Foundation Plan and Details: Foundation Legend: General Foundation Notes
Foundation Plan and Details: Foundation Legend: General Foundation Notes
UNDERPINNING SEQUENCE:
FW-10
1. ALL FOOTINGS TO BE 36" BELOW GRADE MIN. (OR AS PER LOCAL CODE IF GREATER) ON VIRGIN SOIL WITH A SOIL BEARING CAPACITY OF 1,500
FT-24 REMOVE EARTH UNDER EXISTING
T/O STEM WALL PSI/SF MIN. 13'-6 3/4"
2. PROVIDE CONTINUOUS FLUID APPLIED WATERPROOFING OF FOUNDATIONS BELOW GRADE; PAINT OR SEAL ALL EXPOSED CONCRETE ABOVE FOUNDATION WALLS IN 2'-6" SEGMENTS.
13'-0 3/4" 6"
T/O REINFORCED CONCRETE GRADE
5'-9 1/2" 7'-3 1/4" DO NOT REMOVE MORE THAN ONE
FOUNDATION WALL 3. IF GROUND WATER IS ANTICIPATED WITHIN 4" DEPTH OF FOOTINGS; PROVIDE A FLUID APPLIED WATERPROOFING BETWEEN FOOTINGS &
FOUNDATION WALLS 2/S1.01 FORM SEGMENT LESS THAN 7'-6" APART.
T/O FRAMING LEDGE \ 4. ALL SUMP PUMPS TO HAVE BATTERY BACKUP
BEAM POCKET 5. SEE CIVIL DRAWINGS FOR FIRST FLOOR & SITE GRADE ELEVATIONS REMOVE SEGMENTS IN THE FOLLOWING
5/S1.01 A/ B/ C/ D ORDER.
4/S1.01
6. SEE CIVIL BOUNDARY SURVEY AND/OR DEED FOR PROPERTY & FOUNDATION ANGLES
EXISTING MASONRY WALL 7. G.C. TO MAINTAIN SITE GRADING CONDITIONS DURING CONSTRUCTION TO DIRECT STORM WATER AWAY FROM EXISTING STRUCTURES &
FW-10
3'-10"
AREAS OF EXCAVATION FW-10 1. REMOVE EARTH FROM ALL 'A' 2'-6" SEGMENTS.
FW-10
PIER"B"
8. G.C. TO VERIFY SITE GRADING CONDITIONS PRIOR TO FOUNDATION CONSTRUCTION & NOTIFY ARCHITECT &/OR CIVIL ENGINEER OF ANY FT-24 FT-30
REINFORCED CONCRETE FOOTING 2. PROVIDE 3500 PSI PLACED HI-EARLY STRENGTH
4"
DISCREPANCIES OR CONCERNS FT-30 CS-4A
STEP FOOTING INDICATION 9. IT IS NOT THE ARCHITECT'S RESPONSIBILITY TO OBTAIN PERMISSION TO GAIN ACCESS TO ADJACENT (OR SURROUNDING) PROPERTIES AS CONCRETE UNDERPIN W/ #4 BAR CAGE @ 15" O.C.
MAY BE REQUIRED TO PERFORM WORK. THE G.C. SHALL COORDINATE WITH THE OWNER/DEVELOPER TO ASSIGN THE RESPONSIBLE PARTY EXTEND INTO ADJACENT UNDERPIN BAY 8" MIN
PIER"A"
PERIMETER FOUNDATION DRAINAGE (AS SHOWN ON UNDERPINNING SEQUENCE DETAIL)
10. IT IS THE G.C.'S RESPONSIBILITY TO CONTACT THE D.P.R.C. &/OR SPECIAL INSPECTIONS AGENCY TO SCHEDULE ALL REQUIRED SPECIAL
2'-6"
CONCRETE CONTROL JOINT INSPECTIONS
11. DO NOT EXCAVATE DEEPER THAN ADJACENT FOOTINGS OR FOUNDATIONS UNLESS UNDERPINNING IS DOCUMENTED AND PERMITTED 3'-3" 7'-3 1/4" 3. AFTER ALL 'A' SEGMENTS HAVE CURED
CHANGE IN SLAB ELEVATION AS 12. G.S. SHALL VERIFY THE DEPTHS OF ADJACENT FOUNDATIONS (PRIOR TO FULL EXCAVATION) AND REPORT FINDINGS TO ARCHITECT AND ( MIN. 48 HRS.; MIN. TEMP. OF 55 DEG. F.),
see plns" 10 1/2"
PIER"D"
NOTED ON PLAN ENGINEER OF RECORD FOR REVIEW. THE G.C. IS RESPONSIBLE TO SECURE ENGINEERED DOCUMENTATION AND PERMITS FOR SHORING IF HANDPACK TOP OF NEW UNDERPIN AND
2'-6"
REQUIRED BOTTOM OF EXISTING FOUNDATION WALL
13. ALL REBAR LAP SPLICE LENGTHS TO BE 40 DIAMETERS MIN. WITH 3500 PSI NON-SHRINK GROUT.
PIER"C"
REVISED 3.
2'-6"
12'-0"
3. AFTER ALL 'A' SEGMENTS HAVE CURED
5/S1.01
CS-4 (MIN. 24 HRS.; MIN. TEMP. OF 55 DEG. F.(*)),
PIER"B"
HANDPACK TOP OF NEW UNDERPIN AND
2'-6"
BOTTOM OF EXISTING FOUNDATION WALL
KEY NOTES: FOUNDATION WALL SCHEDULE:
WITH 3500 PSI NON-SHRINK GROUT. ALLOW FOR
5 MIN. 24 HRS. ADDITIONAL CURE TIME OF
PROVIDE DRAIN - SLOPE SLAB TO DRAIN 10" 3500 PSI CONCRETE FOUNDATION WALL 14" 3500 PSI CONCRETE FOUNDATION WALL
PIER"D"
1 S1.00 HANDPACK GROUT AND CONC. SEGMENT PRIOR
PROJECT ADDRESS:
2'-6"
- CONNECT DRAIN TO SEWER / SEWER INVERT W/ #4 BAR VERTICAL AT 16" O.C., EACH FACE W/ #4 BAR VERTICAL AT 16" O.C., EACH FACE TO EXCAVATION OF ADJACENT PIER.
