CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Sign Design Based on AISC 360, ACI 318, and IBC 1805.7 / UBC1806.8
ANALYSIS
CHECK COMBINED COMPRESSION AND BENDING CAPACITY OF COLUMN (AISC 360-05, H1)
P r 8 M rx M ry P r 0.2
, for
P c 9 M cx M cy Pc
1.28 < 4/3 [Satisfactory]
P r M rx M ry P r 0.2
, for
2 P c M cx M cy Pc
A 4.36 h
1 1 for nonconstrained
2
A
d 8.606 ft [Satisfactory]
4.25 Ph
for constrained
bS 3
Where P = Vmax = 4.08 kips
A = 2.34 P / (b S1) = 3.13
h = Mmax / Vmax = 13.82 ft
ANALYSIS
CHECK COMBINED COMPRESSION AND BENDING CAPACITY OF COLUMN (AISC 360-05, H1)
P r 8 M rx M ry P
, for r 0.2
Pc 9 M cx M cy Pc
1.15 < 4/3 [Satisfactory]
P r M rx M ry
, for P r 0.2
2 P M cx M cy Pc
c
A 4.36 h
1 1 for nonconstrained
2 A
d 5.73 ft [Satisfactory]
4.25 Ph
for constrained
bS 3
Where P = Vmax = 2.08 kips
A = 2.34 P / (b S1) = 1.59
h = Mmax / Vmax = 13.65 ft
ANALYSIS
CHECK LIMITING WIDTH-THICKNESS RATIOS FOR WEB (AISC 365-05 Table B4.1)
hc / tw = 16.02 < lr = 143.12
< lp = 94.41
Compact Web
where E= 29000 ksi
lr = 5.7 (E / Fy)0.5 = 143.12
lp = (hc / hp) (E / Fy)0.5 / (0.54 Mp / My -0.09)2 = 88.66 ,for Af,top ≠ Af,bot
lp = 3.76 (E / Fy)0.5 = 94.41 ,for Af,top = Af,bot
hc = 7.13 in hp = 7.50 in
Mp = 128.8 ft-kips My = 114.2 ft-kips
CHECK LIMITING WIDTH-THICKNESS RATIOS FOR FLANGES (AISC 365-05 Table B4.1)
0.5 bf,top / tf,top = 9.17 < lr = 26.16
< lp = 9.54
Compact Flanges
where lr = 1.0 (kc E / FL)0.5 = 26.16
lp = 0.38 (E / Fy)0.5 = 9.54
kc = Min [0.76 , Max (0.35 , 4 / (h / hw)0.5 )] = 0.76
Sxt = 30 in3 Sxc = 30 in3
FL = 32 ksi, (AISC 360-05 Table note B4.1 & Eq F4-6)
DETERMINE CRITERIA FOR ALLOWABLE FLEXURAL STRENGTH (AISC 365-05 Table F1.1)
Chapter F Sections
Required Conditions F2 F3 F4 F5
Double Symmetric x x
Compact Web x x
x
Noncompact Web
Slender Web Mallowable = Mn / Wb = 62.9 ft-kips
Compact Flanges x ( from following analysis)
Noncompact Flanges
Slender Flanges
Applicable Section ok
E 7.18 ft
L p 1.76 r y
Fy
2
E Jc 0.7 F y S xh 0 E
L r 1.95r ts 1 1 6.76
E r ts 29.40 ft
0.7 F y S xh0 Jc 0.7 F y
2
C b 2E Jc L b 58.1394 ksi
F cr 2
1 0.078
Lb S x h 0 r ts
r ts
M p , for L b L p
Lb L p
M n, F 2 Min C b M p M p 0.7 F y S x
, M p , for L p L b L r
105.0 ft-kips
L
r L p
Min F S
cr x , M p , for L r L b
pf
M p M p 0.7 F y S x , for Noncompact Flanges
rf pf
M n, F 3 129.9 ft-kips
0.9 E k c S x
, for Slender Flanges
2
where l = bf / (2 tf) = 9.17
lpf = lp = 9.54 lrf = lr = 26.16
E 5.25 ft
L p 1.1r t
Fy
2
E J S h
L r 1.95r t 1 1 6.76 F L xc 0 29.63 ft
