Professional Documents
Culture Documents
Sigmasys C
Sigmasys C
Overview
1 Introduction ......................................................................................................... 1
5 Interfaces ........................................................................................................... 23
6 Functions ........................................................................................................... 31
12 Monitored lines.................................................................................................. 77
13 SIGMANET ......................................................................................................... 93
Inhalt
1 Introduction ......................................................................................................... 1
1.1 About the manual .................................................................................................. 2
1.2 Further information ................................................................................................ 3
1.2.1 Documentation ...................................................................................................... 3
1.2.2 Information on the Internet .................................................................................... 3
1.2.3 Training courses.................................................................................................... 4
1.3 Notational conventions .......................................................................................... 4
5 Interfaces ........................................................................................................... 23
5.1 Overview of interfaces......................................................................................... 24
5.2 Printers ................................................................................................................ 25
5.2.1 Protocol printer DL3750+ .................................................................................... 25
5.2.2 Protocol printer T2240/9 (DR 2030) .................................................................... 26
5.2.3 Thermal printer FD60 .......................................................................................... 26
5.2.4 Printer protocol converter .................................................................................... 27
5.3 GMA Manager (TOPSIS) .................................................................................... 27
5.3.1 Spur operating panels (Version 3.0 and later)..................................................... 27
5.3.2 D100 Interfaces (Version 3.0 and later) .............................................................. 28
6 Functions ........................................................................................................... 31
6.1 Event implementation.......................................................................................... 32
6.2 Daytime/Nighttime ............................................................................................... 32
6.3 Alarm organization .............................................................................................. 32
6.4 Two-detector-zone dependency.......................................................................... 33
6.5 Two-detector dependency................................................................................... 33
12 Monitored lines.................................................................................................. 77
12.1 GMG-S module ................................................................................................... 78
12.1.1 Differences vis-à-vis AMI (SM88) or GMG (BMS)............................................... 79
12.2 Pulse-polling technology in SIGMASYS PMG-S ................................................. 79
12.2.1 Differences vis-à-vis AMP (SM88) or PMG (BMS) Vis-à-vis AMP ...................... 80
12.3 SIGMASYS monitored line .................................................................................. 81
12.3.1 Spur..................................................................................................................... 81
12.3.2 Loop .................................................................................................................... 81
12.3.3 SIGMALOOP detector algorithm ......................................................................... 81
12.4 Line lengths in the loop/spur ............................................................................... 83
12.5 Load factors......................................................................................................... 84
12.6 FDnet – connecting SintesoTM elements ............................................................. 85
12.6.1 Detector network: ................................................................................................ 85
12.6.2 Supported Sinteso™ elements............................................................................ 86
12.6.3 Parameter sets for FDOOT, FDO and FDT detectors......................................... 87
12.6.4 Parameter sets for linear smoke detector FDL241-9 .......................................... 88
12.6.5 Parameter sets for alarm devices........................................................................ 89
12.6.6 Calculating the maximum number of elements and length of lead...................... 89
12.6.7 Load factors......................................................................................................... 90
13 SIGMANET ......................................................................................................... 93
13.1 Features .............................................................................................................. 95
13.1.1 Modem links in SIGMANET................................................................................. 96
13.2 Operation............................................................................................................. 97
13.2.1 Operating panels ................................................................................................. 97
13.2.2 SIGMANET operating panel S24230-F130-A4 ................................................... 97
13.2.3 Operating panel variants ..................................................................................... 98
13.2.4 Operating panel displays..................................................................................... 99
13.2.5 Mobile operating panel ........................................................................................ 99
13.3 AT release ......................................................................................................... 100
13.3.1 Central AT release ............................................................................................ 100
13.3.2 Remote AT release ........................................................................................... 101
1
Introduction
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 1 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
1 Introduction
These planning instructions for the SIGMASYS System are aimed at the sales staff and
commissioning technicians in the region/ZN performing the installation and in the Divisional
Units (DUs), for example:
For the sake of clarity, these planning instructions do not contain details of all variants
of the product nor do they describe every conceivable installation, operation or maintenance
scenario.
If you would like further information or if you encounter problems which are not dealt with in
the planning instructions in sufficient detail, you can request the information you need from
your local Siemens branch or the SBT hotline (tel. ++49 (0) 89/9221-8000).
We would also like to point out that the information contained in these planning instructions
is not part of and should not change any earlier or existing agreement, undertaking or legal
relationship. All obligations on the part of Siemens result from the respective sales contract
which also contains the complete and exclusively valid warranty agreement.
These contractual warranty provisions are neither extended nor restricted by the information
contained in these planning instructions.
This manual is available both in printed form and in electronic form as a PDF file.
You will find the latest version of this manual as a PDF file on the Siemens Intranet under the
following address:
Company/organisation URL
SBT https://workspace.sbt.siemens.com/content/00001123/de
fault.aspx
You can display PDF files using the ‘Acrobat Reader’ program provided free of charge by the
company ‘Adobe Systems Incorporated’.
Use Acrobat Reader version 5.x or above for optimum results when displaying and
printing PDF files.
1.2.1 Documentation
The permanent collection contains further information such as short descriptions, product
sheets, product catalogs, etc.. This is also where you will find the latest version of these in-
structions and the latest version of the documents listed on page Fehler! Textmarke nicht
definiert. of the “Documents” section in PDF format. All information is continuously being ex-
panded and updated!
You will find the collection in the Siemens Intranet under the following address:
Company/Organization URL
SBT DE https://intranet.sgt.siemens.de/zs/bs/pages/standsammlung.asp
You will find general information about Siemens building services engineering and alarm cen-
ters in the Internet under:
Company/Organization URL
SBT DE https://intranet.sgt.siemens.de/zs/bs/pages/startseite.asp
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 3 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
1 Introduction
The personnel responsible for installing and commissioning the systems will receive all the in-
formation they need in special training courses.
These training courses are offered in the SBT DE Training Center.
You will find information on training courses on the Siemens Intranet under the following ad-
dress:
https://intranet.sbt.siemens.de/page.asp?nid=622
Convention/symbol Explanation
Text which you must enter yourself, (e. g. Internet addresses), is formatted in
http://www.siemens.de
the font ‘Courier New’.
Information which you absolutely must read is indicated by this symbol and
Warning shown on a colored background.
Section references and links are indicated by this symbol and shown on a col-
See section XY ored background.
2
Important notes
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 5 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
2 Important notes
The technical regulations introduced below apply in respect of the Federal Republic of Ger-
many. Users in other countries must be sure to comply with all applicable local regulations.
Danger alarm systems must be installed in accordance with Appendix 1 to DIN VDE 0833 ‘Di-
rectory of relevant standards for electrical safety’ (previously from the DIN VDE 0800 series of
standards). Furthermore, all installation, extension, modification and operation activities must
be performed in accordance with DIN VDE 0833 (‘installation’ in this instance refers to plan-
ning, installation, commissioning and maintaining).
Installation and commissioning of the Voice Alarm System E100 may only be carried out by
an electrical specialist.
This specialist must furthermore be trained in the installation and commissioning of the E100
system.
Extract from DIN VDE 0833:
These project planning instructions apply to the following Control and Indicating Equipment
(BMZ):
SIGMASYS C
SIGMASYS M
M modules in SIGMASYS L or D100
and SIGMASYS periphery.
Delivery dates and features are published in separate sales announcements.
3
Guidelines for project planning
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 7 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
3 Guidelines for project planning
The following must be observed when constructing fire alarm systems in compliance with the
guidelines EN45, VdS 2095 (Association of German Underwriters) and DIN VDE 0833,
Part 2:
3.1 Limitations
3.2 Guidelines for failure of the display unit and signal processor
Failure of Effects in the case of < 512 de- Effects in the case of >512 de-
tectors <12.000 m2 tectors >12.000 m2
Display unit (operating panel) By displaying a general indication. Additional operating panel or zone
Integrated in the operating panel in operating panel or indicator panel
SIGMASYS G. or printer.
Signal processor (SOC or MPC) Control and indicating panel may No effect on the remaining signal
fail. processing operations.
Network e.g. 4 control and indicat- No fault in the event of failure of a Information to superordinate con-
ing panels with <12.000 m2 each = routing path. trol and indicating panel must be
<48.000 m2 Redundancy not re- guaranteed (fault signal from rele-
quired. Redundancy required for vant control and indicating panel
systems with a surveillance area and alarm signal).
>48.000 m2.
Table 1: Guidelines for failure of the display unit and signal processor
4
Project planning for control and indicating panels
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 9 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
4 Project planning for control and indicating panels
The control and indicating panel size is determined by the number and location of the detec-
tors.
To avoid exceeding maximum line lengths in a loop or spur, we recommend installing a num-
ber of smaller SIGMANET-capable control and indicating panels in large-scale systems
(SIGMASYS C).
Overview of control and indicating panel selection
SIGMASYS C SIGMASYS M
Max. number of spurs 8 48 (6 x 8)
Max. number of GMG/PMG, MPL 48 (6 x 8 MPL per module)
Max. number of loops 4 24
Detectors/loop SIGMASYS/FDnet 128 / 126 128 / 126
Detector zones 512 1) 512 (1024)
Objects/areas 8 / 89 8 / 89
Max. number of detectors 512 1) 1700
SIGMANET X X
Possible detectors/peripheral elements
SIGMACON MS 6/7/9 TR TR/GMG-S
SIGMASYS-detectors X X
(BASE/PLUS/EXPERT/SPACE)
Sinteso TM X2) X
MS8 detector on PMG-S module X X
Radio sensor via gateway X X
Zone operating panel 8 8 per MPC max. 32 per control and
indicating panel
Transponder/contact coupler X X
Indicator panel control facility X X
Table 2: Overview of control and indicating panel selection
The following number ranges can be created to facilitate system operation and organization.
Data input guideline for:
Object: max. 9 characters, digits and spaces
Area: max. 9 characters, digits and spaces
Organisational detector zone number: max. 9 characters, digits and spaces
The organisational detector zone numbers are displayed in the case of alarms.
The appropriate OBJ, AZ and ORG numbers must be unique throughout the entire
SIGMANET system.
The decision of numbers by using leading ‘0’ is not allowed.
Operating inputs may be configured only with 4 characters.
A 38-character text can be entered for every object, every area, every detector zone, every
output of the type AT/ST/EV/AL and every detector.
The detector group text is displayed if no detector text is entered.
The detector group text should preferably be programmed in order to save data points.
Additional requirements for number assignment must be observed in the case of D100 con-
nection see section “D100 Interfaces (Version 3.0 and later)” on page 28>.
A maximum of 8 objects can be programmed for each control and indicating panel (255 ob-
jects per system).
Objects cannot be centrally programmed for multiple control and indicating panels.
The object numbers must not contain leading zeros.
Up to 89 areas can be programmed per object (up to Version 2.5: only 32 areas).
200 detector zones can be programmed per area.
With control and indicating panels with a software version lower than V3.1, a maximum of 256
outputs per MPC module
or SIGMASYS C control and indicating panel can be configured.
20 commands per operating input are possible (maximum 200 commands distributed over
100 inputs).
With regard to operating panel function keys, a maximum of 20 commands can be assigned
to one key.
A maximum of 60 commands can be configured per operating panel.
The number of individually identifiable event locations, detector zones and zones must not
exceed 1750 per SIGMASYS control and indicating panel.