FW-10 W/ MIN. 3" COVER TURN 90º IN FOOTING AND FW-14 W/ MIN. 3" COVER TURN 90º IN FOOTING AND 2
CONCRETE CONTROL JOINT @ 12'-0" MAX. (TYP.) #4 BARS HORIZONTAL @ 16" O.C. EACH FACE #4 BARS HORIZONTAL @ 16" O.C. EACH FACE -----
2 LOCATED UNDER WALLS WHEN POSSIBLE W/ MIN. 3" COVER. PROVIDE CONT. W/ MIN. 3" COVER. PROVIDE CONT.
PIER"C"
CONCRETE UNDERPIN W/ #4 BAR CAGE @ 15" O.C. SEAL:
3/S1.01
2'-6"
MANUFACTURER'S FIXTURE REQUIREMENTS
41'-8"
EXTEND INTO ADJACENT UNDERPIN BAY 8" MIN.
12"x30" WIDE CONT. 3500 PSI CONC. FOOTING LAP SPLICE
4 ADJACENT FOUNDATION WALL 4" THICK 3500 PSI CONCRETE SLAB (AS SHOWN ON UNDERPINNING SEQUENCE DETAIL)
W/ (3) #4 BARS EQ. SPACED
35'-10"
W/ 6x6 W4xW4 WWF REINFORCEMENT
PIER"B"
12'-0"
FT-30 & #4 CROSS BARS @ 16" O.C. CS-4
2'-6"
10 MIL VAPOR BARRIER OVER 3. AFTER ALL 'B' SEGMENTS HAVE CURED
& #4 DOWELS (36" LONG W/ 9" EMBEDMENT
4" AASHTO No. 57 CRUSHED STONE (MIN. 24 HRS.; MIN. TEMP. OF 55 DEG. F.(*)),
FOR EA. FACE IN FOUNDATION WALL) @ 16" O.C.
HANDPACK TOP OF NEW UNDERPIN AND
CS-4
PIER"D"
4 BOTTOM OF EXISTING FOUNDATION WALL
2'-6"
WITH 3500 PSI NON-SHRINK GROUT. ALLOW FOR
12"x24" WIDE CONT. 3500 PSI CONC. FOOTING MIN. 24 HRS. ADDITIONAL CURE TIME OF
4" THICK 4000 PSI CONCRETE SLAB 3 HANDPACK GROUT AND CONC. SEGMENT PRIOR
W/ (3) #4 BARS EQ. SPACED
W/ 6x6 W4xW4 WWF REINFORCEMENT
PIER"A"
FT-24 & #4 CROSS BARS @ 16" O.C. CS-4A TO EXCAVATION OF ADJACENT PIER.
2'-6"
10 MIL VAPOR BARRIER OVER 2
& #4 DOWELS (36" LONG W/ 9" EMBEDMENT
4" AASHTO No. 57 CRUSHED STONE -----
FOR EA. FACE IN FOUNDATION WALL) @ 16" O.C.
© 2021 HARMAN DEUTSCH OHLER ARCHITECTURE.
PIER"C"
1. REMOVE EARTH FROM ALL 'C' 2'-6" SEGMENTS. ALL RIGHTS RESERVED.
2'-6"
2. PROVIDE 3500 PSI PLACED HI-EARLY STRENGTH CONSULTANTS:
FW-10 CONCRETE UNDERPIN W/ #4 BAR CAGE @ 15" O.C.
PIER"B"
E.C. CONNECT HORIZONTAL BARS TO ADJACENT PIERS
2'-6"
SUMP FT-30 W/
8" MIN.
11'-10"
T.O. FIRST FLOOR DECK FW-10 (AS SHOWN ON UNDERPINNING SEQUENCE DETAIL)
PIER"D"
-REF. SECTIONS
2'-6"
FT-30
BOLTED CONNECTION DEVICE CS-4 3. AFTER ALL 'C' SEGMENTS HAVE CURED
3/S1.01
OR EXOTHERMIC WELD (MIN. 24 HRS.; MIN. TEMP. OF 55 DEG. F.(*)),
HANDPACK TOP OF NEW UNDERPIN AND
PIER"A"
PROTECTIVE INSULATOR SLEAVE
5/S1.01
BOTTOM OF EXISTING FOUNDATION WALL
2'-6"
1/S1.01 WITH 3500 PSI NON-SHRINK GROUT. ALLOW FOR
MIN. 24 HRS. ADDITIONAL CURE TIME OF
HANDPACK GROUT AND CONC. SEGMENT PRIOR
2'-6"
PIER"C"
1/8" SAWCUT OR 3/8" TOOLED CONTROL JOINT GROUNDING WIRE TO EXCAVATION OF ADJACENT PIER.
(1" DEEP) WITHIN 4-12 HOURS OF PLACEMENT
- DO NOT INTERRUPT MESH -----
- REFER TO FOUNDATION PLAN
11'-4 3/4" 1. REMOVE EARTH FROM ALL 'D' 2'-6" SEGMENTS.
WWF. IN UPPER 1/3 OF SLAB DEPTH ELECTRICAL PANEL 13'-0 3/4" 6" 3
REINF. CONC. SLAB 2. PROVIDE 3500 PSI PLACED HI-EARLY STRENGTH
VERTICAL STEEL REBAR 13'-6 3/4" S1.00
-REFER TO FOUNDATION PLAN CONCRETE UNDERPIN W/ #4 BAR CAGE 15" O.C.
