SIPROTEC Compact 7SK80 Motor Protection Relay: Function Overview

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 36

12 Motor Protection / 7SK80

SIPROTEC Compact 7SK80


Motor Protection Relay
Function overview

Protection functions
• Time-overcurrent protection
(50, 50N, 51, 51N)
• Directional overcurrent protection, ground
(67N)
• Sensitive dir./non-dir. ground-fault
detection (50Ns, 67Ns)
• Displacement voltage (59N/64)
• Inrush restraint
• Motor protection
– Undercurrent monitoring (37)
LSP2874.tif

– Starting time supervision (48)


– Restart inhibit (66/86)
– Locked rotor (14)
– Load jam protection (51M)
• Overload protection (49)
Fig. 12/6 • Temperature monitoring
SIPROTEC 7SK80 • Under-/overvoltage protection (27/59)
motor protection relay • Under-/overfrequency protection (81O/U)
• Breaker failure protection (50BF)
• Phase unbalance or negative-sequence
protection (46)
Highlights • Phase-sequence monitoring (47)
Description • Lockout (86)
Removable current and voltage terminals
The SIPROTEC Compact 7SK80 is a multi- Control functions/programmable logic
provide the ideal solution for fast and
functional motor protection relay. It is de- secure replacement of relays. • Commands for the ctrl. of CB, disconnect
signed for asynchronous induction-type switches (isolators/isolating switches)
motors of all sizes. The relays have all the Binary input thresholds and current taps • Control through keyboard, binary
functionality to be applied as a backup relay are software settings. There is thus no need inputs, DIGSI 4 or SCADA system
to a transformer differential relay. to ever open the relay to adapt the hardware • User-defined PLC logic with CFC
configuration to a specific application. (e.g. interl.)
The 7SK80 features “flexible protection
The relay provides 9 programmable func- Monitoring functions
functions”. 20 additional protection func-
tions can be created by the user. For exam- tion keys that can be used to replace push- • Operational measured values V, I, f
ple, a rate of change of frequency function buttons, select switches and control switches. • Energy metering values Wp, Wq
or a reverse power function can be created. • Circuit-breaker wear monitoring
The battery for event and fault recording • Minimum and maximum values
The relay provides circuit-breaker control, memory can be exchanged from the front • Trip circuit supervision
additional primary switching devices of the relay. • Fuse failure monitor
(grounding switches, transfer switches and The relay is available with IEC 61850 for • 8 oscillographic fault records
isolating switches) can also be controlled incredible cost savings in applications (e.g. • Motor statistics
from the relay. Automation or PLC logic transfer schemes with synch-check, bus Communication interfaces
functionality is also implemented in the interlocking and load shedding schemes). • System/service interface 12
relay. The integrated programmable logic – IEC 61850
(CFC) allows the user to add own func- This compact relay provides protection,
– IEC 60870-5-103
tions, e.g. for the automation of switch- control, metering and PLC logic functional-
– PROFIBUS-DP
gear (including: low voltage starting, auto- ity. Secure and easy to use one page matrix
– DNP 3.0
matic restart, interlocking, transfer and IO programming is now a standard feature.
– MODBUS RTU
load shedding schemes). The user is also The housing creates a sealed dust proof • Ethernet interface for DIGSI 4
allowed to generate user-defined messages. environment for the relay internal elec- • USB front interface for DIGSI 4
The communication module is independ- tronics. Heat build up is dissipated through Hardware
ent from the protection. It can easily be the surface area of the steel enclosure. No • 4 current transformers
exchanged or upgraded to future commu- dusty or corrosive air can be circulated • 0/3 voltage transformers
nication protocols. over the electronic components. The relay • 3/7 binary inputs (thresholds
thus will maintain its tested insulation configurable using software)
characteristic standards per IEC, IEEE, • 5/8 binary outputs (2 changeover/
even if deployed in harsh environment. Form C contacts)
• 0/5 RTD inputs
• 1 live-status contact
• Pluggable current and voltage terminals

Siemens SIP · 2008 Revised July 2010 12/9


12 Motor Protection / 7SK80

Application

Directional (Ground)

LSA4782b-en.eps
Fig. 12/7 Function diagram

The SIPROTEC Compact 7SK80 unit is a Line protection Reporting


numerical protection relay that can perform The 7SK80 units can be used for line pro- The storage of event logs, trip logs, fault
control and monitoring functions and tection of high and medium-voltage net- records and statistics documents are stored
therefore provide the user with a cost-effec- works with grounded, low-resistance in the relay to provide the user or operator
tive platform for asset protection, monitor- grounded, isolated or a compensated all the key data required to operate modern
ing and management, that ensures reliable neutral point. substations.
supply of electrical power to the motors or
other plant assets. The ergonomic design Motor protection Switchgear cubicles for
makes control easy from the relay front high/medium voltage
panel. A large, easy-to-read display was a The 7SK80 relay is specifically designed
key design factor. to protect induction-type asynchronous All units are designed specifically to meet
motors. the requirements of high/medium-voltage
Control applications.
Transformer protection
12 The integrated control function permits In general, no separate measuring instru-
control of motors, contactors, disconnect The relay provides all the functions for ments (e.g. for current, voltage, frequency,
devices, grounding switches or circuit- backup protection for transformer differ- …) or additional control components are
breakers through the integrated operator ential protection. The inrush suppression necessary.
panel, binary inputs, DIGSI 4 or the control effectively prevents unwanted trips that
can be caused by inrush currents. Typically the relay provides all required
or SCADA/automation system (e.g. SICAM,
measurements, thus negating the use of
SIMATIC or other vendors automation sys-
Backup protection additional metering devices like amp, volt
tem). A full range of command processing
or frequency meters. No additional control
functions is provided. The 7SK80 can be used as a stand alone switches are required either. The relay pro-
feeder protection relay or as a backup to vides 9 function keys that can be config-
Programmable logic other protection relays in more complex ured to replace pushbuttons and select
The integrated logic characteristics (CFC) applications. switches.
allow the user to add own functions for
automation of switchgear (e.g. interlock- Metering values
ing) or switching sequence. The user can Extensive measured values (e.g. I, V),
also generate user-defined messages. This metered values (e.g. Wp, Wq) and limit
functionality can form the base to create values (e.g. for voltage, frequency) provide
extremely flexible transfer schemes. improved system management.

12/10 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Application

ANSI No. IEC Protection functions

50, 50N I>, I>>, I>>>, IE>, IE>>, IE>>> Instantaneous and definite time-overcurrent protection (phase/neutral)

51, 51N Ip, IEp Inverse time-overcurrent protection (phase/neutral)

67N IEdir>, IEdir>>, IEp dir Directional overcurrent protection, ground (definite/inverse)

67Ns/50Ns IEE>, IEE>>, IEEp Directional/non-directional sensitive ground-fault detection

Cold load pickup (dynamic setting change)

59N/64 VE, V0> Displacement voltage, zero-sequence voltage

50BF Breaker failure protection

46 I2> Phase-balance current protection (negative-sequence protection)

47 V2>, phase-sequence Unbalance-voltage protection and/or phase-sequence monitoring

48 Starting time supervision

49 ϑ> Thermal overload protection

51M Load jam protection

14 Locked rotor protection

66/86 Restart inhibit

37 I< Undercurrent monitoring

38 Temperature monitoring via internal RTD inputs or external device (RTD-box),


e.g. bearing temperature monitoring

27, 59 V<, V> Undervoltage/overvoltage protection

32 P<>, Q<> Forward-power, reverse-power protection

55 cos ϕ Power factor

81O/U f>, f< Overfrequency/underfrequency protection

81R df/dt Rate-of-frequency-change protection

12

Siemens SIP · 2008 Revised July 2010 12/11


12 Motor Protection / 7SK80

Construction and hardware

LSP2885.tif
Connection techniques and
housing with many advantages
The relay housing is 1/6 of a 19" rack. The Illuminated 6-line display
housing is thus identical in size to the 7SJ50
and 7SJ60 relays that makes replacement Navigation keys
very easy. The height is 244 mm (9.61").
Pluggable current and voltage terminals Numerical key pad/9 function keys
allow for pre-wiring and simplify the ex-
change of devices. CT shorting is done in 8 programmable LEDs
the removable current terminal block.
Control keys
It is thus not possible to open-circuit a
secondary current transformer.
Standard battery exchangeable from the front
All binary inputs are independent and the
pick-up thresholds are settable using soft- USB front port
ware settings (3 stages). The relay current
transformer taps (1 A/5 A) are new soft-
ware settings. Up to 9 function keys can be
programmed for predefined menu entries,
switching sequences, etc. The assigned
function of the function keys can be shown

LSP2877.tif
in the display of the relay.
If a conventional (inductive) set of primary
voltage transformers is not available in the

LSP2878.tif
feeder, the phase-to-ground voltages can be Current terminal
block
measured directly through a set of capacitor
cones in the medium-voltage switchgear.
LSP2876.tif

In this case, the functions directional over-


current protection, ground (ANSI 67N), Voltage terminal
block
voltage protection (ANSI 27/59) and fre-
quency protection (ANSI 81O/U) are available.
Fig. 12/8 7SK80 Front view, rear view, terminals

Protection functions

Time-overcurrent protection Available inverse-time characteristics


(ANSI 50, 50N, 51, 51N) Characteristics acc. to ANSI/IEEE IEC 60255-3
This function is based on the phase- Inverse • •
selective measurement of the three phase
currents and the ground current (four Short inverse •
transformers). Three definite-time over-
Long inverse • •
12 current protection elements (DMT) are
available both for the phase and the Moderately inverse •
ground elements. The current threshold
and the delay time can be set in a wide Very inverse • •
range. Inverse-time overcurrent protection Extremely inverse • •
characteristics (IDMTL) can also be se-
lected and activated.
the reverse movement of the Ferraris disk Cold load pickup/dynamic setting change
Reset characteristics of an electromechanical relay (disk emula- The pickup thresholds and the trip times
tion). of the directional and non-directional
Time coordination with electromechanical
relays are made easy with the inclusion time-overcurrent protection functions can
Inrush restraint
of the reset characteristics according to be changed via binary inputs or by setable
ANSI C37.112 and IEC 60255-3 /BS 142 The relay features second harmonic re- time control.
standards. When using the reset character- straint. If second harmonic content is
istic (disk emulation), the reset process is detected during the energization of a trans-
initiated after the fault current has disap- former, the pickup of non-directional and
peared. This reset process corresponds to directional elements are blocked.

12/12 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Protection functions

Directional overcurrent protection, ground


(ANSI 67N)
Directional ground protection is a separate
function. It operates in parallel to the non-
directional ground overcurrent elements.
Their pickup values and delay times can be
set separately. Definite-time and inverse-
time characteristics are offered. The trip-
ping characteristic can be rotated by
± 180 degrees.
For ground protection, users can choose
whether the direction is to be calculated
using the zero-sequence or negative-
sequence system quantities (selectable).
If the zero-sequence voltage tends to be
very low due to the zero-sequence imped-
ance it will be better to use the negative- Fig. 12/9
Directional determination
sequence quantities. using cosine measurements
for compensated networks
(Sensitive) directional ground-fault detec-
tion (ANSI 59N/64, 67Ns, 67N)
For isolated-neutral and compensated net-
works, the direction of power flow in the (Sensitive) ground-fault detection Breaker failure protection (ANSI 50BF)
zero sequence is calculated from the zero- (ANSI 50Ns, 51Ns / 50N, 51N) If a faulted portion of the electrical circuit
sequence current I0 and zero-sequence
For high-resistance grounded networks, a is not disconnected when a trip command
voltage V0.
sensitive input transformer is connected is issued to a circuit-breaker, another trip
For networks with an isolated neutral, the to a phase-balance neutral current trans- command can be initiated using the breaker
reactive current component is evaluated; former (also called core-balance CT). failure protection which trips the circuit-
for compensated networks, the active cur- breaker of an upstream feeder. Breaker fail-
The function can also be operated in the
rent component or residual resistive cur- ure is detected if, after a trip command is
normal mode as an additional short-
rent is evaluated. For special network issued and the current keeps on flowing into
circuit protection for neutral or residual
conditions, e.g. high-resistance grounded the faulted circuit. It is also possible to make
ground protection.
networks with ohmic-capacitive use of the circuit-breaker position contacts
ground-fault current or low-resistance (52a or 52b) for indication as opposed to
Phase-balance current protection (ANSI 46)
grounded networks with ohmic-inductive the current flowing through the circuit-
(Negative-sequence protection)
current, the tripping characteristics can be breaker.
rotated approximately ± 45 degrees. By measuring current on the high side of
the transformer, the two-element phase-
Two modes of ground-fault direction balance current/negative-sequence protec-
detection can be implemented: tripping tion detects high-resistance phase-to-phase
or “signalling only mode”. faults and phase-to-ground faults on the
It has the following functions: low side of a transformer (e.g. Dy 5 or 12
Delta/Star 150 deg.). This function provides
• TRIP via the displacement voltage VE. backup protection for high-resistance faults
• Two instantaneous elements or one through the transformer.
instantaneous plus one user-defined
characteristic.
• Each element can be set to forward,
reverse or non-directional.
• The function can also be operated in
the insensitive mode as an additional
short-circuit protection.