A maximum of 2500 datapoints can be programmed per SIGMASYS control and indicating
panel. This includes the sum of individually identifiable event locations, detector zones, areas,
outputs and non-coded text.
SIGMASYS control and indicating panel Includes total of:
limitations
2500 datapoints Event locations, detector zones, zones, outputs and non-coded
text
Subset limitations
1750 Event locations, detector zones, zones
1700 Individually identifiable detectors
1512 Detector zones
1512 Non-coded text (38 characters)
1512 Outputs (can be activated system-wide)
Table 3: Control and indicating panel limitations
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 11 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
4 Project planning for control and indicating panels
Peripheral elements Fixed system event Programmable event Total event locations
location locations
Detectors - 1 1
Contact coupler *) 2 4 6
Minitransponder *) 2 2 4
Transponder - 4 4
2 Number of programmed 2 + programmed outputs
Indicator panel *)
outputs
2 Number of programmed 2 + programmed outputs
Multiple control facility *)
outputs
Zone operating panel *) 2 2
Table 4: Allocation of event location numbers
FDnet peripheral element Fixed system Suppliable event loca- Total event locations
event loca- tions
tions
Detector with output - 1 + max. 1 outputs 2
Detector without output - 1 1
Linear smoke detector FDL241 - 1 + max. 1 outputs 2
Infrared flame detector FDF 1 + max. 1 outputs 2
FDCI222 input module *) 2 max. 4 inputs 6
FDCIO222 input/output module *) 2 max. 4 inputs max. 4 out- 10
puts
FDCIO223 FDnet transponder *) 2 2 in- or outputs 4
FDCL221 line disconnector 2 - 2
FDS221 alarm sounder - max. 2 outputs 2
FDSB291 signal base - 1 output 1
Table 5: Allocation of event locations in the peripheral elements in FDnet
*) maximum of 250 peripheral elements per FDC, MPC module or SIGMASYS C can be
connected.
Your marketing representative must be consulted with regard to project planning activities if
the above limitations are exceeded.
The fire alarm control and indicating panel or the operating device is to be installed in a room
adjacent to the main entrance, the surveillance area or an access that is always accessible by
the fire brigade in the event of a fire.
The control and indicating panel should be installed as close as possible to the fire brigade
operating panel.
The maximum cable length for the loop/spur peripherals should also be taken into account
when selecting the location of the control and indicating panel.
It may be advisable to install a number of SIGMASYS C control and indicating panels in the
case of large-scale objects.
The alarm system’s operator terminal should be permanently monitored by trained personnel.
If this is not possible for operational reasons, alarm and fault signals must be forwarded to a
responsible service (see DIN VDE 0833).
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 13 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
4 Project planning for control and indicating panels
SM88 operating panel console 243 443 85 – 92 above the table surface 73
below the table surface
Cutout for console installation 210.5 408
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 15 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
4 Project planning for control and indicating panels
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 17 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
4 Project planning for control and indicating panels
For exact details on where to install the APL20P, see the document
A24230-B60-A1-*-31
The control and indicating panel provides five option slots (OP1 to OP5).
• OP1 to OP3 are designed for equipment with 4 STE control modules (transponders) or
PC board blocks.
• A top hat rail is provided above the PSU as option slot 4 and can be equipped with a 24
V control relay, input/output modules / FDCIO222, FDCL221 line disconnector or
SIGMALOOP splitter.
• Another top hat rail is provided below the PSU as option slot 5 and can be equipped
with a 230 V AC control relay.
EP
SAC SOC 1 SOC 2 EP 1 EP 2 EP 3 EP 4 EP 5 EP 6
BG
SAC 6)
SOC
SOC P 8)
APL20P
MPC 1)
FDC 1) 7)
LPC 3)
GMG-S 2)
PMG-S 2)
APL20
U-APL 5)
APL26 4) 6)
TR-APL
When assigning slots 1 to 6, make sure that the maximum power requirement of 1.4A for all
modules and peripheral elements is not exceeded, even in the event of an alarm.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 19 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
4 Project planning for control and indicating panels
The following table should help you to determine the maximum current:
Device / Module / Current draw Comment
Element Module
MPC 150 mA + load factor of all connected elements
FDC 70 mA + load factor of all connected elements
GMG 80 mA + load factor of all connected elements
PMG 35 mA + load factor of all connected elements
Load factor element 0.25 mA SIGMALOOP-PMG-GMG Sinteso elements
Table 8: Determining maximum current
A fully expanded FDnet loop with 280 load factors has a current draw of
around 70 mA.
A second SOC module (central computer) takes over the task of the first SOC module com-
pletely in the event of a failure.
When installing systems under VdS guidelines with:
• central ÜE activation in SIGMANET
• SIGMASYS M control and indicating panels in SIGMANET
• control and indicating panels that control several extinguishing sectors
If several SIGMASYS C control and indicating panels are networked by SIGMANET and if central
ÜE actuation is required, the ÜE must be connected to a SIGMASYS M control and indicating
panel with Dual SOC.
Warning:
With Dual SOC operation, both modules must have at least S24230-A100-A3
release status.
Both modules must have the same firmware status.
Since March 2007 the SIGMASYS M control and indicating panels and M cores have
been supplied without the SOC module.
The previous SOC module or the SOC P module can be installed as an option. (P stands for
performance)
The SOC P module has a much faster computer, more memory and faster interfaces than the
SOC module.
Control and indicating panels with the "SIGMANET P" SOC P module are networked using
the FN2001-D1 networking module, which must be ordered separately. In the case of Dual
SOC P operation, both SOC P modules must each be equipped with an FN2001-D1 network-
ing module.
The interfaces of the SOC P module are made available on the APL20 P, which must be or-
dered separately.
With Dual SOC P operation an additional crossover Ethernet cable, order number
A5Q00019146, is required. Only one APL20 P is needed for both SOC P modules.
SIGMANET P control and indicating panels are networked using 2-pole copper wire which
can be up to 1000 meters long. A SAFEDLINK repeater can be used to increase the range.
SIGMASYS C control and indicating panels and SIGMANET operating panels can be con-
nected either to SIGMASYS M control and indicating panels with SOC P as a spur or to
SIGMANET P using a SIGMANET P coupler.
SIGMANET P couplers exist for:
• SIGMASYS C control and indicating panels S24230-B72-A1
for attaching to a SIGMASYS C operating panel (S24230-F515-A2)
The couplers include all the modules and mechanical parts required for connection or installa-
tion, including the SIGMASYS SOC P module, FN2001-D1 networking module, SIGMASYS
APL 20 P.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 21 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
5 Interfaces
5
Interfaces
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 23 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
5 Interfaces
The devices listed in the following overview can be connected depending on the SIGMASYS
terminal or interface.
Interface / device 1 2 3 4
SIGMASYS C V.24 V.24 TTY TTY
(standalone) PLAN, DIAG, of SMC-GRPL S24230- printer, (SCI) printer, (SCI)
FBF-A, printer, GMA A501-A5 PLAN, DIAG,
Manager, (SCI) FBF-A, printer, GMA
SIGMAPORT Manager, (SCI)
spur operating panel SIGMAPORT spur op-
erating panel
SIGMASYS C V.24 V.24 TTY TTY
SIGMANET PLAN, DIAG, SMC-GRPL S24230- SIGMANET SIGMANET
FBF-A, printer, GMA A501-A5 PLAN, DIAG, fixed assign- fixed assign-
Manager, (SCI) FBF-A, printer, GMA ment ment
SIGMAPORT Manager, (SCI)
spur operating panel SIGMAPORT spur op-
erating panel
SIGMASYS M V.24 V.24 TTY TTY
(standalone SOC) PLAN, DIAG, PLAN, DIAG, printer, (SCI) printer, (SCI)
FBF-A, printer, GMA FBF-A, printer, GMA
Manager, (SCI) Manager, (SCI)
SIGMAPORT SIGMAPORT
spur operating panel spur operating panel
SIGMASYS M V.24 V.24 TTY TTY
SIGMANET PLAN, DIAG, PLAN, DIAG, SIGMANET SIGMANET
FBF-A, printer, GMA FBF-A, printer, GMA fixed assign- fixed assign-
Manager, (SCI) Manager, (SCI) ment ment
SIGMAPORT SIGMAPORT spur op-
spur operating panel erating panel
SOP TTY TTY V.24
S24230-F130-A1 SIGMANET SIGMANET PLAN, DIAG,
up to A3 fixed assignment fixed assignment printer,
GMA Manager,
(SCI)
SIGMAPORT
SOP-NET V.24 V.24 TTY or V.24 TTY or V.24
S24230-F130-A1 PLAN, DIAG, PLAN, DIAG, SIGMANET SIGMANET
(as of version V2.6) printer, printer,
GMA Manager, GMA Manager,
(SCI) (SCI)
SIGMAPORT SIGMAPORT
spur operating panel spur operating panel
Table 9: Overview of interfaces
5.2 Printers
The V.24 interfaces 1 and 2 of SIGMASYS control and indicating panels, interface 3 of the
SOP S24230-F130-A1 to A3 and interfaces 1 and 2 of the SIGMANET operating panel
S24230-F130-A4 can be connected to DL3700, DL3750+, T2240/9 (DR2030 / DR215) print-
ers and to standard printers directly via DPU up to a distance of 30 meters. The TTY inter-
faces 3 and 4 can be connected only to the DL 3700 printer, or to a standard printer via DPU.
When a printer is connected to the RS232 (V.24) interface on the new SIGMASYS C, S24230-
C500-A7, S24230-C600-A10 control and indicating panel and when using the new TTY/V.24
V24230-Z7-A1 coupler, the RS232 isolator is not required, since the interfaces are electrically iso-
lated.
The following is required instead of connector line V24265-K105-A *): 2 x 25-pin SUB-D con-
nectors with housing and cable LIYCY 8 x 1 x 0.14. Instead of connector line V24262-K35-A1:
1 x 25-pin SUB-D connector with housing and a 9-pin SUB-D socket with housing when con-
necting the printer to SIGMANET Operating Panel S24230-F130-A4. Cable LIYCY 8 x 1 x
0.14.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 25 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
5 Interfaces
SIGMPLAN V2.6 supports a new printer type: “Printer DPU”. This printer operates as an IBM
Proprinter (not a laser printer) with 8 bits. The DR215 printer should be programmed in
SIGMAPLAN if the ECMA font is required. The DPU is connected at the TTY or V.24 interface
on the SIGMASYS C standalone control and indicating panel or at the V.24 interface on
SIGMANET control and indicating panels.
The GMA’s serial interface settings must be fixed at:
baud rate 4800, 7 bits, interface type: V.24 or TTY half duplex active.
Name Order number Remark <30 m up to 300 m
Default printer IBM Proprinter; character X X
set 1 (default). ECMA
character set for param-
eterised DR215. Line print-
ing (not a laser printer)
TTY/ V.24 converter V24230-Z2-A1 V.24 >30 m X
DPU S24230-B146-A1 Connection cable DPU X X
printer; order standard
Centronics with printer
Plug-in power supply 12-27V connector X 1) X
DIN 45232 +pin outside
SUB-D socket 9-pin with housing X2 X2
SUB-D connector 25-pin with housing X
LIYCY 8 x 1 x 0.14 Cable X X
RS 232 isolator WIS: 88001 X
Table 14: Printer protocol converter
1)
Can be used, otherwise PSU from GMZ in separate cable
2)
In the case of connection of DPU to operating panel S24230-F130-A4
The GMA Manager can be connected at the V.24 interface of a control and indicating panel or
SOP-NET. It is not considered to be a ring element, but is treated as a control centre operat-
ing panel. IMT and BMT responsibilities (including mixed) are possible. The GMA Manager
cannot be used as a standby operating panel.