WIRE TIE BARS TOGETHER FW-14 CONNECT HORIZONTAL BARS TO ADJACENT PIERS
FT-30 W/
STEEL REBARS 20' OR GREATER IN 8" MIN. LAP SPLICE
LENGTH (AS SHOWN ON UNDERPINNING SEQUENCE DETAIL)
T.O. SLAB 1 FOUNDATION PLAN 3. AFTER ALL 'D' SEGMENTS HAVE CURED
-REF. SECTIONS
S1.00 1/4" = 1'-0" (MIN. 24 HRS.; MIN. TEMP. OF 55 DEG. F.(*)),
HANDPACK TOP OF NEW UNDERPIN AND
BOTTOM OF EXISTING FOUNDATION WALL # DATE ISSUE / REVISION
VAPOR BARRIER AS PER FOUND. PLAN WITH 3500 PSI NON-SHRINK GROUT. ALLOW FOR 1 06.17.21 BLDG SUBMISSION
MIN. 24 HRS. ADDITIONAL CURE TIME OF
EXPANDED POLYSTYRENE RIGID INSULATION
HANDPACK GROUT AND CONC. SEGMENT PRIOR
COMPACTED AGGREGATE TO EXCAVATION OF ADJACENT PIER.
UNDERPINNING NOTES:
2 CONC. CONTROL JOINT DETAIL 3 GROUNDING ROD DETAIL 1. CONTRACTOR SHALL PROTECT EXISTING FOUNDATIONS FROM
PROPERTY
S1.00 1 1/2" = 1'-0" S1.00 1" = 1'-0" WEATHER AND ENSURE EXCAVATED AREA IS MAINTAINED.
CONTRACTOR SHALL MAINTAIN GRADING ON THE SITE TO DIRECT
LINE
WATER AWAY FROM EXISTING WALLS & EXCAVATION PITS.
EXISTING ADJACENT
ANGLE OF REPOSE OF 1'-0" VERTICAL TO 2'-0" HORIZONTAL. IF
HAND PACK 3" MIN. HEIGHT AREA
G.C.ELECTS TO STEP PIT EXCAVATIONS PER OSHA STANDARDS & AS
W/ 3000 PSI NON-SHRINK GROUT
SITE SOIL CONDITIONS PERMIT, THE G.C. SHALL SECURE A SHEETING
PROVIDE BOND BREAK TO ENSURE
AND SHORING DRAWING FOR REVIEW AND RECORD.
INDEPENDENT MOVEMENT OF FOUNDATION
KEYWAY SEE X/S1.XX HORIZONTAL BARS (EA. FACE) TO EXTEND 8" MIN. HARMAN DEUTSCH OHLER ARCHITECTURE HEREBY
INTO ADJACENT PIER 3. CONTRACTOR SHALL PARGE THE EXISTING BASEMENT STONE RESERVES IT'S COMMON LAW COPYRIGHT AND ALL
REINF. CONC. UNDERPINNING PROPERTY RIGHTS IN THESE DRAWINGS, IDEAS AND
WALL PRIOR TO UNDERPINING.
PIER W/ HORIZ. AND VERT. 2'-6" 2'-6" 2'-6" 2'-6" DESIGNS. THE INFORMATION ON THIS SHEET IS NOT
FOR MIN. LAP SPLICE
SEE TABLE GGGHG
REBAR REINFORCEMENT PER 15" 15" 15" 15" 15" 15" 15" 15" TO BE REPRODUCED, MODIFIED OR COPIED IN ANY
4. IT IS NOT THE ARCHITECT'S RESPONSIBILITY TO OBTAIN MANNER. THE INFORMATION ON THIS SHEET IS NOT
FOUNDATON PLAN TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT THE
PERMISSION TO GAIN ACCESS TO ADJACENT (OR SURROUNDING)
-PROVIDE MIN. 3" COVER EXPRESSED WRITTEN CONSENT OF HARMAN
PROPERTIES AS MAY BE REQUIRED TO PERFORM WORK. THE G.C. DEUTSCH OHLER ARCHITECTURE.
1/2" PREMOLDED FILLER W/ BACKER ROD SHALL COORDINATE WITH THE OWNER/DEVELOPER TO ASSIGN THE
STL. REINF. CONC. FOOTING AS SPECIFIED RESPONSIBLE PARTY.
DOWEL W/ RADIUS BEND DRAWINGS PREPARED BY:
6'-0" MAX. HT.
TYPICAL SLAB C A D B C
S1.00
⅊
FIRST FLOOR FRAMING
@ RECESSED ENTRY
FIRST FLOOR
AS PER SCHEDULE FIRST FLOOR FRAMING
(SEE FRAMING PLANS)
AS PER SCHEDULE
T.O. FIRST FLOOR T.O.FIRST FLOOR DECK T.O. FIRST FLOOR
-0'-0" 0'-0" -0'-0"
GUARDRAIL
1/2" Ø GALV. ANCHOR BOLTS @ 32" O.C.
3'-6" MIN.
BRICK & CONCRETE ENTRY
STAIRS
6"
AVERAGE GRADE AVERAGE GRADE
-3'-10" -3'-10"
BRICK SHELF
4'-10" V.I.F.
8" MIN.
-4'-6" REIN. CONC. FOUNDATION WALL
AS PER SCHEDULE
6" 8" PROVIDE CONT. WATER PROOFING
PROVIDE CONT. WATER PROOFING
8"
PROVIDE CONT. WATER PROOFING T.O. WELL SLAB
3'-1"
3'-0" min.
