Connected Utilities

EA_Gatekeeper 2200 Model Line


Ultimate flexibility, reliability & performance
The EA_Gatekeeper provides distributed intelligence throughout the
EnergyAxis AMI network. It transmits schedules, collects meter data,
manages firmware updates, and enforces communication priorities as well as
establishing secure and robust communication paths–even during outages.
All EA_Gatekeepers use the standard Honeywell gatekeeper electronics
module to provide data collection and communication on the EnergyAxis
mesh network.
Utilities can select the gatekeeper style and options that meet the
requirements for their geographies and their communications infrastructure.
See the product guide (PG42-1023) and the data sheet (EMT-DS-NAEN-
001003) for more information on the role gatekeepers play in the network as
well as information on the meter-based EA_Gatekeeper.
The various gatekeeper components are assembled and protected in a NEMA Superior performance, robust design, and
enclosure. Like the meter-based gatekeeper, the core of a gatekeeper 2200 multiple deployment options coupled with
model line is the Honeywell gatekeeper electronics module. Unlike the meter- exceptional communications flexibility make
based gatekeeper, the gatekeeper 2200 model line also includes a back-up the EA_Gatekeeper 2200 model line the best
battery, surge protection, significantly more mounting and powering options, choice in advanced smart-grid and smart-
as well as support for a wide range of additional WAN choices. meter communications for utilities.

WAN flexibility
Honeywell’s EA_Gatekeeper enables utilities to change the wide area network
(WAN) media across the entire system or at a single point. The change-out
requires minimal service effort by the utility in the field, saving the cost and
time of returning the gatekeeper to the manufacturer for reconfiguration.
This also simplifies purchasing and inventory tracking, and allows the utility
to adapt its WAN communications to take advantage of future technology
development and price reductions.
The product is designed to support the most commonly used 3rd party WAN
communications options1 and the enclosure is sized with a physical space
designed to accommodate the majority of popular WAN hardware. See Model
2200 gatekeeper questionnaire for more information.

Mounting & powering flexibility


The 2200 model line gatekeepers are designed for easy mounting at a variety
of locations such as a transformer, pole, tower, or building. Gatekeepers can
be used in gas or water only service areas as well as electricity and combined
electricity, water and/or gas service areas. Each gatekeeper comes with
universal mounting hardware that enables the gatekeeper to be installed on a
utility pole, tower, or structure.
An input voltage range of 120 VAC to 277 VAC provides flexibility for powering
the device, particularly on street light installations.

Highly configurable Reduced maintenance Easy to add or change 1. Modem hardware can be sourced by the utility or
third party WAN ordered through Honeywell as a separate line item.
Improved protection Easy to install
communications1
Built to last
14.7
The EA_Gatekeeper 2200 model line is designed [373]
8.0
[203]
to operate reliably for 20 years in the field.

Protection against environmental


degradation
The gatekeeper is housed in a NEMA 4X
rated polycarbonate enclosure designed for 16.7
[424]
either indoor or outdoor use. UV stabilized
polycarbonate provides a strong lightweight
housing with brass threaded inserts and
stainless steel hardware for extra corrosion
resistance. Inside the enclosure is a 50 Watt,
thermostatically controlled, anti-condensation
Approximate dimensions in inches [millimeters]
heater to prevent potential moisture accumu-
Approximate EA_Gatekeeper model line 2200
lation due to condensation on internal parts. dimensions in inches [millimeters]

Improved surge and electrical transient


protection
The gatekeeper is equipped with an enhanced
3-mode surge protective device to reduce
damage by both common and transverse mode
surges.

Robust design minimizes damage or


tampering
A metal enclosure vent eliminates possibility
of the damage during installation. And,
when locked, the NEMA enclosure prevents
unauthorized personnel from accessing
hazardous electrical components.

Long life battery reduces maintenance


The EA_Gatekeeper uses a pure lead acid battery
which outperforms standard SLA, VRLA, or AGM
technologies in equivalent operational backup EA_Gatekeeper model 2210
environments. Battery replacement interval is
10 years; although it may be somewhat less in
areas with high ambient temperatures.