The number of control and indicating panels which can be installed on SIGMANET as regards
the operating panels otherwise necessary but no longer required in SIGMANET is not af-
fected by the installation of spur operating panels, for example, in the SIGMASYS M or in the
SIGMASYS L cabinet.
In contrast to the operating panels in SIGMANET, spur operating panels are only operated
with one interface and therefore have no redundancy interface.
Spur operating panels must therefore be installed in VdS systems in the control and indicating
panel or in the immediate vicinity of the control and indicating panel (in the same room).
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 27 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
5 Interfaces
Spur operating panels can be connected to all V.24 interfaces in the SIGMASYS control and
indicating panel and operating panels.
Spur operating panels cannot be connected to spur alarm control and indicating panels.
The SIGMANET operating panel or the GMA operating panel can be connected as spur op-
erating panels. If possible, SIGMANET operating panels should always be connected to the
SIGMASYS standalone control and indicating panels with SIGMANET, for redundancy rea-
sons.
N.B.: A spur operating panel which has been programmed as a local operating
panel does not display faults with the connection.
In Version V3.0 and later, SIGMASYS control and indicating panels can be coupled with
D100 control and indicating panels without SIGMALINK. In this coupling form, the control mo-
dule in level 1 (K01) is the head of the system where all messages are accumulated. Connec-
tion to a D100 control module is via an available V.24 interface on SIGMASYS C, M, M mod-
ule or SIGMASYS operating panel.
A maximum of 99 units can operated using the D100 system. Control modules, as well as all
SIGMANET units and SIGMANET operating panels, even if they are being operated as spurs,
are included in this figure. GMA operating panels are not included.
A total of 8 SIGMANETs, each with 16 units, can be connected to an control module at level 1
(K01).
A total of 8 SIGMANETs, each with 8 units, can be connected to an control module at level
(e.g. K10 – K80).
A total of 8 SIGMANETs, each with 2 units, can be connected to an control module at level
(e.g. K11 – K88).
IMPORTANT!
If additional S modules are connected on the same level, this reduces the number of
possible SIGMANET connections by the number of connected S modules.
The number of units on a core on the second level may be reduced depending on the
number of objects. (see project planning instructions D100,
order number: A24205-A334-A846 each in their current versions).
ÜE and ÖA may not be operated by means of general system control.
Control must come from the source upwards to the K01.
N.B.: Object and zone number allocation is limited when using D100 coupling.
Example
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 29 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
6 Functions
6
Functions
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 31 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
6 Functions
When an event is identified by a detector and its associated evaluation module, this normally
leads to an alarm being generated in the control and indicating panel.
Events are implemented by appropriate configuration with PLAN:
• on a signal, which is displayed on the control units in the signal list.
• on a fault, which is displayed on the control units in the fault list.
Events configured on signals or faults do not normally need resetting.
6.2 Daytime/Nighttime
The “alarm organisation” operating mode enables operators to find out the cause of an alarm
before the alarm transceiver for fire alarm signals is tripped.
Alarm organisation is manually activated with a button and automatically deactivated at a
freely programmable time (night time).
A separate prealarm and reconnaissance time can be set for every zone via SIGMAPLAN.
The reconnaissance time can be restarted for every zone.
The alarm transceiver is activated directly if an alarm from a different detector zone is tripped
in the same zone when the reconnaissance time is started.
Versions of the control and indicating panel up to V3.0 contain the following function:
If a second alarm is triggered in the same detector zone, the reconnaissance time already
started is retained.
Versions of the control and indicating panel later than V3.1 contain the following func-
tion:
If a second alarm is triggered in the same detector zone, the reconnaissance time is inter-
rupted and the routing equipment is actuated.
Alerting facilities, alarm transceivers and fire protection facilities are tripped when two defined
detector zones switch to fire alarm mode. A pre-alarm is triggered when there is an alarm in
the first detctor zone.
Alerting facilities, alarm transceivers and fire protection facilities are tripped when two detec-
tors in a detector zone switch to fire alarm mode. . A pre-alarm is triggered when there is an
alarm in the first detctor zone.
Threshold detectors:
The detector is reset after it detects an event. The detector signals the event if it recurs within
60 seconds.
Master 20 and the ABM module support alarm buffering.
SIGMASYS and Sinteso detectors do not support alarm buffering.
Virtual inputs and outputs can be used for signalling and for the automatic execution of oper-
ating commands.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 33 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
6 Functions
In this case, a freely programmable output controls a programmable input without the need
for hardware
Restrictions:
Not for zone operating panel displays. The ANZ detector display or ANZ event display control
patterns are not available.
The operator can change the assignment of a control in a detector zone for starting a ÜE on
operating level 3. The command can be given in one detector zone or all detector zones of a
fire alarm system area.
The ÜE assignment commands are displayed in the "System changes" lists on the DT1000
operating panel or "Messages" in the SIGMASYS operating panel.
Warning:
The ÜE removal and ÜE assignment commands have the same effect on the day and night
configurations, i.e. the command produces the same control behavior both by day and by
night.
To help improve the sensitivity of detectors to variable conditions within premises, in addition
to existing multiple alarm-related or detector zone-related options, you can change the
evaluation characteristics of detectors to suit your mode of operation.
In the configuration tool, in the 'Set detectors' window, you can now configure Algorithm 2 in
addition to Algorithm 1.
Switching between the 2 detector algorithms is done using 2 commands:
MD.ALGO1 to set Algorithm 1
MD.ALGO2 to set Algorithm 2
On operating level 2 the operator can use a command to switch between the two detector al-
gorithms for one fire alarm system detector zone or all detector zones in a fire alarm system
control area.
The operation can be assigned to function keys on the operating panel or to an operating in-
put.
The switchover to algorithm 2 is displayed either in the 'System changes' list of the DT1000
BF or the 'Messages' list of the SIGMASYS BF, depending on the system.
Warning: In order to display the switchover in the system lists, all operating panels
must have the new firmware V3.2. In a D100 system this includes, as well as the
SIGMASYS operating panels (apart from not relevant local operating panels), also all SM88
operating panels on the way to the root and the SIGMASYS C control and indicating panel
with control panel.
The time of the SIGMASYS control and indicating panels can be synchronised once a day
with the Time synchronisation” feature.
The synchronising pulse is derived from the main clock and transmitted via an operating input
to a contact coupler, minitransponder or transponder / 4STE.
Synchronisation only requires a single operating step in SIGMANET.
The date must be set manually when putting the GMA into service.
The synchronisation time is set to 4:00 and the pulse length to 3 seconds (minimum).
The response time of a zone operating panel used as a status indicator panel can be reduced
by setting the cycle time to 250 ms in a BMT loop/spur
Prerequisite:
Separate loop/spur for zone operating panel (no BMT detectors can be operated in this
loop/spur as these detectors operate with a 1-second cycle).
Mixed mode means that the BMT and IMT branches can be operated simultaneously within a
SIGMASYS control and indicating panel. This is achieved by creating a BMT and an IMT de-
tector object. Branches can be mixed within an MPC module.
Only one branch can be selected within a monitored alarm line.
The standard outputs are activated as follows within a SIGMASYS control and indicating
panel in the case of IMT/BMT mixed mode
Name
General alarm BMT objects and control and indicating panel object
General fault BMT/IMT objects and control and indicating panel object
Minus AL BMT objects and control and indicating panel object
Alarm transceiver (AT) BMT AT (1)
Local alarm (AL) IMT AT (1)
BMT AT (2) as of Version 2.6
Table 17: BMT/IMT mixed mode
The various alarm counters are freely created and parameterised on the VEA module. The
status can be displayed by pressing a function key or entering an operating input
Name In SIGMAPLAN Text 3 Trip criteria Control sources
DIN counter AZ1 DIN-C Alarms (BMT+IMT) Objects
VdS counter AZ2 VDS-C Alarms (BMT only) BMT ATs and
alerting facilities
General counter AZ1 DIN-C Alarms (BMT+IMT) Objects, zones
faults/alarms inspection and groups
Table 18: Alarm counters
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 35 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
6 Functions
7
Control unit connections
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 37 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
7 Control unit connections
An alarm device can be operated for local alerting. The alarm device is installed on the sys-
tem’s connection board. Loads with an internal resistance of 200 to 1000 Ohm can be con-
nected. The maximum line resistance is 10% of the load resistance.
An alarm receiver is used for alerting the responsible service (e.g. fire brigade, police) via a
dedicated line. The alarm transceiver is installed on the system's connection board.
The output is only activated on an object-specific basis. Loads with an internal resistance of
200 to 1000 Ohms can be connected. The maximum line resistance is 10% of the load resis-
tance.
The alarm transceiver and local alarm outputs can be freely programmed. 2 BMT ATs can be
activated as of Version 2.6. The control and operating panel delay time before acknowledge-
ment by AT can be set.
N.B.: The function of the fire brigade operating panel is always permanently
linked to the objects of the first AT. An object must not be assigned to more than one
alarm transceiver.
The key depot (KD), previously fire brigade key safe (FSK), is installed on the system’s con-
nection board. External adapters are not required for the connection. The key depot is used
for housing keys to the building.
Only keys certified by the VdS may be used.
The key depot must be connected to the same control and indicating panel as the alarm
transceiver.
The fire brigade operating panel is an add-on unit for fire alarm control and indicating panels
and is used to display the operating status and for operation of the fire alarm system by the fi-
re brigade.
The FBF is connected to the system’s connection board without add-ons. Four input and four
outputs are available on the system’s connection board for fire brigade operation.
Inputs: General reset
AT disablement
Local alarm enablement/disablement
Activate/deactivate control in case of fire
N.B.:
• The function of the fire brigade operating panel is always permanently linked to the ob-
jects of the first AT.
• The FBF must be connected to the same control and indicating panel as the alarm
transceiver.
• All detector groups which activate the AT must be powered by separate objects.
• Signals which do not trigger the AT should be located on separate objects.
If this system is not followed, the AT may not be actuated.
As long as an event from the object actuating the AT persists, the AT will not be actuated
again.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 39 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
8 Transponders and loop elements
8
Transponders and loop elements
8.1 General................................................................................................................ 42
8.2 Loop elements..................................................................................................... 42
8.2.1 Maxitransponder SPF 3500, 4STE control module ............................................. 42
8.2.2 Input/output module FDCIO222 (FDCI222)......................................................... 44
8.2.3 Fdnet Transponder FDCIO223 (from mid-2006) ................................................. 45
8.2.4 Contact coupler SPF 5300 .................................................................................. 47
8.2.5 SIGMASPACE gateway ...................................................................................... 48
8.2.6 Zone operating panel SPF 3300 ......................................................................... 48
8.3 Outputs................................................................................................................ 49
8.3.1 Indicator panel control facility SPF 3200 ............................................................. 49
8.3.2 Control module SPF 5100 ................................................................................... 49
8.3.3 Multiple control facility SPF 5200 ........................................................................ 50
8.3.4 External alarm display module SPF 3110 ........................................................... 50
8.3.5 SIGMALOOP Splitter (V2.6)................................................................................ 50
8.4 Technical data, voltage, current, dimensions ...................................................... 52
8.5 Cycle time for signals from transponders and contact couplers.......................... 53
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 41 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
8 Transponders and loop elements
All elements described in this document may only be used in dry rooms. This means also
cable ducts and false floors.