2x4 KEY -PROVIDE MIN. 3" COVER
T.O. CELLAR SLAB AS PER SCHEDULE T.O. CELLAR SLAB
-10'-0" REIN. CONC. FOOTING -10'-0"
4" 4"
4" 4"
AS PER SCHEDULE SEAL:
1'-0"
1'-0"
1'-0"
1'-0"
4" INT. PERIMETER DRAIN 4" INT. PERIMETER DRAIN
B.O. FOOTING - CONNECTED TO SUMP - CONNECTED TO SUMP B.O. FOOTING
-11'- 8" -11'-8"
4" INT. PERIMETER DRAIN 2'-6" 2'-0" ALIGN
2'-6" 6" 6" 2'-6"
- CONNECTED TO SUMP
CONSULTANTS:
GUARDRAIL
1/2" Ø GALV. ANCHOR BOLTS @ 32" O.C.
3'-6" MIN.
3'-6" MIN.
SEAL EXPOSED
CONCRETE (TYP.)
6"
7'-4"FOUNDATION WAL
REIN. CONC. FOUNDATION WALL REIN. CONC. FOUNDATION WALL
AS PER SCHEDULE 4" COMPACT AGGREGATE 10" AS PER SCHEDULE
10" 10" PROVIDE CONT. WATER PROOFING
1/2" PMF
T.O. WELL SLAB @ EXT. FACE OF # DATE ISSUE / REVISION
-7'-9 1/2" FOUNDATION WALLS (TYP.) 4" 3500 PSI CONC. SLAB W/
REIN. CONC. FOUNDATION WALL
6x6 W4xW4 WWF PLACED ON 1 06.17.21 BLDG SUBMISSION
AS PER SCHEDULE
10 MIL VAPOR BARRIER
PROVIDE MIN. 16" LAP SPLICE
3'-0" MIN.
4" 4"
AS PER SCHEDULE AS PER SCHEDULE AS PER SCHEDULE
1'-0"
1'-0"
1'-0"
CAST-IN-PLACE CONCRETE LAP SPLICE LENGTHS FOR CONCRETE STRAIGHT BAR DEVELOPMENT HARMAN DEUTSCH OHLER ARCHITECTURE HEREBY
RESERVES IT'S COMMON LAW COPYRIGHT AND ALL
PROPERTY RIGHTS IN THESE DRAWINGS, IDEAS AND
CLEAR COVER FOR REINFORCING CLASS B SPLICE LENGTHS (INCHES) LENGTHS LENGTHS (INCHES) DESIGNS. THE INFORMATION ON THIS SHEET IS NOT
TO BE REPRODUCED, MODIFIED OR COPIED IN ANY
MANNER. THE INFORMATION ON THIS SHEET IS NOT
3,000 PSI CONCRETE 4,000 PSI CONCRETE 5,000 PSI CONCRETE 6,000 PSI CONCRETE 3,000 PSI CONCRETE 4,000 PSI CONCRETE 5,000 PSI CONCRETE 6,000 PSI CONCRETE TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT THE
TYPE COVER EXPRESSED WRITTEN CONSENT OF HARMAN
BAR SIZE TENSION TENSION TENSION TENSION BAR SIZE TENSION TENSION TENSION TENSION DEUTSCH OHLER ARCHITECTURE.
FOOTINGS, GRADE BEAMS, CAISSONS AND OTHER CONCRETE CAST AGAINST COMP COMP COMP COMP COMP COMP COMP COMP
3" TYP TOP TYP TOP TYP TOP TYP TOP TYP TOP TYP TOP TYP TOP TYP TOP
AND PERMANENTLY EXPOSED TO EARTH
FORMED CONCRETE EXPOSED TO EARTH OR WEATHER (#6 BAR AND LARGER) 2" #3 21 27 12 18 24 12 17 22 12 17 20 12 #3 16 21 9 14 18 8 13 17 8 12 16 8 DRAWINGS PREPARED BY:
FORMED CONCRETE EXPOSED TO EARTH OR WEATHER (#5 BAR AND SMALLER) 1 1/2" #4 29 38 15 25 32 15 22 29 15 20 26 15 #4 22 29 11 19 25 9 17 22 9 15 20 9 V.H
INSIDE FACE OF WALLS 1" #5 37 47 19 31 40 19 28 36 19 25 33 19 #5 28 36 14 24 31 12 21 29 12 19 25 12 DRAWINGS CHECKED BY:
BEAMS AND COLUMN TIES/STIRRUPS (NOT EXPOSED TO EARTH OR WEATHER) 1 1/2" #6 43 56 23 38 48 23 34 43 23 31 39 23 #6 33 43 17 29 37 14 26 33 14 24 30 14 V.H.
#7 62 82 27 54 70 27 49 63 27 45 58 27 #7 48 63 19 42 54 17 38 49 16 34 45 16 DRAWING TITLE:
CAST-IN-PLACE CONCRETE CLEAR COVER NOTES:
1. MINIMUM REINFORCING COVER SHALL BE PROVIDED PER THIS TABLE UNLESS SHOWN OR #8 72 92 30 62 80 30 56 72 30 51 66 30 #8 55 71 22 48 62 19 43 56 18 39 51 18
NOTED OTHERWISE ON PLANS AND SECTIONS. #9 81 104 34 70 91 34 63 81 34 57 74 34 #9 62 80 25 54 70 21 48 63 20 44 57 20 FOUNDATION
#10 90 116 39 79 102 39 71 92 39 64 84 39 #10 69 89 28 61 79 24 54 71 23 50 64 23
WALL SECTIONS
NOTES: NOTES:
1. DEVELOPMENT AND LAP SPLICE LENGTHS SHOWN ARE FOR UNCOATED ASTM A615 GRADE 60 1. DEVELOPMENT AND LAP SPLICE LENGTHS SHOWN ARE FOR UNCOATED ASTM A615 GRADE 60 DRAWING NUMBER:
(Fy = 60,000 PSI) DEFORMED BAR REINFORCING. (Fy = 60,000 PSI) DEFORMED BAR REINFORCING.
