To understand how wireless communication networks are powered, you
5
need to begin with the basics—which really haven’t changed all that Powering small cell metro networks
20
much since Thomas Edison lit up Manhattan’s Financial District (NYC) on
September 4, 1882. Sure, we’ve seen a lot of refinements, improvements 6
and safety measures since then, but the principles of power generation PowerShift ® Metro 24
and distribution still apply.
Chapter 1: Introduction 2
Introduction Putting power in context
Every year, our reliance on always-on technology grows. We expect to be able What’s at stake from a business perspective? Plenty. A reliable power infrastructure
to place a call or surf the internet with our cell phones at any time, under any has significant implications for both cost and revenue. Running power to thousands
circumstances. However, the electrical infrastructure that powers our wireless of small cells will be expensive. Cutting cost by even a point or two can generate
networks has not kept pace with the demand for more macro cells and small cells. major savings, as can reducing deployment times by a day or two. On the revenue
side, we know the effect that network outages have on churn rates. With the vast
The challenge goes deeper than powering additional cell sites. The architectures of
majority of cell sites relying on older power grids for primary power, the need for
cellular access are changing dramatically. Customer demand is pushing 5G rollouts
reliable backup power is more important than ever.
which, in turn, require more RF equipment. Additional radios, more frequencies and
increasing use of remote radio units, plus an entire small cell layer that still needs to
be built out are pushing outdated power systems to the brink.
That’s why CommScope has developed this ebook, to help keep you out in front.
Here, you’ll find the “what,” “why” and “how” to help guide your power decisions
as you navigate what’s next. We’ve broken it down into easy-to-digest chapters and
sections that walk you through the key issues of powering your macro and small cell
networks. Along the way, we added the CommScope innovations designed to help you
realize the more efficient, future-ready power solutions needed to keep you and your
networks moving forward.
Chapter 1: Introduction 3
Elements of power
To understand how wireless communication networks
are powered, you need to begin with the basics—
which really haven’t changed all that much since
Thomas Edison lit up Manhattan’s Financial District
(NYC) on September 4, 1882. Sure, we’ve seen a lot
of refinements, improvements and safety measures
Thomas Edison’s Pearl Street Station was the first commercial central power
since then, but the principles of power generation and plant in the United States. It was located in the Financial District of Manhattan
(New York City). Fired by coal and powered by six dynamos, it came on line
distribution still apply.
September 4, 1882 and served an initial load of 400 lamps at 82 customers.
The international energy agency (IEA) in its latest global energy projection, the Renewable energy Reduction in Renewable energy Reduction in
Network operator Target year Baseline year
utilization (%) emissions (%) utilization (%) emissions (%)
World Energy Outlook 2018 (WEO2018), has reported that global energy demand is
Deutsche Telecom 52% 2% 100% 90% 2021 1 , 2030 2 2017
expected to grow by about 27 percent, or 3,743 million tons oil equivalent worldwide
Telefonica 81% 18% 100% 70% 3
2030 2015
from 2017 to 2040.1 At the same time, the annual energy consumption by the mobile
Telstra Negligible 40% 4 Not stated 50% 2030 2017
industry has increased from 219 TWh in 2007 to 519 TWh in 2019, and it is speculated
T-Mobile 100% 9% Already 100% Not stated N/a N/a
that the demand will rise at a yearly rate of 10 percent.2 Consequently, the electricity
Verizon N/a 28% 5 50% 50% 2025 2016
bill of telecom networks globally amounts to above US$10 billion per year.3
Virgin Media 100% 22% Already 100% Not stated 2020 2014
The importance of estimating future energy requirements and their consequent Vodafone 15% 3% Not stated 50% 2025 2017
carbon emissions cannot be ignored when developing an effective energy policy Source: Sustainability Journal; 9 Feb. 2021
for the future.4 And, in fact, the industry is gradually moving toward the use of
renewable sources such as wind, water and solar power. The table on the right
Green energy solutions taking shape
shows where the world’s major wireless providers are in their efforts to transition to
greener energy and reduce their carbon footprints. To meet their ambitious energy green peak shaving, MNOs run their macro artificial intelligence to power RRUs up
goals, the world’s cellular network sites via the grid when prices are low and down based on traffic. This reduces
To accommodate the shift toward renewables, wireless infrastructure partners have
operators are getting creative in how and switch to battery power during energy consumption, thermal loading
begun to introduce solutions that enable service providers to integrate alternative
they power their systems. peak rate hours. and their associated costs.
energy sources into their overall power infrastructure. One such solution is a more
flexible rectifier, discussed in the next chapter. In some European countries, for Operators are also employing PID To learn more about minimizing power
example, energy costs vary throughout (proportional–integral–derivative) consumption with PID controllers,
1 World Energy Outlook 2018, Aug. 2020
2 Sustainable power supply solutions for off-grid base stations, Energies, Sep. 2015 the day depending on supply and controllers to boost energy efficiency. download CommScope’s white paper,
3 Towards Energy Efficient Load Balancing for Sustainable Green Wireless
demand for power. Using strategies like PIDs use special scripting, automation or “Potential energy savings using PID.”