8.1 General
Standard inputs and outputs are provided in the basic configuration of SIGMASYS C and M
control and indicating panels for external displays (FBF, KD, external alarm). In addition, eight
free outputs are available on each module when using GMG-S and PMG-S modules.
The detection of signals via floating contacts (technical messages) or the execution of moni-
tored and non-monitored control facilities are generally performed via loop elements (e. g.
transponders). The cable network normally required for control facilities can thus be elimi-
nated.
Inputs and control facilities near the control and indicating panel can be implemented by addi-
tional components that are accommodated on the option slots of the SIGMASYS control and
indicating panel and the SIGMASYS empty housing.
The following relays can be used in the case of higher currents and voltages and for control-
ling lines with applied voltage:
Relay modules A5Q00001234 2 changeover contacts
Technical data
Control voltage 18 V … 30 V
Coil resistance 900 Ohm
Control current approx. 24 mA
Contact load
Two changeover contacts with maximum switching voltage 250 V AC, 220 V DC
Switched current in light-duty zone µA from 100 mA to 24 V
Minimum switched current 10 mA (with one charge over 100 mA)
Maximum switched current at 30 /110 / 220 V DC 8 A / 0.3 A / 0.12 A
Maximum breaking capacity 230 V AC 400 VA
Dimensions (H x W x D) in mm 84 x 16 x 70
Temperature range 0 … 60 °C
Installation on 35 mm top-hat rail
Table 19: Relay module - technical data
These relays are designed for installation on the 35 mm top-hat rails provided in the control
and indicating panels
The relay modules 9AR, 5AR and 5ARD cannot be used at transponders.
A transitory current limit must be set for appliances with a high transitory current such as elec-
tric light bulbs and flash lights. The maximum current of the relay in use must not be exceed.
The function of the transponder is the same as that of the 4STE control module. The 4STE
control module consists of a transponder module and is intended for installation in
SIGMASYS control and indicating panels (1 option slot).
In SPF 3500, the transponder module is accommodated in an IP54 housing.
Application:
• To connect special detectors, operating inputs and signals.
• Ex-line connection (see “Fire alarm signaling in explosion-hazard areas”A24205-A331-
A292)
• All detectors for threshold detector zones (MS 6/7, MS 9) and SIGMACON detectors
can be connected to SIGMALOOP via the transponder.
• For control facilities with adjustable current up to 126 mA per output for direct connec-
tion of loads or connection via disconnected relays.
• Programmable control pattern: static, flashing 1 s, dynamic.
If transponder outputs are programmed as control facilities, then these outputs are monitored
as monitored lines with a surveillance current of approx. 2 mA.
If an output is programmed with the “Control facility [VdS]” actuator type (as of Version 2.6),
then the output complies with the VdS 2489 guideline and is monitored for insidious wire
breakage and short circuits.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 43 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
8 Transponders and loop elements
IMPORTANT!
The contact (switch or button) must be depressed for at least 5 seconds, while the
alarm (operating input) is sent to the control and indicating panel.
The 3k01 line termination always lies parallel to the contact on all connections 1-4. On con-
nections 3 and 4 a resistance of 1k15 is also applied in series to a connector cable.
The 4 outputs on the FDCIO222 are potential-free contacts, which can be configured as NCC
or NOC.
In addition, you can also configure how the output should behave in the event of an FDnet
fault: unchanged, inactive or active "fail save position".
Like all Sinteso elements, the FDCIO222 and FDCI222 do not require an external supply
voltage.
Monitored actuation can be implemented with the FDCIO222. This requires an A5Q00001243
all-or-nothing relay and an external supply voltage. One input is required for fault monitoring
of the actuation.
The output is configured as the "control with monitored input" connection type and the asso-
ciated input as "fault monitoring."
A resistance of 3k015 must be used for FDCIO222 up to ES30.
For FDCIO222 from ES31 a resistance of 4k16 must be used.
The FDnet FDCIO223 transponder has the same mechanical dimensions as the FDCIO222.
The FDnet transponder can be installed on a top hat rail or on a flat surface or in the
FDCH291 or FDCH292 housing.
The FDnet transponder has two in-/outputs which can be configured as desired.
The FDnet transponder is operated on the FDnet and occupies one address.
The FDnet transponder requires a 24V DC (18-32V) power supply, which must be protected
with a maximum 2A fuse.
General features:
• Operation on FDnet
• Maximum two collective monitored lines (= threshold monitored line)
- Detector with voltage limit on alarm event
- Detector with alarm resistance (e.g. Synova 300)
• Operation with SB 3 safety barrier (ex-zone 1). Applies to detectors with voltage limit
on alarm event
• Maximum two monitored contact inputs
• Maximum two monitored control lines
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 45 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
8 Transponders and loop elements
Compatible with threshold detectors with alarm resistance which meet the following
conditions (e.g. Synova 300):
• Max. rest current on all detectors in a line < 3.2 mA
• Pulse current on alarm event approx. 80 mA
• Reset voltage <1V
• Reset time <3s
• Settling time after reset < 10 s
• Alarm status: 410 Ω … 600 Ω
• Voltage in event of alarm: 4 V … 14 V
• Alarm holding current: < 10 mA
• Monitoring current 17 mA
• Terminal Transzorb diode
20 V ±5%
1.5 kW pulse power
• Maximum line data 150 Ω
1 µF
Contact inputs:
• Rest resistance 3k3
• Signal resistance: 560 Ω
• Inverse monitoring: configurable
• Maximum line data 150 Ω
1 µF
Control facilities:
• Control element Relay
• Switched current: <2A
• Output voltage: Input voltage
• Protection after transponder: 2A M
• Monitored control: - homopolar
30 Ω to 3k3
- reverse polar
3k3
- with feedback
• Resistivity: see below
With homopolar monitoring the internal resistance of the connected equipment is monitored
within a range of between 30 and 3300 ohms. (VdS monitored control line)
With reverse polar monitoring a blocking diode is required on each item of equipment with a
terminator resistance of 3k3 at the end of the cable.
The maximum control line resistance is 10% of the equipment resistance, up to a maximum of
150 ohms.
For further details see the "FDCIO223 Transponder Technical Documentation" EDMS Num-
ber 009122
The contact coupler SPF 5300 is a multiple input module and is used for recording up to four
items of information or commands via floating, monitored contacts. The inputs can be seized
with contacts, e.g. from announcement systems, sprinkler systems, technical alarms, techni-
cal faults, third-party systems, key-operated switches.
The contact coupler cannot be used for automatic detectors which are powered via
the primary line.
The advantage of this element is that power is supplied to the element from the loop so that
no external PSU is required. This can significantly reduce the cost of installation. Voltage
supply is not available for contacts with LED
Every input can be separately addressed, including as a detector zone.
UP to 128 contact coupler modules may be connected to one SIGMALOOP. The contact
coupler module occupies one address in the SIGMALOOP. Contact types of the contacts to
be connected: Gold, Reed or equivalent.
Elements fed by the MPL may not be connected.
The inputs are to be programmed in strict consecutive order starting with input 1.
Line connection
The contact coupler module can connect four lines.
The maximum length of all contact lines is 40 metres.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 47 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
8 Transponders and loop elements
Installation
The contact coupler SPF 5300 can be installed on a 15 mm top-hat rail in the space provided
for option equipment in the control and indicating panel or in a distribution cabinet (AP…).
The gateway radio is a loop element which can administer up to 30 radio components inside
a radio cell (spatial area). From the perspective of SIGMALOOP, the gateway is the same as
a transponder that occupies a separate address for itself and each radio component.
Concept
• similar to transponder
• occupies a variable number of address elements depending on the number of radio
components used: up to 31, the gateway occupies a loop address. Max. number on
loop see chapter Load factors" on page 84.
There are two radio gateways for connecting radio detectors to SIGMASYS control and indi-
cating panels.
• SPU6102 gateway in the housing
• SPU6100 gateway as intermediate ring for SIGMASYS detector base SPF 3600.
The radio gateways connect the radio detector DOW 1171 to SIGMALOOP.
The SIGMASPACE hybrid system documentation in the standard collection are to be used for
project planning, “Project planning a radio cell”, A24205-A337-A910.
The SIGMASYS zone operating panel is an operating and display element for all SIGMASYS
control and indicating panels. It requires an address as an element for the SIGMALOOP
transmission procedure.
57 texts with 16 characters each can be assigned and are freely programmable.
The first event is displayed. The others can be viewed by scrolling.
Events can only be sent by the MPC to which the zone operating panel is connected. An
event can only be assigned to one zone operating panel.
Technical signals are displayed as alarms. Detector numbers are not displayed.
The detector type is displayed in line 1 depending on the priority:
• Alarm
• Fault
• Disablement
8.3 Outputs
64 freely programmable outputs for controlling site plan indicator panels or non-monitored un-
critical control facilities.
N.B.:
Indicator panel outputs can be deleted in the short-term by a restart or EMC influences. Con-
sequently, these outputs should only be used for uncritical control facilities. Output current per
output is approx. 8 mA.
No series resistor is required when connecting LEDs to the indicator panel control facility.
Bright LEDs with a power consumption of between 5 and 10 mA should preferably be used.
Two entries are available in SPF 3200 for disabling the acoustic signal and for the “Lamp test”
function.
The indicator panel control facility occupies one address on the loop. The indicator panel con-
trol facility is supplied as a PCB for installation in boards or housing to be installed on the
building side.
A metallic housing should be used to avoid unwanted interference.
The indicator panel control facility requires a power supply unit
Connection
A maximum of 6 connection cables are available for each of the ten (eleven) LED connec-
tions for the indicator panel control facility.
Ten-LED connection line C24217-A26-B2 as standard flat cable 1500 mm in length and post
connector at one end.
Six Opto control modules each with 11 C97117-Z3004-C1 relays can be connected to the in-
dicator panel control module.
Opto control module: 11 relays each with 2 potential-free changeovers
Maximum contact load: 3 A / 250 VAC, 5A / 30 VDC, 100 V/0, 5 A/10 W
Programmable control pattern: static or flashing 1 s
The control module SPF 5100 is connected to the detector outputs of the automatic
SIGMASYS detector (BASE, PLUS, EXPERT, COMBO) (max. line length from detector to the
control module: 10 m).
A floating changeover contact is provided on the output side. Rating 30 V / 1 A.
The control module does not occupy an address on the loop and also supports cross-loop
programming.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 49 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
8 Transponders and loop elements
Use for close-and-retain systems (FSA) and all non-monitored control facilities.
The control module is installed in conventional distribution cabinets.
Programmable control pattern: static, flashing 10 s, dynamic 10/60 s
The multiple control facility is used for connecting up to eight non-monitored alarm lines or for
the selective activation of alerting and operating devices via eight relay outputs (changeover
contact).
The multiple control facility occupies one address on the SIGMASYS monitored alarm line.
The multiple control facility is supplied as a PCB without housing.
The multiple control facility can be installed with the angle bracket in the space provided for
optional equipment in the control and indicating panel.
