Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

HISTORY 6 – Each family dwelling unit, abutting to public sewer

17th century - birth of the plumbing profession in the or PSDS shall have 1WC, 1KS. Further 1Lav, 1BTub/SHo
Philippines 7 – Plumbing Fixtures shall be made of smooth non-
WALLED CITY - known as Intramuros was established absorbent mat’l, free from concealed fouling surfaces
by the Spaniards as a model community and located in ventilated enclosures
20th Century – plumbing took a great leap 8 – Drainage system,
1902 – Plumbing trade was duly recognized by govt 9 – All pipings of plumbing system shall be made of
John F. Hass – first Chief of Division of plumbing durable NAMPAP-APPROVED materials
construction and inspection 10 – Each fixture, shall be equipped with a water-
Plumbing Code of the United States – basis for building sealed trap
code for city of manila 11 - Drainage piping system be designed to provide
1935 – NAMPAP was organized adequate circulation of air, trap seals under ordinary
City Ordinance 2411 – Plumbing Code for City of Manila use
1954, 3rd Congress of Rep. of Phil, 2nd Session – 12 – Vent terminals shall extend to outer air
approved third reading House Bill No. 962 13 – Plumbing systems shall be subjected to such tests
RA 1378 – Plumbing Law of the Philippines 14 – No substance which will clog, destroy pipes,
June 18, 1955 - RA 1378 was signed by Ramon produce explosive matls or interfere with PSDS shall
Magsaysay enter building drainage system
January 28, 1959 – NPC was prepared by NAMPAP and 15 – Proper protection, to prevent contamination of
was promulgated and approved by Malacanang food, water, sterile goods. Such shall be connected
National Waterworks and Sewerage Authority indirectly with building drainage system
(NAWASA) – NAMPAP also assisted the passage of law 16 – No water closet, be located in room not properly
1966-1969, Feati University – NAMPAP prepared a lighted and ventilated
curriculum for plumbing engineering 17 – If water closets or other pf are installed in bdgs w/
November 28, 1967 – first amendment to National no sewer, disposie it by accepted method of sewage
Plumbing Code was approved, including “Asbestos- treatment disposal such as septic tank
Cement Pipe” as an approved material 18 – Where a plumbning drainage system may be
RA 6541, National Building Code – was passed with NPC subjected to backflow of sewage, suitable provision
of 1959 as referral code in full text in 1972 shall be made
1996, Jaime Cabase – spearheaded updating of Revised 19 –Plumbing systems shall be maintained in
National Plumbing Code serviceable condition by Registered Master Plumbers.
1999, Fortunato H. Amosco – submitted draft code to 20 – All plumbing fixtures, properly space to be
Board of Master Plumber accessible for intended use
Hermogenes Pobre – PRC Chairman, adopted Revised 21 – Plumbing shall be installed by Registered Master
Plumbing Code of 1999 Plumbers
Pres. Joseph Ejecito Estrada, Dec 21 1999 – approved it, 22 – Sewage which may be deleterious, shall not
RA 1378 known as Plumbing Law discharge into ground, unless first rendered innocuous
through subjection to some acceptable treatment
PRINCIPLES
1 – All premises for human habitation, shall be ETHICS
supplied of pure water not connected to unsafe water 1 – Act in unprofessional manner and demand any
nor subject to backsiphonage remuneration
2 – Plumbing Fixtures, devices, appurtenance be 2 – Supplant another RMP
supplied with water in sufficient volume, w/out undue 3 – Underbid another RMP
noise under normal conditions of use 4 – Take advantage of a salaried government position
3 – Plumbing shall be designed to use min. quantity of 5 – Allow use of his/her licenseas RMP for fee to
water consistent unlicensed RMP
4 – Devices for heating and storing water must be 6 – Injure falsely, or maliciously,the reputation of
prevented from explosion through overheating another RMP
5 – Every building shall be connected to sewer system 7 – Advertise in self-laudatory language, act in any
manner which tend to bring dishonour
CHAPTER 1: ADMINISTRATION 120 days – void of permit if not commenced after
Permit Issued by – OBO having jurisdiction under suspension or abandonment
DPWH, DILG or City Mayor ½ original fee – renewal of permit
Permit Issued to – RMP 72 hours – request of inspection, after such
6 sets – submitted by RMP for permit replacement work of plumbing equipment
1 set – retained by Admin Authority 3 working days – request for inspection
2 sets – returned to applicant and owner, 1 shall be Writing & signed by Owner and RMP – request for
kept at jobsite at all time while work is in progress inspection
1 year – permit will be null and void if not commenced

CHAPTER 5: INSPECTION AND TEST Building Sewer Test – plug end of building sewer to
3 days – advance notice for inspection public sewer or PSDS then fill with water from lowest
3m or 10ft, 15 minutes – water test (no section shall be to highest point thereof
tested with less than 3m 344.5kPa, 50psi, 15mins – air pressure substituted for
Entire or Sections – water test water test in water piping
All opening except the highest opening – filled with Plus 50% - water piping test, water pressure not less
water, water test than working pressure under which is to be …..