Networks Under Optimal Power Supply; IEEE Access, vol. 8, 2020
4 Analysis of Renewable Energy Usage by Mobile Data Network Operators; Sustainability Journal; 9 Feb. 2021
Multiple rectifier modules are usually required to supply power for the base station’s
load. Modules are connected in parallel, enabling them to share an equal part of
the load. This load sharing allows operators to design in a degree of redundancy to
guard against individual rectifier module failures.
Batteries
– dc Utility grid
R
– dc
ac 10
ac 30
R R B D
E E A I ac ac
L
C C T S inverter out
To O
Utility T T T T misc A
ac
dc dc loads D
converter out S
ac or dc generator
+ dc + dc dc fuel cell
A block diagram of a basic telecommunications power system Power source flexibility lets rectifiers draw from conventional or renewable sources
Bus bar conductors corresponding negative lead of the Fuses vs. circuit breakers protection. Fuses are generally used for these surges on sensitive electronics.
In the macro layer, the cell site’s battery. The battery return bus provides While both fuses and breakers provide lower loads and offer the advantages
An SPD features a non-linear voltage-
distribution system is supported by the a common return point for the loads overcurrent protection, they do it in of lower cost, greater flexibility and fast
current characteristic that reduces unsafe
bus bar conductors, which physically connected to the power system. This different ways. Fuses are designed to action. Circuit breakers are preferred
voltages by increasing the conducted
connect the rectifiers to the batteries common point is grounded to provide a melt under unsafe currents—physically for larger loads and do not require
current. In this case, a cell site’s SPD
and dc loads. There are two bus bar low-impedance path for transients and breaking the connection between the replacement every time they are tripped.
operates on the same principle as a
connectors: the charge bus and battery noise and offers a ground reference to power source and the load. Circuit
Surge protection surge protector does in your home—
return bus. all connected equipment. breakers have internal switches that safeguarding expensive electronics from
pop to the “off” position under unsafe Typical variations in ac power are not
The charge bus is a current-carrying Within the power distribution system lightning-induced surges.
conditions—again providing a physical the only threat to a cell site. Electrical
conductor that connects the rectifier’s there are a number of sub-systems
break in the circuit. events like lightning can also produce
output to the battery string. For designed to prevent overloads, over-
excessive voltages and currents—
instance, in a –48 V system the heating and other unsafe conditions. Sensitive wireless equipment requires
events known as “electrical surges.”
negative rectifier lead would terminate These sub-systems include fuses and “fast blow” fuses or short delay
Surge protection devices (SPDs) are
on the charge bus along with the circuit breakers and surge protectors. curve breakers to provide the needed
incorporated to reduce the effects of
The following are some of the key functions and capabilities that controllers provide:
Plant control This is useful for maintenance on VRLA in the backup batteries, the controller that allow easy disconnection for
Control functions are extended from batteries—equalizing cell voltage can open additional contacts to maintenance or replacement. Some
the supervisory panel to control other within a battery string. equalize voltage and close them disconnects incorporate safety measures
power system components. These again when levels equalize. This such as overcurrent fusing or breakers.
High-voltage shutdown/
panels communicate directly with helps prevent damage to sensitive
overvoltage protection electronics and protect the battery
the rectifiers and, in some cases, can
(HSVD/OVP) from over-discharging. LVDs also
coordinate the sequenced restart of
all rectifiers to prevent power surges Controllers can automatically shut down enable the operator to prioritize which
during switchovers from external ac to rectifiers when dc output overvoltage components are disconnected, and
a backup power source. conditions are detected—avoiding costly in which order—preserving limited
Some wireless sites require multiple have an associated battery connected technology—offering new services while to assign numbers to the distribution
dc voltage outputs. Installing a second to its output, it isn’t bound by a battery maintaining older standards. positions of each voltage. A selectable
rectifier plant is one solution, but system’s requirement for precise output voltage distribution panel makes this
Disadvantages of
requires a second battery backup array. voltage. However, since it is necessarily organization possible.