Siemens SIP · 2008 Revised July 2010 12/13


12 Motor Protection / 7SK80

Protection functions

Flexible protection functions


The 7SK80 enables the user to easily add
up to 20 additional protective functions.
Parameter definitions are used to link
standard protection logic with any chosen
characteristic quantity (measured or calcu-
lated quantity) (Fig. 12/10). The standard
logic consists of the usual protection ele-
ments such as the pickup set point, the set
delay time, the TRIP command, a block
function, etc. The mode of operation for
current, voltage, power and power factor
quantities can be three-phase or single-
phase. Almost all quantities can be oper- Fig. 12/10 Flexible protection functions
ated with ascending or descending pickup
stages (e.g. under and over voltage). All
stages operate with protection priority.
Protection functions/stages available are Trip circuit supervision (ANSI 74TC) Protection of motors require an additional
based on the available measured analog One or two binary inputs can be used for time constant. This is used to accurately
quantities: monitoring the circuit-breaker trip coil determine the thermal heating of the stator
including its incoming cables. An alarm during the running and motor stopped con-
Function ANSI No. signal occurs whenever the circuit is gener- ditions. The ambient temperature or the
ated. The circuit breaker trip coil is moni- temperature of the coolant can be detected
I< 37
tored in the open and closed position. either through internal RTD inputs or via
I>, IE> 50, 50N
Interlocking features can be implemented an external RTD-box. The thermal replica
V<, V>, VE> 27, 59, 64 to ensure that the beaker can only be closed of the overload function is automatically
if the trip coil is functional. adapted to the ambient conditions. If nei-
3I0>, I1>, I2>, I2/I1 50N, 46 ther internal RTD inputs nor an external
3V0>, V1><, V2>< 59N, 47
Lockout (ANSI 86) RTD-box exist, it is assumed that the ambi-
P><, Q>< 32 ent temperatures are constant.
All binary output statuses can be memo-
cos ϕ (p.f.)>< 55 rized. The LED reset key is used to reset Settable dropout delay times
f>< 81O, 81U the lockout state. The lockout state is also
stored in the event of supply voltage fail- If the relays are used in conjunction with
df/dt>< 81R electromechanical relays, in networks with
ure. Reclo- sure can only occur after the
lockout state is reset. intermittent faults, the long dropout times
For example, the following can be imple- of the electromechanical relay (several
mented: hundred milliseconds) can lead to prob-
Thermal overload protection (ANSI 49)
• Reverse power protection (ANSI 32R) lems in terms of time coordination/grad-
To protect cables and transformers, an ing. Proper time coordination/grading is
• Rate-of-frequency-change protection overload protection function with an only possible if the dropout or reset time is
(ANSI 81R) integrated warning/alarm element for approximately the same. This is why the
temperature and current can be used. parameter for dropout or reset times can
12 The temperature is calculated using a be defined for certain functions such as
thermal homogeneous body model time-overcurrent protection, ground
(per IEC 60255-8), it considers the energy short-circuit and phase-balance current
entering the equipment and the energy protection.
losses. The calculated temperature is con-
stantly adjusted according to the calculated
losses. The function considers loading his-
tory and fluctuations in load.

12/14 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Protection functions

n Motor protection
Restart inhibit (ANSI 66/86)
If a motor is subjected to many successive
starts, the rotor windings or rotor bars can
be heated up to a point were the electrical
connections between the rotor bars and the
end rings are damaged. As it is not possible
to physically measure the heat of the rotor
we need to determine the heat by mea-
suring the current the rotor is drawing
through the stator to excite the rotor. A
thermal replica of the rotor is established
using a I2t curve. The restart inhibit will
block the user from starting the motor if the
relay determined that the rotor reached a
temperature that will damage the rotor
should a start be attempted. The relay will
thus only allow a restart if the rotor has a
sufficient thermal reserve to start (Fig. 12/11).
Fig. 12/11
Emergency start-up
If the relay determines that a restart of the
for I > IMOTOR START Load jam protection (ANSI 51M)
motor is not allowed, the relay will issue a
block signal to the closing command, effec- 2 Load jam is activated when a sudden high
t = ⎛⎜ A ⎞⎟ ⋅ TA
I
tively blocking any attempt to start the mo- load is applied to the motor because of me-
⎝ I⎠
tor. The emergency startup will defeat this chanical failure of a pump for example. The
block signal if activated through a binary I = Actual current flowing sudden rise in current is detected by this
input. The thermal replica can also be reset function and can initiate an alarm or a trip.
IMOTOR START = Pickup current to detect a
to allow an emergency restart of the motor. motor start The overload function is too slow and thus
t = Tripping time not suitable.
Temperature monitoring (ANSI 38)
IA = Rated motor starting current
The relay can be applied with 5 internal Phase-balance current protection (ANSI 46)
RTDs. Two RTDs can be applied to each TA = Tripping time at rated motor (Negative-sequence protection)
bearing (the cause of 50% of typical motor starting current
If a rotating flux is set up in the stator that
failures). The remaining RTD is used to The relay equation is optimally adapted turns in the opposite direction of rotation
measure the ambient temperature. Stator based on the state of the motor. The value of the rotor. This flux will cause eddy cur-
temperature is calculated in by the current applied on TA is dependant on the state of rents in surface of the rotor bars and subse-
flowing through the stator windings. Up the motor, cold or warm. This warm or quently heat will be generated causing the
to 12 RTDs can be applied using external cold state of the motor is determined by rotor to heat up. This unwanted rotating
RTD modules. The RTDs can also be used the thermal model of the rotor. flux is caused if the supply voltage are un-
to monitor the thermal status of trans- symmetrical. This unsymmetrical supply
Because the flow of current is the cause of
formers or other pieces of primary equip-
the heating of the motor windings, this will cause a negative sequence current to 12
ment. (see “Accessories” , page 12/26). flow causing a rotating flux in the opposite
equation will accurately calculate the start-
ing supervision time. The accuracy will not direction to the machine rotation.
Starting time supervision/Locked rotor
protection (ANSI 48/14) be affected by reduced terminal voltage
that could cause a prolonged start. The trip Undercurrent monitoring (ANSI 37)
Starting time supervision protects the mo- time is an inverse current dependant char- A sudden drop in current, which can occur
tor against unwanted prolonged starts that acteristic (I2t). due to a reduced load, is detected with this
might occur in the event of excessive load function. This may be due to shaft that breaks,
torque or excessive voltage drops within Block rotor can also be detected using a
no-load operation of pumps or fan failure.
the motor, or if the rotor is locked. Rotor speed sensor connected to a binary input
temperature is calculated from measured of the relay. If activated it will cause an in-
Motor statistics
stator current. The tripping time is calcu- stantaneous trip.
lated according to the following equation: Essential statistical information is saved by
the relay during a start. This includes the
duration, current and voltage. The relay will
also provide data on the number of starts,
total operating time, total down time, etc.
This data is saved as statistics in the relay.

Siemens SIP · 2008 Revised July 2010 12/15


12 Motor Protection / 7SK80

Protection functions Customized functions (ANSI 51V, etc.) Switching authority


Additional functions, which are not time Switching authority is determined by set
n Voltage protection critical, can be implemented using the CFC parameters or through communications to
measured values. Typical functions include the relay. If a source is set to “LOCAL”,
Overvoltage protection (ANSI 59)
reverse power, voltage controlled over- only local switching operations are possi-
The two-element overvoltage protection current, phase angle detection, and zero- ble. The following sequence for switching
detects unwanted network and machine sequence voltage detection. authority is available: “LOCAL”; DIGSI
overvoltage conditions. The function can PC program, “REMOTE”.
operate either with phase-to-phase, phase-
to-ground, positive phase-sequence or There is thus no need to have a separate
negative phase-sequence voltage. Three- Control and automatic functions Local/Remote switch wired to the breaker
phase and single-phase connections are coils and relay. The local/remote selection
Control can be done using a function key on the
possible.
In addition to the protection functions, the front of the relay.
Undervoltage protection (ANSI 27) SIPROTEC Compact units also support all
control and monitoring functions that are Command processing
The two-element undervoltage protection
required for operating medium-voltage or This relay is designed to be easily integrated
provides protection against dangerous
high-voltage substations. into a SCADA or control system. Security
voltage drops (especially for electric ma-
chines). Applications include the isolation features are standard and all the function-
The main application is reliable control of
of generators or motors from the network ality of command processing is offered.
switching and other processes.
to avoid undesired operating conditions This includes the processing of single and
and a possible loss of stability. Proper oper- The status of primary equipment or auxil- double commands with or without feed-
ating conditions of electrical machines are iary devices can be obtained from auxiliary back, sophisticated monitoring of the con-
best evaluated with the positive-sequence contacts and communicated to the 7SK80 trol hardware and software, checking of
quantities. The protection function is ac- via binary inputs. Therefore it is possible the external process, control actions using
tive over a wide frequency range (45 to 55, to detect and indicate both the OPEN and functions such as runtime monitoring and
55 to 65 Hz). Even when falling below this CLOSED position or a fault or intermedi- automatic command termination after
frequency range the function continues to ate circuit-breaker or auxiliary contact po- output. Here are some typical applications:
sition.
work, however, with a decrease in accu- • Single and double commands using 1,
racy. The switchgear or circuit-breaker can be 1 plus 1 common or 2 trip contacts
The function can operate either with controlled via: • User-definable bay interlocks
phase-to-phase, phase-to-ground or posi- – integrated operator panel
– binary inputs • Operating sequences combining several
tive phase-sequence voltage, and can be switching operations such as control of
monitored with a current criterion. – substation control and protection system
– DIGSI 4 circuit-breakers, disconnectors and
Three-phase and single-phase connections grounding switches
are possible.
Automation / user-defined logic • Triggering of switching operations,
Frequency protection (ANSI 81O/U) With integrated logic, the user can create, indications or alarm by combination with
through a graphic interface (CFC), specific existing information
Frequency protection can be used for over-
frequency and underfrequency protection. functions for the automation of switchgear
or a substation. Functions are activated Assignment of feedback to command
Electric machines and parts of the system
are protected from unwanted frequency using function keys, binary input or The positions of the circuit-breaker or
deviations. Unwanted frequency changes through the communication interface. switching devices and transformer taps are
in the network can be detected and the acquired through feedback. These indica-
12 load can be removed at a specified fre- tion inputs are logically assigned to the
quency setting. corresponding command outputs. The
unit can therefore distinguish whether the
Frequency protection can be used over indication change is a result of switching
a wide frequency range (40 to 60 (for operation or whether it is an undesired
50 Hz), 50 to 70 (for 60 Hz). There are spontaneous change of state.
four elements (individually set as overfre-
quency, underfrequency or OFF) and each
element can be delayed separately. Block-
ing of the frequency protection can be per-
formed by activating a binary input or by
using an undervoltage element.