34.5kPa, 5psi, 254mm Hg, 15mins – air test (attach an Water tightness, filling water to level of rough
air compressor testing apparatus after closing all inlets threshold, both upper and under sides of sub pan –
and outlets) test for shower receptor
Hand delivered – notice of correction

CHAPTER 4: PLUMBING FIXTURES


Porcelain Enamel Surfaces – shall be acid resistant Dishwasher drain – shall not be connected to a sink
Elongated Bowl Types w/ open-front seat – Water tailpiece, cont waste or trap of discharge side of food
closet for public use waste disposal unit
Soapstone, Chemical Stoneware, Lined with Lead, Watertight – joint between fixture and wall
Copper Base Alloy, Nickel Copper Alloy – material for Metal supporting members – support of wall-hung
special use fixtures fixtures
Gauge No. 16 US B&S 1.6mm thk – restaurant kitchen & Non-corrosive screws or bolts – secure water closet
other special use sinks and urinal flush tanks
Overflow outlet – waste shall be arranged that standing 0.375m – water closet to wall
water inside fixture cannot rise inside overflow way 0.75m – water closet to water closet
when stopper is closed nor remain inside overflow way 0.3m – urinal to wall
when fixture is empty 0.6m – urinal to urinal
Strainers serving shower drain = area tailpiece Automatic Flushing Tanks – for flushing more than one
0.3m – least dimension of access panel of connections urinal
with concealed slip joint Strainer Plate – provided for each floor drain, area of
Gauge No. 20 B&S 0.8mm thk – continuous waste and small holes is equal to cross section of tailpiece
fixture tailpiece may be made of seamless drawn brass 25.4mm, 1in – curb, finished dam of shower receptor
38mm OD – tailpiece/cont. waste for sink, lower than outside floor
dishwashers, laundry tubs, bathtubs, urinal 51mm to 228mm, 2in to 9in – dam or threshold depth
32mm OD – lavatories, drinking fountains 2% 20mm/m to 4% 40mm/m – finshed floor receptor
Brass/Copper – not be used for urinal tailpiece or trap slope
559MM, 22in wide door – threshold width when spaced from the inside edge of spout opening a
1.2m – minimum distance between door to drain for distance
special shower compartment for wheelchair use 4 times Ø of effective opening for a single wall – side
0.6sqm – finished interior area shower receptor walls, ribs or similar obstruction do not affect airgaps
762mm, 30in – circle encompassing shower rec 4 times effective opening for two intersecting wall – –
1.78m – min. area and dimensions shall be from a side walls, ribs or similar obstruction do not affect
point above shower drain outlet to this height with no airgaps
protrusions AVB installation – upright position, no valves
76mm, 3in – rough side of walls to a height of no less downstream, minimum 150mm above all piping and
than this above top of finished dam or threshold shall flood level rim
be first lined with sheet lead or copper DCV installation – horizontal, 30.5cm minimum
76mm, 3in – lining materials shall extend upward on clearance at bottom for maintenance, doesn’t