2. DEVELOPMENT LENGTHS ARE BASED ON NORMAL WEIGHT CONCRETE. FOR LIGHT WEIGHT 2. DEVELOPMENT LENGTHS ARE BASED ON NORMAL WEIGHT CONCRETE. FOR LIGHT WEIGHT
CONCRETE MULTIPLY THE LENGTHS SHOWN BY 1.3. CONCRETE MULTIPLY THE LENGTHS SHOWN BY 1.3.
3. MINIMUM BAR CLEAR COVER SHALL BE 1 BAR DIAMETER. MINIMUM BAR CLEAR SPACING IS 1 3. MINIMUM BAR CLEAR COVER SHALL BE 1 BAR DIAMETER. MINIMUM BAR CLEAR SPACING IS 1
4.
BAR DIAMETER IN BEAMS AND COLUMNS AND 2 BAR DIAMETERS IN OTHER CONCRETE
ELEMENTS. MULTIPLY THE DEVELOPMENT LENGTH SHOWN BY 1.5 FOR REINFORCING WITH
COVER AND SPACING LESS THAN DESCRIBED ABOVE.
USE THE LAP SPLICE LENGTHS IN THE "TOP" COLUMN FOR HORIZONTAL BARS WITH MORE
THAN 12" OF CONCRETE BELOW THE BAR.
4.
BAR DIAMETER IN BEAMS AND COLUMNS AND 2 BAR DIAMETERS IN OTHER CONCRETE
ELEMENTS. MULTIPLY THE DEVELOPMENT LENGTH SHOWN BY 1.5 FOR REINFORCING WITH
COVER AND SPACING LESS THAN DESCRIBED ABOVE.
USE THE LAP SPLICE LENGTHS IN THE "TOP" COLUMN FOR HORIZONTAL BARS WITH MORE
THAN 12" OF CONCRETE BELOW THE BAR.
S1.01
FRAMING NOTES TOP FLANGE
- PROVIDE MIN. (3) 2X6 POSTS WITHIN 2X6 BEARING WALLS @ ALL BEAM LOCATIONS -
JOIST HANGERS
ALL POSTS TO BE CONTINUOUS TO FOUNDATION REQUIRED FASTENERS
BLOCK FLOOR SYSTEM SOLID UNDER ALL POST LOCATIONS (TYP.) JOIST SIZE ACTUAL SIZE MODEL NUMBER
PROVIDE BRIDGING WITHIN STUD WALLS AT 1/3 AND 2/3 WALL HEIGHT HEADER JOIST
- BEAMS TO BE FLUSH WITH FLOOR JOISTS UNLESS OTHERWISE NOTED. 2x8 1-1/2" x 7-1/4" SIMPSON HU28TF 10-16d 4-10d x 1-1/2"
(2) 2x8 (2) 1-1/2" x 7-1/4" SIMPSON HU28-2TF 12-16d 4-10d x 2-1/2"
- PROVIDE WOOD HEADERS IN BEARING WALLS AS SCHEDULED UNLESS OTHERWISE NOTED
2x10 1-1/2" x 9-1/4" SIMPSON HU210TF 12-16d 4-10d x 1-1/2"
- PROVIDE DOUBLE TOP PLATES IN ALL BEARING WALLS
(2) 2x10 (2) 1-1/2" x 9-1/4" SIMPSON HU210-2TF 14-16d 6-16d x 2-1/2"
- PROVIDE BRIDGING BETWEEN FLOOR JOISTS @ 7'-0" O.C. (3) 2x10 (3) 1-1/2" x 9-1/4" SIMPSON HU310-3TF 14-16d 6-16d x 1-1/2"
- ALL BUILT UP BEAMS TO HAVE 1/2" PLYWOOD CORES AND BE CONNECTED WITH 1/2" DIA. 2X12 1-1/2" x 11-1/2" SIMPSON B1.56 / 11.25 10-16d 6-10d x 1-1/2"
THROUGH-BOLTS AT 16" O.C. STAGGERED 1-1/2" ABOVE AND BELOW THE NEUTRAL AXIS. (2) 2X12 (2) 1-1/2" x 11-1/2" SIMPSON B3.12 / 11.25 14-16d 6-16d x 2-1/2"
- PROVIDE 4" MIN. BEARING @ ALL JOISTS & BEAMS (3) 2X12 (3) 1-1/2" x 11-1/2" SIMPSON HU212-3TF 16-16d 6-16d x 1-1/2"
NOTE:
- ALL FLOOR DECKING TO BE 3/4" PLYWOOD BOTH GLUED & SCREWED TO FLOOR JOISTS - ALL JOIST HANGERS TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. ALL EXTERIOR
FASTENERS TO BE GALVANIZED.
- PROVIDE FULL DEPTH JOIST HANGERS @ ALL JOIST TO BEAM CONNECTIONS; FASTEN PER
MANUFACTURER. SPECIFICATIONS - SCHEDULE APPLIES TO SIMPLY SUPPORTED FLOOR JOISTS @ 16" O.C., WITH DISTRIBUTED LOADING.
SPAN NOT TO EXCEED 18', U.N.O.