FL S xc h 0 E J
b fc
rt 2.28 in
1 2
12 h 0 a w h
d 6 h 0d
Mp
, for h c / t w pw
M yc
R pc 1.12752
Min M p M p 1 pw , M p , for h c / t w pw
M yc M yc rw pw M yc
2
C b 2E 1 0.078 J L b
F cr 2 58.7353 ksi, (for Iyc / Iy = 0.50 > 0.23, AISC 360-05 F4-5 )
Lb S xc h 0 r t
rt
R pc M yc , for L b L p
Lb L p
M n, F 4.2 Min C b R pc M yc R pc M yc F L S xc , R pc M yc , for L p L b L r
103.2648 ft-kips
L r L p
Min F S
cr xc , R pc M yc , for L r L b
(cont'd)
R pc M yc , for Compact Flanges
pf
R pc M yc R pc M yc F L S xc , for Noncompact Flanges 128.8 ft-kips
M n, F 5.3 rf pf
0.9 E k c S xc
, for Slender Flanges
2
M p
, for h c / t w pw
M yt
R pt 1.12752
Min M p M p 1 pw , M p , for h c / t w pw
M yt M yt rw pw M yt
F y , for L b L p
L b L p
Min C b F y 0.3F y
, F y ,
for L p L b L r
L r L p
31.9212 ksi
F cr , F 5.2
C b 2E
Min 2
, F y , for L r L b
Lb
r
t
Section Left 0.00 S 0.00 S 0.00 S 0.00 S 0.00 S Point 0.17 S 0.33 S 0.50 S 0.67 S 0.83 S Right
Distance 0 0.00 0.00 0.00 0.00 0.00 0.00 3.00 6.00 9.00 12.00 15.00 18.00
d (in) 8 8 8 8 8 8 8 8 8 8 8 8 8
y (in) 4 4 4 4 4 4 4 4 4 4 4 4 4
I (in4) 118 118 118 118 118 118 118 118 118 118 118 118 118
Wt (plf) 35.5 35.5 35.5 35.5 35.5 35.5 35.5 35.5 35.5 35.5 35.5 35.5 35.5
V (kips) 0.32 0.32 0.32 0.32 0.32 0.32 0.00 -0.21 -0.11 0.00 0.11 0.21 0.32
M (ft-k) 0 0 0 0 0 0 0 1 1 1 1 1 0
(cont'd)
Moments
0
-10
-20
-30
-40
-50
-60
-70
Length
-57.50
-58.00
-58.50
-59.00
-59.50
Length
5w L 4 0.06415 Pb
L 2 b 2
3/ 2
DL 0.02 in ( L / 8794 )
384 EI EIL (for camber, self Wt included.)
5w L 4 0.06415Pb
L 2b 2
3/ 2
LL 0.00 #DIV/0!
384 EI EIL
w= 1/4 in
wmin = 3/16 in, < w
wmax = 5/16 in, > w
W= 2.0
Vmax = 0.32 kips
Q = Af(d - y - 0.5 tf,top) = 14 in3
vmax = Vmax Q / I = 0.04 kips / in
A= 24 in B
0.6 F EXX 0.707 w A 2386 in. o.c.
v max
USE 1/4 in - 24 in @ 2386 in o.c.
DESIGN STIFFENERS
1. BEARING STIFFENERS ARE REQUIRED AT EACH END SUPPORT. (AISC 360-05, J10.8)
2. CHECK LOCAL WEB YIELDING FOR THE CONCENTRATED LOAD. (AISC 360-05, J10.2)
R=P= 0.00 kips
N= 0 in, bearing length, point.
k = tf,top + w = 0.70 in
W= 1.5
R
, for c d
t w N 5k
0.00 < Fy / W [Satisfactory]
R
, for c d
t w N 2.5 k
(cont'd)
3. CHECK WEB CRIPPLING FOR THE CONCENTRATED LOAD. (AISC 360-05, J10.3)
W= 2.0
1.5
2 N t w EF ywt f , for c 0.5d
0.80t w 13 d
t f tw
Rn / 1 / 91.49 > P [Satisfactory]
1.5
0.40t 2w 13 N t w EF ywt f , for c 0.5d
d t f tw
(Note : If item 2, local web yielding is Satisfactory, this item does not need to be checked.)