rough jambs of shower opening to a point no less than discharge water
this above top of finished dam PVB installation – upright position, valves downstream,
3 layers, 6.8kg asphalt-impregnated roofing felt – 30.5cm min above all piping and flood level rim,
metallic shower sub pan or linings discharges water
101mm, 4in – all folds, laps and reinforcing webbing RPP installation – horizontal, 30.5cm minimum
shall extend to this in all directions clearance at bottom for maintenance, discharge water
0.9kg/mm – mesh for webbing tensile strength Spill-Proof Pressure Type Vacuum Breaker – upright
25.4mm, 1in – lining shall not be nailed or perforated position minute of six 152mm or list of distance above
at any point all pipe and flood rim receptor
Non-skid surface – floors of public shower rooms Certified Backflow Assembly Tester – testing backflow
Rounded corners – gutters in public or gang shower prevention assembly
rooms 0.305mm, 1ft – minimum access and clearance for
2% - slope of gutter of public testing maintenance and repair between lowest
4.9m – spacing of drains in gutters portion of assembly and grade, floor or platform
48.88°C, 150° - limit stops shall be provided on such Installations elevated more than 1.52m – need
valves to deliver hot water with this maximum permanent platform for testing and maintenance
temperature 25mm,1in, 2Ø outlet – airgap minimum
19.6kg/m2 – lead and copper sub-pans or linngs 43.3°C, 110°F – backflow prevention for hot water over
material construction this shall be listed type
Gauge No. 24 B&S, 0.5mm thk – thickness of copper 152mm, 6in – critical level AVB
pans or liners 25mm, 1in – ballcock
Soldered / Brazed – joints in copper pans or liners 2 separate walls w/ positive, vented leak detection path
Whirlpool Bathtubs – removable panel for access – separates potable water from fluids or gasses
pump, circulation pump located above crown weir of AVB - lawn sprinkling system, potable water outlets
trap, pump and circulation piping shall be self-draining, with hose attachments, inlets to tanks, vats, sumps,
suction fittings swimming pools
DANGER-UNSAFE WATER – posting in non-potable
CHAPTER 6: WATER SUPPLY DISTRIBUTION water line which may be used for drinking or domestic
Atmospheric Vacuum Breaker – body checking puposes
member, atmospheric opening CCI, B&S, F&F ends, DCI, GWI, GS, PE and PVC – water
Double Check Valve BPA – two independently acting pressure pipes
internally or externally loaded check valves CPVC – for hot and cold water distribution system
Pressure Vacuum Breaker BPA– two properly loaded Galvanized – cast iron fittings up to 51mm and all
test cocks small-sized malleable iron water fittings
Reduced Pressure Principle BPA – differential pressure 8% - prohibited lead content of water pipes and fittings
relief valve Fullway gate valve – installed on discharge side of each
3 times Ø of effective opening for a single wall, - side water meter, water supply tanks, cold water supply
walls, ribs or similar obstruction do not affect airgaps pipe to eachwater heater.