- PROVIDE FULL DEPTH HANGERS @ ALL BEAM TO BEAM CONNECTIONS; FASTEN/INSTALL PER
MANUFACTURER. SPECIFICATIONS
- ALL LUMBER IN DIRECT CONTACT WITH MASONRY TO BE WOLMANIZED; ALL EXTERIOR LUMBER TO BE
WOLMANIZED (UNLESS OTHERWISE NOTED)
HEADER SCHEDULE PROJECT ADDRESS:
- WHERE FIBERGLASS ROOF DECK IS INSTALLED, USE 12" ON CENTER FRAMING FOR JOIST MEMBERS WOOD HEADERS/ FRAMED WALLS
MAX SPAN WOOD STUD FRAMING BWP BWP BWP BWP BWP
- WHERE INDICATED ON PLANS, HOT TUB READY AREA OF ROOF DECK INDICATES AN AREA THAT IS HEADER HEADER PER HEADER PER
DESIGNED TO WITHSTAND A LOADING OF 6,000 LBS. A HOT TUB IS NOT INCLUDED ON THE PERMIT OF PER SCHEDULE SCHEDULE SCHEDULE
2x4 2x6
THESE PLANS.
3'-0" (2)2"X8" PLY-WD. CORE (3)2"X8" PLY-WD. CORE(S) HEADER PER SEAL:
- WHERE ENGINEERED LUMBER IS PROPOSED, THE G.C. SHALL REQUEST AND SECURE SIGNED & 4'-0" (2)2"X10" PLY-WD. CORE (3)2"X8" PLY-WD. CORE(S) SCHEDULE
SEALED ENGINEERED SHOP DRAWINGS FROM THE MANUFACTURER INDICATING ENGINEERED JOIST & 5'-0" (2)2"X12" PLY-WD. CORE (3)2"X10" PLY-WD. CORE(S)
BEAM SIZES, SPACING, PLACEMENT, REINFORCING REQUIREMENTS, AND JOIST & BEAM CONNECTOR
SPECIFICATIONS. THE G.C. SHALL NOTIFY THE ARCHITECT & ENGINEER OF RECORD OF ANY 6'-0" (3)2"X12" PLY-WD. CORE (3)2"X12" PLY-WD. CORE(S)
DEVIATIONS FROM THE ENCLOSED FRAMING PLANS.
NOTES 2х12 H.F.№2 @16” c/c 2х12 H.F.№2 @16” c/c
SEE ADDITIONAL NOTES LISTED IN DIVISION 02: EXISTING CONDITIONS: OF THE SPECIFICATION SHEET 2х12 H.F.№2 @16” c/c
FOR SITE REQUIRMENTS 1.) IF HEADER SPAN IS GREATER THAN 6'-0" AND NOT INDICATED ON THE
DRAWINGS, NOTIFY ARCHITECT IMMEDIATELY FOR SIZING OF STRUCTURAL
MEMBER PER FIELD CONDITIONS. [A ] [A ]
] (3 [A B] AB
)2x 6 (3) [
2x 2x x6
6 (3) 2
[A
]
(3)
B
2.) G.C. MAY SUBSTITUTE MANUFACTURER OF STRUCTURAL MEMBERS INDICATED 6
B]
[A
6
LINTEL SCHEDULE x
(3
ON DRAWINGS WITH APPROVAL FROM ARCHITECT, AND REQUIRED LOCAL )2
)2
(3
x6
[A ] [A [A
AUTHORITIES AS APPLICABLE. ] (3 [A B] B] B]
6 A (3) [
)2x 2x (3) 6[ 2x 2 x6 © 2021 HARMAN DEUTSCH OHLER ARCHITECTURE.
6 (3) 2 x6 2x 6 (3) ALL RIGHTS RESERVED.
STEEL LINTELS FOR MASONRY VENEER OPENINGS 3.) ALL WOOD HEADERS SHALL BE CONTINUOUS WITH NO SPLICING ALLOWED OF (3)
ANY MATERIAL(S), INCLUDING PLY-WD. CORES
CONSULTANTS:
MAX MASONRY WALL THICKNESS 3 1/2" x 11 1/4" PSL BEAM 3 1/2" x 11 1/4" PSL BEAM 3 1/2" x 11 1/4" PSL BEAM DN
OPENING 4.) HEADERS TO BEAR ON MIN. ONE JACK/ STUD, SPANS GREATER THAN 4'-0" TO
(3
(3 (3
x6 x6
)2
4" VENEER RECEIVE TWO JACKS PER SIDE W/ FULL DEPTH BEARING OF STRUCTURAL
6
(3
)2 )2
3 1/2" x 11 1/4" PSL BEAM
x6
)2 )2
2x
x6
)2
x6 x6
(3)
(3 (3
)2
3)
(3) ]
x6
MEMBER A]
[A
[B [
(3
]
B] [B]
2x AB
](
UP TO 2'-11" 3-1/2"X3-1/2"X1/4" [A 2
[
6[
B
B
A]
x6 6[ [
]
[A
x6
[A
4'-0" TO 4'-11 5"X3-1/2"X5/16"
5'-0" TO 6'-11" 7"X4"X3/8" 2х12 H.F.№2 @16” c/c [A 2х12 H.F.№2 @16” c/c [A
B] A B] B]
(3 [
7'-0" TO 9'-0" 8"X4"X1/2" (3) 6[ )2x x6
2 2x 2
x6
(3)
6 (3)
NOTES
1.) STEEL LINTELS TO HAVE MIN. BEARING OF 4" STABLE MASONRY. 2х12 H.F.№2 @16” c/c
[A] (3) [A
] A] [B] B] B]
(3) 2x
6[
A 6[ (3) 6[
2.) ALL EXTERIOR STEEL LINTELS TO BE HOT DIPPED GALVANIZED FINISH [A] 2x6 6[
)2x 2 x 2 2 x (3) 6[
(3) A]
(3 (3) 6 [A] x6 (3 ) 2x 2x
2x 2x
6 (3)
6 (3)
3 1/2" x 11 1/4" PSL BEAM 3 1/2" x 11 1/4" PSL BEAM
(3) (3) ] (3 (3
STRUCTURAL LEGEND 2x A] 2x AB )2 3 1/2" x 11 1/4" PSL BEAM )2
x6
[ 6[
x6
6[ 6[ x x6
x6 6
)2
AB
)2
A] 2x
3)2
(3
] (3
( ] (3 )
B]
[A
[
[B
[A
B ]
[B
](
3)
2x
X
POST BELOW
[A
](
3)
E.C.
