Simple Calculations For Pulling Cable

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 5

Simple Calculations for Pulling Cable

November 1, 2001 12:00 PM, By John DeDad, Editorial Director EC&M http://ecmweb.com/mag/electric_simple_calculations_cable/

You can keep from damaging cables during the cable pulling process by paying attention to installation
parameters and correctly sizing bends.

Even if your crew has taken all the necessary precautions in paying out cable and handling the reels, a cable pull can
still go sour if you damage the cable's outer insulation during the process. However, with the help of a few
calculations and a working knowledge of arithmetic, you can prevent problems in recently energized feeders by
calculating the maximum allowable pulling tension for any installation — and you don't even need to know calculus.

Mathematical proficiency aside, you do have to know the following installation parameters:

 Raceway size
 Cable configuration
 Correction factor for cable weight
 Jamming potential
 Conductor clearance
 Sidewall bearing pressure

Now, let's see how these factors apply in a sample pulling tension calculation.

Sample power feeder installation. Suppose


you're involved in a design/build project for a
paper mill and your client needs a 400A, 15kV
feeder to run as shown in Fig. 1 (right). The
client has required all feeders on the site to be
pull-in-pull-out type in galvanized rigid steel
(GRS) conduit. The client has also stipulated you
use 90°C, single-conductor, grounded neutral,
MV cables with tape shielding; XLPE insulation;
and an overall PVC jacket. After referring to NEC
Table 310.73, size the feeder at 500kcmil. With
these requirements in hand, check with the cable
manufacturer and you'll find the MV cable you
need has an outer diameter (d) of 1.60 in. and a
weight of 2.2 lb/ft.

Now it's time to size the conduit. Table 1 in


Chapter 9 of the NEC, states the allowable
percentage of conductor fill is 40%. You can calculate the total area of the three MV cables using the following
equation:

Area = 3 x (pi ÷ 4) x d2
Area = 3 x .785 x 1.602
Area = 6.03 sq. in.

In this situation, Table 4 (Rigid Metal Conduit) in Chapter 9 of the NEC calls for a 5-in. conduit. This conduit size will
allow you to slip under the allowable percentage of conductor fill by 10%.

Position makes a difference. It may not seem important, but each cable's
geometric position (Fig. 2 right) has a unique effect on the amount of
frictional force, or drag, the conductors endure during the pull. In addition, the
positioning affects the weight factor. By using the ratio of the raceway's inside
diameter (D) to the conductor's outside diameter (d), you can find what
geometric position you can expect to see.

Although the position of one cable is easy to predict (Fig. 2A at the top of
page 41), other positions are not as obvious:
 Triangular (Fig. 2B): This occurs when you pull three individual conductors from three separate reels, and their
D/d ratio is less than 2.5. If you pull individual triplexed conductors from a single reel, they also will sit in this
position.

 Cradle (Fig. 2C): This position may occur when you pull three individual conductors from three separate reels,
and their D/d ratio is between 2.5 and 3.0. This position is the least favorable because it yields the worst-case
scenario of drag during the pull.

 Diamond (Fig. 2D): This position occurs when you pull four individual conductors from four separate reels, and
their D/d ratio is less than 3.0. If you pull quadruplexed individual conductors from a single reel, the multiconductor
cable will also sit in this position.

To determine how the conductors will sit in the conduit, refer to Table 4 for the inside diameter (D) of the 5-in. GRS
conduit, which is 5.07 in. Use the ratio of the conduit's inside diameter (D) to the cable's outside diameter (d) to find
how the single conductors will sit in the conduit. In this case, this ratio is:

D÷d
5.07in. ÷ 1.60 in.
= 3.17

Because this ratio results in a number greater than 3.0, the individual conductors will sit in a cradle configuration in
the conduit.

Conductors “weigh” more than you think. Now that you know the cable positioning, it's necessary to determine
how the conductors' weight will affect the pull.
Weight correction factor is important because when you pull two or more conductors in a raceway, the sum of the
forces developed between the conductors and the raceway is always greater than the sum of the individual conductor
weights.

The equations in Table 1 (right) for determining


weight correction factor for specific installations
are based on the inside diameter of the raceway
and the outside diameter of the conductor.

When you have three single conductors of equal


diameter and weight (which is the most common
scenario), you can expect a higher weight factor
for the cradle position than the triangular
position. What does this mean to you? It means
you should assume the conductors would sit in the cradle position (unless you are pulling triplexed individual
conductors from a single reel), because this will yield a higher and more conservative pulling tension calculation. Use
the following equation to find the weight correction factor:

W = 1 + {(4 ÷ 3) x [d ÷ (D-d)2}
W = 1 + {(4 ÷ 3) x [160 ÷ (3.47)2}
W = 1.28

Don't jam those cables. When sizing your raceway system, you should always consider the possibility of cables
jamming or wedging. This usually occurs when you have three or more individual conductors lying side by side in a
single plane. As you pull the conductors through a bend, the curvature of the bend tends to squeeze the conductors
together.

However, if you're pulling one or two conductor cables, a multiconductor cable with an overall jacket, or a
nonjacketed multiconductor cable made of a triplexed or quadruplexed conductor assembly, you probably don't have
to worry about jamming.

Use the following formula to determine the likelihood of jamming. Use the inside diameter of the raceway and the
outside diameter of the individual conductor:

1.05 x (D ÷ d)

The constant 1.05 factor is a reflection of the fact that bends are actually oval in the sectional view.

 If the value is less than 2.5, you will not have a jamming problem.
 If the value is less than 3.0 but greater than 2.8, jamming is very possible.

 If the value is greater than 3.0, you won't have a jamming problem.

