Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Project: ETAP Page: 1

Location: 16.0.0C Date: 13-08-2021


Contract: Revision: Base
Engineer:
Filename: adana_r1 Protective Device Settings

OCR: R_GOKBEY
MFR: GE Multilin Tag #: CT Base kV If (kA)
Model: F650 Phase: 800/5,000

GND: 800/5,000
Sen. GND: 800/5,000
OC Level: OC1
Range Setting
Phase TOC I^2T
Pickup (Tap) 0,05 - 160 Sec - 5A 0.460
Time Dial 0.080
Phase INST Pickup 0,05 - 160 Sec - 5A 1.150
Time Delay 0 - 900 Sec 0.000
Ground INST Pickup 0,05 - 160 Sec - 5A 0.160
Time Delay 0 - 900 Sec 0.000

OCR: R_OSB
MFR: GE Multilin Tag #: CT Base kV If (kA)
Model: F650 Phase: 80/5,000

GND: 80/5,000
Sen. GND: 80/5,000
OC Level: OC1
Range Setting
Phase TOC I^2T
Pickup (Tap) 0,05 - 160 Sec - 5A 5.000
Time Dial 0.100
Phase INST Pickup 0,05 - 160 Sec - 5A 15.000
Time Delay 0 - 900 Sec 0.000
Ground INST Pickup 0,05 - 160 Sec - 5A 2.000
Time Delay 0 - 900 Sec 0.000

OLR: R_GOKBEY
MFR: GE Multilin Tag #: CT Base kV If (kA)
Model: F650 Phase: 800/5,000

GND: 800/5,000

OLR: R_OSB
MFR: GE Multilin Tag #: CT Base kV If (kA)
Model: F650 Phase: 80/5,000

GND: 80/5,000