Fullway gate valve – used to control two or more Zinc coating – not enough outside protection for
openings ferrous pipings
Shutoff gate valve – provided for each fixture Rustproofing – protection for ferrous pipings
Single Control Gate Valve – ahead any automatic Copper tubing – installed without joints where possible
metering valve supplying battery of fixtures Brazed Copper Tube, Wrough Copper Tube – when
Gravity Storage Tanks - shall be tightly covered, covers joints are permitted
shall be vented with return-bend vent pipe with area Bitumastic Coating, Fiberglass Wrapping – protects
not less than area of down-feed riser pipe copper tube, installed inside a split rigid casing
14-18 mess per 25mm – fine corrosion-resistant screen 0.3m – union in water supply piping away from
opening of vent for gravity supply tanks regulating equipment
103kPa, 15psi to 551kPa, 80psi – water pressure in 61m or less – maximum length of supply piping, each
main or other source of supply water piping system 50Fu shall be sized in accordance
Hydro-pneumatic pressure tank – will provide if less with table 6-6
than 15 psi or inadequate water pressure 19mm Ø – building water service pipe minimum
Pressure regulator – installed to reduce if more than 1219mm, 4ft at end of branches ; change of direction or
80psi or excessive water pressure elevation - intervals for support of all pipings
80% - percentage of reduced pressure of all pipe size Vertical piping – supported at each story
determination when using table 6-6 Mid-story guide – used in alignment of vertical piping
Pressure Relief Valve – provided to a pressure maintained between floors
regulating device or check valve, or any water system 914mm, 3ft – in excess of this, support trap arms as
containing storage water heating equipment, water close as possible to trap
heating device Corrosive resistant fasteners, w/ top surface 1/4in
76mm I.D. storage instantaneous heaters – does not above finish floor – closet rings
need pressure relief valve Thrust Blocking – change in direction, chang in size,
Expansion tank – for intermittent operation for thermal dead ends, valves
expansion control when building supply pressure is
greater than required relief valve pressure setting CHAPTER 7: EXCRETA DRAINAGE SYSTEM
1033kPa, 150psi – pressure relief valve setting
Relief Valves – inside building shall have drain and not CI, DI, GS, GWI, Lead, Copper, Brass, Series 1000 PVC
smaller than relief valve outlet DWV, extra-strength vitrified clay pipe – excreta
0.6m – extension of drain from valve to outside of drainage pipings
building ABS, PVC DWV – used in high-rise buildings
152mm – above ground and pointing downward, the CI, MI, Lead, Brass, Copper, ABS, PVC, Vitrified Clay –
drain of relief valve drainage fittings
Drainpipe of the former – not be trapped, not 152mm above ground – no gwi or galvanized steel pipe
threaded, not capped shall be used underground
CT&PRV Combination Temperature & Pressure Relief Vitrified Clay pipes - not above ground, not used in
Valve – shall be installed in water heating device, be pressurized piping, shall be kept 0.3m below FGL
provided with drain Fitting on screwed pipe joints – shall be of recessed
Copper tubing – only change in direction that may be drainage type
made with bend Tapped – threads of drainage fittings to alow 2%
Clay materials – water piping materials that shall not Clotheswashers in group of 3 – rated as 6Fu, for
be laid in same trench as building sewer common horizontal and vertical waste pipe sizing
0.3m – water service yard piping below finish ground Water Closet is 6Fu – when determining septic tank
level; above top of sewer or drain line; horizontal size
distance between sides from side of sewer or drain line Capacity over 3.15L/s or 50gal/min – FU will be
Ferrous piping - shall have outside protective coating determined by Administrative Authority
Field bitumastic coating and wrapping – provide 2fu for every 1 gal/min – from sump pump, ejector or
protection, applicationis only to short pipe lengths at aircon equipment, or continuous flow into drainage
point of connection with fittings necessarily stripped system
for threading and jointing
Single Vertical Drainage Pipe – can serve 2 fixtures set
back to back, side by side
Double Sanitary Tee, Double Wye,1/8 bend – waste
separately served by single vertical drainage pipe