Note: Keep away from jam ratios of 2.8 to 3.2 for Type MV extruded dielectric power cables.

Using the values for inside diameter of the raceway and the outside diameter of the individual conductor from the
example, you get the following value:

1.05 x (D ÷ d)
1.05 x (5.07 in. ÷ 1.60 in.)
= 3.33

Because this calculation results in a number greater than 3.0, you probably won't have a jamming problem.

Conductors need headroom, too. Don't forget you must also have adequate clearance between the uppermost
conductor and the top of the raceway to ensure a safe and easy pull. For straight pulls, you can have a clearance as
small as ¼ in. and still be safe. For more
complex pulls, you should have between ½ in.
and 1 in.
Use the equations in Table 2 (right) on page 42
(which are based on worst-case scenarios) to
find the clearance distance for a given raceway
and cable sitting position. Note that these
equations include a 5% increase (a factor 1.05)
to compensate for variations in cable and
raceway diameters and the oval shape of the
raceway sections at bends. However, because the conductors in the current example will sit in the cradle position,
you will not need to check for clearance.

Calculating the pulling tension. Now that


you've checked most of the factors that affect
cable pulling, it's time to start calculating the
pulling tension, using the following equation:

T=LxwxfxW

where T is the total pulling tension (lb), L is the


length (ft) of cable feeder you're pulling, w is the
total weight (lb/ft) of the conductors, f is the
coefficient of friction (usually 0.5 for well-
lubricated conditions), and W is the weight
correction factor. (See Table 3 for coefficients of
friction of various raceway/cable configurations.)

Assuming you're pulling from Point A to Point H,


you should begin the calculation in incremental
parts. Refer to Table 4 for bend multiplier values:

Step 1: TA-B = 10 ft x 6.6 lb/ft x 0.5 x 1.28


TA-B = 42 lb

Step 2: TA-C = TA-B 90° bend multiplier


TA-C = 42 lb x 2.2
TA-C = 92 lb

Step 3: TC-D = 75 ft x 6.6 lb/ft x 0.5 x 1.28


TC-D = 317 lb

Step 4: TA-D = TA-C + TC-D


TA-D = 92 lb + 317 lb
TA-D = 409 lb
Step 5: TA-E = TA-D x 90° bend multiplier
TA-E = 409 lb x 2.2
TA-E = 900 lb

Step 6: TE-F = 635 ft x 6.6 lb/ft x 0.5 x 1.28


TE-F = 2,682 lb

Step 7: TA-F = TA-E + TE-F


TA-F = 900 lb + 2,682 lb
TA-F = 3,582 lb

Step 8: TA-G = TA-F x 90° bend multiplier


TA-G = 3,582 lb x 2.2
TA-G = 7,880 lb

Step 9: TG-H = 30 ft x 6.6 lb/ft x 0.5 x 1.28


TG-H = 127 lb

Step 10: TA-H = 7,880 lb + 127 lb


TA-H = 8,007 lb

Based on the proper calculations, you'll need approximately 8,000 lb of pulling tension to pull the 15kV conductors,
but you're not done yet.

Cables are sensitive to pressure on their walls. The final step in the cable-pulling process is determining whether
the pulling tension will compromise the conductor's sidewall bearing pressure limit. When you pull a cable or
individual conductors through a raceway bend or around a sheave, sidewall bearing pressure (SWBP) develops
between the cable or conductor wall and the bend or sheave.
This pressure has a very dramatic effect on power feeder raceway system design because it relates directly to the
radii of bends, pulling tension, and the cable or conductors' weight. Most of the time, you can omit this weight factor
from your SWBP calculation because it's relatively small in comparison to pulling tension.

Usually, SWBP is expressed in terms of tension


out of the bend (lb), divided by the bend radius
(ft). The calculated result is a unit of force-per-
unit-length. Use the equations in Table 5 (right)
to find the SWBP for various cable/raceway
configurations and specific radius bends. If
you're pulling a multiconductor cable, use the
single-conductor equation. Looking at Table 5,
you can see that as you increase the bend
radius, the SWBP decreases. In addition, each equation defines the specific conductor in each conductor position
that will experience the maximum crushing force:

 Cradle position: center conductor.

 Diamond position: bottommost conductor.

 Triangular position: bottom two conductors.

Refer to Table 6 (right) for recommended SWBP


limits for various cable types and constructions.
You can use these limits in your raceway system
design efforts. For example, if the design calls for
pulling three single-conductor 600V XLPE
conductors around a bend and your pulling
tension calculation yields a value of 3,600 lbs,
then the minimum bend radius would be 3,600
lbs divided by 1,200 lbs/ft, or 3 ft. Verify the three
90° bends have a sufficient radius to limit the
SWBP on the conductors to 750 lb.

Because tension TA-C (92 lb) is relatively small,


you can use standard elbows and not worry
about exceeding the 750-lb SWBP limit. Tension TA-G, however, is another matter — it is imperative that you don't
exceed the 750-lb SWBP limit.

Use the SWBP equation for a cradled position and solve for radius (R):

SWBP = [(3W - 2) x T] ÷ 3R
750 = {[(3 x 1.28) - 2] x 7,880} ÷ 3R
R = 14,499 ÷ 2,250 = 6.44 ft

This means you need to bend a 10-ft length of conduit into a large-radius sweep. (You'll need the extra length to
compensate for the bend.)

Pulling cable is hard enough if you know what you're doing, so failing to follow the proper procedure can make the job
that much more arduous, not to mention pointless if your feeders fail shortly after the pull. Because even the slightest
oversights in determining maximum allowable pulling tension can cause problems in new feeders, it's crucial that you
implement the correct calculations to get the job done right the first time.

You might also like