Project Name Client Name PO No Document Description RESIDENT TOWER Vendor Document : RESIDENT TOWER INTERNATIONAL TRADE AND DEVELOPMENT, COMPANY 2 150048 BATTERY CALCULATION Document Number S187-01C-021 ‘Vendor Document Review FIRE ALARM SYSTEM DIESEL TANK ROOM Action Code Description 1 ‘Approved with comments, ___| Vendor to submit for Final 5 ‘Approved with comments, Vendor to amend and re-submit for Final 7 ‘Approved with comments, L ‘Vendor to amend and re-submit for Approval Not Reviewed / Considered unacceptable Quality, - Re-submit for Review By: Date: 0 |06-04-2015 Issued For Approval SAM HAQ | At -d rev. | Dat Deseigon\, | Prepared | Checked | Approved | APRS Ps _ RELEASING PANEL, RED coe a Tamm |Site [+ fosoernay = a site —[-seen eeee er a ete see 1 Reem = ate an eee sea Sar eee = ae om ee re ae ss Bo ee a eee oe a ae a ee See Sate seeyemuiiee on RESIDENT TOWER Project Name Client Name PONo Document Description Vendor Document : RESIDENT TOWER INTERNATIONAL TRADE AND DEVELOPMENT, COMPANY 2 150048 BATTERY CALCULATION Document Number : $187-01C-022 Vendor Document Review Action Code Deseription 1 ‘Vendor to submit for Final ‘Approved with comments, Approved with comments, : FIRE ALARM SYSTEM GENERATOR ROOM Z Vendor to amend and re-submit for Final z ‘Approved with comments, Vendor to amend and re-submit for Approval Not Reviewed / Considered unacceptable Quality, 4 Re-submit for Review By: Date: 0 (06-04-2015 Issued For Approval SAM HAQ AS A d Rev. Date iption Prepared | Checked | Approved ‘lien = aCe == [sere fies oe oe roti tt Faget = =| = aoe = os = a eee |e — a eee : : ee ete See ee seeycasime & na oar anid ewe ETC Sate 204 Gt tin RESIDENT TOWER Ven iment Project Name : RESIDENT TOWER Client Name : INTERNATIONAL TRADE AND DEVELOPMENT ‘COMPANY PONo + 150048 Document Description: FIRE ALARM SYSTEM DIESEL TANK ROOM BCAUSE AND EFFECT MATRIX Document Number + $187-01Z-023 Vendor Document Review Action Code. Description 7 “Approved with comments, Vendor to submit for Final " ‘Approved with comments, Vendor to amend and re-submit for Final 4 “Approved with comments, Vendor to amend and re-submit for Approval ‘Not Reviewed / Considered unacceptable Quality, 4 Re-submit for Review By: Date: 5 0 [06-04-2015 Issued For Approval SAM HAQ AS. ‘Approved Rev. Prepared | Checked | Approved | “Pho YORU 40 NOISSINe NALLNHM HORA 3HL LNOHLUM MOS ANY NI Alaa MIM ANY O1 G3SOTOSIG YO GaONGOME JE LON AW LN3IWNOOA YO ONIMWEA SIL yaw] x nes fuy NOON DIVE. 7138310 voor wrane L Leon ms aunssa, aunssa, iijseh stash way pang pau ene| x x uous anssaig | noow yn T3SaI0 uping ainssaig * m x x eee WOOe ¥NVL 738310 young Hoay , 12 nd s40| so ssapsetes wea] x ‘sv00b 940 Adu VE Woy paeseU98 neing| x x x uonenayrenuen | NOON NV 135310 ‘se0;eu way © x x x sopseareeH | now yNvL TasaI0 seyeanoy 20128100 J80H z paseq S| wesSeg soey3 F ESNED BY) Jo INOKET| t x x sopaisaieeH | MOow Nv TaS3I0 seiemy 2180 We} L Fee Ble § fonuoy esejou wey | FE |S = : 3dAL LNdNI NolLv901 wondusseg ‘ON eg |E 2/3 2 Belz eel> gia g' sowmoyomaa | 58/2 £8 E songoz1 # salon -Twuana0 abs asnvo Fl 2) § Woow NV 738310 a]; 8] = oj uirshe uorssorddns s| 8 eee eee i 1oaada Le He0us seg) WOOY MNVITAS3IC LV : (b-dow4) TANVd ONISV3134 — mee NoIssauddns uro0r YVdaan XTYLVIN LO3443 ONY aSnvo RemoTS on 20] RESIDENT TOWER Vendor Document Project Name : RESIDENT TOWER Client Name INTERNATIONAL TRADE AND DEVELOPMENT COMPANY PONo 150048 Document Description : FIRE ALARM SYSTEM GENERATOR ROOM CAUSE, AND EFFECT MATRIX Document Number : $187-01Z-024 Vendor Document Review Action Code Description i “Approved with comments, ‘Vendor to submit for Final a ‘Approved with comments, ‘Vendor to amend and re-submit for Final Z “Approved with comments, Vendor to amend and re-submit for Approval ‘Not Reviewed / Considered unacceptable Quality, Bt Re-submit for Review By: Date: 0 [06-04-2015 | Issued For Approval | SAM | _HAQ AS. Description Prepued | Chocked | Approves | Approved Ea serie CAUSE AND EFFECT MATRIX nas no 5 REDA 4004R SUPPRESSION = TE RELEASING PANEL (FACP-1) AT GENERATOR ROOM Page reek tott EFFECT z Release Foam Fire 3s |2 Suppression Syston for 2 : f GENERATOR ROOM CAUSE = |E _|3. GENERAL NOTES & LEGENDS EB |2 2/23) electric Actuator & 2/8 2/88 zdegizs No. Description LocaTion, INPUT TYPE, = ale | 3 | AccntRelease contro! 1 Heat Detector Actuates | GENERATORROOM | Heat Detector x x 1 foayoutot the Cause 8 Erects Diagram is based lon Project Speccatons and NFPA 2 Heat Detector Activates | GENERATOR ROOM | Heat Detector x x x 3 Generator room | —ManusiAcuaton |x x x louput generated rom en input he 40048 x [Panel Guput witrespond opt regardless of other Input condions 4 Abort Sitch GENERATORROOM | —Nanuaiacuaton | * x 1 s Pressure Switch cenerarornoom | Pressureaten | x x nee [Ono Zod Sepa oo ret 4004, 7 Feutin4004R GENERATOR ROOM soy Faut x 1 Prerant THIS DRAWING OR DOCUMENT MAY NOT BE REPRODUCED OR DISCLOSED TO ANY THIRD PARTY IN ANY FORM VWITHOUT THE PRIOR WRITTEN PERMISSION OF REDA

You might also like