Specifications

Operating temperature range -40 °C to +60 °C (may be limited due to third party WAN specifications)
Operational relative humidity range 5 % to 95 %
AC input voltage range 85 VAC to 305 VAC
Cable exits Cord grip glands to maintain NEMA rating
Unused enclosure entry/exit points Plugs provided to maintain NEMA rating
Product weight Approximately 30 pounds
FCC compliance Part 15, Class A
Model 2200 Gatekeeper Questionnaire

1. What type of LAN antenna configuration is required?


AC Gatekeeper External Local (antenna mounted on enclosure): EAC0M0Q7M85
AC External Remote (antenna mounted remotely): EAC0M07DM85
Solar External Remote (antenna mounted remotely): EAC0Q07GG80

2. Is a local external antenna required?


If yes, no further LAN antenna hardware is needed. Skip questions 3 and 4.

3. Is an external remote LAN antenna required?


If yes, a LAN antenna kit is an option: 7S1812G001
If an external remote LAN antenna is required, a remote RF cable is needed. Choose one of the
standard options below.
REMOTE LAN CABLE SELECTION GUIDE
PART NUMBER CABLE LENGTH (FEET) CABLE TYPE
7S1816H001 10 LMR-400 N to N terminations
7S1816H002 15 LMR-400 N to N terminations
7S1816H003 25 LMR-400 N to N terminations
7S1816H004 35 LMR-400 N to N terminations
7S1816H005 50 LMR-400 N to N terminations
7S1816H006 100 LMR-400 N to N terminations

Note: The following installation literature is required for the Ethernet WAN styles listed above: IL42-5039.

The product above ships with all the necessary hardware required to install the gatekeeper 2200
with an Ethernet WAN.
If a 3rd party WAN option is needed, you can acquire the WAN hardware by purchasing it using
normal distribution channels or through Honeywell.
The following questions walk you through the Honeywell approved 3rd party WAN options for the
gatekeeper 2200.

4. Is a cellular WAN backhaul required from Honeywell?


If no, proceed to question 6.
If yes, choose from the following carrier option list.
Note: GX450 replaces the GX440. The GX440 is obsolete.

SUPPORTED THIRD PARTY WAN COMMUNICATIONS OPTIONS


SERVICE PROVIDER HONEYWELL PN DESCRIPTION
AT&T 1B12552H06 Sierra wireless air link GX450, 4G
VERIZON 1B12552H05 Sierra wireless air link GX450, 4G
CANADIAN CARRIERS (ROGERS, BELL MOBILITY, TELUS) 1B12552H07 Sierra wireless air link GX450, 4G

If the modem is purchased using normal distribution channels or through Honeywell, a modem
installation hardware kit is still required. This kit includes brackets, fasteners, local externally
mounted antennas, and RF cables.
AC kit: 1C12599G01
Solar kit: 1C12599G01
Note: The following installation literature is required for the Sierra Wireless Air Link GX450 WAN option: IL42-5041 and PG42-1051.
5. Is a GE MDS SD2 radio required from Honeywell?
If no, proceed to question 7.
If yes, the GE MDS SD2 radio part number is: 1B12552H04
If the radio is purchased using normal distribution channels or through Honeywell, a radio
installation kit, antenna, and antenna cable are still required. These part numbers are listed below:

Required parts:
DESCRIPTION HONEYWELL PN
RADIO INSTALLATION KIT 1C12599G02
YAGI DIRECTIONAL ANTENNA 3A35598H01

Chose one of the standard options below:


REMOTE LAN CABLE SELECTION GUIDE
PART NUMBER CABLE LENGTH (FT.) CABLE TYPE
7S1816H001 10 LMR-400 N to N Terminations
7S1816H002 15 LMR-400 N to N Terminations
7S1816H003 25 LMR-400 N to N Terminations
7S1816H004 35 LMR-400 N to N Terminations
7S1816H005 50 LMR-400 N to N Terminations
7S1816H006 100 LMR-400 N to N Terminations

Note: The following installation literature is required for the GE MDS SD2 WAN option: IL42-5042.

6. Are other Honeywell approved 3rd party WAN options available?


No.

7. Is the gatekeeper solar?


If yes, a 65W solar panel kit is required. The kit number is: 5D26180G01.
The kit includes the mounting brackets and a 10-foot cable.
If a longer cable is needed, choose the 25-foot extension cable: 1C12708.

Find Out More


SmartEnergy@Honeywell.com
800-786-2215 (Honeywell Smart Energy
sales information)
866-554-9007 (Product support)

Honeywell Smart Energy


208 S. Rogers Lane
Raleigh, NC 27610 SEA-PB-NAEN-002033 | 05/17
www.HoneywellSmartEnergy.com © 2017 Honeywell International Inc.