energized by the primary dc power
converting voltage
Instead, many operators use a dc-
system, that demand must be figured On the downside, converting to a given
dc converter that changes a dc input
into the power system’s initial design. voltage is inherently less efficient than
voltage to a different dc output voltage.
drawing that voltage directly from the
The solution consists of multiple dc
Advantages of converting voltage rectifiers, so losses increase as more and
converters arranged in parallel and may
Modern dc-dc converters are essentially more dc power is converted away from
feature many of the same functions as
“plug and play” devices designed to the primary voltage.
the primary dc power system, such as
fit in the racks alongside rectifiers and
distribution. It also has dedicated fuses Mapping the positions
or circuit breakers isolating it from the other converters. This approach offers
Since a single power plant can generate
rest of the system. communications providers the greatest
varying amounts of both primary and
remote radio heads being deployed and the ramp-up Typical power feed for a remote radio head
of 5G services.
Remote radio heads (RRHs) have become tower isn’t feasible because of weather
one of the most important subsystems risks, so it must be housed in the shelter,
of today’s distributed base stations. far away from the RRH. Therefore, a
In an RRH deployment, the baseband heavier gauge of power transmission
equipment remains on the ground while line is needed to sustain the voltage
the remote radio head, containing the required to operate the RRH. This adds
base station’s RF circuitry, analog/digital a significant weight onto the already-
and up/down converters, is positioned overloaded tower.
on the tower. This frees up more space
Alternatively, you can convert the power
in the base station shelter and reduces
feed, based on its voltage drop, to a
cooling costs. At the top of the tower,
higher voltage at ground level to ensure
the RRHs make MIMO operation easier
the correct voltage at the RRH.This would
and increase base station efficiency.
enable operators to deliver the right
In addition to the optical fiber amount of power to the RRHs without
connecting it to the base station, the RRH having to substantially increase the
also requires a power feed. Herein lies conductor gauge and risk exceeding the
the challenge. tower’s loading capacities. This alternative
has, in fact, been developed and is being
Each RRH needs a battery backup to
used successfully. For more, see the next
ensure operation in case of a power
section in this ebook on PowerShift.
failure. Locating the battery on the
To address these space limits, fuses or breakers and cabling tie-downs Online inverters feature a dc input
CommScope produces integrated to distribute power to the load. and an ac output with an optional ac
system includes one or more shelves necessary ac voltage. There are two switch maintains equalized voltage to
ac Return Return
Generator of rectifiers along with one or more basic types of inverters. the load by switching automatically
Voltage
1.2
volt drop when the cell site
copper is really needed to support the power needs of 1.1 is on battery (48 volts). When
End of exponential zone
the site? There is no single standard for determining the 1 the battery powers the cell
End of nominal zone site, it will provide 48 volts, so
right size of conductors to use when connecting dc power 0.9
the tower-top electronics will
0 1 2 3 4 5 6
to tower-top electronics; so, to make a good selection, initially receive 43 volts and
Time (hours)
the tower-top electronics will
consider the following factors.
remain powered until it sees
about 38 volts (which means the
Voltage drop battery starts at 48 volts and will drain the current for efficiency since the Cost battery has drained down to 43
Due to the resistance of the cable itself, until the battery disconnect is triggered rectifiers provide 54 Vdc power to the The initial cost of the cable and volts). If the conductors are sized
tower-top electronics will always have or the electronics reach their low- RRUs when primary power is connected. installation should be weighed against based on voltages supplied by
a lower voltage than the power plant voltage drop-out value. battery backup time, tower loading,
Electrical codes the rectifiers while the primary
or the ground-mounted equipment. permit costs, etc., in order to select the
Battery backup time As the power requirements at the top
power is connected, it is likely
The lower the input voltage the higher optimum conductor size. the tower-top electronics will
Depending on the required cell site of the tower have increased to 1600+
the current needs to be to maintain the either drop out when the
reliability, the battery backup should watts, electrical codes have become a Future proofing
output power level. Voltage delivered at battery is engaged or there will
last until the technician can reach factor since the amperages in conductors Consider the site evolution over the
the tower-top will depend on the power be little backup time.
the site and ensure the generator has can be exceeded. In the U.S., reference next few years so an upgrade is not
plant voltage and the size and length of
successfully started. This can range from the latest NEC table 400.5(A)(1) and needed soon after the cell site cabling is Here are some links to tools
the conductors.
one to eight hours. 400.5(A)(3) if using SO type cables completed. that will help properly size
Design case and Table 310.15(B)(16) and 310.15(B) conductors.