2x
X
SUMP
[A
POST ABOVE
B]
BEARING WALL
TRIPLE STUD BEARING WALL SHORING
- REFER TO PARITION TYPES
[BEAM SIZE]
FLUSH BEAM
FRAMING PLANS
DRAWING NUMBER:
S1.02
FRAMING NOTES TOP FLANGE
- PROVIDE MIN. (3) 2X6 POSTS WITHIN 2X6 BEARING WALLS @ ALL BEAM LOCATIONS -
JOIST HANGERS
ALL POSTS TO BE CONTINUOUS TO FOUNDATION REQUIRED FASTENERS
BLOCK FLOOR SYSTEM SOLID UNDER ALL POST LOCATIONS (TYP.) JOIST SIZE ACTUAL SIZE MODEL NUMBER
PROVIDE BRIDGING WITHIN STUD WALLS AT 1/3 AND 2/3 WALL HEIGHT HEADER JOIST
- BEAMS TO BE FLUSH WITH FLOOR JOISTS UNLESS OTHERWISE NOTED. 2x8 1-1/2" x 7-1/4" SIMPSON HU28TF 10-16d 4-10d x 1-1/2"
(2) 2x8 (2) 1-1/2" x 7-1/4" SIMPSON HU28-2TF 12-16d 4-10d x 2-1/2"
- PROVIDE WOOD HEADERS IN BEARING WALLS AS SCHEDULED UNLESS OTHERWISE NOTED
2x10 1-1/2" x 9-1/4" SIMPSON HU210TF 12-16d 4-10d x 1-1/2"
- PROVIDE DOUBLE TOP PLATES IN ALL BEARING WALLS
(2) 2x10 (2) 1-1/2" x 9-1/4" SIMPSON HU210-2TF 14-16d 6-16d x 2-1/2"
- PROVIDE BRIDGING BETWEEN FLOOR JOISTS @ 7'-0" O.C. (3) 2x10 (3) 1-1/2" x 9-1/4" SIMPSON HU310-3TF 14-16d 6-16d x 1-1/2"
- ALL BUILT UP BEAMS TO HAVE 1/2" PLYWOOD CORES AND BE CONNECTED WITH 1/2" DIA. 2X12 1-1/2" x 11-1/2" SIMPSON B1.56 / 11.25 10-16d 6-10d x 1-1/2"
THROUGH-BOLTS AT 16" O.C. STAGGERED 1-1/2" ABOVE AND BELOW THE NEUTRAL AXIS. (2) 2X12 (2) 1-1/2" x 11-1/2" SIMPSON B3.12 / 11.25 14-16d 6-16d x 2-1/2"
- PROVIDE 4" MIN. BEARING @ ALL JOISTS & BEAMS (3) 2X12 (3) 1-1/2" x 11-1/2" SIMPSON HU212-3TF 16-16d 6-16d x 1-1/2"
NOTE: BWP BWP BWP
- ALL FLOOR DECKING TO BE 3/4" PLYWOOD BOTH GLUED & SCREWED TO FLOOR JOISTS HEADER PER HEADER PER
- ALL JOIST HANGERS TO BE INSTALLED PER MANUFACTURER'S SPECIFICATIONS. ALL EXTERIOR
SCHEDULE SCHEDULE
FASTENERS TO BE GALVANIZED.
- PROVIDE FULL DEPTH JOIST HANGERS @ ALL JOIST TO BEAM CONNECTIONS; FASTEN PER
MANUFACTURER. SPECIFICATIONS - SCHEDULE APPLIES TO SIMPLY SUPPORTED FLOOR JOISTS @ 16" O.C., WITH DISTRIBUTED LOADING.
SPAN NOT TO EXCEED 18', U.N.O.
- PROVIDE FULL DEPTH HANGERS @ ALL BEAM TO BEAM CONNECTIONS; FASTEN/INSTALL PER
MANUFACTURER. SPECIFICATIONS
- ALL LUMBER IN DIRECT CONTACT WITH MASONRY TO BE WOLMANIZED; ALL EXTERIOR LUMBER TO BE
WOLMANIZED (UNLESS OTHERWISE NOTED)
HEADER SCHEDULE PROJECT ADDRESS:
- WHERE FIBERGLASS ROOF DECK IS INSTALLED, USE 12" ON CENTER FRAMING FOR JOIST MEMBERS WOOD HEADERS/ FRAMED WALLS
(3
)2
)
- WHERE ENGINEERED LUMBER IS PROPOSED, THE G.C. SHALL REQUEST AND SECURE SIGNED &
2x
4'-0" (2)2"X10" PLY-WD. CORE (3)2"X8" PLY-WD. CORE(S) ] (3
6[
SEALED ENGINEERED SHOP DRAWINGS FROM THE MANUFACTURER INDICATING ENGINEERED JOIST & B
AB
5'-0" (2)2"X12" PLY-WD. CORE (3)2"X10" PLY-WD. CORE(S) [A 3 1/2" x 11 1/4" PSL BEAM
]
BEAM SIZES, SPACING, PLACEMENT, REINFORCING REQUIREMENTS, AND JOIST & BEAM CONNECTOR
6'-0" (3)2"X12" PLY-WD. CORE (3)2"X12" PLY-WD. CORE(S)
SPECIFICATIONS. THE G.C. SHALL NOTIFY THE ARCHITECT & ENGINEER OF RECORD OF ANY x6
(3
)2
)2
DEVIATIONS FROM THE ENCLOSED FRAMING PLANS. ] (3
x6
B
[B
[A
]
NOTES
SEE ADDITIONAL NOTES LISTED IN DIVISION 02: EXISTING CONDITIONS: OF THE SPECIFICATION SHEET
2х12 H.F.№2
FOR SITE REQUIRMENTS 2х12 H.F.№2
@16” c/c
1.) IF HEADER SPAN IS GREATER THAN 6'-0" AND NOT INDICATED ON THE
@16” c/c
DRAWINGS, NOTIFY ARCHITECT IMMEDIATELY FOR SIZING OF STRUCTURAL
MEMBER PER FIELD CONDITIONS.
