10- MPK708A Trouble list

In case of failure occurring or working under irregular


conditions during the time of elevator’s running, the
commissioning personne can conduct the failure predication
by the means of the failure logging of main
controller 、inverter. MPK708Acan store 50 pieces of failure
logging.
No.of whether the floor
Connect Method of renew
fault display the failure
yes,computer Security circuit turn to
E1 Security circuit opened
register the failure. gight
yes,computer
Door Lock error Or over time Door Lock closed
register the failure.
E2
Door Lock open , elevator yes,computer
Door Lock closed
stop register the failure.
Cannot detect the door zone No ,register the Only register,not
E3
signal or crawl time over(10s). failure treat with
Can’t Find the Deceleration
Point ( run time yes,computer Level floor renew after
E4
over“Floor protect”menu register the failure. door opened
time limit)
yes,computer Up Limited Switch
E5 Up Limited Switch Opened
register the failure. renew.
yes,computer Down Limited Switch
E6 DownLimited Switch Opened
register the failure. renew.
No ,register the
E7 Deceleration Switch Error Slow leveling floor
failure
yes,computer
E8 Contact Not Release Release the point
register the failure.
Taco Direction Error or yes,computer Level floor renew after
E9
impulse error. register the failure. door opened
yes,computer
E10 Brake Error Check or power off
register the failure.
yes,computer
E11 Run Time Error Check or power off
register the failure.
yes,computer Connect the monitor
E12 Inverter Error
register the failure. and control] point
E13 Door Contact not Release yes,computer Check or door lock
No.of whether the floor
Connect Method of renew
fault display the failure
register the failure. close
After leveldown run
No ,register the
E14 take count ofimpulse error to lower base station
failure
revise
The number of impulse and No ,register the
E15 Do not treat with
inductor is not same failure
In the condition of E22the signal
E16 / /
of terminal station wrong.
The lock of car door closed
E17 over 2s , which of landing door / /
is no response.
Start up over 5Scan notcheck yes,computer
E18 Check or power off
the input point oftransducer. register the failure.
The input point of transducer yes,computer
E19 Input point turn right.
closed register the failure.
Switch opened the elevator is No ,register the
E20 /
not at terminal station failure
Elevator stop yes,computer
E21 Switch resleased
,switchofbrakeis closed. register the failure.
No ,register the
Elevator is at terminal station , Elevator turn to
E22 failure, turn to down
speed change switch closed down terminal station
terminal station
Button locked and the time
E23 / /
over 30s
The door lock closed over 3S,
and the switch of close door
final limit is not open, the
computer will register the
Start up inspection or
failure E24, the outer calling
the door lock open
and inner selection displayt E24 yes,computer
E24 over 2S,or the final
at the sametime ,the door will register the failure.
limit of close door
open in the opposite
open .
direction .If there is not 2# door
operator , the input point of
close door final limit should not
be connected.
E25 There is pre-open door yes,computer Detect the input point
function , if the PM708 register the failure. of door zone or start up
enlargement board can not inspection .
detect the input point of door
No.of whether the floor
Connect Method of renew
fault display the failure
zone.
Detect the PM708
There is pre-open door
enlargement board or
function , if the PM708 yes,computer
E26 start up inspection or
enlargement board can not be register the failure.
cancel the test function
detected
of enlargement board
There is pre-open door
function , if the PM708
yes,computer
E27 enlargement board can not Start up inspection
register the failure.
detect the input of safety
touching point, the lift stop.
There is pre-open door
function , if the PM708
enlargement board can not
detect the input of speed test, /
E28
the door will not open when the
lift arrive the appointed stop
and the open door button can
not work.