The SIGMASYS empty housing is used for remote operation.
Programmable control pattern: static, flashing 10 s
The multiple control facility SPF 5200 requires a power supply unit 24 V.
The external alarm display module SPF 3110 is connected directly to the detector output of
the SIGMASYS or Sinteso detector. The line length of 10 m must not be exceeded. The alarm
display module support cross-loop activation from any detector.
Dimensions (L x W x H) in mm: 82 x 82 x 46
Control pattern: flashing 1 s
SIGMALOOP Splitter is installed in the SIGMASYS control and operating panel or in a similar
system housing adjacent to the control and operating panel.
There is room for five SIGMALOOP Splitters on a 110mm top-hat rail.
This configuration can be installed in option slot 2 in the SIGMASYS C control and operating
panel. For all other control and operating panels, it can be installed in a free option slot.
The outgoing spurs must be clamped in consecutive order (without gaps), starting with the
first terminal pair. Thus, the terminal pair must first be assigned for spur 1, then spur 2 and so
on. At least one element must be connected to the spur in use. Spurs not in use (3, 4 or 5)
remain unassigned.
In accordance with VDE 0833 the following can be connected to a SIGMALOOP Splitter:
Automatic detectors max. 32
Non-automatic detectors max. 10
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 51 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
8 Transponders and loop elements
8.5 Cycle time for signals from transponders and contact couplers
Different operating conditions (polling cycles) can be selected for contacts connected via con-
tact couplers or minitransponders.
Loop cycle time 0,25 sec 1 sec – Zyklus
Op. cond 1-stage-poll 2-stage-poll 3-stage-poll 1-stage-poll 2-stage-poll 3-stage-poll
(for fault-free (for fault-free (for fault-free (for fault-free (for fault-free (for fault-free
environments) environments) environments) environments) environments) environments)
Coupler
C / S *) C / S *) C / S *) C / S *) C / S *) C / S *)
Contact coupler 1,4 / 1,7 sec 1,7 / 2,0 sec 1,9 / 2,2 sec 2,2 / 3,2 sec 3,2 / 4,2 sec 4,2 / 5,2 sec
SPF 5300
Minitransponder 0,2 / 0,7 sec 0,2 / 1,0 sec 0,2 / 1,3 sec 0,2 / 2,2 sec 0,2 / 3,2 sec 0,2 / 4,2 sec
SPI 3400 (BMT & IMT)
Table 21: Cycle time for signals from transponders and contact couplers
*) C = contact actuation time Uninterrupted time for which the contact must be closed.
S = system response time Delay until the signal is displayed or the first control is tripped
(from start of contact actuation).
In general, the basic setting in SIGMAPLAN is “3-stage poll”.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 53 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
9 Special control facilities
9
Special control facilities
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 55 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
9 Special control facilities
General:
One extinguishing zone can be activated per line module in SIGMASYS M.
Only one extinguishing zone can be activated per control and indicating panel in SIGMASYS
C.
Please observe the VdS 2496 guideline with regard to extinguishing system activation.
As of Version 2.6
VdS permits up to eight extinguishing zones per loop. The prerequisite for this, however, is
that the connection module is redundant.
A dual MPC is required to operate more than six extinguishing zones with a single
SIGMASYS M.
Thus, up to 8 x 4 = 32 extinguishing zones can be activated at an MPC module with dual
MPC.
A maximum of 64 extinguishing zones per SIGMASYS M is permitted in the case of two dual
MPCs.
Example of a configuration with dual MPC (MPC2).
MPC (master) and MPC2 (slave) only differ when programmed via SIGMAPLAN.
The slave MPC must always be installed on the right of the master MPC. The U-APL module
(S24230-A133-A1) is installed at the connection slot of the slave MPC. The lines are con-
nected at an APL20 on the slot of the master MPC. The modules are connected via the flat
cable provided.
In the event of a fault, the slave MPC connected on the right of an MPC completely takes
over the function of the defective master MPC after re-initialisation.
The alarm lines are switched to the slave MPC with the U-APL module (16 changeover con-
tacts) of the master MPC.
MPC2 cannot be installed at slot 6 of the SIGMASYS M control and indicating panel. The
standard cables supplied are too short. Slot 6 can be used in the M module in SIGMASYS M.
Both modules must be available in release S24230-A103-A5 at least for dual MPC
operation.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 57 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
9 Special control facilities
All detector zones that control asprinkler system must be assigned adetector type with
the following properties:
Check “ST even when door open” under “Set detector zone type” and “Control”
The SIGMALOOP extinguishing interface consists of several SPF5200 control modules and
two SPF5300 contact couplers as well as a special regenerative coupling unit to avoid inad-
vertent tripping and LOOP monitoring on a module which can be installed in the “32-pole
plug-in card block”.It can b eused as the VdS extinguishing interface for all extinguishing func-
tions (water, gas, powder and foam)
Extinguishing control outputs Inputs = messages from extinguishing control
- Extinguishing command - Fault signal
- Prealarm or revering electromagnetic - Tripping in extinguishing zone
valve - Activated emergency stop key
- 4 freely programmable outputs for acti- - Automatic extinguishing zone tripping disabled
vating the relays - Extinguishing zone mechanically blocked
- Loss of extinguishing agent
Reseve battery activated
Table 22: SIGMALOOP extinguishing interface-overview of the features
N.B.: The lines required for the inputs (e.g. fault signal, extinguishing zone)
must not be exceed 40 m in length.
Device for closing fire protection traps (doors, openings for conveyors) in a fire section.
Under normal circumstances, the fire section doors are held open by the FSA. In the event of
an alarm or a detector fault in the relevant fire section, the doors are automatically closed by
the FSA. The locking device is a GMA element with its own power supply unit. It is activated
by the GMA. It must be ensured that the locking device operates even if the detectors as-
signed to the fire section fail in order to protect the fire section. Possible faults are, for exam-
ple, a failure or deactivation of the MPL, failure of the control and indicating panel, mains
power failure, etc.
In accordance with DIBt (German institute for structural engineering), detectors should be
provided for and specially dedicated to FSA. Subject to approval, the smoke detectors may
control the FSA.
For the FSA control, a control output is programmed with SIGMAPLAN at the next
SIGMALOOP- or Sinteso detector output. This is connected via the control module SPF 5100.
The detector output is activated if the associated detector zone(s) is(are) idle.
The control output is reset in the case of:
alarm
fault detector
fault detector zone
fault loop
disablement detector zone
inspection (as long as the detector is in inspection alarm)
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 59 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
9 Special control facilities
10
Programming of control facilities
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 61 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
10 Programming of control facilities
General:
All control facilities in the system can be configured, apart from the FSA control pattern, fire
sector control facility, detector diagram and event diagram.
This means that in control and indicating panels networked using SIGMANET signals from
different control and indicating panels, an output can be set in any control and indicating
panel.
In PLAN D100 under "Organization", "Set MG types" on the "Controls" tab of the detector
zone, you can choose whether the ÜE, AL, RAL, ST outputs should be controlled by day, by
night and also when the control and indicating panel is opened.
You can specify whether a control facility can be disabled using the fire brigade operating
panel "Disable fire control" key for each control pattern in the configuration under "Control
properties", "Reset".
Control facilities ST, ALA, RAL can be monitored for faults and/or actuation.
An alerting facility is used to acoustically signal a fire alarm in order to alert the emergency
service (works fire brigade).
If an alerting facility is activated, it can be deactivated and, if necessary, re-activated with the
operating panel button “LA on/off”.
If the alerting facility on the operating panel is deactivated and another alarm associated with
this alerting device is tripped, then the alerting facility is activated once again (re-triggerable).
Press the FBF (fire brigade operating panel) button “Acoust. signals off” once to deactivate all
alerting facilities: alerting facilities will not be tripped by another alarm. Press this button again
to reactivate all alarm-tripping alerting facilities.
The source (e. g. detector objects, alarm zones or detector zones) that tripped an alerting fa-
cility (AL) can be established for every facility. Operators can also choose from a number of
different control patterns. It is thus possible to vary the signalling criteria (alarm, prewarning,
prealarm, signal).
It is possible to parameterise whether the alerting facility is to be tripped when the door is
open in the control and indicating panel that detected the alarm (detector zone type).
The activation list of an alarm should only contain objects that enable the "local alarm on/off"
operation to be performed from the operating panel or fire brigade operating panel.
The actuators in the control facility category are used for activating and deactivating control
equipment in response to certain signals
The source (e. g. detector objects, alarm zones, detector zones, detectors or actuator states)
that tripped the control facility can be established for every facility. Operators can also choose
from a number of different control patterns. It is thus possible to vary the signalling criteria
(alarm, prewarning, prealarm, signal) and the activation form (static, flashing or dynamic).
A control facility can also be enabled and disabled or activated and reset via a command at
the operating panel.
A control facility can be monitored for tripping or fault (monitored control facility).
In the detector zone types, the operator can select whether the control facility should be trip-
ped when the door is open in the control and indicating panel that detected the alarm.
10.1.4 Monitored control lines according to VdS via transponder SPF 3500
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 63 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
10 Programming of control facilities
The maximum line resistance must not exceed 10 % of the load resistance.
The actuators in the Display category serve as indicators for the status of detectors, detector
zones or outputs
Display is mainly used for programming detector outputs when connecting detector shunt dis-
plays and for the indicator panel control facility SPF 3200.
The source (e. g. detector objects, alarm zones, detector zones, detectors or actuator statu-
ses) that tripped a display can be established for every facility. Operators can also choose
from a number of different control patterns. It is thus possible to vary the signalling criteria
(alarm, prewarning, prealarm, fault, signal) and the activation form (static, flashing or dy-
namic).
Displays cannot be activated by command. Displays cannot be tripped in operating panel
lists.
10.1.6 Close-and-retain system (FSA) control facility and fire section control facility
FSA
The FSA control facility is an inverse-operated output that is released in the event of a fault. It
is released in the event of an alarm, signal, fault, inspection, disablement of the activating de-
tector. It is also command-driven. The close-and-retain equipment is connected via the con-
trol module SPF 5100 to a detector output of a SIGMASYS detector.
Actuators of this type can only be tripped by sources that are connected to the same module.
Instead of selecting one of the predefined control patterns, you can define your own control
behavior for the output. This is done by breaking down the existing control patterns and ac-
tuation criteria [AK], control facility reset criteria [SR] and signal forms [SF] and configuring
them to your own specifications.
Descriptions on how to configure the control patterns can be found in the PLAN D100 online
help.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 65 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
10 Programming of control facilities
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 67 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
10 Programming of control facilities
11
Power supply
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 69 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
11 Power supply
A separate electric circuit with individual, specially identified fuses must be used for the power
supply from the electrical mains.
The control and indicating panel is to be connected to a mains distribution cabinet via a con-
2
ductor cross section of at least 3 x 1.5 mm (NYM-J). A fuse (max. 16 A) is to be connected in
series in the distribution cabinet.
The fire alarm system can be operated at the following supply voltages:
Supply voltage I max. 150W SV Supply frequency
230 V +10 –15 % 1,2 A 50 / 60 Hz
Table 25: Mains supply
11.2 Earthing
SIGMASYS control and indicating panels have a “function and protection earth” (FPE) (VDE
2
0800, Part 2, Paragraph 6). A cross section of at least 6 mm is to be used.