12/16 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

There is no exact mathematical method to


Further functions
calculate the wear or the remaining service
life of a circuit-breaker that takes arc-
Measured values
chamber’s physical conditions into account
The r.m.s. values are calculated from the when the CB opens. This is why various
acquired current and voltage along with methods of determining CB wear have
the power factor, frequency, active and evolved which reflect the different operator
reactive power. The following functions philosophies. To do justice to these, the
are available for measured value process- relay offers several methods:
ing:
• I
• Currents IL1, IL2, IL3, IE, IEE (67Ns) • Σ I x, with x = 1... 3
• Voltages VL1, VL2, VL3, VL1L2, VL2L3, VL3L1 • Σ i 2t
• Symmetrical components The devices also offer a new method for
I1, I2, 3I0; V1, V2, V0 determining the remaining service life:
• Power Watts, Vars, VA/P, Q, S • Two-point method
(P, Q: total and phase selective)
The CB manufacturers double-logarithmic
• Power factor (cos ϕ), switching cycle diagram (see Fig. 12/12) and
(total and phase selective) the breaking current at the time of contact
• Frequency opening serve as the basis for this method.
After CB opening, the two-point method
• Energy ± kWh, ± kVarh, forward and
calculates the remaining number of possible
Fig. 12/12 CB switching cycle diagram reverse power flow
switching cycles. Two points P1 and P2 only
• Mean as well as minimum and maximum have to be set on the device. These are speci-
Chatter disable current and voltage values fied in the CB’s technical data.
The chatter disable feature evaluates • Operating hours counter All of these methods are phase-selective
whether, in a set period of time, the num- • Mean operating temperature of the over- and a limit value can be set in order to ob-
ber of status changes of indication input load function tain an alarm if the actual value falls below
exceeds a specified number. If exceeded, or exceeds the limit value during determi-
the indication input is blocked for a certain • Limit value monitoring
nation of the remaining service life.
period, so that the event list will not record Limit values can be monitored using pro-
excessive operations. grammable logic in the CFC. Commands Commissioning
can be derived from this limit value indi-
cation. Commissioning could not be easier and
Indication filtering and delay
is supported by DIGSI 4. The status of
Binary indications can be filtered or de- • Zero suppression the binary inputs can be read individually
layed. In a certain range of very low measured and the state of the binary outputs can be
values, the value is set to zero to suppress set individually. The operation of switch-
Filtering serves to suppress brief changes in interference. ing elements (circuit-breakers, disconnect
potential at the indication input. The indi-
devices) can be checked using the switch-
cation is passed on only if the indication Metered values ing functions of the relay. The analog
voltage is still present after a set period of
For internal metering, the unit can calcu- measured values are represented as wide-
time. In the event of an indication delay,
late an energy metered value from the ranging operational measured values. To
there is a delay for a preset time. The infor-
measured current and voltage values. If an prevent transmission of information to
mation is passed on only if the indication
voltage is still present after this time.
external meter with a metering pulse out- the control center during maintenance, 12
put is available, the 7SK80 can obtain and the communications can be disabled to
Indication derivation process metering pulses through an indica- prevent unnecessary data from being trans-
tion input. mitted. During commissioning, all indica-
User-definable indications can be derived tions with test tag for test purposes can be
from individual or a group of indications. The metered values can be displayed and
connected to a control and protection
These grouped indications are of great passed on to a control center as an accu-
system.
value to the user that need to minimize the mulated value with reset. A distinction is
number of indications sent to the system made between forward, reverse, active and Test operation
or SCADA interface. reactive energy.
During commissioning, all indications can
Circuit-breaker wear monitoring be passed to a control system for test pur-
poses.
Methods for determining circuit-breaker
contact wear or the remaining service life
of a circuit-breaker (CB) allow CB mainte-
nance intervals to be aligned to their actual
degree of wear. The benefit lies in reduced
maintenance costs.

Siemens SIP · 2008 Revised July 2010 12/17


12 Motor Protection / 7SK80

System interface protocols (retrofittable)


Communication
IEC 61850 protocol
The relay offers flexibility with reference to Since 2004, the Ethernet-based IEC 61850
its communication to substation automa- protocol is a global standard for protection
tion systems and industrial SCADA or and control systems used by power utili-
DCS systems. The communication module ties. Siemens was the first manufacturer to
firmware can be changed to communicate implement this standard. This protocol
using another protocol or the modules can makes peer-to-peer communication possi-
be changed completely for a different con- ble. It is thus possible to set up masterless
nection or protocol. It will thus be possible systems to perform interlocking or transfer
to move to future communication proto- schemes. Configuration is done using
cols like popular Ethernet based protocols DIGSI.
with ease.
IEC 60870-5-103 protocol
USB interface
The IEC 60870-5-103 protocol is an inter-
There is an USB interface on the front of national standard for the transmission of
the relay. All the relay functions can be protective data and fault recordings. All Fig. 12/13
set using a PC and DIGSI 4 protection messages from the unit and also control IEC 60870-5-103: Radial fiber-optic connection
operation program. Commissioning tools commands can be transferred by means of
and fault analysis are built into the DIGSI published, Siemens-specific extensions to
program and are used through this inter- the protocol. As a further option a redun-
face. dant IEC 60870-5-103 module is available
as well. With the redundant module it will
Interfaces be possible to read and change single
A number of communication modules parameters.
suitable for various applications can be
fitted at the bottom of the housing. The PROFIBUS-DP protocol
modules can be easily replaced by the user. PROFIBUS-DP is a widespread protocol
The interface modules support the follow- in industrial automation. Through
ing applications: PROFIBUS-DP, SIPROTEC units make
• System/service interface their information available to a SIMATIC
Communication with a central control controller or receive commands from a
system takes place through this interface. central SIMATIC controller or PLC.
Radial or ring type station bus topologies Measured values can also be transferred
can be configured depending on the cho- to a PLC master.
sen interface. Furthermore, the units can
exchange data through this interface via MODBUS RTU protocol
Ethernet and the IEC 61850 protocol and This simple, serial protocol is mainly
can also be accessed using DIGSI. used in industry and by power utilities, and Fig. 12/14
Alternatively up to two external tempera- is supported by a number of relay manu- Bus structure for station bus with Ethernet and
ture monitoring boxes with a total of 12 IEC 61850, fiber-optic ring
facturers. SIPROTEC units function as
measuring sensors can be connected to MODBUS slaves, making their informa-
the system/service interface. tion available to a master or receiving in-
12 • Ethernet interface formation from it. A time-stamped event
The Ethernet interface was implemented list is available.
for fast access to a number of protection
units using DIGSI. It is also possible to
connect up to two external temperature
monitoring boxes (RTD-box for
Ethernet) with a total of 12 measuring
sensors to the Ethernet interface.
LSP2810.tif

Fig. 12/15
Optical Ethernet communication module
for IEC 61850 with integrated Ethernet-switch

12/18 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Communication

DNP 3.0 protocol


Power utilities use the serial DNP 3.0 (Dis-
tributed Network Protocol) for the station Max. 12
and network control levels. SIPROTEC temperatures
units function as DNP slaves, supplying
RJ45
their information to a master system or
receiving information from it. RTD box

System solutions for protection and station


control
Units featuring IEC 60870-5-103 interfaces
can be connected to SICAM in parallel via
the RS485 bus or radially by fiber-optic
link. Through this interface, the system is

LSA4818a-en.eps
open for the connection to other manufac-
turers systems (see Fig. 12/13).
Because of the standardized interfaces, 7SK80 7SK80 7SK80 7SK80
SIPROTEC units can also be integrated
into systems of other manufacturers or in
SIMATIC. Electrical RS485 or optical in-
terfaces are available. The best physical
data transfer medium can be chosen thanks
to opto-electrical converters. Thus, the Fig. 12/16
RS485 bus allows low-cost wiring in the System solution/communication
cubicles and an interference-free optical
connection to the master can be estab-
lished.
To substation Max. 12
For IEC 61850, an interoperable system so- controller temperatures
lution is offered with SICAM. Through the
100 Mbits/s Ethernet bus, the units are
linked with SICAM electrically or optically RTD box
to the station PC. The interface is stan-
dardized, thus also enabling direct connec-
tion to relays of other manufacturers and
into the Ethernet bus. With IEC 61850,
however, the relays can also be used in
other manufacturers’ systems (see Fig. 12/14).
Port B Port A

RJ45

12
LSA4825a-en.eps

7SK80
USB

DIGSI 4
(Local for
commissioning)

Fig. 12/17
Connection of an RTD box to 7SK80 using Ethernet

Siemens SIP · 2008 Revised July 2010 12/19


12 Motor Protection / 7SK80

Typical connections

n Connection of current
and voltage transformers
Standard connection
For grounded networks, the ground cur-
rent is obtained from the phase currents by
the residual current circuit.

Fig. 12/18
Residual current
circuit without direc-
tional element

Fig. 12/19
Sensitive ground-
current detection
without directional
element

12

Fig. 12/20
Residual current
circuit with direc-
tional element (no
directional element
for phase)

12/20 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Typical connections

Connection for compensated networks


The figure shows the connection of two
phase-to-ground voltages and the VE volt-
age of the broken delta winding and a
phase-balance neutral current transformer
for the ground current. This connection
maintains maximum precision for direc-
tional ground-fault detection and must
be used in compensated networks.

Fig. 12/21
Sensitive directional
ground-fault detec-
tion (no directional
element for phase)

Fig. 12/22 shows sensitive directional


ground-fault detection.

Fig. 12/22
Sensitive directional
ground-fault detec-
tion

Connection for all networks


The figure shows the connection to three
current transformers and two voltage 12
transformers in V-connection. Directional
ground overcurrent protection is not pos-
sible since the displacement voltage cannot
be calculated.

Fig. 12/23
Residual current
circuit with voltage
functions (no direc-
tional element for
phase)

Siemens SIP · 2008 Revised July 2010 12/21


12 Motor Protection / 7SK80

Typical applications

Overview of connection types


Type of network Function Current connection Voltage connection
(Low-resistance) grounded network Time-overcurrent protection Residual circuit, with 3 phase-current –
phase/ground non-directional transformers required, phase-balance
neutral current transformer possible
(Low-resistance) grounded networks Sensitive ground-fault protection Phase-balance neutral current –
transformers required
Isolated or compensated networks Time-overcurrent protection Residual circuit, with 3 or 2 phase –
phases non-directional current transformers possible
(Low-resistance) grounded networks Time-overcurrent protection Residual circuit, with 3 phase-current Phase-to-ground connection or
phases directional transformers possible phase-to-phase connection
Isolated or compensated networks Time-overcurrent protection Residual circuit, with 3 or 2 phase- Phase-to-ground connection or
phases directional current transformers possible phase-to-phase connection
(Low-resistance) grounded networks Time-overcurrent protection Residual circuit, with 3 phase-current Phase-to-ground connection
ground directional transformers required, phase-balance required
neutral current transformers possible
Isolated networks Sensitive ground-fault Residual circuit, if ground current 3 times phase-to-ground connection
protection > 0.05 IN on secondary side, other- or phase-to-ground connection with
wise phase-balance neutral current broken delta winding
transformers required
Compensated networks Sensitive ground-fault protection Phase-balance neutral current 3 times phase-to-ground connection
cos ϕ measurement transformers required or phase-to-ground connection with
broken delta winding