4. CHECK SIDESWAY WEB BUCKING FOR THE CONCENTRATED LOAD. (AISC 360-05, J10.4)
dc = d - 2k = 6.63 in
Cr = 960000 ksi
(dc / tw ) / (l / bf) = 0.56
W= 1.76
3 3
C r t wt f 0.4 d c / t w , for d c / t w 1.7
h 2 l / b f l/bf
3
C r t 3wt f
Rn / 1 / 10.4 d c / t w , for 1.7 d c / t w 2.3 30.01 > P [Satisfactory]
h
2 l/b f l/b f
dc / tw
P , for l / 2.3
bf
(Note : If item 2, local web yielding is Satisfactory, this item does not need to be checked.)
tw = 1/4 in , bst = 3 in
R= 0.3 kips
Wc = 1.67 , (AISC 365-05 E1)
Kl/r= 0.75 h / ( I / Aeff)0.5 = 4.4
Cc = 4.71 (E/ Fy)0.5 = 118
2E 14502.71 ksi
Fe
kl / r 2
Fy kl
0.658 F e F y , for Cc
r
R n / c A g / c 106.6 kips, (AISC 360-05 E2)
kl
0.877 F e , for r Cc > R [Satisfactory]
Techincal Reference:
1. AISC: "Steel Construction Manual 13th Edition", American Institute of Steel Construction, 2005.
ROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Plate Girder Design Based on AISC Manual 13th Edition (AISC 360-05)
ANALYSIS
CHECK LIMITING WIDTH-THICKNESS RATIOS FOR WEB (AISC 365-05 Table B4.1)
hc / tw = 29.10 < lr = 137.27
< lp = 90.55
Compact Web
where E= 29000 ksi
lr = 5.7 (E / Fy)0.5 = 137.27
lp = (hc / hp) (E / Fy)0.5 / (0.54 Mp / My -0.09)2 = 87.11 ,for Af,top ≠ Af,bot
lp = 3.76 (E / Fy)0.5 = 90.55 ,for Af,top = Af,bot
hc = 7.13 in hp = 7.67 in
Mp = 96.3 ft-kips My = 87.1 ft-kips
CHECK LIMITING WIDTH-THICKNESS RATIOS FOR FLANGES (AISC 365-05 Table B4.1)
0.5 bf,top / tf,top = 8.13 < lr = 24.14
< lp = 9.15
Compact Flanges
where lr = 1.0 (kc E / FL)0.5 = 24.14
lp = 0.38 (E / Fy)0.5 = 9.15
kc = Min [0.76 , Max (0.35 , 4 / (h / hw)0.5 )] = 0.70
Sxt = 21 in3 Sxc = 21 in3
FL = 35 ksi, (AISC 360-05 Table note B4.1 & Eq F4-6)
DETERMINE CRITERIA FOR ALLOWABLE FLEXURAL STRENGTH (AISC 365-05 Table F1.1)
Chapter F Sections
Required Conditions F2 F3 F4 F5
Double Symmetric x x
Compact Web x x
x
Noncompact Web
Slender Web Mallowable = Mn / Wb = 38.1 ft-kips
Compact Flanges x ( from following analysis)
Noncompact Flanges
Slender Flanges
Applicable Section ok
E 5.68 ft
L p 1.76 r y
Fy
2
E Jc 0.7 F y S xh 0 E
L r 1.95r ts 1 1 6.76
E r ts 18.98 ft
0.7 F y S xh0 Jc 0.7 F y
2
C b 2E Jc L b 37.4383 ksi
F cr 2
1 0.078
Lb S x h 0 r ts
r ts
M p , for L b L p