To avoid interference, the earth is to be placed at the buildings main earthing bus.
The H07V-K fine-strand wires should preferably be used
VDE 0833 and VdS 2095 guidelines stipulate the need for two independent power sources for
supplying power to fire alarm systems. This is achieved by using the AC network as the po-
wer supply unit and batteries as the secondary power supply unit. The batteries are always
kept fully charged by the power supply unit (standby parallel mode).
A 24 V/150 W power supply unit V24230-Z6-A2 is installed in SIGMASYS C and
SIGMASYS M.
11.4 Battery
Two 12V/25Ah batteries connected in series can be used in the SIGMASYS C control and in-
dicating panel. The SIGMASYS battery cabinet can be used for larger batteries.
The maximum current requirement for the control and indicating panel is to be calculated us-
ing the form When calculating the alarm current, only the largest fire section should be taken
into account (largest current requirement of the system), i. e. when tripping the fire section
with the monitored alarm lines and the monitored control lines (max. value during simultane-
ous activation is decisive).
To calculate the power requirement for the Sinteso detector periphery you can also use the
Excel tables in the PSP (Product Support Platform). https://psp.sbt.siemens.com
The size of the battery capacity is determined on the basis of the system’s idle current and
the required bridging time. The battery bridging times are defined as follows in compliance
with VDE 0833 or VdS 2095:
On the basis of the control and indicating panel’s and the external device’s alarm current in
the event of an alarm. The alarm current for the alerting facility of the fire section with the
highest current requirements must be available for 0.5 hours (see VdS 2095).
The battery capacity (K) depends on the bridging time (tü) required and is calculated using
the following formula:
Bridging time tÜ = 4 h K = 1.56 * (tÜ ·* IR + 0.5 * IAL) [Ah] and
Bridging time tÜ ≥ 30 h K = 1.25 * (tÜ ·* IR + 0.5 * IAL) [Ah]
IR = idle current or recharging current
IAL = alarm current
The formulae are marked on the calculation form.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 71 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
11 Power supply
Note:
The total of the current requirement values calculated and the value of the recharging current
must notexceed the maximum current supplied by the power supply unit. Otherwise, two
power supply unitsmust be used.
To avoid interference from the peripherals (line network), a separate mains supply and batter-
ies should be provided to power the peripherals.
The line network must be specially calculated for the power supply to the peripherals (trans-
ponder/ indicator panel).
Wires 3 and 4 in the existing 2 x 2 x 0.8 cable can be used for short distances and low cur-
rents.
N.B.: observe the voltage at the terminals in the loop/spur ( see section
“Monitored lines” on page 77). Minimum control and indicating panel voltage is 22 V.
(Transponder: the minimum 21 V voltage leads to a voltage drop dU = 1 V.)
(Indicator panel: the minimum 18 V voltage leads to a voltage drop dU = 4 V.)
The SIGMASYS empty housing of the SIGMASYS control and indicating panel can be used
for connecting multiple threshold monitored alarm lines via a transponder or for connecting
other loads with battery support.
The SIGMASYS empty housing can be fitted with a 150 Watt power supply unit.
Two 24 Ah batteries can be installed in the SIGMASYS empty housing.
The terminal blocks with 9 and 10 pins must be ordered seperately.
Possible empty housing assembly: examples of (S24230-A512-A1):
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 73 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
11 Power supply
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 75 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
12 Monitored lines
12
Monitored lines
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 77 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
12 Monitored lines
– 2-MG dependency
– ALORG (alarm organization)
– ALZ, parameterisable
• Alarm zone formation
– cross-module formation possible
– mixing with MPC and PMG detector zones possibl
• Operating inputs, parameterisable
• MPL terminals, 3.3 K or 4.7 K, parameterisable in the SIGMAPLAN
• Maximal line resistance 200Ω.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 79 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
12 Monitored lines
12.3.1 Spur
Up to 64 address can be assigned for connected detectors and devices (transponders, indica-
tor panel, zone operating panel) as a spur on a SIGMASYS monitored line.
According to the guidelines (VdS 2095), however, there should only be max. 32 auto-
matic detectors in a detector zone (fire section) or 10 non-automatic fire detectors connected
to a spur.
12.3.2 Loop
A loop is created by joining two monitored lines (spurs), 1 with 5, 2 with 6, 3 with 7 and
4 with 8.
The element sequence is always counted from the lowest to the highest monitored line. Up to
128 SIGMASYS elements can be connected to a loop. Advantages of a loop compared to a
spur:
• Protection against failures. All elements continue to work even in the event of a failure,
e. g. wire breakage.
• Connection of control facilities system-wide.
•
2
A monitoring surface of up to 6000 m .
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 81 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
12 Monitored lines
*) Use filtered priming systems for light dust (e.g. from cement, feed industry)!
Shielded installation cables, e. g. IY(ST)Y are to be used as lines for the loop.
The maximum wire diameter that can be clamped in the standard detector base is 0.8 mm.
The maximum line length depends on:
• the number of detectors and the cable type
• the maximum line resistance including the resistance of the connected elements (R
max. = 200 Ω)
• the maximum line capacity including all connected capacities (C max. = 200 nF).
Ohm/km, or . element nF/km, or element
IY (St) Y 2x2x0,8 73,2 Ohm 100 nF
IY (St) Y 2x2x0,6 130 Ohm 100 nF
NYM 1,5 mm² 25 Ohm 250 nF
Loop element 0,8 Ohm -
Table 29: Line parameter
Element capacity is very low with regard to the line capacity and therefore not relevant.
The combo detector SDF3500 counts as two address elements in the per-detector line length
calculation.
Figure 17 shows the relationships for a 0.8 diameter line. The spur line is a real subset of the
loop line, i.e. up to 64 address elements can be operated on a 2 km line both in the loop and
on the spur. A large number of address elements can only be operated in the loop, the maxi-
mum possible line length drops to approx. 11 m⁄element.
Figure 15: Address element number and line lengths for a 0.8 diameter line
Behaviour is similar in the case of a 0.6 diameter line. The maximum line length here is 1.540
m in the case of zero elements. The maximum possible line length per element drops by ap-
m
prox. 6 ⁄element and measures 1.150 m in length with 64 address elements (spur/loop) and 750
in the case of a fully configured loop (128 address elements).
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 83 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
12 Monitored lines
Figure 16: Address element number and line lengths for a 0.6 diameter line
The sheath wire of the cable shield is to be laid at the clamps provided in the detectors and
devices. The cable is earthed at the corresponding clamps in the SIGMASYS control and in-
dicating panels. The unshielded wires and the sheath wire should be as short as possible to
avoid interference.
According to VdS 2095, the loop cable must be laid out as a real ring if the detector zone con-
tains more than 32 automatic or more than 10 non-automatic detectors, or if automatic and
non-automatic detectors are mixed. In other words, forward and reverse lines must be laid in
separate cables and separate lines.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 85 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
12 Monitored lines
Loop planning
Nothing needs to be mechanically adjusted on the detectors themselves. The detectors are
supplied ex works with the appropriate sets of parameters. The PLAN D100 configuration tool
can be used to adjust the detectors optimally to the conditions of the installation site. By se-
lecting the right parameters you can set the detector to specific potential fire events and likely
environmental influences.
For the FDOOT241-9 neural fire detector you can also select the parameter sets of the
FDO241 wide spectrum smoke detector and the FDT241 heat detector. In this case the
FDOOT241-9 neural fire detector will behave like the FDO241 wide spectrum smoke detector
or FDT241 heat detector.
For S-LINE detectors the switching of the parameter sets can be controlled on a
time/process-related basis.
Two parameter sets within DOOT or DO or DT can be switched using an operating input on
the control and indicating panel, an operation on the operating panel of the control unit, or us-
ing the time controls on the control and indicating panel. Both parameter sets are fixed in both
PLAN D100 and in SIGMASYS detectors.
Two customized detector parameter sets can be selected for S-LINE detectors with PLAN
D100 and downloaded to the detectors via the line tester.
Installation conditions for Sinteso™ detectors and their associated parameters can be found
in the detectors' technical description.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 87 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
12 Monitored lines
DOOT: suppression X
DO: universal X X
DO: robust X X X Standard
DO: sensitive X X X Standard plus
DT: 60°C ROR (A1R) X X X
DT: 80°C ROR (BR) X X X
DT: 60°C stat. (A1S) X X
DT: 80°C stat. (B1S) X X
Customized/ X X X
Download 1
Customized/ X X X
Download 2
Table32: Parameter sets for FDOOT, FDO and FDT detectors
= Default setting
ROR = Rise Of Rate Differential detector
= Default setting
SR = Sun resistance
standard UB=fault
standard UB=Alarm
sensitive UB=fault
sensitive UB=Alarm
very sens. UB=fault
very sens. UB=Alarm
Customized / Download
1
Customized / Download
2
Technically, the possible length of line depends on what cable you are using (capacity and
resistance), as well as the load imposed by buzzers and sounders.
Threshold values for FDnet:
Maximum 180 ohms per loop and/or spur and maximum 330 nF for shielded and 500 nF for
unshielded lines.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 89 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
12 Monitored lines
These limits apply to an FDnet with an expansion capacity of up to 126 elements each with
one load factor.
For example, if you are using IY(ST) Y 2x0,8 mm Ø cable (73 ohms and 100 nF per km), the
following maximum line lengths can be achieved:
• a loop with a 2.5 km line length
• a spur with a 2.5 km line length
With IYY 2x0.8 mm Ø cable the loop and T-taps may measure no more than 3.3 km if the ca-
ble is shielded and no more than 5 km if the cable is unshielded (the assembled cable length
depends mainly on the line capacity). Note here that the distance from the furthest element to
each control and indicating panel connection must be no more than 2.5 km.
The maximum load factor connection per loop including T-taps is 280
To simplify the calculation, FDnet element numbers are calculated with load factors.
Element Load factor in Additional load
S-Line C-Line
in Fdnet idle state factor on alarm
Optical detector 1 FDO241 FDO221 1 1
Heat detector 1 FDT241 FDT221 1 1
Combination detector 1 FDOOT241 FDOOT221 1 1
Flame detector 1 FDF241-9 FDF221-9 3 1
Linear smoke detector 1 FDL241-9 5 1
Manual detector 1 FDM223 1 1
Alarm sounder 1 FDS221 1 14
Signal base 0 FDSB291 0,5 4,5
4 x IN 1 FDCI222 2 0
4 x IO 1 FDCIO222 3 0
Line disconnector 1 FDCL221 1 0
FDnet transponder 1 FDCIO223 3 0
Table36: List of load factors for elements
In the case of an additional load factor on alarm, alarm indicators or control modules con-
nected to the detector are already included.
For control modules such as fixed close-and-retain systems (FSA) that are actuated by a de-
tector, an additional load factor of 1 must be allowed for in the idle state.
The number of additional signal bases and alarm sounders allowed for a given load factor in
the FDnet can be determined from the following table:
Figure 18: Additional signal bases and alarm sounders allowed for a given load factor
Warning:
The table applies only to short line lengths:
For cables with 0.6mm ∅ < 625m
For cables with 0.8mm ∅ < 1125m
Example: With 100 existing load factors and a maximum permitted load factor of 280, another
11 alarm sounders can be installed, or 3 alarm sounders and 21 signal bases (including de-
tectors).
T-taps :
A T-tap can be up to 2.5 km long.