12

12/22 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Technical data

General unit data Binary inputs


Analog current inputs Type 7SK801/803/805/806 7SK802/804
Rated frequency fN 50 or 60 Hz (adjustable) Number (marshallable) 3 7
Rated current Inom 1 or 5 A Rated voltage range 24 to 250 V DC
Ground current, sensitive INs w 1.6 · Inom linear range1) Current input, energized Approx. 0.4 mA
Burden per phase and ground path (independent of the control voltage)
at Inom = 1 A Approx. 0.05 VA Secured switching thresholds (adjustable)
at Inom = 5 A Approx. 0.3 VA for rated voltages V high > 19 V DC
for sensitive ground fault Approx. 0.05 VA 24 to 125 V DC V low < 10 V DC
detection at 1 A
for rated voltages V high > 88 V DC
Load capacity current path 110 to 250 V DC V low < 44 V DC
Thermal (rms) 500 A for 1 s
150 A for 10 s for rated voltages V high > 176 V DC
20 A continuous 220 and 250 V DC V low < 88 V DC
Dynamic (peak value) 1250 A (half-cycle) Maximum permissible voltage 300 V DC
Loadability input for sensitive Input interference suppression 220 V DC across 220 nF at a
ground-fault detection INs 1) recovery time between two
Thermal (rms) 300 A for 1 s switching operations W 60 ms
100 A for 10 s
Output relay
15 A continuous
Dynamic (peak value) 750 A (half-cycle) Type 7SK801/803/805/806 7SK802/804
Analog voltage inputs NO contact 3 6
Rated voltage 34 to 225 V NO/NC selectable 2 (+ 1 live contact 2 (+ 1 live contact
(phase-to-ground connection) not allocatable) not allocatable)
34 to 200 V Switching capability MAKE Max. 1000 W/VA
(phase-to-phase connection)
Switching capability BREAK 40 W or 30 VA at L/R ≤ 40 ms
Measuring range 0 to 200 V
Switching voltage 250 V DC/AC
Burden at 100 V Approx. 0.005 VA
Admissible current per contact 5A
Overload capacity in voltage path (continuous)
Thermal (rms) 230 V continuous
Permissible current per contact 30 A for 1 s (NO contact)
Input voltage range UL 300 V (close and hold)
Auxiliary voltage
DC voltage Electrical tests
Voltage supply via an integrated Specification
converter
Standards IEC 60255 (product standard)
Rated auxiliary voltage Vaux DC 24 to 48 V 60 to 250 V ANSI/ IEEE C37.90 see individual
Permissible voltage ranges DC 19 to 60 V 48 to 300 V functions
AC ripple voltage, peak-to-peak, w 15 % of the auxiliary voltage VDE 0435
IEC 60255-11 for more standards see also
individual functions
Power input
Quiescent Approx. 5 W Insulation tests
Energized Approx. 12 W Standards IEC 60255-27 and IEC 60870-2-1
Bridging time for failure/ W 50 ms at V W 110 V DC High-voltage test (routine test) 2.5 kV, 50 Hz 12
short-circuit, IEC 60255-11 W 10 ms at V < 110 V DC All circuits except power supply,
(in the quiescent state) binary inputs, communication
AC voltage interface

Voltage supply via an integrated High-voltage test (routine test) 3.5 kV DC


converter Auxiliary voltage and binary inputs

Rated auxiliary voltage Vaux AC 115 V 230 V High-voltage test (routine test) 500 V, 50 Hz
Only isolated communication
Permissible voltage ranges AC 92 to 132 V 184 to 265 V interfaces (A and B)
Power input (at 115 V AC/230 V AC) Impulse voltage test (type test) 6 kV (peak value); 1.2/50 µs; 0.5 J;
Quiescent Approx. 5 VA All process circuits (except commu- 3 positive and 3 negative impulses at
Energized Approx. 12 VA nication interfaces) against the inter- intervals of 1 s
Bridging time for failure/short- W 10 ms at V = 115/230 V AC nal electronics
circuit (in the quiescent state)

1) Only in models with input for sensitive ground-fault detection


(see ordering data)

Siemens SIP · 2008 Revised July 2010 Technical Data page 1


12 Motor Protection / 7SK80

Technical data

Insulation tests (cont'd) Shock Semi-sinusoidal


Impulse voltage test (type test) 5 kV (peak value); 1.2/50 µs; 0.5 J; IEC 60255-21-2, class I; 5 g acceleration, duration 11 ms; each
All process circuits (except commu- 3 positive and 3 negative impulses at IEC 60068-2-27 3 shocks (in both directions of 3 axes)
nication interfaces) against each intervals of 1 s Seismic vibration Sinusoidal
other and against the productive IEC 60255-21-3, class II; 1 to 8 Hz: ± 7.5 mm amplitude
conductor terminal class III IEC 60068-3-3 (horizontal axis)
EMC tests for immunity; type tests 1 to 8 Hz: ± 3.5 mm amplitude
(vertical axis)
Standards IEC 60255-6 and -22 8 to 35 Hz: 2 g acceleration
(product standard) (horizontal axis)
IEC/EN 61000-6-2 8 to 35 Hz: 1 g acceleration
VDE 0435 (vertical axis)
For more standards see individual Frequency sweep 1 octave/min
functions 1 cycle in 3 orthogonal axes
1 MHz check, class III 2.5 kV (peak); 1 MHz; During transport
IEC 60255-22-1; IEC 61000-4-18; τ =15 µs; 400 surges per s;
IEEE C37.90.1 test duration 2 s; Ri = 200 Ω Standards IEC 60255-21 and IEC 60068

Electrostatic discharge, class IV 8 kV contact discharge; Vibration Sinusoidal


IEC 60255-22-2 15 kV air discharge; IEC 60255-21-1, class II; 5 to 8 Hz: ± 7.5 mm amplitude
and IEC 61000-4-2 both polarities; 150 pF; Ri = 330 Ω IEC 60068-2-6 8 to 150 Hz; 2 g acceleration
Frequency sweep 1 octave/min
Radio frequency electromagnetic field, 10 V/m; 80 MHz to 2.7 GHz; 20 cycles in 3 orthogonal axes
amplitude-modulated, class III 80 % AM; 1 kHz
IEC 60255-22-3; or IEC 61000-4-3 Shock Semi-sinusoidal
IEC 60255-21-2, class I; 15 g acceleration, duration 11 ms,
Fast transient disturbance variables/ 4 kV; 5/50 ns; 5 kHz; IEC 60068-2-27 each 3 shocks (in both directions
burst, class IV burst length = 15 ms; of the 3 axes)
IEC 60255-22-4 and repetition rate 300 ms; both polarities;
IEC 61000-4-4, IEEE C37.90.1 Ri = 50 Ω; test duration 1 min Continuous shock Semi-sinusoidal
IEC 60255-21-2, class I; 10 g acceleration, duration 16 ms,
High-energy surge voltages (SURGE), Impulse: 1.2/50 µs IEC 60068-2-29 each 1000 shocks (in both directions
Installation class III of the 3 axes)
IEC 60255-22-5; IEC 61000-4-5
Auxiliary voltage Common mode: 4 kV; 12 Ω; 9 µF
Diff. mode: 1 kV; 2 Ω; 18 µF Climatic stress tests
Measuring inputs, binary inputs Common mode: 4 kV; 42 Ω; 0.5 µF Temperatures
and relay outputs Diff. mode: 1 kV; 42 Ω; 0.5 µF
Standards IEC 60255-6
HF on lines, amplitude-modulated, 10 V; 150 kHz to 80 MHz;
Type test (in acc. with IEC 60068-2-1 –25 °C to +85 °C or –13 °F to +185 °F
class III; IEC 60255-22-6; 80 % AM; 1 kHz
and -2, Test Bd for 16 h)
IEC 61000-4-6,
Permissible temporary operating –20 °C to +70 °C or –4 °F to +158 °F
Power system frequency magnetic 30 A/m continuous; 300 A/m for 3 s
temperature (tested for 96 h) (clearness of the display may be
field
impaired from +55 °C or +131 °F)
IEC 61000-4-8, class IV
Recommended for permanent –5 °C to +55 °C or +23 °F to +131 °F
Radiated electromagnetic interference 20 V/m; 80 MHz to 1 GHz;
operation (in acc. with IEC 60255-6)
ANSI/IEEE C37.90.2 80 % AM; 1 kHz
Limit temperatures for storage –25 °C to +55 °C or –13 °F to +131 °F
Damped oscillations IEC 61000-4-18 2.5 (peak value)
100 kHz; 40 pulses per s; Limit temperatures for transport –25 °C to +70 °C or –13 °F to +158 °F
test duration 2 s; Ri = 200 Ω Storage and transport with factory packaging
12 EMC tests for noise emission; type tests Humidity
Standard IEC/EN 61000-6-4 Permissible humidity Mean value per year w 75 % relative
Radio noise voltage to lines, only 150 kHz to 30 MHz, limit class A humidity; on 56 days of the year up
auxiliary voltage IEC/CISPR 11 to 93 % relative humidity; condensa-
tion must be avoided!
Interference field strength 30 to 1000 MHz, limit class A
IEC/CISPR 11 It is recommended that all devices be installed such that they are not ex-
posed to direct sunlight, nor subject to large fluctuations in temperature
that may cause condensation to occur.
Mechanical stress tests
Unit design
Vibration, shock stress and seismic vibration
Type 7SK80**-*B 7SK80**-*/E
During stationary operation
Housing 7XP20
Standards IEC 60255-21 and IEC 60068
Dimensions See dimension drawings
Oscillation Sinusoidal
Housing width 1/6 1/6
IEC 60255-21-1, class II; 10 to 60 Hz: ± 0.075 mm amplitude;
IEC 60068-2-6 60 to 150 Hz: 1 g acceleration Weight in kg
Frequency sweep rate 1 octave/min Surface-mounting 4.5 kg (9.9 lb)
20 cycles in 3 orthogonal axes Flush-mounting 4 kg (8.8 lb)

Technical Data page 2 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Technical data

Unit design (cont'd) System interface


Degree of protection IEC 60870-5-103 protocol, single (continued)
acc. to EN 60529 Fiber optic
For equipment in the IP 50 Connection fiber-optic cable ST connector
surface-mounting housing
Terminal At the bottom part of the housing,
For equipment in the Front IP 51
mounting location “B”
flush-mounting housing Back IP 50
Optical wavelength λ = 820 nm
For operator protection IP 2x for current terminal
IP 1x for voltage terminal Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm
Degree of pollution, IEC 60255-27 2 Bridgeable distance Max. 1.5 km/0.9 miles
IEC 60870-5-103 protocol, redundant
Communication interfaces RS485, isolated
Operating interface (front of unit) Terminal At the bottom part of the housing,
Terminal USB, type B mounting location “B”, RJ45 socket

Transmission speed Up to 12 Mbit/s Test voltage 500 V/50 Hz

Bridgeable distance 5m Transmission rate Min. 2400 Bd, max. 57600 Bd;
factory setting 19200 Bd
Ethernet service interface (Port A)
Bridgeable distance RS485 Max. 1 km/3300 ft
Ethernet electrical for DIGSI or RTD box
IEC 61850 protocol
Operation With DIGSI
Ethernet, electrical (EN100) for IEC 61850 and DIGSI
Terminal At the bottom part of the housing,
mounting location “A”, RJ45 socket, Terminal At the bottom part of the housing,
100BaseT in acc. with IEEE 802.3 mounting location “B”, two RJ45
LED yellow: 10/100 Mbit/s (ON/OFF) connectors, 100BaseT in acc. with
LED green: connection/no connection IEEE 802.3
(ON/OFF) Test voltage 500 V/50 Hz
Test voltage 500 V/50 Hz Transmission rate 100 Mbit/s
Transmission speed 10/100 Mbit/s Bridgeable distance Max. 20 m/65.6 ft
Bridgeable distance 20 m (66 ft) Ethernet, optical (EN100) for IEC 61850 and DIGSI
Service interface for DIGSI 4/modem (Port B) Terminal At the bottom part of the housing,
Isolated RS 232/RS 485 mounting location “B”, LC connector,
100BaseT in acc. with IEEE 802.3
Terminal At the bottom part of the housing,
9-pin subminiature connector Transmission rate 100 Mbit/s
(SUB-D) Optical wavelength λ = 1300 nm
Test voltage 500 V/50 Hz Bridgeable distance Max. 2 km/1.24 miles
Transmission rate Min. 1200 Bd, max. 115200 Bd PROFIBUS DP
Bridgeable distance RS232 Max. 15 m/49.2 ft RS485, isolated
Bridgeable distance RS485 Max. 1 km/3300 ft Terminal At the bottom part of the housing,
Fiber optic (FO) mounting location “B”, 9-pin
subminiature connector (SUB-D)
Terminal At the bottom part of the housing,
Test voltage 500 V/50 Hz
ST connector
Transmission rate Up to 1.5 Mbaud
12
Optical wavelength λ = 820 nm
Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm Bridgeable distance 1000 m/3300 ft w 93.75 kbaud;
500 m/1640 ft w 187.5 kbaud;
Bridgeable distance Max. 1.5 km/0.9 miles 200 m/656 ft w 1.5 Mbaud
System interface (Port B) Fiber optic
IEC 60870-5-103 protocol, single Connection fiber-optic cable ST connector, double ring
RS 232/RS 485 Terminal At the bottom part of the housing,
mounting location “B”
Terminal At the bottom part of the housing,
mounting location “B”, 9-pin Optical wavelength λ = 820 nm
subminiature connector (SUB-D) Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm
Test voltage 500 V/50 Hz Bridgeable distance Max. 2 km/1.24 miles
Transmission rate Min. 1200 Bd, max. 115000 Bd, MODBUS RTU, DNP 3.0
factory setting 9600 Bd
RS485
Bridgeable distance RS232 15 m/49.2 ft
Terminal At the bottom part of the housing,
Bridgeable distance RS485 1 km/3300 ft mounting location “B”, 9-pin
subminiature connector (SUB-D)
Test voltage 500 V/50 Hz