Lb L p
M n, F 2 Min C b M p M p 0.7 F y S x
, M p , for L p L b L r
63.6 ft-kips
L
r L p
Min F S
cr x , M p , for L r L b
pf
M p M p 0.7 F y S x , for Noncompact Flanges
rf pf
M n, F 3 98.7 ft-kips
0.9 E k c S x
, for Slender Flanges
2
where l = bf / (2 tf) = 8.13
lpf = lp = 9.15 lrf = lr = 24.14
E 4.05 ft
L p 1.1r t
Fy
2
E J S h
L r 1.95r t 1 1 6.76 F L xc 0 19.19 ft
FL S xc h 0 E J
b fc
rt 1.84 in
1 2
12 h 0 a w h
d 6 h 0d
Mp
, for h c / t w pw
M yc
R pc 1.10526
Min M p M p 1 pw , M p , for h c / t w pw
M yc M yc rw pw M yc
2
C b 2E 1 0.078 J L b
F cr 2 37.9722 ksi, (for Iyc / Iy = 0.50 > 0.23, AISC 360-05 F4-5 )
Lb S xc h 0 r t
rt
R pc M yc , for L b L p
Lb L p
M n, F 4.2 Min C b R pc M yc R pc M yc F L S xc , R pc M yc , for L p L b L r
63.73789 ft-kips
L r L p
Min F S
cr xc , R pc M yc , for L r L b
(cont'd)
R pc M yc , for Compact Flanges
pf
R pc M yc R pc M yc F L S xc , for Noncompact Flanges 96.25 ft-kips
M n, F 5.3 rf pf
0.9 E k c S xc
, for Slender Flanges
2
M p
, for h c / t w pw
M yt
R pt 1.10526
Min M p M p 1 pw , M p , for h c / t w pw
M yt M yt rw pw M yt
F y , for L b L p
L b L p
Min C b F y 0.3F y
, F y ,
for L p L b L r
L r L p
20.6711 ksi
F cr , F 5.2
C b 2E
Min 2
, F y , for L r L b
Lb
r
t
Section Left 0.00 S 0.00 S 0.00 S 0.00 S 0.00 S Point 0.17 S 0.33 S 0.50 S 0.67 S 0.83 S Right
Distance 0 0.00 0.00 0.00 0.00 0.00 0.00 3.00 6.00 9.00 12.00 15.00 18.00
d (in) 8 8 8 8 8 8 8 8 8 8 8 8 8
y (in) 4 4 4 4 4 4 4 4 4 4 4 4 4
I (in4) 81 81 81 81 81 81 81 81 81 81 81 81 81
Wt (plf) 23.6 23.6 23.6 23.6 23.6 23.6 23.6 23.6 23.6 23.6 23.6 23.6 23.6
V (kips) 0.21 0.21 0.21 0.21 0.21 0.21 0.00 -0.14 -0.07 0.00 0.07 0.14 0.21
M (ft-k) 0 0 0 0 0 0 0 1 1 1 1 1 0
(cont'd)
Moments
0
-5
-10
-15
-20
-25
-30
-35
-40
Length
-34.00
-34.20
-34.40
-34.60
-34.80
-35.00
-35.20
Length
5w L 4 0.06415 Pb
L 2 b 2
3/ 2
DL 0.02 in ( L / 9108 )
384 EI EIL (for camber, self Wt included.)
5w L 4 0.06415Pb
L 2b 2
3/ 2
LL 0.00 #DIV/0!
384 EI EIL
w= 3/16 in
wmin = 2/16 in, < w
wmax = 3/16 in, > w
W= 2.0
Vmax = 0.21 kips
Q = Af(d - y - 0.5 tf,top) = 10 in3
vmax = Vmax Q / I = 0.03 kips / in
A= 24 in B
0.6 F EXX 0.707 w A 2604 in. o.c.
v max
USE 3/16 in - 24 in @ 2604 in o.c.