Power line losses
The critical factor when sizing (3) (A). Outside the U.S., reference the
Power loss is a function of the cable’s
applicable standard for flexible cable
conductors is knowing the voltage of
resistance multiplied by the square value
ampacity.
FTTA Power Calc ™
the power source when the cell site
of the current. Use 54 volts to calculate
switches to backup battery power. The
for delivering dc power to the tower, opening new Backhaul Backhaul Backhaul Backhaul
PowerShift, operators can: including RRUs including RRUs efficient voltage the
RRU can receive
efficient voltage the
RRU can receive
Programmable -50 Programmable -50
to -75 VDC to to -75 VDC to
power RRU power RRU
Baseband Battery
Baseband Baseband
Battery Battery
Baseband Battery
Extend RF battery uptime backup backup backup backup
by up to 50 percent 120/220 Vac mains 120/220 Vac mains 120/220 Vac mains 120/220 Vac mains
How it works
Achieve 97.7% power efficiency
PowerShift gives you back the balance drop challenge discussed in the previous major concern, ensuring full utilization
of power by delivering the most section. PowerShift is inserted between of backup battery runtime by the RRU.
efficient voltage to your RRUs in real the battery plant and the trunk cable at
Build future-ready infrastructure to PowerShift also eliminates having
time automatically—regardless of power the base of the tower. The battery output
accept higher-powered radios supply, distance, conductor size or RRU is fed into PowerShift, which adjusts its
to oversize the power plant and
battery backup to handle a worst case
power requirements. That optimization output voltage (VPS) to compensate for
scenario. So, MNOs can save cost and
enables you to decrease the cost of the cable voltage drop (VC), providing a
Improve cost effectiveness network rollouts and upgrades and start regulated, programmable voltage to the
accommodate higher-power RRUs in
the future.
of RRU upgrades earning a greater return on investment RRU input (VL).
from day one. PowerShift also offers
As the battery discharges down to 42
the system design flexibility you need to Watch this brief video
volts, PowerShift continues to boost its
create an agile, future-ready network. to learn more about the
All while evolving their macro layer network to support output to maintain the programmed
CommScope PowerShift
PowerShift works by optimizing backup input voltage to the RRU. This effectively
and deliver 5G-enabled services and beyond. Macro solutions
battery power by solving the voltage- eliminates the RRU dropout voltage as a
Where cell capacity is critical, you can now Get the highest level of reliability with two Four 2,000-watt, -54 Vdc circuits in a 1-RU Designed to meet budget constraints for
power up to 12 RRUs in 1-RU of rack space independent, redundant circuits per RRU chassis deliver the power and agility to applications involving a low number of
with 1,460 watts and -54 Vdc per RRU. with bypass redundancy in a 3-RU chassis. support future network growth. high-power RRUs, where deployment
• 4 modules, 3 RRUs per module • 12 hot-swappable modules for • Modular from 1-RU to 3-RU (4-12 RRUs) speed is key.
• Manual or Automatic setup for any power full redundancy • 4 dedicated 2000W output circuits • 3 high-power circuits in 1-RU chassis
level or conductor length • 12 dedicated 2,000 watts circuits (1 per RRU) (per 1-RU) • 2,166 watts per circuit, 6,500 watts
• Pulsar® controller (optional) to • Manual or Automatic setup for any power • Ganged front input and output per shelf
manage performance level or conductor length connections for easy installation in • Ability to gang the output circuits
• All active electronics are centralized • Pulsar® controller to manage performance tight spaces • Front access for quick connectivity to
• Extended battery backup life for • Easy wiring, open accessible design • Pulsar® controller to manage input and output connections
service continuity performance • Plug & play requires no configuration
• Extended battery back up life for
• Dynamic voltage regulation at the RRU service continuity • Extended battery back up life for or training
service continuity
• Dynamic voltage regulation at the RRU
• Dynamic voltage regulation at the RRU
The trend of increased power demand by remote radio units will continue, with
RRUs approaching 2,000 watts already on the drawing board and even higher
power radios expected in the future. CommScope continues to expand and evolve
the capability of the PowerShift Macro portfolio to keep pace with these demands
and support our customers’ need to maximize cell site reliability.
power configurations on the fly. The following are some engineers discover there is no electrical diesel generator, there are additional solutions that can integrate with street
power close to some of the proposed permitting and environmental issues to furniture or are available pre-assembled
of the key differences between powering macro and for faster turn-up can help operators
small cell locations. Tapping power overcome as well.
small cell networks. from existing buildings and/or getting deal with these challenges.