Siemens SIP · 2008 Revised July 2010 Technical Data page 3


12 Motor Protection / 7SK80

Technical data

System interface (cont'd) Dropout characteristics with


Transmission rate Up to 19200 baud disk emulation
IEC Inverse (type A), very inverse (type B),
Bridgeable distance Max. 1 km/3300 ft acc. to IEC 60255-3 or BS 142 extremely inverse (type C),
Fiber optic long inverse (type B)
Connection fiber-optic cable ST connector transmitter/receiver ANSI/IEEE Inverse, short inverse, long inverse,
moderately inverse, very inverse,
Terminal At the bottom part of the housing, extremely inverse, definite inverse
mounting location “B”
Pickup threshold IEC and ANSI Approx. 1.1 · Ip
Optical wavelength λ = 820 nm
Dropout setting IEC and ANSI
Permissible path attenuation Max. 8 dB, for glass fiber 62.5/125 µm Without disk emulation Approx. 1.05 · Ip setting value for
Bridgeable distance Max. 1.5 km/0.9 miles Ip/Inom W 0.3, corresponds to
approx. 0.95 · pickup value
With disk emulation Approx. 0.9 · Ip setting value
Functions
Tolerances
Definite-time overcurrent protection (ANSI 50, 50N, 67N) Pickup/dropout thresholds Ip, IEp 3 % of setting value or 75 mA1)
Operating modes 3-phase (standard) or 2-phase Trip time for 2 w I/Ip w 20 5 % of reference (calculated) value
A (L1) and C (L3) + 2 % current tolerance or 30 ms
Number of elements (stages) 50-1, 50-2, 50-3 (I>, I>>, I>>>) Dropout time for I/Ip w 0.9 5 % of reference (calculated) value
(phases) + 2 % current tolerance or 30 ms
50N-1, 50N-2, 50N-3 (IE>, IE>>, Determination of direction for ground faults
IE>>>) (ground)
Polarization/type With zero-sequence quantities
Setup setting ranges 3V0, 3I0 or
Pickup current 0.5 to 175 A or ∞1) (in steps of 0.01 A) with negative-sequence quantities
50-1, 50-2, 50-3 (phases) 3V2, 3I2
Pickup current 0.25 to 175 A or ∞1) (in steps of 0.01 A)
Forward range Vref,rot ± 86 °
50N-1, 50N-2, 50N-3 (ground)
Rotation of reference voltage Vref,rot –180 ° to 180 ° (in steps of 1 °)
Delay times T 0 to 60 s or ∞ (in steps of 0.01 s)
Directional sensitivity
Dropout delay time 50/50N 0 to 60 s (in steps of 0.01 s) Zero-sequence quantities 3V0, 3I0 VN ≈ 2.5 V displacement voltage,
TDROPOUT (DO) measured
Times 3V0 ≈ 5 V displacement voltage,
Pickup times (without inrush calculated
restraint, with inrush restraint Negative-sequence quantities 3V2 ≈ 5 V negative-sequence voltage
+ 10 ms) 3V2, 3I2 3I2 ≈ 225 mA negative-sequence
current 1)
With twice the setting value Approx. 30 ms
With ten times the setting value Approx. 20 ms Times
Pickup times (without inrush
Dropout time Approx. 30 ms
restraint; with inrush restraint
Dropout ratio Approx. 0.95 for I/Inom W 0.3 + 10 ms) 50-1, 50-2, 50N-1, 50N-2
Tolerances With twice the setting value Approx. 45 ms
Pickup 3 % of setting value or 75 mA1) With ten times the setting value Approx. 40 ms
Delay times T, TDO 1 % or 10 ms Dropout time 50-1, 50-2, 50N-1, 50N-2 Approx. 40 ms
Inverse-time overcurrent protection (ANSI 51, 51N, 67N) Tolerances
Operating mode 3-phase (standard) or Angle faults for phase and earth ± 3 ° electrical
2-phase A (L1) and C (L3) faults
12 Setting ranges Inrush restraint
Pickup currents 51 (phases)/(IP) 0.5 to 20 A1) (in steps of 0.01 A) Controlled functions Time-overcurrent elements, I>, IE>,
Pickup currents 51N (ground)/(IEp) 0.25 to 20 A1) (in steps of 0.01 A) Ip, IEp (directional, non-directional)
Time multiplier T for 51, 51N 0.05 to 3.2 s or ∞ (in steps of 0.01 s) 50-1, 50N-1, 51, 51N, 67N-1
(IP, IEp) (IEC characteristics) Lower function limit At least one phase current
Time multiplier D for 51, 51N 0.50 to 15 s or ∞ (in steps of 0.01 s) (50 Hz and 100 Hz) W 125 mA for
(ANSI characteristics) Inom = 5 A, W 50 mA for Inom = 1 A
Trip characteristics
Upper function limit (setting range) 1.5 to 125 A1) (in steps of 0.01 A)
IEC Inverse (type A), very inverse (type B),
acc. to IEC 60255-3 or BS 142 extremely inverse (type C), Setting range, stabilization factor I2f /I 10 to 45 % (in steps of 1 %)
long inverse (type B) Crossblock IA(L1), IB(L2), IC(L3) ON/OFF
ANSI/IEEE Inverse, short inverse, long inverse,
moderately inverse, very inverse,
extremely inverse, definite inverse

1) At Inom = 1 A, all limits divided by 5.

Technical Data page 4 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Technical data

Cold-load pickup/dynamic setting change Overvoltages 59-1, 59-2 (V>, V>>)


Controllable functions Time-overcurrent protection (sepa- Measured quantity used with
rated acc. to phases and ground) Three-phase connection Positive-sequence system of the voltages
Negative-sequence system of the volt-
Initiation criteria Current criterion “BkrClosed/MIN”
ages Highest phase-to-phase voltage
CB position via aux. contacts,
Highest phase-to-ground voltage
binary input, auto-reclosure ready
Single-phase connection Connected single-phase-to-ground
Time control 3 time elements
voltage
(TCB Open, TActive, TStop)
Setting ranges
Current control Current threshold “BkrClosed/MIN”
Connection of phase-to-ground
(reset on dropping below threshold;
voltage:
monitoring with timer)
Evaluation of phase-to-ground 20 to 150 V (in steps of 1 V)
Setting ranges voltages
1)
Current control 0.2 to 5 A (in steps of 0.01 A) Evaluation of phase-to-phase 20 to 260 V (in steps of 1 V)
Time until changeover to 0 to 21600 s (= 6 h) (in steps of 1 s) voltages
dynamic setting TCB Open Evaluation of positive-sequence 20 to 150 V (in steps of 1 V)
Period dynamic settings are 1 to 21600 s (= 6 h) (in steps of 1 s) system
effective after a reclosure TActive Evaluation of negative-sequence 2 to 150 V (in steps of 1 V)
system
Fast reset time TStop 1 to 600 s (= 10 min.) or ∞
Connection of phase-to-phase
(fast reset inactive) (in steps of 1 s)
voltages:
Dynamic settings or pickup currents Adjustable within the same ranges Evaluation of phase-to-phase 20 to 150 V (in steps of 1 V)
and time delays or time multipliers and with the same steps (increments) voltage
as the directional and non-directional Evaluation of positive-sequence 20 to 150 V (in steps of 1 V)
time-overcurrent protection system
Voltage protection (ANSI 27, 59) Evaluation of negative-sequence 2 to 150 V (in steps of 1 V)
system
Undervoltages 27-1, 27-2 (V<, V<<) Connection single phase 20 to 150 V (in steps of 1 V)
Measured quantity used with Dropout ratio r
Three-phase connection Positive-sequence system of the voltages for 59-1, 59-2 (V>, V>>) 0.90 to 0.99 (in steps of 0.01 V)
Lowest phase-to-phase voltage Dropout threshold for r · 59-1 (V>) Max. 150 V for phase-to-phase voltage
Lowest phase-to-ground voltage r · 59-2 (V>>) Max. 260 V for phase-to-ground volt.
Single-phase connection Connected single-phase-to-ground Hysteresis Min. 0.6 V
voltage
Time delay T59-1, T59-2 (V>, V>>) 0 to 100 s (in steps of 0.01 s)
Setting ranges or ∞ (disabled)
Connection of phase-to-ground 10 to 120 V (in steps of 1 V)
voltage Times
Connection of phase-to-phase 10 to 120 V (in steps of 1 V) Pickup times
voltage Undervoltage 27-1, 27-2 (V<, V<<)
Connection of single phase 10 to 120 V (in steps of 1 V) 27-1 V1, 27-2 V1 Approx. 50 ms
Dropout ratio2) r 1.01 to 3 (in steps of 0.01) Overvoltage 59-1, 59-2 (V>, V>>) Approx. 50 ms
for 27-1, 27-2 (V<, V<<) Overvoltage 59-1 V1, 59-2 V1,
59-1 V2, 59-2 V2 Approx. 60 ms
Dropout threshold for r · 27-1 (V<) Max. 130 V for phase-to-phase voltage
r · 27-2 (V<<) Max. 225 V for phase-to-ground volt. Dropout times
Undervoltage 27-1, 27-2 (V<, V<<)
Hysteresis Min. 0.6 V 27-1 V1, 27-2 V1 Approx. 50 ms
Overvoltage 59-1, 59-2 (V>, V>>) Approx. 50 ms
Time delays T27-1(V<), T27-2 (V<<) 0 to 100 s (in steps of 0.01 s)
Overvoltage 59-1 V1, 59-2 V1,
or ∞ (disabled) 12
59-1 V2, 59-2 V2 Approx. 60 ms
Current criterion “BkrClosed/MIN” 0.2 to 5 A1) (in steps of 0.01 A)
Tolerances
Pickup voltage limits 3 % of setting value or 1 V
Delay times T 1 % of setting value or 10 ms

1) At Inom = 1 A, all limits divided by 5. 2) r = Vdropout/Vpickup.