DESIGN STIFFENERS
1. BEARING STIFFENERS ARE REQUIRED AT EACH END SUPPORT. (AISC 360-05, J10.8)
2. CHECK LOCAL WEB YIELDING FOR THE CONCENTRATED LOAD. (AISC 360-05, J10.2)
R=P= 0.00 kips
N= 0 in, bearing length, point.
k = tf,top + w = 0.59 in
W= 1.5
R
, for c d
t w N 5k
0.00 < Fy / W [Satisfactory]
R
, for c d
t w N 2.5 k
(cont'd)
3. CHECK WEB CRIPPLING FOR THE CONCENTRATED LOAD. (AISC 360-05, J10.3)
W= 2.0
1.5
2 N t w EF ywt f , for c 0.5d
0.80t w 13 d
t f tw
Rn / 1 / 36.94 > P [Satisfactory]
1.5
0.40t 2w 13 N t w EF ywt f , for c 0.5d
d t f tw
(Note : If item 2, local web yielding is Satisfactory, this item does not need to be checked.)
4. CHECK SIDESWAY WEB BUCKING FOR THE CONCENTRATED LOAD. (AISC 360-05, J10.4)
dc = d - 2k = 6.76 in
Cr = 960000 ksi
(dc / tw ) / (l / bf) = 0.83
W= 1.76
3 3
C r t wt f 0.4 d c / t w , for d c / t w 1.7
h 2 l / b f l/bf
3
C r t 3wt f
Rn / 1 / 10.4 d c / t w , for 1.7 d c / t w 2.3 14.42 > P [Satisfactory]
h
2 l/b f l/b f
dc / tw
P , for l / 2.3
bf
(Note : If item 2, local web yielding is Satisfactory, this item does not need to be checked.)
tw = 1/4 in , bst = 3 in
R= 0.2 kips
Wc = 1.67 , (AISC 365-05 E1)
Kl/r= 0.75 h / ( I / Aeff)0.5 = 3.5
Cc = 4.71 (E/ Fy)0.5 = 113
2E 22890.16 ksi
Fe
kl / r 2
Fy kl
0.658 F e F y , for Cc
r
R n / c A g / c 66.4 kips, (AISC 360-05 E2)
kl
0.877 F e , for r Cc > R [Satisfactory]
Techincal Reference:
1. AISC: "Steel Construction Manual 13th Edition", American Institute of Steel Construction, 2005.
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Flagpole Footing Design Based on Chapter 18 of IBC & CBC
INPUT DATA & DESIGN SUMMARY
IS FOOTING RESTRAINED @ GRADE LEVEL ? (1=YES,0=NO) 0 no P
LATERAL FORCE @ TOP OF POLE P= 4.08 k
HEIGHT OF POLE ABOVE GRADE H= 13.8235 ft
DIAMETER OF POLE FOOTING B= 2 ft H
LATERAL SOIL BEARING CAPACITY S= 0.266 ksf / ft
ISOLATED POLE FACTOR (IBC 1804.3.1 or UBC note 3 on Tab 18-I-A) F= 2
FIRST TRIAL DEPTH ===> D = 8 ft
ANALYSIS
NONCONSTRAINED CONSTRAINED
LATERAL FORCE @ TOP OF POLE P => 4.08 k 4.08 k
HEIGHT OF POLE ABOVE GRADE H => 13.8 ft 13.8 ft
DIAMETER OF POLE FOOTING B => 2.00 ft 2.00 ft
LATERAL SOIL BEARING CAPACITY FS => 0.53 ksf / ft 0.53 ksf / ft
ANALYSIS
NONCONSTRAINED CONSTRAINED
LATERAL FORCE @ TOP OF POLE P => 2.08 k 2.08 k
HEIGHT OF POLE ABOVE GRADE H => 13.7 ft 13.7 ft
DIAMETER OF POLE FOOTING B => 3.00 ft 3.00 ft
LATERAL SOIL BEARING CAPACITY FS => 0.53 ksf / ft 0.53 ksf / ft