having inlet opening at same level Gravity – practicable drain into public sewer or PSDS
Upper Terminal, @every 15 meter – cleanout provided Backwater valve – installed when flood level rim of
Hor. Drain Line less than 1.5 – cleanout omitted fixture is below elevation of upstream manhole invert
Short Hor drainage pipe @ 72° from vertical line or 1/5 of public sewer
bend – cleanout omitted Watertight sump or receiving tank then lifted and
Hor Line, offset angle exceeding 135° - cleanout discharged to building drain or sewer through
provided mechanical device – when drainage piping serving
Right angles – cleanout fixtures is located below crown level of the main sewer
Wye branch & end of line cleanout – installed vertically 50.8mm, 2in – minimum size of any pump discharge or
above flow line of pipe discharge pipe from a sump connected to water closet
Cleanout extension – considered as drainage piping Swing check valve and gate valve –for vertical discharge
Each 90° cleanout extension – shall be extended from a line from such ejector, or mechanical device to
wye type fitting or O.A.F.E.S horizontal drainline,
Cleanout for interceptor – outside interceptor Top of hor line through wye fitting – connection of
Cleanouts– above grade, readily accessible, located to former valves stated
serve purpose it is intended Discharge side of backwater /check valve - gate valve
Cleanout under cover plate – installed to provide location (stated earlier)
clearance and accessibility 2fu – for each 1gal per min or 0.063L/s. discharge from
any pump or ejector
Watertight masonry pit – enclosing backwater valves,
gate valve, motors, compressors air tanks and other
mechanical device
Watertight, Concrete, Metal ; automatically discharging
– sumps and receiving tanks
Dual pumps - provide for sumps rates as “public use”
Bolt and gasket type Manhole – substantial cover of
Not less than 305mm – clearance of cleanout in piping sumps and RT for access
51mm or less Vent of Sump – extend separately through the roof or
Not less than 450mm – clearance of cleanout piping when allowed, may be combined with other vent,
51mm or greater Not less than Table 7-5 or 51mm, 2in – vent of sump
0.45m vertical, 0.75m horizontal – extension of Air operating sewage Ejector – its vent shall not
cleanout in underfloor piping above finish floor or combing to other vents
outside building Air tanks – maintain air pressure of not less than 3kg
6.1m – max clearance/dist of underfloor cleanout to for each meter height of sewage raised
access door, trap door or crawl hole Suds-producing fixtures – not connected to horizontal
Pressure drainage systems – cleanout provided excreta drainage piping system w/in 2.4m of any
Countersunk cleanout plugs – installed where raise vertical and horizontal change od direction of stack
heads may cause hazard to passing personnel/vehicle Exceptions – single family residences, stacks receiving
discharge from less than 3 stories
4WC of 6Fu – allowed on any vertical pipe stack
3Wc, 6Fu – allowed on any horizontal branch/drain
32mm, 1.25in, 1/2Ø of drain connected – Ø of
individual vent

Hubless blind plug – complete coupling and pplug shall CHAPTER 8: INDIRECT WASTE PIPING, WET-VENTED
be accessible for removal or replacement SYSTEM AND SPECIAL WASTES
Airbreak - evaporative cooler, air washer, air The former discharged to an expose fixture – brass
conditioning equipment tailpiece
Airgap – cold storage room, refrigerator, cooling Either diluted before or after discharge – condensate
counter, compartment, receptacle, appurtenance, waste from a fuel burning condensing appliance
device used for storage or holding of food or drink, Domestic dishwashing machine – not directly
dishwashing, culinary sink in any food preparation connected to food waste disposer drainage system
room used for soaking, washing or preparing reasy to w/out airgap fitting od DM
serve food, all food equipment Airgap – installed with flood level marking or
Airgap does not apply to – walk in refrigerators, drainboard whichever is higher
combination walk-in and reach in refrigerators used for Cooling medium (water) – through inlet side of a fixture
storage and sales of products packaged in bottles, trap in event that a suitable fixture is not available to
cartons or containers receive such discharge
25mm – airgap for drainage, between plumbing Funnel Shaped Receptagle, not less than 154mm above