Siemens SIP · 2008 Revised July 2010 Technical Data page 5


12 Motor Protection / 7SK80

Technical data

Negative-sequence protection (ANSI 46) Times


Definite-time characteristic (ANSI 46-1 and 46-2) Pickup times f >, f< Approx. 80 ms
Dropout times f >, f< Approx. 80 ms
Setting ranges
Unbalanced load tripping element Dropout difference
46-1, 46-2 (I2>, I2>>) 0.5 to 15 A or ∞ (disabled)1) Δ f = |pickup value – dropout value| 0.02 to 1 Hz
(in steps of 0.01 A) Dropout
Delay times 46-1, 46-2 (TI2>, TI2>>) 0 to 60 s or ∞ (disabled)1) Ratio undervoltage blocking Approx. 1.05
(in steps of 0.01 s) Tolerances
Dropout delay times 46 TDropout 0 to 60 s (in steps of 0.01 s) Pickup thresholds
Functional limit All phase currents w 50 A1) Frequency 81O/U f >, f< 15 mHz (with V = Vnom, f = fnom)
Times Undervoltage blocking 3 % of setting value or 1 V
Pickup times Approx. 35 ms Delay times 1 % of the setting value or 10 ms
Dropout times Approx. 35 ms Starting time monitoring for motors (ANSI 48)
Dropout ratio Setting ranges
Characteristic Approx. 0.95 for I2/Inom W 0.3 Startup current of the motor 2.5 to 80 A1) (in steps of 0.01)
46-1, 46-2/I2>, I2>> ISTARTUP
Tolerances Pickup threshold IMOTOR START 2 to 50 A1) (in steps of 0.01)
Pickup values 3 % of the set value or 75 mA 1) Permissible startup time 1 to 180 s (in steps of 0.1 s)
46-1, 46-2/I2>, I2>> Tmax. STARTUP
Delay times 1 % or 10 ms Maximum startup time with 0.5 to 180 s or disabled (in steps of 0.1 s)
warm motor Tmax. STARTUP W
Inverse-time characteristic (ANSI 46-TOC) Maximum startup time with 0 to 80 % or disabled (in steps of 1 %)
Setting ranges cold motor
Pickup value 46-TOC/I2p 0.5 to 10 A1) (in steps of 0.01 A) Permissible locked rotor time 0.5 to 180 s or disabled (in steps of 0.1 s)
Time multiplier TI2p (IEC) 0.05 to 3.2 s or ∞ (disabled) TLOCKED-ROTOR
(in steps of 0.01 s) Tripping time characteristic 2
Time multiplier DI2p (ANSI) 0.5 to 15 s or ∞ (disabled) ⎛I ⎞
For I > IMOTOR START t TRIP = ⎜ STARTUP ⎟ ⋅ Tmax. STARTUP
(in steps of 0.01 s) ⎝ I rms ⎠
Functional limit All phase currents w 50 A1) ISTARTUP = Motor starting
Trip characteristics acc. to current setting
IEC Inverse, very inverse, I = Actual current
extremely inverse flowing
ANSI Inverse, moderately inverse, Tmax. STARTUP = Tripping time for
very inverse, extremely inverse rated motor startup
current
Pickup threshold IEC and ANSI Approx. 1.10 · I2p IMOTOR START = Pickup threshold
Tolerances setting, used to
1)
Pickup threshold I2p 3 % of the setting value or 75 mA detect motor startup
Time for 2 w I/I2p w 20 5 % of reference (calculated) value tTRIP = Tripping time in
+ 2 % current tolerance or 30 ms seconds
Dropout characteristic with disk Inverse, moderately inverse, Dropout ratio IMOTOR START Approx. 0.75
emulation acc. to ANSI very inverse, extremely inverse Tolerances
Pickup threshold 3 % of setting value or 75 mA1)
Dropout value
Delay time 5 % or 30 ms
IEC and ANSI without disk Approx. 1.05 · I2p setting value,
emulation corresponds to approx. 0.95 · pickup Load jam protection for motors (ANSI 51M)
ANSI with disk emulation Approx. 0.90 · I2p setting value Setting ranges
12 Tolerances Current threshold for 2.5 to 60 A1) (in steps 0.01 A)
Dropout value I2p 3 % of the set value or 75 mA 1) alarm and trip
Delay times 0 to 600 s (in steps 0.01 s)
Time for 2 w I2/I2p w 0.90 5 % of reference (calculated) Blocking duration after 0 to 600 s (in steps 0.01 s)
value +2 % current tolerance, or 30 ms motor start
Frequency protection (ANSI 81O/U) Tolerances
Pickup threshold 3 % of setting value or 75 mA1)
Number of frequency elements 4, each can be set to f > or f<
Delay time 1 % or 10 ms
Setting ranges
Pickup values f > or f< 40 to 60 Hz (in steps of 0.01 Hz)
for fnom = 50 Hz
Pickup values f > or f< 50 to 70 Hz (in steps of 0.01 Hz)
for fnom = 60 Hz
Delay times T 0 to 100 s or ∞ (disabled)
(in steps of 0.01 s)
Undervoltage blocking, with 10 to 150 V (in steps of 1 V)
positive-sequence voltage V1

1) At Inom = 1 A, all limits divided by 5.

Technical Data page 6 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Technical data

Restart inhibit for motors (ANSI 66) Thermal overload protection (ANSI 49)
Setting ranges Setting ranges
Motor starting current relative 1.1 to 10 (in steps of 0.1) Factor k 0.1 to 4 (in steps of 0.01)
to rated motor current Time constant 1 to 999.9 min (in steps of 0.1 min)
IMOTOR START/IMotor Nom
Rated motor current IMotor Nom 1 to 6 A1) (in steps of 0.01 A) Thermal alarm ΘAlarm /ΘTrip 50 to 100 % of the trip excessive
Max. permissible starting time 1 to 320 s (in steps of 1 s) temperature (in steps of 1 %)
TStart Max. Current warning stage IAlarm 0.5 to 20 A (in steps of 0.01 A)
Equilibrium time TEqual 0 min to 320 min (in steps of 0.1 min)
Extension factor when stopped 1 to 10 with reference to the time
Minimum inhibit time 0.2 min to 120 min (in steps of 0.1 min)
kτ factor constant with the machine running
TMIN. INHIBIT TIME
(in steps of 0.1)
Max. permissible number of 1 to 4 (in steps of 1)
warm startups nWARM Rated overtemperature (for Inom) 40 to 200 °C (in steps of 1 °C)
Difference between cold and 1 to 2 (in steps of 1) Tripping characteristic
(I / k ⋅ Inom ) − (I pre / k ⋅ I nom )
2
warm startups nCOLD – nWARM For (I/k · Inom) ≤ 8 t = τ th ⋅ ln
(I / k ⋅ I nom ) − 1
2
Extension of time constant at 0.2 to 100 (in steps of 0.1)
stop kτ at STOP
Extension of time constant at 0.2 to 100 (in steps of 0.1) t = Tripping time in minutes
running kτ at RUNNING τth = Temperature-rise time
constant
Restart threshold
I = Actual load current
− ( n cold − 1 ) ⋅ TSTART max
⎛ I STARTUP ⎞ ⎛ ⎞
2
Ipre = Preload current
⎟ ⋅ ⎜⎜ 1– e ⎟
τR
ΘRESTART = ⎜ k = Setting factor acc. to
⎝ I Motor Nom ⋅ k R ⎠ ⎝ ⎟
⎠ IEC 60255-8
Where: ΘRESTART = Temperature limit Inom = Rated (nominal) current of
below which restarting the protected object
is possible Dropout ratios
kR = k-factor for the rotor Θ/ΘTrip Drops out with ΘAlarm
ISTARTUP = Startup current Θ/ΘAlarm Approx. 0.99
IMOT Nom = Motor rated current I/IAlarm Approx. 0.97
TSTART max = Max. startup time Tolerances
τR = Thermal rotor time With reference to k · Inom 3 % or 75 mA1)
constant 2 % class acc. to IEC 60255-8
ncold = Max. number of cold
starts With reference to tripping time 3 % or 1 s for I/(k · Inom) > 1.25
3 % class acc. to IEC 60255-8
Undercurrent monitoring (ANSI 37)
(Sensitive) ground-fault protection (ANSI 59N/64, 50Ns, 51Ns, 67Ns)
Signal from the operational Predefined with programmable logic
measured values Displacement voltage element for all types of ground fault (ANSI 59N/64)
Temperature detection Setting ranges
Displacement voltage (measured) V0> 1.8 to 200 V (in steps of 0.1 V)
Temperature detection through internal module (only 7SK805/7SK806) Displacement voltage (calculated) 3V0> 10 to 225 V (in steps of 0.1 V)
Number of temperature detectors 5 Delay time TDelay pickup 0.04 to 320 s or ∞ (in steps of 0.01 s)
Measuring method Pt 100 Ω or Ni 100 Ω or Ni 120 Ω Additional trip delay TV Delay 0.1 to 40,000 s or ∞ (in steps of 0.01 s)
3-wire connection, shielded cable Operating time Approx. 50 ms
Installation identification “Oil” or “Ambient” or “Stator” or Dropout ratio 0.95 or (pickup value –0.6 V)
“Bearing” or “Other”
Tolerances (measurement)
Temperature detection through external RTD boxes Pickup threshold V0 (measured) 3 % of setting value or 0.3 V
Pickup threshold 3V0 (calculated) 3 % of setting value or 3 V
12
Connectable RTD-boxes 1 or 2
Delay times 1 % of setting value or 10 ms
Number of temperature detectors Max. 6
per RTD-box Phase detection for ground fault in an ungrounded system
Measuring method Pt 100 Ω or Ni 100 Ω or Ni 120 Ω Measuring principle Voltage measurement
Selectable 2- or 3-phase connection, (phase-to-ground)
shielded cable Setting ranges
Mounting identification “Oil” or “Ambient” or “Stator” or Vph min (ground-fault phase) 10 to 100 V (in steps of 1 V)
“Bearing” or “Other” Vph max (healthy phases) 10 to 100 V (in steps of 1 V)
Thresholds for indications Tolerance 3 % of setting value or 1 V
For each measuring detector Measurement tolerance
Stage 1 –50 °C to 250 °C (in steps of 1 °C) acc. to VDE 0435, Part 303
–58 °F to 482 °F or ∞ (no indication)
Stage 2 –50 °C to 250 °C (in steps of 1 °C)
–58 °F to 482 °F or ∞ (no indication)

Siemens SIP · 2008 Revised July 2010 Technical Data page 7


12 Motor Protection / 7SK80

Technical data

(Sensitive) ground-fault protection (ANSI 59N/64, 50Ns, 51Ns, 67Ns) (cont'd) Minimum voltage Vmin.
Ground-fault pickup for all types of ground faults V0 measured 0.4 to 50 V (in steps of 0.1 V)
3V0 calculated 10 to 90 V (in steps of 1 V)
Definite-time characteristic (ANSI 50Ns) Phase angle 50Ns ϕ –180 ° to 180 ° (in steps of 0.1 °)
Setting ranges Delta phase angle 50Ns Δ ϕ 0 ° to 180 ° (in steps of 0.1 °)
Pickup current 50Ns-2 Pickup, Angle correction for cable CT
50Ns-1 Pickup; (IEE>, IEE>>)
For sensitive 5-A-transformer 0.005 to 8 A1) (in steps of 0.005 A) Angle correction F1, F2 0 ° to 5 ° (in steps of 0.1 °)
For normal 5-A-transformer 0.25 to 175 A1) (in steps of 0.05 A) (for resonant grounded system)
Delay times T for 50Ns-2 Delay, 0 to 320 s ∞ (disabled) Current value I1, I2 for angle
50Ns-1 Delay (TIEE>, TIEE>>) (in steps of 0.01 A) correction
Dropout delay time TDropout 0 to 60 s (in steps of 0.01 s) For sensitive 5-A-transformer 0.005 to 8 A1) (in steps of 0.005 A)
Operating times w 50 ms (directional/non-directional) For normal 5-A-transformer 0.25 to 175 A1) (in steps of 0.05 A)
Dropout ratio Approx. 0.95 for 50Ns/IEE > 50 mA Tolerances
For sensitive 5-A-transformer 3 % of setting value or 5 mA1)
Tolerances (measurement) Approx. 20 % for setting values < 10 mA
Pickup threshold For normal 5-A-transformer 3 % of setting value or 75 mA1)
For sensitive 5-A-transformer 3 % of setting value or 5 mA1) Angle tolerance 3°
Approx. 20 % for setting values < 10 mA
For normal 5-A-transformer 3 % of setting value or 75 mA1) Note: Due to the high sensitivity, the linear range of the measuring input
Delay times 1 % of setting value or 10 ms Inom with integrated sensitive input transformer is from 0.001 · Inom
Ground-fault pickup for all types of ground faults to 1.6 · Inom. For currents greater than 1.6 · Inom correct direction
Inverse-time characteristic (ANSI 51Ns) determination can no longer be guaranteed.

