Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Project:

Offer Nr.:
Customer:
Address:
Country:
Contact person:
Tel., Email: ,

HRU units

HRV70EC-CF-P-N-EN-74-R-P0

Inflow branch Exhaust branch


Required airflow 550 m3/h Required airflow 600 m3/h
Required external pressure 200 Pa Required external pressure 200 Pa

Winter air parameters Winter air parameters


Outside air temperature -12 °C Inside air temperature 22 °C
Outside relative humidity 80 % Inside relative humidity 50 %

Summer air parameters Summer air parameters


Outside air temperature 32 °C Inside air temperature 22 °C
Outside relative humidity 50 % Inside relative humidity 60 %

Height 360 mm
Width 846 mm
Length 1505 mm
Weight 41 kg
Maximal airflow 870.8 m3/h
U 230-50 V-Hz

Summer air parameters


AV = 550 m3/h AV = 600 m3/h

T = 23 °C EFF = 89.9 % T = 29.9 °C


RH = 84.6 % P = -1.6 kW RH = 37.5 %

T = 22 °C T = 32 °C
RH = 60 % RH = 50 %

Winter air parameters


AV = 550 m3/h AV = 600 m3/h

T= 19 °C Eff = 89.6 % T = 4 °C
P = 5.3 kW RH = 95.1 %

19 °C

T = 22 °C T = -12 °C
RH = 50 % RH = 80 %

Page 1/5 2/15/2022 20:49:54 Copyright 2VV

2VV s.r.o. Fáblovka 568 Pardubice-Staré Hradiště 533 52


Details

VENUS ventilation unit is particularly suitable for ventilation of apartments and houses. The unit is intended for indoor use in
dry environments with ambient temperatures ranging from +3 ° C to +40 ° C, relative humidity of 80% for air transport within a
temperature range from -20 ° C to +40 ° C and relative humidity up to 90%. VENUS unit is made with AC or EC motors and
can be equipped with an integrated pre-heating. Comfort version uses an advanced control system with the possibility of using
sensors of air quality.

Inflow branch Exhaust branch


Airflow volume - supply in 550 m3/h Airflow volume - exhaust in 600 m3/h
Pressure drop - supply [Pa] 87 Pa Pressure drop - exhaust [Pa] 112 Pa
Exchange efficiency - supply 89.6 % Condensation - exhaust -2.4 l/h
Mass flow - supply in [kg/h] 729 kg/h D250 / D250 mm
D250 / D250 mm

Height 360 mm
Width 846 mm
Length 1505 mm
Weight 41 kg
Maximal airflow 870.8 m3/h
U 230-50 V-Hz

Eco-design
qnom 705 m3/h
Δpsext 155 Pa
ηfan %
SFPint 0,262 W/m3/s
ηt_nrvu EN308 84,60 %

Unit characteristics

Page 2/5 2/15/2022 20:49:54 Copyright 2VV

2VV s.r.o. Fáblovka 568 Pardubice-Staré Hradiště 533 52


Dimensional scheme

Page 3/5 2/15/2022 20:49:54 Copyright 2VV

2VV s.r.o. Fáblovka 568 Pardubice-Staré Hradiště 533 52


Noise characteristics
Profile of distribution in space: Q1 (in free space)

63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz total


Lw(A) EHA
. 46.2 47.4 62 56.7 56.9 56.4 46.7 0.2 64
Lw(A) SUP
. 54.3 59.3 68.5 62.9 70 76.4 66.4 56.3 75
Lw(A) ETA
. 0 0 0 0 0 0 0 0 0
Lw(A) ODA
. 0 0 0 0 0 0 0 0 0
Lw(A) ambi
. 33.3 44.8 52.5 56.2 56 55 41.3 26.7 61.3

63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz total


Distance 1 m:
Lp(A) ambi
. 16.3 16.3 35.5 39.2 39 38 24.3 9.7 50.3
Distance 3 m:
Lp(A) ambi
. 8.7 20.2 27.9 31.6 31.4 30.4 16.7 2.1 40.8

Summary results

Airflow volume - supply in 550 m3/h Airflow volume - supply in 550 m3/h
Airflow volume - exhaust in 600 m3/h Airflow volume - exhaust in 600 m3/h
Temperature - supply in -7.2 °C Temperature - supply in 32 °C
Temperature - exhaust in 22 °C Temperature - exhaust in 22 °C
Rel. humidity - supply in 80 % Rel. humidity - supply in 50 %
Rel. humidity - exhaust in 50 % Rel. humidity - exhaust in 60 %
Condensation - supply 0 l/h Condensation - supply 0 l/h
Condensation - exhaust -2.4 l/h Condensation - exhaust 0 l/h
Temperature - supply out 19 °C Temperature - supply out 23 °C
Temperature - exhaust out 4 °C Temperature - exhaust out 29.9 °C
Rel. humidity - supply out 12.9 % Rel. humidity - supply out 84.6 %
Rel. humidity - exhaust out 95.1 % Rel. humidity - exhaust out 37.5 %
Exchange efficiency - supply 89.6 % Exchange efficiency - supply 89.9 %
Exchange efficiency - exhaust 61.4 % Exchange efficiency - exhaust 79.5 %
Heat recovery - supply 5.3 kW Heat recovery - supply -1.6 kW
Heat recovery - exhaust -5.3 kW Heat recovery - exhaust 1.6 kW

Preheater calculation
Power 963.7 W

Page 4/5 2/15/2022 20:49:54 Copyright 2VV

2VV s.r.o. Fáblovka 568 Pardubice-Staré Hradiště 533 52


Accessories

N/A

Regulation

Control using a remote control


Control based on CO2 concentration, relative humidity, occupancy
Manual speed control - 3 steps
Manual adjustment of each fan speed
Stepless regulation of el. heater power
El. heater overheating protection
Control of shutting flaps
Diagnostics of malfunctions and their reporting
Boost – Time adjustable ventilation on maximum airflow
Possibility of time period setting for filter replacement
Antifreeze protection setpoint adjustment
Adjustable offset of exhaust fan

Page 5/5 2/15/2022 20:49:54 Copyright 2VV

2VV s.r.o. Fáblovka 568 Pardubice-Staré Hradiště 533 52


Page 6 2/15/2022 20:49:55 Copyright 2VV

2VV s.r.o. Fáblovka 568 Pardubice-Staré Hradiště 533 52