Space constraints
municipal approval involves negotiations
A macro tower site is pre-designed with
with building owners, tenants and local
the power cabinet and power meter
agencies, and takes time.
Power from the grid in space-constrained urban locations and to deliver power for small cells. The However, the small-diameter copper device port. As such, its use in a small
For the vast majority of mobile network satisfying tougher aesthetic regulations. challenges with HFC networks are that pairs provide limited power under the cell environment is limited to very
operators, tapping the utility grid it is still not ubiquitous and, where current standard and exhibit high power low-powered Wi-Fi access points. In
Hybrid fiber coaxial (HFC)
is the go-to solution for powering operators do not own their own losses over extended distances. At a addition, PoE is also distance limited,
HFC networks are now the mainstay
wireless networks. However, the process backhaul networks, they must lease length of 3,000 meters, the 100 watts with PoE++ rated for a maximum
of the cable television industry. HFC’s
requires intense planning and project from other providers. of injected power drops to about 60 distance of 100 meters, although
power-carrying capability can also
management. This method becomes watts of effective power. Additionally, solutions like CommScope’s Powered
provide an alternative solution to Twisted pair
less attractive as mobile network there is a general lack of documentation Fiber Cable System extends PoE use up
the small cell power challenge. As A second possibility involves tapping the
operators shift from deploying fewer regarding available copper wires within to three kilometers. While it removes
operators push HFC deeper into the power-carrying capability of the legacy
and larger-capacity macro-based cell the public-switched telephone network the distance limitations, the power
network, they’re upgrading their copper telephone networks, also known
sites to thousands of smaller capacity (PSTN). So, identifying the right power limitation remains. Moreover, the speed
60/90 Vac power plant, adding more as remote feed telecommunications
small cells. Challenges include the cost injection points is also a challenge. and latency requirements for small cell
power injection points and deploying (RFT) circuits. There are essentially two
and time involved in getting a power backhaul dictate the use of fiber, which
remote distributed-access architectures. approaches to this solution. RFT-C is Power over Ethernet (PoE)
drop (metered or un-metered) to each further weakens the business case for
This allows them to use coaxial cable, a current-limited technique, whereas The latest power over Ethernet
individual node. Additionally, network power over Ethernet.
running in parallel with the fiber, RFT-V is voltage-limited; both enable standard, IEEE P802.3bt (PoE++),
engineers must solve the issue of
as a back-feed from an optical node you to re-use the existing copper plant. supports up to 71.3 watts (dc) per
equipping each site with battery backup
This is where having a go-to solution that has already been field-
tested and vetted can be a major help. As noted earlier, a fast, flexible
and repeatable process that enables operators to deploy quickly and
efficiently—regardless of backhaul needs, power requirements or
proximity to the grid—is essential to a successful small cell rollout.
supply, rectifier and battery backup— the solution. In most cases, the cable can
Cabinet
that can be deployed from any central be co-routed with other communications
location or macro site. Grid power feeds cabling. PowerShift Metro can also be
the power hub, which distributes the leveraged to supply various types of
power and fiber to clusters of small infrastructure such as fixed-wireless
cells arrayed in a “spoke and hub” access points, mobile edge computing,
architecture. Each hub provides power hybrid fiber coaxial cabinets and smart
CommScope’s PowerShift Metro, an integrated, end-to-end solution,
and data connections to as many as four city installations. delivers power and backhaul from one central location—which can be
small cell clusters and supports a variety
Planning and provisioning for next- anywhere that has access to power and the optical network—to clusters
of topologies. The power hub also
generation applications like smart city,
contains enough battery backup to fully of neighboring small cells.
IoT and edge computing is easier, too.
power the small cells should the grid
A unique, expandable bus structure
power fail.
lets you add edge nodes or additional
Power cabling and fiber connections are power, often without cable upgrades.
integrated and routed together, in full Real-time monitoring delivers a wide
compliance with the latest standards range of data—like voltage, current, and
for distributed power connectivity. operating temperature—onsite or from
PowerShift Metro delivers kilowatts of any web browser.
power and up to 144 fiber strands in a
single composite cable.
Chapter 7: Conclusion 28
Always prepared, always pushing
ourselves to do it better and smarter,
keeping you ready for whatever is next.
www.commscope.com
Visit our website or contact your local CommScope representative for more information.
© 2021 CommScope, Inc. All rights reserved.
All trademarks identified by ® or ™ are registered trademarks or trademarks, respectively, of CommScope, Inc.
This document is for planning purposes only and is not intended to modify or supplement any specifications or warranties relating to CommScope products or services.
CO-116104-EN (09-21)