fixture/appliance/appurtenance and rim of the floor overflowrim of the future – trap connection of the
sink or receptor former by means of pipe connected to inlet side
1.5m to 4.6m indirect waste pipes –shall be directly Steam Pipe – not connected to any part of plumbing or
trapped but need not be vented drainage system
Vent for indirect waste pipe – shall not combine to any Above 60°C – temp of water not to be discharged
excreta connected vent under pressure directly to drainage system
13mm, Ø of tailpiece/drain outlet – indirect waste Boiler pipes – discharge to open or closed condenser
pipes less than 4.6m or intercepting sump
0.45m to 0.8m – standpipe receptor for clothewasher Full size above the roof – vent extension of closed
extension above its trap condensers or sump
0.15m to 0.45m – no trap for any clotheswasher 152mm bottom of tank – deep seal trap of condensers
standpipe receptor shall be installed below the floor, 19mmØ – top of deep seal trap opening
but shall be roughed above the floor within this Not less than ½ capacity of condenser/sump – water
No installation of indirect waste receptor – toilet room, line to be maintained
closet, cupboard, storeroom nor any other portion of Inlets – above water line
building not for general use by occupants Open sump – condenser receving steam/hot water
Clotheswasher standpipe – may be installed in toilet uner pressure will pass here before entering drainage
and bathroom when clotheswasher is installed in same 102mm thk, 13mmthk plaster – concrete sump
room Gauge No.12 US 2.77mm – metal condensers, and be
Removable Beehive Strainer – provided in every protected by bituminous coating
indirect waste interceptor receving discharge Vol. not less than twice volume of water removed from
containing particles that clogs the receptor drain boiler when water level is reduced not less than 102mm
Pipe and equipment carrying waste or producing – sump capacity (contain)
wastes, or other discharges under pressure – shall NOT 9.29m2 – heating surface used in table 8-1
be connected to any part of drainage system Chemical / Industrial Liquid – pre-treated to render
Sump pump, pressure-wasting plumbing fixture – them innocuous prior to discharge into drainage
foregoing shall not apply to this system
Sterile Equipment – airgap Chemical-resistant glass-lined pipe, high silicon iron
Fixture w/ pumps & drips – approved type open pipe, lead pipe not less than 3.2mm, ceramic glazed,
receptor unglazed vitrified clay – pipe for chemical waste
Condensate waste from air conditioning coils Wet Venting – limited to vertical drainage pipine, from
discharged by direct connection to lavatory tailpiece – trap arm of 1 and 2 FU; vertical piping between any
shall be located in area controlled by same person two consecutive inlets
controlling air conditioned space Wet vented fixtures – same floor level
Undiluted condensate waste from fuel burning 1 pipe larger than reqd min waste pipe of upper fixture
appliance discharged to drainage system – cast iron, / 1 pipe larger reqd min pipe size for sum of FU served
galvanized iron and plastic by wet vented section / 51mm Ø – wet vented section
Special Venting for island dixtures – wye fitting; extend 3m, 0.9m – vent termination from, and above any
vent line to nearest partition then through roof to openable window, door opening, air intake or vent shaft
open air; connected to other vents not less than 0.15m – vent termination above roof or fire wall
152mmabove flood level rim of fixtures served; 2% 3m,2.1m – vent termination from, and above roof for
slope; return bend used under drainboard 45deg other puposes
elbow Flagpoling – prohibited, except other than weather
CW&VS – Combination Waste and Vent Systems protection
Branch More than 4.6m length – separately vented 10 stories & more – served by parallel vent stack
(CWVS Yoke vent @ every 5th flr – at pt. below the horizontal
@least ½ cross sec are of drain pipe – minimum area of soil waste branch connection to stack and at nearby
any vent (CWVS) vent stack above same floor to provide relief vent
Downstream of the Uppermost Fixture – vent Soil stack Ø vent stack Ø – size of yoke vent
connection(CWVS) 1m above floor level – placing of yoke vent connection
2 pipe size larger than Chapter 7 – waste pipe and trap with vent stack
0.6m – tailpiece(CWVS) Table 7-5 – sizing of vent piping