User-defined characteristic Defined by a maximum of 20 pairs Breaker failure protection (ANSI 50BF)
of current and delay time values,
Setting ranges
directional measurement method
Pickup thresholds 0.25 to 100 A1) (in steps of 0.01 A)
“cos phi and sin phi”
Delay time 0.06 to 60 s or ∞ (in steps of 0.01 s)
Setting ranges
Pickup current 51Ns; IEEp Times
For sensitive 5-A-transformer 0.005 A to 7 A1) (in steps of 0.005 A) Pickup times
For normal 5-A-transformer 0.25 to 20 A1) (in steps of 0.05 A) with internal start is included in the delay time
Time multiplier T51Ns, IIEEp 0.1 to 4 s or ∞ (disabled) with external start is included in the delay time
(in steps of 0.01 s) Dropout times Approx. 25 ms

Pickup threshold Approx. 1.1 · I51Ns/1.1 · IEEp Tolerances


Pickup thresholds 3 % of setting value or 75 mA1)
Dropout ratio Approx. 1.05 · I51Ns/1.05 · IEEp Delay time 1 % or 20 ms
for I51Ns (IEEp) > 50 mA
Flexible protection functions (e.g. ANSI 27, 32, 37, 47, 50, 55, 59, 81R)
Tolerances
For sensitive 5-A-transformer 3 % of setting value or 5 mA 1) Operating modes/measuring quantities
Approx. 20 % for setting values < 10 mA 3-phase I, I1, I2, I2/I1, 3I0, V, V1, V2, 3V0,
For normal 5-A-transformer 3 % of setting value or 75 mA1) Pforward, Preverse, Qforward, Qreverse, cos ϕ
Operating time tolerance 7 % of reference (calculated) value 1-phase I, IN, INS, IN2, V, VN, Vx,
in linear range for 2 w I/I51Ns (IEEp) w 20 + 2 % cur- Pforward, Preverse, Qforward, Qreverse, cos ϕ
rent tolerance, or 70 ms Without fixed phase relation f, df/dt, binary input
Pickup when Exceeding or falling below threshold
Direction determination for all types of ground-faults (ANSI 67Ns) value
Measuring method “cos ϕ/sin ϕ” Setting ranges
Direction measurement IN and VN measured or Pickup thresholds
12 3I0 and 3V0 calculated Current I, I1, I2, 3I0, IN 0.25 to 200 A1) (in steps of 0.01 A)
Current ratio I2/I1 15 to 100 % (in steps of 1 %)
Measuring principle Active/reactive power measurement
Sensitive ground current INS 0.001 to 1.5 A (in steps of 0.001 A)
Setting ranges
Voltages V, V1, V2, 3V0 2 to 260 V (in steps of 0.1 V)
Measuring enable IRelease direct.
Displacement voltage VN 2 to 200 V (in steps of 0.1 V)
(current component perpendicu-
lar (90 °) to directional limit line) Power P, Q 10 to 50000 W1) (in steps of 0.1 W)
For sensitive 5-A-transformer 1)
0.005 to 8 A (in steps of 0.005 A) Power factor (cos ϕ) –0.99 to +0.99 (in steps of 0.01)
For normal 5-A-transformer 0.25 to 175 A1) (in steps of 0.05 A) Frequency fN = 50 Hz 40 to 60 Hz (in steps of 0.01 Hz)
Dropout ratio Approx. 0.8 fN = 60 Hz 50 to 70 Hz (in steps of 0.01 Hz)
Rate-of-frequency change df/dt 0.1 to 20 Hz/s (in steps of 0.01 Hz/s)
Direction phasor ϕCorrection –45 ° to +45 ° (in steps of 0.1 °)
Dropout ratio >- element 1.01 to 3 (insteps of 0.01)
Dropout delay TReset delay 1 to 60 s (in steps of 1 s)
Dropout ratio <- element 0.7 to 0.99 (in steps of 0.01)
Measuring method “ϕ (V0/I0)” Dropout difference f 0.02 to 1 Hz (in steps of 0.01 Hz)
Direction measurement IN and VN measured or Pickup delay time (standard) 0 to 60 s (in steps of 0.01 s)
3I0 and 3V0 calculated Pickup delay for I2/I1 0 to 28800 s (in steps of 0.01 s)
Trip delay time 0 to 3600 s (in steps of 0.01 s)
Note: When using the sensitive transformer, the linear range of the mea-
Dropout delay time 0 to 60 s (in steps of 0.01 s)
suring input for sensitive ground fault detection is from 0.001 A to
1.6 A or 0.005 A to 8 A. The function is however still preserved for
higher currents. 1) At Inom = 1 A, all limits divided by 5.

Technical Data page 8 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Technical data

Flexible protection functions (e.g. ANSI 27, 32, 37, 47, 50, 55, 59, 81R) (cont'd) Voltages
Times Phase-to-ground voltages In kV primary, in V secondary
Pickup times VA-N, VB-N, VC-N or in % Vnom
Current, voltage Phase-to-phase voltages
(phase quantities) VA-B, VB-C, VC-A, VSYN
With 2 times the setting value Approx. 30 ms VN, Vph-N, Vx or V0
With 10 times the setting value Approx. 20 ms Positive-sequence component V1
Current, voltages Negative-sequence component V2
(symmetrical components) Range 10 to 120 % of Vnom
With 2 times the setting value Approx. 40 ms Tolerance*) 1.5 % of measured value or 0.5 % of Vnom
With 10 times the setting value Approx. 30 ms S, apparent power In kVAr (MVAr or GVAr) primary
Power and in % of Snom
Typical Approx. 120 ms
Maximum (low signals and Approx. 350 ms Range 0 to 120 % of Snom
thresholds) Tolerance*) 1.5 % of Snom
Power factor 300 to 600 ms for V/Vnom and I/Inom = 50 to 120 %
Frequency Approx. 100 ms P, active power With sign, total and phase-
Rate-of-frequency change segregated in kW (MW or GW)
With 1.25 times the setting value Approx. 220 ms primary and in % Snom
Binary input Approx. 20 ms
Range 0 to 120 % of Snom
Dropout times Tolerance*) 2 % of Snom
Current, voltage (phase < 20 ms for V/Vnom and I/Inom = 50 to 120 %
quantities) and ⏐cos ϕ⏐ = 0.707 to 1 with
Current, voltages (symmetrical < 30 ms Snom = 3 ⋅ Vnom ⋅ I nom
components)
Q, reactive power With sign, total and phase-
Power
segregated in kVAr (MVAr or GVAr)
Typical < 50 ms
primary and in % of Snom
Maximum < 350 ms
Power factor < 300 ms Range 0 to 120 % of Snom
Frequency < 100 ms Tolerance*) 2 % of Snom
Rate-of-frequency change < 200 ms for V/Vnom and I/Inom = 50 to 120 %
Binary input < 10 ms and ⏐sin ϕ⏐ = 0.707 to 1 with
Tolerances Snom = 3 ⋅ Vnom ⋅ I nom
Pickup thresholds cos ϕ, power factor (p.f.) Total and phase-segregated
Current 3 % of setting value or 75 mA1) Range –1 to +1
Current (symmetrical 4 % of setting value or 100 mA1) Tolerance*) 2 % for ⏐cos ϕ⏐ ≥ 0.707
components)
Voltage 3 % of setting value or 0.2 V Frequency f In Hz
Voltage (symmetrical 4 % of setting value or 0.2 V Range fnom ± 5 Hz
components) Tolerance*) 20 mHz
Power 3 % of setting value or 2.5 W 1)
(for rated values) Temperature overload protection In %
Power factor 3 degrees Θ/ΘTrip
Frequency 15 mHz Range 0 to 400 %
Rate-of-frequency change 5 % of setting value or 0.05 Hz/s Tolerance*) 5 % class accuracy per IEC 60255-8
Times 1 % of setting value or 10 ms
Temperature restart inhibit In %
ΘL/ΘL Trip
Additional functions Range 0 to 400 %
Operational measured values Tolerance*) 5 % class accuracy per IEC 60255-8 12
Currents In A (kA) primary, Restart threshold ΘRestart/ΘL Trip In %
IA(L1), IB(L2), IC(L3) in A secondary or in % Inom Inhibit time TReclose In min
Positive-sequence component I1
Negative-sequence component I2 Currents of sensitive ground-fault In A (kA) primary and in mA
IE or 3I0 detection (total, active, and reactive secondary
current) INs, INs active, INs reactive;
Range 10 to 150 % Inom (IEE, IEE active, IEE reactive)
Tolerance*) 1.5 % of measured value or 1 % Inom
and from 151 to 200 % Inom Range 0 mA to 8000 mA for Inom = 5 A 1)
3 % of measured value Tolerance*) 3 % of measured value or 1 mA

*) With rated frequency.


1) At Inom = 1 A, all limits divided by 5.

Siemens SIP · 2008 Revised July 2010 Technical Data page 9


12 Motor Protection / 7SK80

Technical data

Long-term averages Oscillographic fault recording


Time window 5, 15, 30 or 60 minutes Maximum 8 fault records saved,
Frequency of updates Adjustable memory maintained by buffer battery
in case of loss of power supply
Long-term averages
of currents IAdmd, IBdmd, ICdmd Recording time 5 s per fault record, in total up to 18 s
(IL1dmd, IL2dmd, IL3dmd) I1dmd in A (kA) Sampling rate for 50 Hz 1 sample/1.00 ms
of active power Pdmd in W (kW, MW) Sampling rate for 60 Hz 1 sample/0.83 ms
of reactive power Qdmd in VAr (kVAr, MVAr) Energy/power
of apparent power Sdmd in VAr (kVAr, MVAr)
Meter values for power Wp, Wq in kWh (MWh or GWh) and
Max./Min. report (active and reactive power demand) kVARh (MVARh or GVARh)
Report of measured values With date and time Tolerance*) w 2 % for I > 0.1 Inom, V > 0.1 Vnom
Reset, automatic Time of day adjustable (in minutes, and ⏐cos ϕ⏐ (p.f.) W 0.707
0 to 1439 min) Motor statistics
Time frame and starting time adjust-
able (in days, 1 to 365 days, and ∞) Total number of motor start-ups 0 to 9999 (resolution 1)
Total operating time 0 to 99999 h (resolution 1 h)
Reset, manual Using binary input, Total down-time 0 to 99999 h (resolution 1 h)
using keypad, Ratio operating time/down-time 0 to 100 % (resolution 0.1 %)
via communication Active energy and reactive energy See operational measured values
Min./Max. values for current IA(L1), IB(L2), IC(L3) Motor start-up data: Of the last 5 start-ups
I1 (positive-sequence component) – Start-up time 0.30 s to 9999.99 s (resolution 10 ms)
Min./Max. values for voltages VA-N, VB-N, VC-N (VL1-E, VL2-E, VL3-E) – Start-up current (primary) 0 A to 1000 kA (resolution 1 A)
V1 (positive-sequence component) – Start-up voltage (primary) 0 V to 100 kV (resolution 1 V)
VA-B, VB-C, VC-A (VL1-L2, VL2-L3, Switching statistics
VL3-L1) Saved number of trips Up to 9 digits
Min./Max. values for power S, P, Q, cos ϕ, frequency Accumulated interrupted current Up to 4 digits
Min./Max. values for overload Θ/ΘTrip (segregated acc. to pole)
protection Operating hours counter
Min./Max. values for mean values IAdmd, IBdmd, ICdmd (IL1dmd, IL2dmd, Display range Up to 7 digits
IL3dmd) Criterion Overshoot of an adjustable current
I1 (positive-sequence component); threshold
Sdmd, Pdmd, Qdmd (element 50-1, BkrClosed IMIN)
Local measured values monitoring Circuit-breaker monitoring
Current asymmetry Imax/Imin > balance factor, Calculation methods On r.m.s.-value basis:
for I>Ibalance limit ΣI, ΣIx, 2 P
Voltage asymmetry Vmax/Vmin > balance factor, On instantaneous value basis:
for V>Vlim i2t
Current sum ⏐iA + iB + iC +kJ · iN ⏐> limit value Measured-value acquisition/ Phase-selective
Current phase sequence Clockwise (ABC) / processing
counter-clockwise (ACB) Evaluation One limit value each per subfunction
Voltage phase sequence Clockwise (ABC) / Saved number of statistical values Up to 13 digits
counter-clockwise (ACB)
Trip circuit monitoring
Fault event recording
With one or two binary inputs
12 Recording of indications of the last
Commissioning aids
8 power system faults
Phase rotation test, operational
Recording of indications of the last
measured values, circuit-breaker
3 power system ground faults
test by means of control function,
Time stamping creation of a test fault report,
Resolution for event log 1 ms creation of messages
(operational annunciations) Clock
Resolution for trip log 1 ms Time synchronization Binary input,
(fault annunciations) communication
Maximum time deviation 0.01 % Setting group switchover of the function parameters
(internal clock)
Number of available setting groups 4 (parameter group A, B, C and D)
Battery Lithium battery 3 V/1 Ah, Switchover performed Via keypad, DIGSI using the operator
type CR 1/2 AA, message “Battery interface, protocol using port B or
Fault” for insufficient battery charge binary input

*) With rated frequency.