(3
x6
UP TO 2'-11" 3-1/2"X3-1/2"X1/4"
)2
)2
BWP
x6
] (3
[A
B
3'-0" TO 3'-11 4"X3-1/2"X5/16"
B]
[A
4'-0" TO 4'-11 5"X3-1/2"X5/16"
5'-0" TO 6'-11" 7"X4"X3/8"
7'-0" TO 9'-0" 8"X4"X1/2"
NOTES
2.) ALL EXTERIOR STEEL LINTELS TO BE HOT DIPPED GALVANIZED FINISH 2х12 H.F.№2 @16” c/c
SOLID BLOCKING
3)
2x
@ EACH SIDE
X
POST BELOW
[A
](
4"
3)
BWP BWP
X
LINTEL SCHEDULE
[A
-PROVIDE 8 8d TOE NAILS MIN. STAGGERED @ 12" O.C. # DATE ISSUE / REVISION
POST ABOVE AND BELOW
℄
5"
@ EACH SIDE
5/8"
2x RIM JOIST
JOIST / BEAM HANGERS 2x FLOOR BLKING. @ INSIDE OF WALL
EDGE
HARMAN DEUTSCH OHLER ARCHITECTURE HEREBY
FLOOR JOIST DIRECTION 1 ROOF FLOOR FRAMING PLAN 2 P.H. ROOF FRAMING PLAN RESERVES IT'S COMMON LAW COPYRIGHT AND ALL
PROPERTY RIGHTS IN THESE DRAWINGS, IDEAS AND
S1.03 1/4" = 1'-0" S1.03 1/4" = 1'-0"
DESIGNS. THE INFORMATION ON THIS SHEET IS NOT
NOTE:
TO BE REPRODUCED, MODIFIED OR COPIED IN ANY
FLOOR JOIST EXTENTS REFER TO ARCHITECTURAL DETAILS MANNER. THE INFORMATION ON THIS SHEET IS NOT
FOR WATER PROOFING & INSULATION TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT THE
* NOT SHOWN FOR CLARITY EXPRESSED WRITTEN CONSENT OF HARMAN
DEUTSCH OHLER ARCHITECTURE.
CANT BACKSPAN
(3x CANT.)
4/S1.03 BRICK RELIEF ANGLE DETAIL SCALE: 1 1/2" = 1'-0"
DRAWINGS PREPARED BY:
V.H
DRAWINGS CHECKED BY:
V.H.
DRAWING TITLE:
FRAMING PLANS
DRAWING NUMBER:
S1.03
Pilot House Pilot House
R1 R3
Parapet Parapet
T3 T4 Т5
T2 Т1 PROJECT ADDRESS:
3 rd.FL. 3 rd.FL.
SEAL:
S3 S4 S5
S2 S1
2 nd.FL. 2 nd.FL.
F2 © 2021 HARMAN DEUTSCH OHLER ARCHITECTURE.
ALL RIGHTS RESERVED.
7 F4 F5 F6 CONSULTANTS:
0
F3 8 F1
1 st.FL. 1 st.FL.
GRADE GRADE
COND
F6 F5 S5 S4 S3 T5 T4 T3
TRANSOM
30 24DW
F4
60"
R3
LINEN
WETBAR HARMAN DEUTSCH OHLER ARCHITECTURE HEREBY
30" REF.
RESERVES IT'S COMMON LAW COPYRIGHT AND ALL
T6 R4 PROPERTY RIGHTS IN THESE DRAWINGS, IDEAS AND
DESIGNS. THE INFORMATION ON THIS SHEET IS NOT
UP TO BE REPRODUCED, MODIFIED OR COPIED IN ANY
DN DN
S8 T7 DN
DN
MANNER. THE INFORMATION ON THIS SHEET IS NOT
TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT THE
EXPRESSED WRITTEN CONSENT OF HARMAN
DEUTSCH OHLER ARCHITECTURE.
F3 F1 S2 S1 T2 T1
F2
FIRST FLOOR BRACED WALL PANELS SECOND FLOOR BRACED WALL PANELS THIRD FLOOR BRACED WALL PANELS PILOT HOUSE BRACED WALL PANELS S2.0
NTS
1 2 3 4
NTS NTS
1/2" INTERIOR FINISH GWB
2X6 STUDS @ 16" O.C.
2X6 BASE PLATE
- PROVIDE DOUBLE END STUDS
- ANCHORED TO DECK WOOD STUDS
@ 16" O.C.
1/2" PLYWOOD SHEATHING 3/4" T&G PLYWOOD DECKING
OVER FLOOR JOISTS
3-16d FASTENERS @ 16" O.C. ALONG
LENGHT OF BRACED PANEL
1/2" GWB
16d FASTENERS
2X FLOOR JOISTS
@ 24" O.C.
- REFER TO FRAMING PLANS
CONT. 2x RIM JOISTS BRACED PANEL WIDTH VARIES
DOUBLE 2x6 TOP PLATE
REFER TO S-1.0
STRUCTURAL
BRACING DETAILS
DRAWING NUMBER:
3
S2.1
B.W.P. CONNECTION TO FOUNDATION (PARALLEL TO FRAMING)
SCALE: 1 1/2" = 1'-0"
S2.1 SCALE: 1-1/2" = 1'-0"
S2.1