Tailpiece not less than 51mm – cleanout not required 32mm, 1/2Ø of drain connected – individual vent
(CWVS) diameter
Clear wastewater – airgap, water lifts, expansion tanks,
cooling jackets, sprinkler system, drip or overflow pans CHAPTER 10: TRAPS AND INTERCEPTORS

CHAPTER 9: VENTS AND VENTING Each plumbing fixture – required approved-type


waterseal trap, except having intergral traps
Vent Piping omitted – interceptor acting as primary 1trap = 1trap arm
settling tank and discharging through a horizontal 0.75m apart, 3 single compartment sinks/laundry tubs
indirect waste pipe into secondary interceptor; same depth – may be served by one trap
equipment of bars, soda fountains Food waste disposal – separate trap
Secondary Interceptor – tapped and vented 0.6m – tailpiece (fixture outlet to trap weir)
CI, DCI, GS, GWI, Lead, Copper, Brass, Schedule 40, ABS, 2Ø of trap arm, Table 10-1 – trap arm dev. Length
DWV, Series 1000, PVC, DWV – materials for ventins Less than 90° - trap arm change in direction w/out
15cm – no GWI, GS used underground but shall be cleanout
kept above ground at this 76mmØ &larger, 22.5° & greater change in direction –
Copper, CI, GWI, PVC – horizontal and vertical vent cleanout required
lines and vent stacks 1.8m – dev. Length between trap of WC to inner edge
CI, GMI, GS, Lead, Copper, Brass ABS, PVC – vent fittings of vent
Stained or Bent –NO vent pipe Gauge 17 B&S 1.1mm thk – tubing trap used on fixtures
Vent Aggregate cross sec area not less than largest discharging domestic sewage but shall exclude urine
required building sewer No more than one approved slip joint fitting may be
May exceed 1/3 of tot length of vertical and horizontal used on the outlet side of a trap
portions by table 7-5 – length of horizontal portion of a S Bell, Crown Vented Traps, Double Trap – prohibited
vent Drum Trap – installed only when permitted, not
152mm – rise of vent vertically above highest flood installed without vent
level rim of fixtures before offsetting horizontally 2in to 4in – water seal
1 pipe size – VSTR reconnection point of stack vent and Backwater valve – equipped when floor drain trap are
horizontal vent subject to reverse flow
Not below weir of trap – vent pipe opening from a soil Automatic – means of maintain water seals for floor
or waste pipe except water closets drain or similar traps
2 fixtures – may be served by a common vertical vent, 152mm – water seal for sand interceptor
but they should wastes into approved double branch Relief Vent – interceptor or clarifier be designed that
fitting having inlet openings at same level they will not become air bound if closed covers are
0.15m – stack vent termination above roof used
0.3m – stack vent termination vertical surface nearby
Use of Ladder / Removal of Bulky equipment – to GI, Schedule 30, CISP, SQ Type DWV copper tube,
service interceptor or clarifier is a violation Schedule 40 ABS, DWV, Series 1000, PVC DWV –
Slaughter House/ Packing Establishment – discharge to rainwater piping located within a medium height
a screening device then into a grease interceptor building
Auto Wash Rack – to interceptor to separate oil and Cast Iron, Copper – Roof drain
grease before effluent reach public stream 102mm above surface – roof drains with strainers
Grease Trap – sinks and drains in restau, cafes, lunch extension above roof
counter, cafeterias, bars and club, hotel, hospital, Dome type Strainer – total net inlet area is 1 ½ times
sanitarium, factory or school kitchens, establishment area of outlet pipe where drain is connected
where grease is introduced Flat-surface type, roof deck strainers – for sun decks,
1.3L/s to 3.4L/s – rate flow for grease trap parking decks and similar occupied areas; inlet area is 2
Flow control/ Restricting device – installed in readily timearea of outlet pipe
accessible and visible location in tailpiece of grease Roof drains passing through int. of bdg – CI w/
trap; no adjustable or removable parts integrally cast waterstop ring
Inlet more than 1.2m lower than outlet, not less than Inside-caulk / Female screwed – all strainers stated
50% greater in Table 2 nor 4 separate fixture – grease 102mm/hr – rainfall in Manila Area
trap Where vertical walls project above roof to permit storm
1.2m hor dist bet outlet and grease trap, vertical drain water to drain to adjacent roof are below, total roof
pipe – grease trap may be used as a fixture outlet area considered:
Water jacketed grease trap – not allowed 1 wall – 50% of area of wall to roof area
51mm, Ø of outlet – water seal of grease trap 2 adjacent wall – 35% total wall areas to roof area
6ft – dev length between trap of a water closet or 2 opposite wall, same ht – no additional
similar to inner edge vent 2 opposite wall, diff ht – 50% of wall area above top of
# of meals per peak hour x waste flow rate x retention lower wall to roof area
times x storage factor = interceptor size (liquid cap) Wall on 3 sides – 50% of area of inner wall below top of
Interceptor w/ wire basket – laundries that doesn’t lowest wall, plus allowance for area of wall above top
have integral strainers of lowest wall
12.7mm or larger – dimension of solids in laundries Wall of 4 sides – no alloance for wall areas below top
that must be prevented to pass of lowest wall, add areas for above top lowest wall
Sand Interceptor – drain containing solid or semi solids Area of side of tall building exposed to rain –taken as ½
heavier than water; can be for multiple drains; shall of gross area
have baffle – for full separation on interceptor in 2
sections; shall have two(2) opening of same Ø as outlet CHAPTER 12: HOUSE DRAINS AND HOUSE SEWERS
pipe; same invert as outlet pipe
Outlet pipe = inlet pipe (76mm min) 61meters – public sewer may not be considered
Invert inlet pipe no lower than invert outlet available beyond this distance
0.2sqm – min dimension sand interceptor Rain, surface, subsurface water, cesspool, septic tank
5gal/min over 20gal/min increase area by 0.09sqm effluents, seepage pit, underdrain system, commercial
50% inlet section – outlet section minimum area food waste grinder- shall now be connected to public
sewer or PSDS
CHAPTER 11: STORM DRAINAGE SYSTEM 150mm, 6in or Ø diameter – minimum building sewer
2% - slope
CI, GSI, Brass, Copper, Lead, Schedule 40, ABS, DWV, 1% - for 102.4mm and 150mm
Series 1000, PVC DWV – rainwater downspout or 0.5% - 203mm and larger
conductor placed within interior of building inside 0.6m – building sewer from outer face of any building
vertical pipe chase 0.3m – below finish surface of ground
26ga galvanized sheet metal – rainwater downspout or Two way clean-out fitting -
conductor located on exterior side of a low height 15m, change in direction exceeding 135° – additional
building building sewer cleanout
Steel Pipe / Cast Iron – bottom of foregoing Does not exceed 3m of building sewer branch – no
conductor’s catch basin storm drain or storm sewer cleanout
At right angles thereto, horizontal lines – cleanout shall
be installed to
Wye branch and end of cleanout – cleanout installed
vertically
Strong yard boxes w/ hinged cover OR extending top
cover w/ countersunk operating nut flush – cleanouts
installed under concrete or asphalt paving
Manholes – in lieu of cleanouts
91m – max distance between manholes
3m – water pipe joints installation away from sewer
line in both direction
1.5m – every abandoned building sewer shall be
plugged or capped
0.6m – min hor dist of bdg sewer to Building structures
Clear - min hor dist of bdg sewer to property line
adjiong private property
15.2m - min hor dist of bdg sewer to water supply wells
15.2 - min hor dist of bdg sewer to streams
0.3m - min hor dist of bdg sewer to on-site domestic
water service line
0.3m - min hor dist of bdg sewer to public water main
7.6m – distance from water supply wells may be
reduced up to this

CHAPTER 13: JOINTS AND CONNECTIONS

Caulked Joints – for bell-and-spigot CISP and other


similar joints shall be firmly packed with oakum or
hemp and filled with molten pig lead to a depth not
less than 25.4mm. Finished joint shall not extend more
than 3.2mm below rim of the hub
Threaded Joints – IPS pipe and fittings shall be standard
taper pipe threads | Plastic, factory cut or molded |
Threded plastic pipe shall be Schedule 80 minimum wall
| Tubing threads shall conform to fine tubing thread
standards | Cleanout plugs and caps be lubricated with
water-insoluble, non-hardening material | Tape is
acceptable for use on male threads only if screwed pipe
joint
Wiped Joints – joints in lead, brass or copper pipe,
ferrules, solder nipples or traps shall be full-wiped lead
joints | Wiped lead joints shall have exposed surface on
each side of a joint not less than 19mm and at least as
thick as the material being joined

You might also like