CABLE A SOLICITAR DESDE TABLERO DE CONTROL TRIFASICO

5x 5x 7x 7x 7x
A BARRAS A BARRAS A BOMBA A BOMBA A BOMBA
HP CORRIENTE a 380 Volt. AWG CONDUIT AWG 1 CONDUIT 2 CONDUIT
3,0 5,1 12 25 14 1x25
4,0 6,6 12 25 14 1x25
5,0 8,0 12 25 14 1x25
5,5 8,6 12 25 14 1x25
7,5 11,7 12 25 14 1x25
10,0 15,5 12 25 14 1x25
12,5 20,5 10 32 12 1x32
15,0 22,4 10 32 12 1x32
20,0 30,0 8 40 10 1x32
25,0 37,0 8 40 10 1x32
30,0 44,0 6 50 8 1x40 2x32
34 0
34,0 50 0
50,0 6 50 8 1 40
1x40 2 32
2x32
40,0 59,0 6 50 8 1x50 2x32
45,0 65,0 6 50 8 1x50 2x32
50,0 72,0 4 63 6 1x63 2x40
54,0 77,0 4 63 6 1x63 2x40
60,0 85,0 4 63 6 1x63 2x40
70,0 97,0 2 63 4 1x63 2x50
75,0 104,0 2 63 4 1x63 2x50
80,0 111,0 2 63 4 1x63 2x50
85,0 118,0 2 63 4 1x63 2x50
100,0 139,0 1 63 2 1x75 2x50
110,0 149,0 1 63 2 1x75 2x50
125,0 171,0 1/0 75 1 1x75 2x63
150,0 205,0 2/0 75 1/0 2x63
180,0 245,0 3/0 90 2/0 2x75
190,0 260,0 3/0 90 2/0 2x75
200,0 273,0 4/0 90 3/0 2x75
254,0 335,0 250 2x90 4/0 2x75
270,0 372,0 250 2x90 250 2x75