11:4.7.1.4]

6.6.3.1 Storage tanks shall have capacities to accommodate N 6.7.2.5* Foam solution pipe shall be in accordance with
the needed quantities of foam concentrate plus space for ther‐ NFPA 13.
mal expansion. 6.7.3* Rubber-gasketed fittings shall be permitted to be used
6.6.3.2 Foam concentrate outlets from the tanks shall be loca‐ to connect pipe in fire-exposed areas where the foam-water
ted to prevent sediment from being drawn into the system. system is automatically controlled.

6.6.3.3 When determining the quantity of foam concentrates, 6.7.3.1 Fire-exposed areas in which these fittings are located
the volume of the sediment pocket shall be added to the quan‐ shall be protected by automatic foam-water systems or other
tity needed for system operation. approved means.

6.6.3.4* Tanks shall be equipped with conservation-type vents, 6.8 Strainers for Foam Concentrate.
access handholes, or manholes that are located to provide for N 6.8.1 Strainers shall be provided for foam concentrate lines
inspection of the following: only where required by the manufacturer’s written recommen‐
(1) Interior tank surfaces dations.

Shaded text = Revisions. Δ = Text deletions and figure/table revisions. • = Section deletions. N = New material. 2019 Edition