The maximum line length is limited by the capacity of all lines in an FDnet
T-tap and LOOP. (330nF shielded 500nF unshielded).
Each FDnet has a limit of 280 load factors with any distribution over loop or T-tap.
The longer the line lengths in the loop, the fewer load factors can be connected.
The following diagram shows the maximum load factors that can be connected for an FDnet
(idle load factors + additional load factors in alarm state) in relation to the cable length and
line diameter. The diagram applies to both shielded and unshielded cable.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 91 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
12 Monitored lines
Figure 19: Load factors in relation to line diameter and line length
Example: For a 2000m cable with 0.8 mm ∅, a maximum of 150 load factors may be con-
nected.
The curves allow for the leakage currents occurring with a creeping short circuit and a load
factor increase of 5 detectors with load factor 1 in alarm state.
The line capacity can limit the line length if lines are very long.
Note:
If SIGMALOOP/spur or MS8 wires are run in the same cable as FDnet wires, faults
may occur (above all in the initialization phase) in the SIGMALOOP or when trigger-
ing the alarms of MS8 detectors.
FDnet alarm lines from different modules can be run in the same cable.
To calculate the power requirement for the Sinteso detector periphery you can also
use the Excel tables on the PSP (Product Support Platform). https://psp.sbt.siemens.com/
13
SIGMANET
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 93 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
13 SIGMANET
SIGMANET networks SIGMASYS C and M control and indicating panels and operating pan-
els. Mixed operation of IMT and BMT control and indicating panels is possible in SIGMANET.
SIGMANET is a network for danger alarm systems. It is based on serial connections and
takes the form of a bidirectional ring.
Data is transmitted around the ring as standard in a preferred direction. If the ring is broken at
a particular point, bidirectional transmission is initiated to ensure that all units remain accessi-
ble.
The ring can carry all forms of communication including events and commands.
As from version V3.0 of the control and indicator panels and operating panels, spur line oper-
ating panels can be connected via a free RS232 (V24) interface to the control and indicator
panels in the SIGMANET (1).
If configuring with PLAN D100 V5.2 and control and indicator panel software version 3.0 or
higher, spur line control and indicator panels (2) can be connected to control and indicating
panels in the SIGMANET.
Control and indicating panels and operating panels connected to control and indicating panels
in the SIGMANET via a spur line (2) do not count as network units.
With systems constructed according to EN 54-2 and VdS guidelines, the spur line control and
indicating panel or spur line operating panel must be installed in the same housing or imme-
diately next to the connected SIGMANET control and indicating panel, since there is no cable
redundancy in a spur connection.
13.1 Features
Note:
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 95 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
13 SIGMANET
The operating panels include all devices operated on the SCI interface including
SIGMAPORT, FAT, FBF-A, etc., plus all operating panels connected in the SIGMANET and
in the spur to SIGMASYS control and indicating panels.
13.2 Operation
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 97 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
13 SIGMANET
The following operating panel variants can be parameterised for all operating panels (incl.
SIGMASYS C control and indicating panels):
• Control center operating panel:
Normally permanently busy, no screen-blanking feature. This operating panel can be
assigned an operating panel with standby function that automatically takes over the re-
sponsibilities of a failed control centre operating panel on an object-specific basis.
• Local (on-site) operating panel:
Not permanently busy, screen-blanking feature for IMT available, cannot be assigned a
standby operating panel.
• Infopanel:
Used as a straightforward display terminal without operating function (excluding polling
function) and is also installed in addition to a control centre/on-site operating panel.
Screen-blanking function available. Cannot be assigned a standby operating panel.
• Standby function for control center operating panels:
For redundancy for a control centre operating panel, the operating and display functions
can be taken over by one or more operating panels if the control centre operating panel
fails. In normal operation, it is not possible to display information or perform operations
at a standby operating panel. The standby function is assigned on an object-specific
and criteria-specific basis. A command must be entered to reassign the responsibility
once the on-site operating panel is put back into operation. The standby function only
becomes active if an object is no longer supported by a control centre operating panel.
Only one standby operating panel may be programmed per object.
If no standby function is programmed, the control center operating panel with the lowest num-
ber takes over the responsibility in the event of operating panel failure.
Parallel operation is possible if multiple control centre/on-site operating panels are parameter-
ised with the same responsibilities: alarm display is updated simultaneously at all responsible
operating panels (with an internal acoustic alarm) and can be modified at all responsible
operating panels. Modifications to an alarm via a processing operation are displayed at all
operating panels.
Reaction of the operating field keys in the case of multiple control and indicating panel re-
sponsibilities:
Reset: based on the object or alarm
Acoustic off: based on the event, acoustic VdS alarm device and internal
alarm off
At least one control centre operating panel must be programmed in the system
All detector objects must be assigned at least one control centre operating panel.
Operating panel with GMA user interface with list counter for alarm, signal, fault
(not EN 54-2).
as of Version 2.6)
The “mobile operating panel” function is required by Maintenance in order to be able to oper-
ate a SIGMASYS M on site (otherwise, every SIGMASYS M must have an operating panel).
An operating panel is specially provided for this task in the project planning in SIGMANET. It
is permanently in operation and can easily be removed as required (TAE-N connector, TAE-N
socket) and then reconnected to the mains in another place equipped with the relevant so-
cket. SIGMANET operates like a bus line in this case (unit position not important). We rec-
ommend installing the operating panel in the OP console to increase portability.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 99 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
13 SIGMANET
13.3 AT release
Central AT release means that the appropriate central alarm transceiver (AT) is tripped by all
BMT or IMT control and indicating panels in SIGMANET in the event of failure. The control
and indicating panel in which this AT resides is known as the “AT Master BMT Control and
Indicating Panel” or the “AT Master IMT Control and Indicating Panel”.
The other SIGMANET control and indicating panels are known as “sub-control and indicating
panels”.
If the AT is disabled at the AT master control and indicating panel, this is displayed at all af-
fected SIGMANET units.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 101 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
14 Order Overview
14
Order Overview
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 103 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
14 Order Overview
SIGMASYS C Bestellübersicht
SIGMASYS C control and indicating S24230-C500-A7 Control and indicating panel without operat-
panel ing panel with power supply unit (PSU) 150
W and without battery
SIGMASYS C Sinteso control and in- S24230-C600-A10 Control and indicating panel without operat-
dicating panel ing panel
SIGMASYS C Foil for operating panel S24230-F515-A2 Operating panel for SIGMASYS C control
and indicating panel
SIGMASYS C dummy plate C24230-A13-C54 For SIGMASYS C without operating panel
Battery 12V 25 Ah GBI: 13013 For installation in SIGMASYS C
Battery 12V 65 Ah V24069-Z103-A7 For installation in SIGMASYS battery cabi-
net
SIGMASYS Battery cabinet S24230-C109-A1 Battery cabinet for 2 x 12 V / 65 Ah batteries
SIGMASYS M
SIGMASYS M Bestellübersicht
SIGMASYS M control and indicating S24230-C107-A6 Basic unit with SV 150W , SAC and SOC
panel without operating panel, without line mod-
ules, upgradable with the following options
SIGMASYS M control and indicating S24230-C107-A7 Basic unit with SV 150W , SAC
panel without SOC, operating panel, without line
modules, upgradable with the following op-
tions
SIGMASYS SOC S24230-A100-A4 Standard processor module with
SIGMANET
SIGMASYS SOC P S24230-B60-A Performance processor module
SIGMASYS APL 20 P S24230-B70-A1 SOC P Interface connection board
Crossover Ethernet cable A5Q00019146 For dual SOC operation
FN2001-D1 Netmodule (SAFEDLINK) A5Q00020525 for SOC P / SIGMANET P network
SAFEDLINK Repeater S24236-B2502-A1 SIGMANET P extensiom
SIGMANET operating panel S24230-F130-A4 Operating panel for installation in
SIGMASYS M control and indicating panel,
OP-housing, OP console installation
SIGMASYS M dummy plate C24230-A12-B17 Dummy plate for SIGMASYS M in remote
operating panel
SIGMASYS Battery cabinet OP hous- S24230-C109-A1 Battery cabinet für 2 x 12V 65Ah batteries
ing remote
SIGMASYS FDnet Ansch. FDC S24230-B150-A1 SintesoTM detector Loop connection
SIGMASYS MPC S24230-B103-A6 SIGMASYS detector Loop connection
SIGMASYS GMG-S S24230-A106-A2 Threshold detector connection
SIGMASYS PMG-S S24230-A105-A1 Pulse-polling detector connection
SIGMASYS APL 26 S24230-A122-A1 Connection board for PMG-S
SIGMASYS APL 20 S24230-A123-A2 Connection board for MPC
SIGMASYS U-APL S24230-A133-A1 Connection board for dual-MPC/FDC
SIGMASYS LPC Anschaltung S24230-B139-A1 Transliner Ringbus connection
TR-APL S24230-A145-A1 Connection board for LPC
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 105 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
14 Order Overview
Flat cable for SPF 3200 LED C24217-A26-B2 For indicator panel control facility Connec-
tion line for 10 LED
Opto control module C97117-Z3004-C1 eleven LED connections for the indicator
panel control facility.
MS8-Terminal connection G32930-U 2033 For indicator panel control facility For 10
outputs
Control module SPF5100 S24218-A15-A2 Connection to detector output possible
Special detectors
FDF221-9 flame detector A5Q00003902 C-Line one-eyed (no interference)
FDF241-9 flame detector A5Q00003006 S-Line two-eyed (sun resistance)
FDFB291 flame detector base A5Q00003310 Base for FDF221-9, FDF241-9
FDL241-9 linear smoke detector A5Q00002298 S-Line
FDLB291 linear detector base A5Q00003941 for FDL241-9
Manual detectors
Hfm red FDM223 (complete) A5Q00008098 Complete with shield and cable gripper
FDMH223 L24213-L8000-A224 With reinforced housing
FDME223 switching unit A5Q00003087 Pushbutton detector unit
FDMH293-R housing red A5Q00004023 Housing for pushbutton detector unit
Window shield GBI:1530415 Fire brigade/fire alarm
Cable gripper GBI:20671 for AP cable entry
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 107 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
14 Order Overview
15
Project planning examples
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 109 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
15 Project planning examples
If the above limits are observed, multiple incoming and outgoing loop lines can be fed via a
single cable, e.g. 1 loop for automatic detectors and 1 loop for non automatic detectors.
If functional endurance is required of the cable (applicable building and construction law), this
can be achived by laying the loop in such a way that forward and reverse lines are fed via dif-
ferent fire sectors (riser ducts).
