2090 THE SECTION IS DIVIDED INTO TWO SPACING OF LEFT
SIDE OF 2350MM IN SPACING OF COLUMN OF PILES
800 IN X-X AND RIGHTER SIDE IS OF 1875MM IN X-X.
G
THE y-y SPACING OF BOTH PILE IS 2000MM.

NUMBER OF PILES : 17 x 14 = 238 NOS OF 750 MM


4000 4000
DIA PILE.
8 NOS OF ADDITIONAL PILE FOR OUTER CIRCULAR
800mm THICK SLAB COLUMNS.
800 TOTAL NUMBER OF PILE = 246
F 12764
TOTAL VOLUME (M25) OF RAFT = 1071.45 M2*0.8M =
857.16 M3
TOTAL VOLUME M25 FOR PILE=
4000 16246 4000 0.4419*8.5*246 = 923.77 M3

TOTAL REINFORCEMENT VOLUME (Fe500) INCLUDING


LAP AND WASTAGE
E 20 MM = 87.20 MT
12MM = 44.81 MT
8MM = 12.88 MT

4000 150mm C/C 4000

1351
13558 PROVIDE 100MM THICK PCC (1:4:8) & 100MM STONE
SOLING BELOW RAFT AS CUSHION.
28350 D 24230 24234 28350
VOLUME OF PCC 1:4:8: 1071.45M2*0.1M=100.252M3
STONE SOLING VOLUME = 107.14M3

4000 4000 THE LENGTH OF THE PILE IS 8.5M.


2220

THE TOP OF PILE IS AT 2M FROM THE FGL.


800mm THICK SLAB
C THE LOAD OF TRANSFORMER IS APPLIED LOADING OF
9675
800 55KN/M2 (65-10(FLOOR LOAD)) KN/M2 AND FOR GIS
2350
& WHOLE FLOOR OF 10KN/M2.

800
THE MINIMUM PILE EMBEDMENT OF PILE INTO RAFT
1/B 4700
SHOULD BE ATLEAST 3 INCH.

2350

B 10633

1349 150mm C/C


3300 3300

800
A 4001 800
2000 2000

2350 2350 1875 1875


2030 2141 2030

800

2000 1800 3450 3450 1800 1800 3450 3450 1800 3300 4000 4000 2500 1175

954 38195

RAFT REINFORCEMENT PLAN


BOTTOM
1 2 3 4 5 6 7 8 9 10 11 12 13 14

954 2103 34635 1990 1570

2000 1800 3450 3450 1800 1800 6900 1800 5100 4000 4000 2500

4273

21767 1366 1366


8652
800 800

1/G 800 800

2090 2090
2000 2000

800
G

4000 4000

800mm THICK SLAB


800

F 12764

4000 16246 4000

4000 150mm C/C 4000

1351
13558

D 24230 24234

4000 4000
2220

800mm THICK SLAB


C
9675
800

2350

800

1/B 4700

2350

B 10633

1349 150mm C/C


3300 3300

800
A 4001 800

2030 2141 2030

800

2000 1800 3450 3450 1800 1800 3450 3450 1800 3300 4000 4000 2500 1175

954 38195

RAFT REINFORCEMENT PLAN


TOP
DETAILS AT B-B DETAILS AT A-A

600 900 900 900 900 900 900 900

DETAILS AT A-A SECTION AT A-A

100MM THICK PCC


800
100MM THICK STONE SOLING
800 800

954 2350 2350 2350 2350 2350 2350 2350 2350 2350 1875 1875 1875 1875 1875 1875 1875

SECTION AT J-J

100MM THICK PCC 800


100MM THICK STONE SOLING
800 800

2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000

SECTION AT K-K
900

Lateral ties 8mm dia @150c/c


Provide 16mm dia
stiffner Ring at 1.5m c/c
CROSS-SECTION OF PILE
FOUNDATION

800 RAFT/PILE CAP

Ld
Ld
Ld
800
Pile Embeddement 75 mm
100mm thick PCC 1:4:8
100mm Stone/Brick Soiling

750 1125 750

1875

SECTION AT A-A

8500

50mm clear cover from Helical cover

Provide 16mm dia


stiffner Ring at 1.5m c/c
Ld
800

750

150

SECTION OF PILE FOUNDATION AT A-A SECTION AT B-B


Ld 1000 Ld 1000

11800 6400

L2
800 MM L3 200
200 L1
12000
L1= 12000 mm
L2= 12000 mm
REINFORCEMENT IN Y-Y DIRECTION RAFT
L3= 5940 mm

12000
11800
L2 L4
L1 L3
200 12000 200
L1= 12000 mm 4675
L2= 12000 mm
LD (1000) LD (1000) LD (1000)
L3= 12000 mm
L=9150 MM L4= 4070 mm
REINFORCEMENT IN X-X DIRECTION RAFT
8350 MM

REINFORCEMENT IN PILE