Technical Data page 10 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Technical data

Breaker control
Number of switching units Depends on the binary inputs and
outputs available
Interlocking Freely programmable
Messages Feedback messages, closed, open,
intermediate position
Control commands Single command / double command
Switching command to circuit- 1-, 1½- and 2-pole
breaker
Programmable logic controller PLC logic, graphic input tool
Local control Control via menu,
assignment of function keys
Remote control Via communication interfaces,
using a substation automation and
control system (e.g. SICAM),
using DIGSI 4 (e.g. via modem)

CE conformity
This product is in conformity with the Directives of the European Commu-
nities on the harmonization of the laws of the Member States relating to
electromagnetic compatibility (EMC Council Directive 89/336/EEC) and
electrical equipment designed for use within certain voltage limits (Council
Directive 73/23/EEC).
This unit conforms to the international standard IEC 60255, and the Ger-
man standard DIN 57435/Part 303 (corresponding to VDE 0435/Part 303).
Further applicable standards: ANSI/IEEE C37.90.0 and C37.90.1.
The unit conforms to the international standard IEC 60255, and the Ger-
man standard DIN 57435/Part 303 (corresponding to VDE 0435/Part 303).
This conformity is the result of a test that was performed by Siemens AG in
accordance with Article 10 of the Council Directive complying with the
generic standards EN 50081-2 and EN 50082-2 for the EMC Directive and
standard EN 60255-6 for the “low-voltage Directive”.

Notes
Subject to change without prior notice.
We reserve the right to include modifications.
Drawings are not binding.
If not stated otherwise, all dimensions in this catalog are given in mm/inch.
The information in this document contains general descriptions of the tech-
nical options available, which do not always have to be present in individual
cases. The required features should therefore be specified in each individual
case at the time of closing the contract.
12

Siemens SIP · 2008 Revised July 2010 Technical Data page 11


12 Motor Protection / 7SK80

Selection and ordering data Description Order No.


7SK80 motor protection device 7SK80oo – ooooo – oooo
Housing, binary inputs and outputs
Housing 1/6 19’’, 4 x I, 3 BI, 5 BO (2 changeover/Form C),
1 live status contact 1
Housing 1/6 19’’, 4 x I, 7 BI, 8 BO (2 changeover/Form C), see next page
1 live status contact 2
Housing 1/6 19’’, 4 x I, 3 x V, 3 BI, 5 BO (2 changeover/Form C),
1 live status contact 3
Housing 1/6 19’’, 4 x I, 3 x V, 7 BI, 8 BO (2 changeover/Form C),
1 live status contact 4
Housing 1/6 19’’, 4 x I, 3 BI, 5 BO (2 changeover/Form C), 5 RTD inputs,
1 live status contact 5
Housing 1/6 19’’, 4 x I, 3 x V, 3 BI, 5 BO (2 changeover/Form C), 5 RTD inputs,
1 live status contact 6

Measuring inputs, default settings


Iph = 1 A / 5 A, Ie = 1 A / 5 A 1
Iph = 1 A / 5 A, Iee (sensitive) = 0.001 to 1.6 A / 0.005 to 8 A 2

Rated auxiliary voltage


24 V / 48 V DC 1
60 V / 110 V / 125 V / 220 V DC, 115 V, 230 V AC 5

Unit version
Surface-mounting housing, screw-type terminal B
Flush-mounting housing, screw-type terminal E

Region-specific default and language settings


Region DE, IEC, language German (language selectable), standard front A
Region World, IEC/ANSI, language English (language selectable), standard front B
Region US, ANSI, language US-English (language selectable), US front C
Region FR, IEC/ANSI, language French (language selectable), standard front D
Region World, IEC/ANSI, language Spanish (language selectable), standard front E
Region World, IEC/ANSI, language Italian (language selectable), standard front F
Region RUS, IEC/ANSI, language Russian (language selectable), standard front G
Region CHN, IEC/ANSI, language Chinese (language not changeable), Chinese front K

12

12/23 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Selection and ordering data Description Order No. Order


code
7SK80 motor protection device 7SK80oo – ooooo – oHoo L 0 o
Port B (at bottom of device, rear)
No port 0
IEC 60870-5-103 or DIGSI 4/modem, electrical RS232 1 see
IEC 60870-5-103, DIGSI 4/modem or RTD-box, electrical RS485 2 following
page
IEC 60870-5-103, DIGSI 4/modem or RTD-box, optical 820 nm, ST connector 3
PROFIBUS-DP Slave, electrical RS485 9 L0A
PROFIBUS-DP Slave, optical, double ring, ST connector 9 L0B
MODBUS, electrical RS485 9 L 0D
MODBUS, optical 820 nm, ST connector 9 L0 E
DNP 3.0, electrical RS485 9 L0G
DNP 3.0, optical 820 nm, ST connector 9 L0H
IEC 60870-5-103, redundant, electrical RS485, RJ45 connector 9 L0 P
IEC 61850, 100 Mbit Ethernet, electrical, double, RJ45 connector 9 L0 R
IEC 61850, 100 Mbit Ethernet, optical, double, LC connector 9 L0 S

Port A (at bottom of device, in front)


No port 0
With Ethernet interface (DIGSI, RTD-box, not IEC 61850), RJ45 connector 6

Measuring/fault recording
With fault recording 1
With fault recording, average values, min/max values 3

12

Siemens SIP · 2008 Revised July 2010 12/24


12 Motor Protection / 7SK80

Selection and ordering data Description Order No.


7SK80 motor protection device 7SK80oo – ooooo – o H o 0
Designation ANSI No. Description
Basic version 50/51 Time-overcurrent protection phase I>, I>>, I>>>, Ip
50N/51N Time-overcurrent protection ground IE>, IE>>, IE>>>, IEp
50N(s)/51N(s)1) Sensitive ground fault protection IEE>, IEE>>, IEEp
49 Overload protection
74TC Trip circuit supervision
50BF Circuit-breaker failure protection
46 Negative-sequence protection
37 Undercurrent monitoring
86 Lockout
48 Starting time supervision
66/86 Restart inhibit
14 Locked rotor protection
51M Load jam protection
Motor statistics
Parameter changeover
Monitoring functions
Control of circuit-breaker
Flexible protection functions (current parameters)
2)
Inrush restraint D
Basic version + directional (sensitive) ground fault, voltage and frequency protection
n 67N Directional overcurrent protection ground
IE>, IE>>, IEp
67N(s) 1) Directional sensitive ground fault protection
IEE>, IEE>>, IEEp
64/59N Displacement voltage
27/59 Under-/overvoltage
81U/O Under-/overfrequency, f<, f>
47 Phase rotation
32/55/81R Flexible protection functions (current and voltage
parameters): Protective function for voltage, power,
3)
power factor, frequency change E

12

n Basic version included


1) Depending on the ground current input
the function will be either sensitive (Iee)
or non-sensitive (Ie).
2) Only if position 6 = 1, 2 or 5.
3) Only if position 6 = 3, 4 or 6.

12/25 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Sample order Position Order No. + Order code


7SK8051-5EC96-3HD0+L0G

6 I/O’s: 3 BI/5 BO, 1 live status contact, 5 RTD inputs 5


7 Current transformer: Iph = 1 A / 5 A, Ie = 1 A / 5 A 1
8 Power supply: 60 to 250 V DC, 115 V AC to 230 V AC 5
9 Unit version: Flush-mounting housing, screw-type terminals E
10 Region: US, English language (US); ANSI C
11 Communication: System interface: DNP 3.0, RS485 9 L0G
12 Communication: Ethernet interface (DIGSI, not IEC 61850) 6
13 Measuring/fault recording: Extended measuring and fault records 3
14/15 Motor protection function package: Basic version HD

Accessories Description Order No.

DIGSI 4
Software for configuration and operation of Siemens protection units
running under MS Windows 2000/XP Professional Edition/Vista.

Basis Full version with license for 10 computers, on CD-ROM


(authorization by serial number) 7XS5400-0AA00
Professional DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation) 7XS5402-0AA00
Professional + IEC 61850
Complete version:
DIGSI 4 Basis and additionally SIGRA (fault record analysis),
CFC Editor (logic editor), Display Editor (editor for default
and control displays) and DIGSI 4 Remote (remote operation)
+ IEC 61850 system configurator 7XS5403-0AA00

Terminals
Voltage terminal block C or block E C53207-A406-D181-1
Voltage terminal block D (inverse print) C53207-A406-D182-1
Current terminal block 4 x I C53207-A406-D185-1
Current terminal block 3 x I , 1 x INs (sensitive) C53207-A406-D186-1
Current terminal short-circuit links (3 pieces) C53207-A406-D193-1
Voltage terminal short-circuit links (6 pieces) C53207-A406-D194-1

Temperature monitoring box (RTD-box with 12 RTD inputs) for RS485 connection
24 to 240 V AC/DC 7XV5662-6AD10
12
Temperature monitoring box (RTD-box with 12 RTD inputs) for Ethernet
24 to 240 V AC/DC 7XV5662-8AD10

Manual for 7SK80


English E50417-G1140-C344-A4
German E50417-G1100-C344-A4

Mounting rail set for 19" rack C73165-A63-D200-1

Siemens SIP · 2008 Revised July 2010 12/26


12 Motor Protection / 7SK80

Connection diagram

Fig. 12/24 7SK801 connection diagram

12

12/27 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Connection diagram

Fig. 12/25 7SK802 connection diagram

12

Siemens SIP · 2008 Revised July 2010 12/28


12 Motor Protection / 7SK80

Connection diagram

Fig. 12/26 7SK803 connection diagram

12

12/29 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Connection diagram

Fig. 12/27 7SK804 connection diagram

12

Siemens SIP · 2008 Revised July 2010 12/30


12 Motor Protection / 7SK80

Connection diagram

Fig. 12/28 7SK805 connection diagram

12

*) The shielding of the connecting cable


is connected directly to the shield cap.

12/31 Revised July 2010 Siemens SIP · 2008


12 Motor Protection / 7SK80

Connection diagram

Fig. 12/29 7SK806 connection diagram

12

*) The shielding of the connecting cable


is connected directly to the shield cap.

Siemens SIP · 2008 Revised July 2010 12/32


12 Motor Protection / 7SK80

Dimension drawings in mm / inch

Rear view Side view Front view Panel cutout

Fig. 17/22
7SJ80/7SK80 protection unit
for panel flush mounting/cubicle mounting

12

Side view Front view

Fig. 17/23
7SJ80/7SK80 protection unit
for panel-surface mounting

12/33 Revised July 2010 Siemens SIP · 2008

You might also like