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 111 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
15 Project planning examples
16
Appendix
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 113 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
16 Appendix
Feature/Version V2.0 V2.1 V2.2 V2.3 V2.4 V2.5 V2.6 V3.0 V3.1 V3.2 V3.3 V3.5 V3.6 V3.7
06.96 08.96 01.97 5. 97 10.97 04.98 10.99 10.01 4.02 02.03 04.04 08.05 04.06 03.07
Periphery elements
Suction fire detector (EXPERT)
Threshold detector via transponder
C/M
Manual call point SMF 1120
Manual call point SMF 3120
Combo detector SDF3500
EXPERT smoke detector SDF3100
PLUS smoke detector SDF2200
BASE smoke detector SDF1200
Heat detector SDT2100
Detector display SPF 3110
Control module SPF 5100
8-stage control element SPF 5200
Minitransponder SPF 3400
Transpond SPF 3500/4STE control
module
Indictor panel control module SPF
3200
Contact coupler SPF 5300
BASE smoke detector SDF1101
BASE smoke detector SDF1100
BASE heat detector SDF1101
Pulse-polling detector connection
Threshold detector directly at
SIGMASYS M
Gateway radio SPU 6100/ SPU 6101
SIGMASPACE SDF 6100
SIGMALOOP Splitter
Sinteso Elemente Fdnet
FDO221/ FDO241 optical detector
FDT221/ FDT241 heat detector
Multiple criteria detector
FDOOT221 / FDOOT241
FDF221-9 / FDF241-9 flame detector
FDL241-9 linear smoke detector
FDM221/ FDM223 manual detector
Inspection of manual detectors
FDS221 alarm sounder
FDSB291 signal base
FDCI222 input module
FDCIO222 input/output module
FDCL221 line disconnector
FDCIO223 FDnet transponder
FDCIO224 extinguishing interface
FDM224 manual call point
Feature/Version V2.0 V2.1 V2.2 V2.3 V2.4 V2.5 V2.6 V3.0 V3.1 V3.2 V3.3 V3.5 V3.6 V3.7
06.96 08.96 01.97 5. 97 10.97 04.98 10.99 10.01 4.02 02.03 04.04 08.05 04.06 03.07
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 115 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
16 Appendix
06.96 08.96 01.97 5. 97 10.97 04.98 10.99 10.01 4.02 02.03 04.04 08.05 04.06 03.07
Feature/Version V2.0 V2.1 V2.2 V2.3 V2.4 V2.5 V2.6 V3.0 V3.1 V3.2 V3.3 V3.5 V3.6 V3.7
06.96 08.96 01.97 5. 97 10.97 04.98 10.99 10.01 4.02 02.03 04.04 08.05 04.06 03.07
Assembly/ commissioning/
maintenance
Display of element addresses and
non-coded text in DIAG
DIAG preliminary version
Functional check via operating panel
Detector LED test via DIAG
NET diagnosis
SW version and HW status with DIAG
Loop periph. plan/actual comparison
via DIAG
Read mainten. req. opt. smoke det.
with DIAG
Status of MPL/detector/element via
DIAG
One-man inspection
One-man inspection Sinteso HFM
Project planning
Configuration diagram
Data export to the GMA Manager
Parameterisation of the control and
indicating panel interfaces
SW service packages with code in-
puts
Foreign-language version of
SIGMASYS C/M
Configuration diagram
Language independent Firmware of
the control and indicaing panel
Detector zone AT correlation via op-
erating panel
PLAN D100 Version: V2.0 V2.1 V2.2 V2.3 V2.4 V2.5 V2.6 V5.0 V5.1 V5.2 V6.0 V6.1 V6.3 V6.4
The control and indicating panels beginning with V2.0 can be programmed with the actual
PLAN D100 V5.1.
Only features that are available in the control and indicating panel’s software version can
be programmed, otherwise the entire system will not function correctly.
In the case of software versions 2.2 to 2.4, all control and indicating panels in a SIGMANET
must have the same firmware.
Control and indicating panels and operating panels with the software versions V2.5 and V2.6
and V3.x may be operated in a SIGMANET.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 117 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
16 Appendix
All SIGMANET units must operate with version V3.1 if TD-32B-DC and BMXtra modems are
used.
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 119 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
16 Appendix
16.3 Terminology
Actuator Output
Addresses Physical number or numbers of an element (detector, transponder, indicator
panel) on a SIGMASYS monitored line
Alarm zone
Group of multiple detector zones in a fire section
(AZ)
Detector zone (MG) Group of detectors
DPU Printer Protocol Converter
Fire section Portion of a building which is structurally isolated from other building parts
or other buildings in order to obstruct the spread of fire for a defined length
of time
GMG-S Module for connecting threshold detection system elements
LPC Loop Periphery Controler
MPC Connection module for SIGMALOOP – spur monitored lines
(Multifunctional Peripheral Controller)
PMG-S Module for connecting pulse-polling system elements
SAC PCB for monitoring the system peripherals and power supply
(System Alarm Controller)
SCI Interface to third-party computer
(Standard Communication Interface)
SOC SIGMASYS M processor module
(System Organisation Controller)
SOP SIGMASYS Operation Panel
TR-APL Transliner connection plate
U-APL Switch connection plate
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 121 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
Figures
Figures
Sorted in order of appearence
Figure 1: Dimensions for the SIGMASYS control and indicating panel ................................. 13
Figure 2: Console installation DT1000 operating panel console, tiltable ............................... 14
Figure 3: Console installation for empty housing remote operating panel ............................. 15
Figure 4: SIGMASYS C control and indicating panel assignment ......................................... 16
Figure 5: SIGMASYS M control and indicating panel assignment......................................... 18
Figure 6: Alarm organization.................................................................................................. 33
Figure 7: Physical connection ................................................................................................ 51
Figure 8: Dual MPC ............................................................................................................... 56
Figure 9: Close-and-retain systems ....................................................................................... 60
Figure 10: Line lenghts from periphery to power supply unit ................................................. 73
Figure 11: Assembly example 1............................................................................................. 74
Figure 12: Assembly example 2............................................................................................. 74
Figure 13: Assembly example 3............................................................................................. 75
Figure 14: SIGMAPLUS SDF2200 Optical smoke detector................................................... 82
Figure 15: Address element number and line lengths for a 0.8 diameter line........................ 83
Figure 16: Address element number and line lengths for a 0.6 diameter line........................ 84
Figure 17: FDnet overview..................................................................................................... 86
Figure 18: Additional signal bases and alarm sounders allowed for a given load factor ....... 91
Figure 19: Load factors in relation to line diameter and line length ....................................... 92
Figure 20: SIGMANET main block diagram........................................................................... 94
Figure 21: Modem links in SIGMANET .................................................................................. 96
Figure 22: Mobile operating panel connection – diagram of principle.................................... 99
Figure 23: Central AT release.............................................................................................. 100
Figure 24: Project planning form for processing .................................................................. 110
Figure 25: Project planning examplesw SIGMALOOP ........................................................ 110
Figure 26: SIGMALOOP at an existing star-configuration line network ............................... 111
Figure 27: SIGMALOOP lines.............................................................................................. 111
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 123 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
Tables
Tables
Sorted in order of appearence
Table 1: Guidelines for failure of the display unit and signal processor................................... 8
Table 2: Overview of control and indicating panel selection .................................................. 10
Table 3: Control and indicating panel limitations ................................................................... 11
Table 4: Allocation of event location numbers ....................................................................... 12
Table 5: Allocation of event locations in the peripheral elements in FDnet ........................... 12
Table 6: Dimensions for SIGMASYS control and indicating panels....................................... 14
Table 7: Layout of the SIGMASYS M .................................................................................... 19
Table 8: Determining maximum current................................................................................. 20
Table 9: Overview of interfaces ............................................................................................. 24
Table 10: Summary of SIGMASYS M interface with SOC P, SIGMANET P ......................... 25
Table 11: Protocol printer DL3750+....................................................................................... 25
Table 12: Protocol printer T2240/9 ........................................................................................ 26
Table 13: Thermal printer FD60............................................................................................. 26
Table 14: Printer protocol converter....................................................................................... 27
Table 15: Programming in SIGMAPLAN................................................................................ 29
Table 16: Operating panel display ......................................................................................... 29
Table 17: BMT/IMT mixed mode............................................................................................ 35
Table 18: Alarm counters....................................................................................................... 35
Table 19: Relay module - technical data................................................................................ 42
Table 20: Technical data, voltage, current dimensions.......................................................... 52
Table 21: Cycle time for signals from transponders and contact couplers ............................ 53
Table 22: SIGMALOOP extinguishing interface-overview of the features ............................. 58
Table 23: List of approved power supply units....................................................................... 60
Table 24: Monitored control lines........................................................................................... 64
Table 25: Mains supply .......................................................................................................... 70
Table 26: Bridging time .......................................................................................................... 71
Table 27: Pulse-polling detector elements and evaluation procedures ................................. 81
Table 28: Operating conditions and sample applications ...................................................... 82
Table 29: Line parameter....................................................................................................... 83
Table 30: Example of how to calculate the load factor .......................................................... 85
Table 31: Supported Sinteso™ elements ............................................................................... 87
Table32: Parameter sets for FDOOT, FDO and FDT detectors ............................................ 88
Table33: Parameter sets for flame detectors FDF221 and FDF241...................................... 88
Table34: Parameter sets for linear smoke detector FDL241-9 .............................................. 88
Table35: Parameter sets for alarm devices ........................................................................... 89
Table36: List of load factors for elements .............................................................................. 90
Table 37: Using a modem...................................................................................................... 96
Table 38: Operating panels.................................................................................................... 97
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 125 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
Index
Index
Evacuation alarm 63
4 Event delay 33
4STE control module 42 Event display control pattern 64
event implementation 32
A External alarm display module SPF 3110 50
About the manual 2 Extinguishing control module 56
Alarm buffering 33
Alarm counter 35 F
alarm horn 89 FDnet 85
Alarm number 10 FDS221 89
alarm organization 32 FDSB291 89
Alarm transceiver 38 Features SIGMANET 95
Alerting facilities 62 Fire brigade operating panel 38
ANZ 64 fire section control facility 64
Appendix 113 freely configurable control parameters 65
AT release 100 FSA 59, 64
Functions 31
B further information 3
Battery 70
BMT/IMT mixed mode 35 G
Gas extinguishing systems 57
C GMA Manager 27
Central AT release 100 GMG-S module 78
changing ÜE assignment 34 Guidelines for project planning 7
Close-and-retain system 64
Close-and-retain systems 59 I
Contact coupler SPF 5300 47 Important notes 5
Control facility 63 Indicator panel control facility SPF 3200 49
Control module SPF 5100 49 Information on the Internet 3
Control Pattern AL 67 input/output module FDCIO222 44, 45
Control Pattern ANZ 67 installation dimensions 13
Control Pattern EV 67 Introduction 1
Control Pattern ST 68
Control room requirements 13 K
Control unit connections 37 Key depot 38
Copyright and trade names 2
Current requirement calculation 71 L
Cycle time for signals 53 layout 19
Limitations 8
D Line connection 47
D100 Interface 11, 28 line length 89
daytime/nighttime 32 Line lengths 83
description of the control pattern 62 List of approved power supply units 60
Detector display display control pattern 64 load factors 90
determining maximum current 20 Load factors 84
DIN VDE 0833 6 Local alarm 38
Display 64 Loop 81
documentation 3 loop element 41
dual SOC 20 Loop element 42
E M
Earthing 70 Mains supply 70
element numbers 89 Maxitransponder SPF 3500 42
empty housing 73 Measuring the battery capacity 71
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules) 127 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
Index
R
Remote AT release 101
ring cable) 8
S
SIGMALOOP cycle time 35
SIGMALOOP detector algorithm 81
SIGMALOOP extinguishing interface 58, 59
SIGMALOOP Splitter 50
SIGMANET 93
SIGMASPACE gateway 48
SIGMASYS monitored line 81
signal base 89
SintesoTM 85
Software dependant features 114
Special control facilities 55
SPF 3110 50
SPF 3300 48
SPF 5200 50
Spur 81